Loading...
Plans gvp 7-31 City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 September 6, 2007 v RE: FIRE ALARM SYSTEM ALGA Project Information Building Permit: BUP2007 -00379 Construction Type: 5 -B Tenant Name: Nike Socks Occupancy Type: B Address: 15705 SW 72 Ave. Hazard: Light The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition the Oregon Fire Code 2007 edition and NFPA 72. The submitted plans are approved subject to the following. General requirements A key box for building access may be required. Please contact the local Fire Marshal's Office for an order form and instructions regarding installation and placement. (OFC 506) A separate low- voltage electrical permit is required for installation and inspection of alarm wiring. A completed inspection and testing form is required at the time of final inspection containing the information as outlined in NFPA section 10.6.2.3. TESTING — NFPA 72 Chapter 10, OFC 901.2.1, 901.5, 903.5 1. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the building inspector. All functions of the system or alteration shall be tested. 2. A record of completion in accordance with NFPD 72 verifying that the system has been installed in accordance with the approved plans and specifications shall be provided. 3. The permittee shall provide written certification to the Fire Chief that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. VISUAL ALARMS — NFPA 72 - 5.14.5, 7.5.4, OSSC chapter 9 & 11 4. When required; Visual alarms shall be located not less than 80 inches and not more than 96 inches above floor level. When a low ceiling exists, the visual alarm shall be mounted within the dimensions stated above and at least 6 inches below the ceiling. No place in a room shall be more than 50 feet from a visual signal. MANUAL ALARM - 1109.2.3.5, 1109.2.3.6 OSSC Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 5. Manual Fire Alarm activation devices when installed shall be mounted in the following reach ranges: • Forward Reach -15 inches to 48 inches above the floor. • Side Reach — 9 inches to 54 inches above the floor. ALARM SIGNALS — OFC 903.4 6. Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA 72 or, when approved by the fire code official, shall sound an audible signal at a constantly attended location. 7. Duct smoke detectors shall be connected to the building's fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open -area detection. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, • an Nelson, Senior Plans Examiner NAC EOL VOLTAGE CALCULATION i CAPITOL ELECTRIC CO., INC. , (503) 255 -9488 Office (503) 257 -7121 Fax Job Name: NIKE / BRIDGESTONE GOLF Job Address: 15675 / 15705 SW 72nd AVE TIGARD, OR 97224 Job Number: Conductor Wire Guage I 14 I Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C (167 Deg F) I 3.07 I Date: 8/24/2007 Cable Length In Feet (source to end of line) I 690 I Total Circuit Current I 1.455 I Nominal System Voltage I 20.4 I Panel Description: SILENT KNIGHT 5208 FACP Minimum Device Voltage I 16 I Panel No.: NAC 1.0 Output No.: 3 Point To Point Method EOLv I 17.02 I Circuit Within Limits ? I I YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv I 14.24 I Circuit Within Limits ? NO Load Centering Method EOLv I 17.32 I Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet ) • 1 FACP Closet DSM- 12/24 -R (1 CKT ONLY) NA 0.0275 5 20.36 2 Nike Tenant AS- 24MCW -FW (110)H /S WHT -M 110 Cd 0.253 168 18.88 3 Nike Tenant RSS- 24MCW -FW (15) STB WHT 15 Cd 0.060 27 18.69 4 Nike Tenant AS- 24MCW -FW (75) H/S WHT -M 75 Cd 0.190 25 18.52 5 Nike Tenant RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 28 18.36 6 Nike Tenant AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 63 18.02 7 Nike Tenant AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 50 17.78 8 Nike Tenant RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 33 17.64 9 Nike Tenant AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 23 17.54 10 Nike Tenant AS- 24MCW -FW (30) H/S WHT -M 30 Cd 0.110 36 17.42 11 Nike Tenant AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 23 17.35 12 Nike Tenant RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 33 17.27 13 Nike Tenant AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 33 17.20 • 14 Nike Tenant AS- 24MCW -FW (75) H/S WHT -M 75 Cd 0.190 95 17.05 15 Nike Tenant AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 48 17.02 16 17.02 ' 17 17.02 18 17.02 19 17.02 20 17.02 Nike Golf NAC 1.0 EOLv Calc.xls OUTPUT 3 4 FACP BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255 -9488 Office, (503) 255 -1966 Fax JOB NAME: NIKE GOLF JOB ADDRESS: 15705 SW 72nd AVE. TIGARD, OR 97224 DATE: 8/24/2007 PANEL DESCRIPTION: SK 5208 FACP BY: Dan Wilson DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE DESCRIPTION QUANTITY CURRENT CURRENT CURRENT CURRENT FACP INTERNAL COMPONENTS 0.00000 0.000000 Silent Knight Model 5208 FACP 1 0.140 0.14000 0.460 0.460 Silent Knight Model 5235 Remote Annunciator 1 0.030 0.03000 0.050 0.050 0.00000 0.000000 INITIATING DEVICES SPRINKLER WATER FLOW 1 0.00000 0.100 0.100 SMK DET FCI SBS -1101 (Alarm) 1 0.00000 0.100 0.100 SMK DET FCI SBS -1101 (Supv) 1 0.0001 0.00010 0.000 M4nuai Pull Station 1 0.00000 0.100 0.100 DUCT SMK DET Syst Sensor DH400ACDC 4 0.02500 0.10000 0.100 0.400 SMK DETs FIRE SCREEN (Alarm) 1 0.100 0.100 SMK DETs FIRE SCREEN (Supv) 2 0.00012 0.00024 WHS HEAT DETS, MANUAL STATIONS 1 0.100 0.100 Duct Smk Det: AP&C SM -501 2 0.015 0.03000 0.100 0.200 Sprinkler Valve Supv Switch 1 0.00000 0.100 0.100 AUXILLIARY DEVICES 0.00000 0.000000 0.00000 0.000000 0.00000 0.000000 I/O Number 1 (Bridgestone) Wheelock DSM- 12124 -R Synch Module (1/2) 1 0.0275 0.028 Wheelock AS- 24MCW -FW 110 Cd H/S (M) 1 0.253 0.253 Wheelock AS- 24MCW -FW 75 Cd H/S (M) 2 0.190 0.380 Wheelock AS- 24MCW -FW 30 Cd H/S (M) 0.110 0.000 Wheelock AS- 24MCW -FW 15 Cd H/S (M) 4 0.074 0.296 Wheelock RSS- 24MCW -FW 75 Cd Strobe 0.165 0.000 Wheelock RSS - 24MCW -FW 30 Cd Strobe 2 0.092 0.184 Wheelock RSS - 24MCW -FW 15 Cd Strobe 1 0.060 0.060 0.00000 0.000 I/O 1 Alarm Total _ 1.201 UO Number 2 (Bridgestone) Wheelock DSM - 12124 -R Synch Module (1/2) 1 0.0275 0.028 Wheelock AS- 24MCW -FW 110 Cd H/S (M) 0.253 0.000 Wheelock AS- 24MCW -FW 75 Cd H/S (M) 1 0.190 0.190 Wheelock AS- 24MCW -FW 30 Cd H/S (M) 2 0.110 0.220 Wheelock AS- 24MCW -FW 15 Cd H/S (M) 3 0.074 0.222 4 Wheelock RSS - 24MCW -FW 75 Cd Strobe 0.165 0.000 Wheelock RSS - 24MCW -FW 30 Cd Strobe 0.092 0.000 Wheelock RSS - 24MCW -FW 15 Cd Strobe 6 0.060 0.360 0.00000 0.000 I/O 2 Alarm Total 1.020 Nike Golf NAC 1.0 Batt Calc (FACP).xls 5208 Batt Calc FACP BATTERY CALCULATIONS I/O Number 3 (Nike) Wheelock DSM- 12/24 -R Synch Module ( 1/2 ) 1 0.0275 0.028 Wheelock AS- 24MCW -FW 110 Cd HIS (M) 1 0.253 0.253 Wheelock AS- 24MCW -FW 75 Cd H/S (M) 2 0.190 0.380 Wheelock AS- 24MCW -FW 30 Cd H/S (M) 1 0.110 0.110 Wheelock AS- 24MCW -FW 15 Cd H/S (M) 6 0.074 0.444 Wheelock RSS- 24MCW -FW 75 Cd Strobe 0.165 0.000 Wheelock RSS - 24MCW -FW ' 30 Cd Strobe 0.092 0.000 Wheelock RSS - 24MCW -FW 15 Cd Strobe 4 0.060 0.240 0.00000 0.000 • I/O 3 Alarm Total 1.455 I/O Number 4 FCI SNAC NOTIFICATION PWR SUPPLY 1 0.060 0.06000 0.120 0.120 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 I/O 4 Alarm Total 0.120 STANDBY TOTAL CURRENT: ( 0.360340 I STANDBY HOURS: 24 STANDBY AMP HOURS: 8.64816 ALARM TOTAL CURRENT: I 2.911 ALARM MINUTES: 5 ALARM AMP HOURS: 0.2425 TOTAL CALCULATED AMP HOURS 8.891 NAC TOTAL CURRENT: I 3.795 APPLIED SAFETY FACTOR 1.10 MINIMUM AMP HOURS REQURED 9.780 SELECTED BATTERY SIZE 12 EACH 12 VOLT, 12 AMP HOUR BATTERIES Nike Golf NAC 1.0 Batt Calc (FACP).xls 5208 Batt Calc [ '2 -)7oc 7 City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 February 28, 2007 !N . 11 • • - RE: FIRE ALARM 11 Building Permit BUP2007 -00379 Construction Type: VB T I GARD Tenant Name: Nike Socks Occupancy Type: F -2 Address: 15705 SW 72'x. Occupant Load: 10 Area: N/A Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC), 2007 edition; the Oregon Fire Code (OFC), 2007 edition and NFPA 72 Alarm Code. Provide the following conditions prior to permit issuance. 1) Provide alarm at west end of R&D knit room. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. I Of; /i Dan Nelson, Senior Plans Examiner Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772