Loading...
Correspondence 1C, i cici held cITY OF T April 2, 1996 OREGON N Capitol Electric Co., Inc. Attn: Randy Tasker 12810 NE Airport Way Portland, OR 97230 Project: Tetra Plastics Subject: Electrical Plan Review (ELC96 -0149) Dear Mr. Tasker: The plans submitted were reviewed for conformity with the 1993 National Electrical Code (NEC) and the State of Oregon Electrical Specialty Code. The following was noted: 1. The 1993 NEC is the minimum electrical requirement. 2. The feed taps that do not comply with NEC 240 -21 will require overcurrent protection at their source. 3. The Optional Calculations used for this project will need to be supplemented with an electrical interlock to prevent service overload. Please address this protection in future drawings and calculations. 4. The electrical "drops" (your letter dated 3/6/96) that terminate at an overcurrent device are feeders, and those that terminate at equipment are branch circuits. 5. The permit does not indicate any control, low voltage or signal circuits. Please contact Michael Rudd at (503) 639 -4171, ext. 356, to discuss the electrical notes. Thank you for your cooperation, w Michael Rudd Electrical Inspector e1c96- 0149 \tetra.doc 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 - 2772 X 570 5- 16 1`11 April 2, 1996 CITY OF TI GARD OREGON Capitol Electric Co., Inc. Attn: Randy Tasker 12810 NE Airport Way Portland, OR 97230 Project: Tetra Plastics Subject: Electrical Plan Review (ELC96 -0149) Dear Mr. Tasker: The plans submitted were reviewed for conformity with the 1993 National Electrical Code (NEC) and the State of Oregon Electrical Specialty Code. The following was noted: 1. The 1993 NEC is the minimum electrical requirement. 2. The feed taps that do not comply with NEC 240 -21 will require overcurrent protection at their source. 3. The Optional Calculations used for this project will need to be supplemented with an electrical interlock to prevent service overload. Please address this protection in future drawings and calculations. 4. The electrical "drops" (your letter dated 3/6/96) that terminate at an overcurrent device are feeders, and those that terminate at equipment are branch circuits. 5. The permit does not indicate any control, low voltage or signal circuits. Please contact Michael Rudd at (503) 639 -4171, ext. 356, to discuss the electrical notes. Thank you for your cooperation, Michael Rudd Electrical Inspector e1c96- 0149 \tetra.doc 13125 SW Hall BMd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772