Specifications ap 2dct, - S
City of Tigard, Oregon 9 13125 SW Hal 1 Blvd. • Tigard, OR 97223 '
•
•
November 21, 2006
T 1 ARD`
Fire System West, Inc
Jason Sampson
600 SE Mantine Ave Suite 300
Vancouver, WA 98682
RE: FIRE SPRINKLER SYSTEM MODIFICATION - EXISTING RACK STORAGE
Project Information
Building Permit BUP2006 -00521
Tenant Name: Nike Golf
Address: 15675 SW 72' Ave
Hazard: Ordinary Group
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition, Oregon Fire Code 2004 edition; and 2002 NFPA 13. The submitted plans are approved
subject to the following.
HYDROSTATIC TES77NG
Hydrostatic testing of the system shall occur at sprinkler final. The contractor's material
and test certificate required by NFPA 13, 16.1 shall be completed and signed by both the
installer and building owner.
TESTING: - Section 16.2.1
1. Unless permitted by 16.2.1.2 through 16.2.1.6, all piping and attached appurtenances subjected
to system working pressure shall be hydrostatically tested at 200 psi (13.8 bar) and shall maintain
that pressure without loss for 2 hours. Loss shall be determined by a drop in gauge pressure or
visual leakage. The test pressure shall be read from a gauge located at the low elevation point of
the system or portion being tested.
SPRINKLER SYSTEM MONITORING: OSSC 901.6. - NFPA 13 sec 8.16
2. All valves controlling the water supply for automatic sprinkler systems and water -flow switches
on all sprinkler systems shall be electrically monitored where the number of sprinklers are more
than 20.
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard - or.gov • TTY Relay: 503.684.2772
OBSTRUCTIONS /CLEARANCES: section 8.5.5 — 8.12
3. Continuous or noncontinuous obstructions less than or equal to 18 inches below the sprinkler
deflector that prevent the pattern from fully developing shall comply with 8.5.5.2.2.
4. Sprinklers shall be positioned in accordance with the minimum distances and special
requirements of sections 8.6 through 8.12 so that they are located sufficiently away from
obstructions such as truss webs and chords, pipes, columns, and fixtures.
HANGERS: section 9 -2
5. The maximum distance between hangers shall not exceed that specified in Table 9 -2.2.1
6. The maximum distance between hangers for listed nonmetallic pipe shall be modified as
specified in the individual product listings.
SWAY BRACING: - Section 9.3.5
7. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads
and to prevent vertical motion resulting from seismic loads. The structural components to which
bracing is attached shall be determined to be capable of carrying the added applied seismic loads.
Sway braces shall be designed to withstand forces in tension and compression. Bracing shall be
attached directly to feed and cross mains.
8. For feed and cross mains, longitudinal sway bracing shall be spaced a maximum of 80 ft.
Later -al sway bracing shall be spaced a maximum of 40 ft. A length of pipe shall not be braced
to sections of the building that will move differentially.
RESTRAINT O F B R A NCH LINES: Section 9.3.6
9. Restraint is considered a lesser degree of resisting loads than bracing and shall be provided by
use of one of the following.
a. A listed sway brace assembly
b. A wraparound U -hook satisfying the requirements of 6- 4.5.3, Exception Number 3
c. No. 12, 440 -1b wire installed at least 45 degrees from the vertical plane and anchored on
both sides of the pipe
d. Other approved means
10. Wire used for restraint shall be located within 2 ft (610 mm) of a hanger. The hanger closest to a
wire restraint shall be of a type that resists upward movement of a branch line. The end
sprinkler on a line shall be restrained against excessive vertical and lateral movement.
Where upward or lateral movement would result in an impact against the building structure,
equipment, or finish materials, branch lines shall be restrained at intervals not exceeding 30 ft.
SPARE SPRINKLERS: - Section 6.2.9
11. The stock of spare sprinklers shall include all types and ratings installed and shall be as follows:
a. For systems having less than 300 sprinklers, not fewer than six sprinklers
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.3.1 OSSC
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
espectfu lly
Val Henzel,
Senior Plans Examiner
, __
Bulletin 110 Rev.S
® Model G co
'Rentable A utomatic Sprinklers
Spray Upright
Spray Pendent o
And Conventional XI
0
•
•
Product Description s
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of .4: 7. ,- :.,
construction. The fusible alloy is captured in the
cylinder of the solder capsule by a stainless steel ball. i... . :
When the fusible alloy melts, the ball moves into the ' ir° ! 1
cylinder allowing the cylinder to fall away from the :•�i!
sprinkler. When this happens, the lever is released to -,;: 1 • I ..� i
spring free from the sprinkler so that all of the operating ws s co V `
parts clear from the waterway allowing the deflector to ,!w-_z_,2,, ;
distribute the discharging water. °� _
Except for the parts in the cylinder as mentioned
above, the sprinkler components are made from Upright Pendent
copper based alloys for maximum corrosion
protection. Lead plated, wax coated or wax over lead
plated sprinklers are available for specially severe ,
environments. Chrome plated sprinklers are available ''f
for decorative purposes. 1 1 , 1 ;
All sprinklers are individually hydrostatically tested. ! -! ? Pr"
All sprinklers are identified as to their fusing point by
r mi --•
markings that appear on several of the operating parts
il
y
and by an identifying color that appears on the frame. �� = _
Sprinkler Types
Standard Upright - This deflector configuration is Small Orifice Upright Conventional
normally used with exposed piping installations. Water
is distributed laterally and downward in a wide pattern
approximating a hemisphere which is completely and
uniformly filled with water in the form of small drops or
spray.
Standard Pendent - This deflector configuration is Application and Installation
normally used where the space above the piping is Standard sprinklers are used in fixed fire protection
I limited or where a concealed piping installation is systems: Wet, Dry, Deluge or Preaction. Care must be
employed. The discharge characteristics of the exercised that the orifice sizes, temperature ratings,
standard pendent are virtually identical to the deflector styles and sprinkler spacings are in
standard upright as described above. accordance with the latest published standards of the
National Fire Protection Association or the approving
Large and Small Orifice —By varying the orifice size, authority having jurisdiction.
a large or small orifice sprinkler is created that will The sprinklers must be installed with the Reliable
distribute as much as 40% more water or 65% less Model D Sprinkler Wrench. Any other type of wrench
water than the normal Y" (15mm) orifice sprinkler. may damage the sprinkler.
The approvals or listings of Reliable Automatic
Conventional —This deflector configuration is used Sprinklers by major approving organizations are
primarily in those countries where the LPC installation shown in the tabulated list provided on the back of this
rules have precedence. The sprinkler is designed to bulletin.
distribute a portion of its water discharge upward
against the ceiling with the balance downward. It may
be installed in either the upright or the pendent
position. Sprinklers with conventional deflectors are
available with orifice sizes corresponding to light, •Patent No. 4,440,234
ordinary and extra -high hazard installations.
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
Technical Data -
"K" Factor I Sprinkler Identification
i
I Sprinkler I Number (SIN)
Sprinkler Type US Metric Height I Approvals SSU SSP .
Standard - Upright (SSU) and Pendent (SSP)
Deflectors Marked to Indicate Position
/ (15 mm) Standard Orifice with y" NPT (R/ Thread 5.62 81.0 2 (73 mm) 1, 2, 3, 4, 5, 6, 7 R1025 R1015
'%6 ( 11 mm) Orifice with y" NPT (Ry
" ) Thread 4.24 61.0 2 e" (73 mm) 1, 3, 7 R1023 - R1013
X" (10 mm) Small Orifice with y" NPT (Ry) Thread 2.82 40.6 2 Y" (73 mm) 1, 2, 3, 7 R1021 81011
5/
7t6" (8 mm) Small Orifice with y" NPT (Ry) Thread 1.98 28.5 2 Y" (73 mm) 1, 3, 7 R1022 R1012
9/32' (20 mm) Large Orifice with y" NPT (RX) Thread 7.96 114.7 2 Y." (73 mm) 1, 2, 3, 7 R1026 R1016
'/32' (20 mm) Large Orifice with 3;" NPT (R3;)Thread 8.20 118.2 2' e" (75 mm) 1, 2, 3, 7 R1027 R1017
20 mm XHH with 20 mm Thread 8.20 118.2 75.4 mm 4, 5, 6 R1027 R1017
10 mm XLH with 10 mm Thread 4.10 59.1 73 mm 4, 5, 6 R1024 R1014
Conventional — Installed in Upright or Pendent Position
10mm XLH with 10mm Thread 4.10 59.1 73 mm 5 R1074
15mm Standard Orifice with (Ry) Thread 5.62 81.0 73 mm 4, 5, 6 R1075
20mm XHH with (R3;) Thread 8.20 118.2 75.4 mm 4, 5 R1077
Temperature Ratings Maintenance
Maximum Model G Sprinklers should be inspected quarterly and the
Sprinkler Ambient sprinkler system maintained in accordance with NFPA 25. Do
Rating Temperature Frame (1) not clean sprinklers with soap and water, ammonia or any other
Classification °F °C °F °C Color cleaning fluids. Remove any sprinkler that has been painted
Ordinary 135 57 100 38 Black (other than factory applied) or damaged in any way. A stock of
Ordinary 165 74 100 38 Uncolored spare sprinklers should be maintained to allow quick replace -
Intermediate 212 100 150 66 White ment of damaged or operated sprinklers. Prior to installation,
High 286 141 225 107 Blue sprinklers should be maintained in the original cartons and
I - packaging until used to minimize the potential for damage to
(1) Frame color does not apply to painted or plated sprinklers sprinklers that would cause improper operation or
-Use sprinkler rating as identified on operating parts. non -operation. Use only the Model D Sprinkler Wrench for
sprinkler removal and installation. Any other type of wrench may
damage the sprinkler.
Finishes (1)
Standard Finishes Approval Organizations
Bronze —All Temperature Ratings 1. Underwriters Laboratories, Inc.
All Temperature Ratings 2. Factory Mutual Research Corporation
White ( `l —All Temperature Ratings 3. Underwriters' Laboratories of Canada
i Only Frame and Deflector are Painted 4. Loss Prevention Council
I Special Application Finishes 5. Pleniere Assemblee
6. VdS Schadenverhutung
I Bright Brass Plated —Only frame, deflector and cap are plated. 135 °F (57 °C), 165 °F 7. N.Y.C. BS &A No. 587 -75 —SA or
(74 °C), 212 °F (100 °C) Temp. Rating. N.Y.C. MEA 258 -93 -E
Black Plated —Only frame, deflector and cap are plated. All Temp. Ratings.
Polyester Coated (2) —Only frame and deflector are coated.
Lead Plated —165 °F (74 °C), 212 °F (100 °C) and 286 °F (141 °C) Temp. Ratings. Ordering Information
Wax- Coated (3) —165 °F (74 °C) Clear Wax, 212 °F (100 °C) Brown Wax. Specify
Wax- Coated Over 1. Model G
Lead Plated (3) —165 °F (74 °C) Clear Wax, 212 °F (100 °C) Brown Wax. 2. Deflector
• Upright
( Other colors and finishes are available. Consult factory for details. • Pendent
(2) UL listed and NYC MEA Approved only. • Conventional
(3) 212 °F (100 °C) brown wax may be used on 286 °F (141 °C) 3. Nominal Orifice
sprinklers when maximum ambient temperatures do not exceed 150 °F 4. Inlet Thread
(66 °C). UL Listed, FM Approved, NYC MEA 258 -93 -E. 5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association. Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States. Canada and foreign countries.
Manufactured by
• The Reliable Automatic Sprinkler Co., Inc.
Sales Offices
R e n a b' a (800) (800) 848 431 - 1588 Sales Fax PoPer
(914) 668 -3470 Corporate Offices Revision lines indicate updated or new data.
•
www.reliablesprinkler.com In ternet Address
P EG. PmteO in USA 11,04 PIN 9999970005
J
Bulletin 208 Rev.F
` Sprinkler Guards
Co
• Model C N
o
co
• Model D
m
1
Model C Sprinkler Guards [ , r s ,
Model C Series sprinkler guards are designed to be i .y g� -:
assembled onto installed sprinklers. They are: iicf ''.,
constructed of heavy gauge wire welded to steels .
mounting plates and finished with zinc plating. Other -_ , „ �- 1 ilk . - finishes are available. Guards protect automatic, ° -;- W
sprinklers in locations where they are subject to I - ` �`r -�,�
physical damage. Refer to guard selection table for' x R je.
listing and approval information regarding specific;
sprinkler and guard combinations. j ,,, ,
AII Model C guards are certified by FM Approvals. i /
Models C -2 and C -3 also have cULus Listings. i
• Model C -1
- Model C -1 guards are used with pendent, upright,
horizontal sidewall and vertical sidewall sprinklers. -- —
• Model C -2 Model D1 Sprinkler Guard
• Model C -2 guards are used with pendent dry
sprinklers. • Model D -1
• Model C -3 Model D -1 guards can be assembled to pendent,
upright and horizontal sidewall sprinklers.
Model C -3 guards have a water shield attached.
When assembled to an upright sprinkler, the • Model D -3 and D -6
combination is for upright intermediate sprinkler Model D -3 and D -6 guards have a water shield
applications. attached and are assembled to upright sprinklers.
• Model C -5 The sprinkler guard assembly is for upright
intermediate level sprinkler applications.
Model C -5 guards are supplied with a water shield
and 0-Ring which are assembled to the sprinkler • Model D -4 and D -5
before the sprinkler is installed. The guard is then Model D -4 and D -5 guards are D -1 guards supplied
installed to the sprinkler after it is installed in the, with an original water shield which is threaded on (1/2")
fitting. • or passed over (3/4") the sprinkler inlet thread. The
combination forms a pendent intermediate level
Model D Sprinkler Guards
The Model D Series sprinkler guards are Guards and water shields are finished with zinc
supplied as kits to be assembled to the sprinkler at plating. Other finishes are available upon request.
the job site before sprinkler installation. The kit
consists of the guard, 1/2" and 3 /4" locknuts and a All Model D Guards are cULus Listed. Refer to
water shield when being used as an intermediate: guard selection table for listing and approval
level sprinkler. The pendent intermediate has an. information regarding specific sprinkler and guard
0-Ring supplied. combinations.
Each guard type is fabricated of heavy gauge' Patents:
wire welded to steel mounting plates and complies` USA Patent Number 5,893,418
with the latest UL standards. Guards protect Applies to Model D Series Guards
automatic sprinklers in locations where physical
damage can occur. Listings & Approvals
Model D Series guards are also available factory 1. Listed by Underwriters Laboratories, Inc. and
assembled on the sprinkler ready for immediate UL certified for Canada (cULus)
sprinkler /guard installation. Consult factory for 2. Certified by FM Approvals
availability. 3. NYC MEA 258 -93 -E
4. Scientific Services Laboratories (SSL, Australia)*
* For Models 01, C2, C3 guards.
The Reliable Automatic Sprinkler Co., Inc. • 525 North MacQuesten Parkway • Mount Vernon • New York • 10552
t
Model C -1 Guards
•
_14 Ii I ,� , , � ' �'.
go . 1:-__1.' is . , , . k 1, , .
SHOWN MODEL G UPRIGHT SPRINKLER SHOWN MODEL G PENDENT SPRINKLER
208C18
Model C -2 Guards
■1■ mar . °__'_j _,
■ . L
alit ,
iii Ili .
VII LW -. --p. � �
s,! '
;HOWN moon r3 MOON CPRISKI re 200C2C
Model C -3 Guards
. ai —I--- - - r e d / �.
1 1 -" iiir
....- g if .. I i
- t 0 .
Pilk, iiji __4'. __
s_tt:)§ r• ,.:. ,
1 A.-, ,.
,. , 11:• ..
iHGWH MODFL FIFR UPRIGHT SPMNKI FR SMGWN NODFL G UPRIGHT SPRINKIFB $IQPNN MGDFI GFR UPRIGHT SPRINKIFB
2OYSN
Model C -5 Guards
Ai in forilis . 1
tol ,': :1 11 ..
SHOWN MODEL F1 FR PENDENT SPRINKLER SHOWN MODEL F1 PENDENT SPRINKLER ` '�l
SNOWN M00EL G PENDENT SPRINKLER
208CSB
2.
..- 2
-
i
. i
Model D-1 Guards . Model D-3 Guards
ii .....I."_ -aillra■rair."111.-
0 1 111 1;) , _
IMM ii 1111 MI
---,---.=
DOWN NOEL G SPRIKKILB DOWN MODEL Ft SPRItoont
8182011 1031682 .
SHOWN MODFL C CPPINKI FR 2
---
1 - ! 116812ll 1682081
...L ........... --.
__ef„ii_
VIM 111111
- OW.
El Model D-5 Guards
1111 III
_-,7-
3Nove4 moDit r. _SPIttmet re ImOwN MOOFL Ft SPRitoorti :Mir: :MEM
trticell 2C2882ff _A.m.__
. Orli 11.11
. - "me
4W . 1 ,* - eig
Prill
(1C1111141i,%1 r---- 1 bill 1111
- 1 !-- r
1 ,, -
• t! Crialli,,qi , VI, IL: ',1
\ 11 r n SHOWN mOO 6 1/2- NPT 4PENNID 1J2 FII
BaSaititarBilraff itIOWN MODEL Fl r NPT SPRINKLER
EINEELMOZMODAtE
H211 UMELLSEMELEB 4NFANT4 monFL rt tPRINKInt
200 881882821SIDO
208018
F - ...---;-_-:
--- -- .-- ---.
1 iTIMINlin ITMIr:
,
t
_Ifilir I__
Ell 1111
_....
{ i i
Model D-4 Guards !
1111 III
SHOWN MODFI C 3/4" NPT %PRINK, FR sitgrautageuitelaufsuisua
. IX8220-16=C12811 282612C-160:Magr
20806C
i
--..---_-_- ---=-:;.:
!rim_ irri--. Model D-6 Guards
1:Irtill
L
L
RwiP .
- n - i,
bri _...ariv-1-1■11■-
NMI _....0171■1111...
Oral
SHOWN MODFL CFR L/2" NPT SPEW re smthvt1 MDDFL CFR 3/4" MN •LPRrNNIFN Itztl MA
____
• .,..,...N., gill ii11
2aeof-C
!
. i moon C XI N231 VP" MPT NPRINKI Fa Moon 6 xt.0231 3/4- NPT NPRINIC FR
t .020211
"MAW .11882LIJESIfiaga
3.
•
•
Guards are approved to be used with sprinklers listed below.
j Approvals with SIN Number
-
Guard Model (3) Sprinkler Model Sprinkler Type Orifice Sizes MEA , SSL
Application
cULus FM rn
R3611, R3613, R3615,
R3612, R3621, R3623,
R3625, R3622, R3111,
R3113, R3115, R3117,
R3121, R3123, R3125,
R3127, R3635, R3131,
Pendent, Upright, 3/8 ", 7/16 ",' /z ", R3133, R3135, R3137,
D -1 G, GFR, F1, F1FR HSW 17/32" R1711, R17 , R1715,
R1712, R17211, R1723,
R1725, R1722, R1735,
R1011, R1013, R1015,
R1016, R1017, R1021,
R1023, R1025, R1026, •
• R1027, R1231, R1233,
R1235, R1236, R1237
R3625, R3622, R3125,
D -3 G, GFR, F1, F1FR Upright Intermediate '/z ", 17/32" R3127, R1725, R1722,
R1025, R1026, R1027
D 4 G, GFR, F1, F1FR Pendent Intermediate '/z" 17/32 R3115, R3117
(Large Shield)
Pendent Intermediate R3615, R3612, R1715,
D -5 G, F1, F1FR h ", 17/32 R1712, R1015, R1016,
(Small Shield) R1017
D -6 G XLO Upright Intermediate 0.64 R2921
R1011, R1015, R1016,
R1017, R1021, R1025,
Pendent, Upright, R1026, R1027, R1235,
C-1 G, F1, F1FR HSW, Vertical 3/8 ",'' /z 17/32" R1285, R1712, R1715,
Sidewall, Upright & R1721, R1725, R1735,
Pendent R1785, R3612, R3615,
R3622, R3625, R3635,
R3685
C-2 F3, F30R Pendent 1/2" R1616, R5314, R5314, R5714
R5714,R4216
R3625, R3622, 1R3125, R3625, R1725,
C -3 G, GFR, F1, F1FR Upright Intermediate ' /z ", 17/32" R3127, R1725, R1722, R1025, R1027
R1025, R1026, R1027
R1015, R1017,
C -5 G, F1, F1FR Pendent Intermediate ' /z ", 17/32" R3615, R1715,
R1712, R3612
( MEA approval on D -1, D -3, D -4, D -5, C -2, and C -3
( SSL approval on C -1, C -2, and C -3
( Model GFR does not have FM Approval.
( Sprinkler guards are listed and approved only for use with specific sprinklers. The use of any other
guards on these sprinklers may impede their operation or distribution and negate all approvals and warranties.
4.
Overall Cage Size: • Model D Guards
Before a sprinkler is installed into a fitting, assemble
• Models C -1. C -2. C -5 the guard on the sprinkler using the same technique
2 (73mm) High X 2V; "' (70mm) Diameter described above for the Model C Guards. Then
install a /2" or 3 /4" locking nut on to the NPT threads
Models C -3. D -3. D -6 until the nut is tight against the guard. Each guard is
" 4 supplied with both size of locking nuts. The
2y; ( 70mm ) High 9 X /z ( 114mm ) Diameter assembly of sprinkler and guard is then wrenched
into place using an adjustable wrench maximum
Models D -1. D -5 size 8" and a jaw opening of 1Ya" (for D -1, D -3, D -4
2y" (67mm) High X 3" (76mm) Diameter or D -5) or an adjustable wrench maximum size 10"
and a jaw opening of 1,;6" (for D -6).
Model C-4 Wrench must be placed over the guard. Do not
2' /e " High X 4/" Diameter use the wrench directly on the sprinkler wrench
boss. The sprinkler wrench boss requires a
Installation Instructions special wrench.
• Model C Guards t •
With both cups unhooked, slightly spread' open the Finish
guard. Insert steel plate into the installed sprinkler Standard Finish —Zinc with chromate dip.
between the threads and the wrench flats. The steel Other finishes, quoted on request.
plate tabs should face the sprinkler wrench flats and four
contact points engage the sprinkler neck.
For Model C -2, the steel plate fits into the groove in Ordering Information
each wrench flat and the guard is located by the notch in • Guard Type (D -1,D -2 etc.)
both steel plates. • Finish (Standard or other)
Snap the farther locking clip into place, then close the Sprinkler Inlet Thread Size,
near clip. The guard is now securely installed in place. If p
locking clip requires too much force to snap closed or D -4 & D -5 Guards Only.
open, slightly flex the wires on both sides of the clip and • Optional: Consult Factory for assembly on
either close or open the clip. c sprinkler.
Specify Sprinkler:
- Type.
- Temperature Rating.
- Finish.
• Wrench: Not supplied by Reliable
5.
•
ReIiabIe...For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision -made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Supertrol electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by a Recycleo Paper
_ The Reliable Automatic Sprinkler Co., Inc.
fl e�'abl® � (800) 431 -1588 Corporate e orate s
Offices
(800) 848 -6051 Sales Fax
Co Revision lines indicate updated or new data.
(914) 668-3470
www.reliablesprinkler.com Internet Address E.G. Printed in U.S.A. 8/04 P/N 9999970152