Plans VV1 CC a/ 1. 6f7/ City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 April 19, 2007 � 7(� - 1 q wt � Jerry Pillar .. J - ( ? I Arrow Mechanical j i RIj: 10330 SW Tualatin Rd. Tualatin, Or. 97062 RE: VENT FOR SPRAY WASHERS Project Information Building Permit: MEC2007 -00176 Construction Type: NA Tenant Name: Rodgers Machinery Occupancy Type: NA Address: 14600 SW 72" Occupant Load: NA Area: NA Stories: NA The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The submitted plans are approved subject to the following. 1) Show how combustion air will be provided. 2) Provide listing and installation instructions showing attachment to floor. 3) Provide listing of thimble to be used to penetrate the wall. 4) Show how you will secure B -vent to building on exterior. 5) Provide information on the building and construction of floor. 6) Listing for size of B -vent. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC • Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, • / an Nelson, • Senior Plans Examiner Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772