. • • • Listed be is the information for the commodity, how we will store it, and the address.
• • :'Bfusiiness Mtn: UPS Logistics Group (A wholly owned subsidiary of UPS)
• • • • • .$usiness /Mess: 14160 SW 72 " Ave Suite 150 Building E Tigard, OR 97224 • •
•.•••• • •••• •
•
• • Commodiiyglass: IV Non - encapsulated 1999 (NFPA 13) Chapter 7
.••• • •
• •••• •
... ... 1) J PS Logistltt Group will store a Class IV Non - encapsulated commodity.
• • • • '2) High Pile storage up to 16' 6" H of storage in racks. The clear ceiling height is 22'.
' " "' a) NFPA 13 Figure 7- 4.2.2.1.1 (d) Sprinkler Design Curves
b) Curve G Allows for maximum of 20' high of storage with a .60 GPM / 2, 000
SF. (without in rack sprinklers)
c) Figure 7- 4.2.2.1.3 Ceiling Sprinkler Density vs. Storage Height. This allows
for a reduction of GPM with a reduction of storage height. We will store up to
16'6" or 17.5 percent less than 20', which equates to a 17.5 percent reduction
in the GPM (see d below).
d)The building sprinkler density is .495 GPM / 2,000 SF, with 286 degree
heads. This is 17.5 % less than the .60 GPM required for 20' High storage.
4) Racks will be single row and of the open frame type, with open wire mesh decking.
5) Minimum aisle width is 4'8 ".
1997 Uniform Fire Code Article 81 Tables 81A & 81B
1) The venting ratio is 1 SF vented per 100 SF of floor space.
2) The facility is 18,534 SF.
3) The draft curtain (6' depth) areas are less than 10,000 SF.
4) There are 4 Small Valve Hose Stations.
The above listed are shown on an accompanying to scale reflected ceiling plan drawing.
�