Specifications OFFICE COPY (a`'P 2.e November6, 2003 CITY OF TIGARD OREGON Cascade Fire Protection 24023 NE Shea Lane # 110 Wood Village, OR 97060 RE: CONTRACT FURNISHINGS MART, FIRE SPRINKLER SYSTEM Project Information Building Permit: BUP2003 -00629 Construction Type: VN Tenant Name: Contract Furnishings Mart Occupancy Type: S -2 Address: 14160 SW 72 Avenue Occupant Load: NA Area: 10,000 Sq Ft Stories: 1 Hazard: EH -1 Commodity: IV The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. 1. The response to plan review question # 2 indicates that storage will be limited to 20 feet in height. The storage rack design, which is not approved at this time, indicates a shelf at 20 feet. A condition for approval of the fire sprinkler system is that there will be No storage permitted on the top shelf. Any storage on the top shelf will render the fire sprinkler system permit to be revoked and considered null and void. 2. A key box shall be installed within 20 feet of the riser room entrance. The bottom of the key box shall be not less than 8 feet nor more than 10 feet above the walking surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 Contact TVF &R for keybox at 503- 612 -7010 3. A supply of spare sprinklers. (never less than 6) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property. Standard 9 -1, section 2 -2.7.1 OSSC 4. A special sprinkler wrench shall be provided and kept in the cabinet along with the spare sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1, section 2 -2.7.2 OSSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 5. A minimum of 18 inches shall be maintained between top of storage and ceiling sprinkler deflectors. The distance shall be increased to 36 inches for large drop sprinlder heads. Standard 9 -1, section 4 -4.1.6 and 4 -4.3.2 OSSC 6. Clearances shall be provided,around all piping extending through walls, floors, platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 '/s inches shall be not less than 1 inch. Minimum clearance for pipes 4 inches and larger shall be 2 inches. Standard 9 -1, section 4- 5.4.3.4 7. Monitoring, Section 904.3.1 OSSC All valves controlling the water supply for automatic sprinkler systems and all water flow monitoring devices shall be electrically monitored where the number of sprinlders are; • Twenty or more in group I, Divisions 1.1 and 1.2 Occupancies. • One hundred or more in all other occupancies. 8. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. An approved audible sprinlder flow alam? to alert the occupants shall be provided in the interior of the building in a normally occupied location. 904.3.2 OSSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully rian Bl• , Senior Plans Examiner 1 , A ■ CASCADE FIRE PROTECTION co. 24023 N.E. SHEA LANE SUITE #110 WOOD VILLAGE, OREGON 97060 P11: 503- 491 -8755 FX: 503 -491 -8768 email: cascade2 @earthlink.net Brain Blalock Senior Plans Examiner, Tigard City Hall 13125 Hall Blvd. Tigard City, Oregon 97223 Dear Sir, Re: Contract Furnishings Mart, at 14160 S.W. 72 Ave., Suite 110 Tigard, Oregon 97220, Re: Letter of November 3, 2003, Question #1: The ceiling height varies from 24' -0" to 26' -0 ". Question #2: Storage is limited to 20' -0" in height. Sincerely, ,ritg Karon O'Donnell Cascade Fire Protection Co. 24023 N.E. Shea Ln. #110 Wood Village, Or. 97060 1 Z8 30dd NO310dd 3aI3 3Qa0Sd0 89L8I6tEOS 8S:80 EC3O .. SO T T November 3, 2003 Cascade Fire Protection 24023 NE Shea Lane # 110 Wood Village, OR 97060 RE: CONTRACT FURNISHINGS MART, FIRE SPRINKLER SYSTEM Project Information Building Permit: BUP2003 -00629 Construction Type: VN Tenant Name: Contract Furnishings Mart • Occupancy Type: S -2 Address: 14160 SW 72 Avenue Occupant Load: NA Area: 10,000 Sq Ft Stories: 1 Hazard: EH -1 Commodity: IV The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The following information is required prior to the approval of the submitted plans. • • The racks that have been submitted under a separate permit for the above listed project have a storage rack at 20 feet above the finished floor. 1. Clarify the ceiling height of the storage area. 2. Clarify the height of the items to be stored on the top rack. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Brian Blalock, Senior Plans Examiner CASCADE FIRE PROTECTION CO. 24023 N.E. SHEA LANE SUITE #110 WOOD VILLAGE, OREGON 97060 PH: 503 - 491 -8755 FX: 503 - 491 -8768 email: cascade2 @earthlink.net Tigard City Building Inspector, Tigard City Hall 13125 Hall Blvd. Tigard City, Oregon 97223 • Dear Sir, Contract Furnishings Mart, at 14160 S.W. 72 Ave., Suite 110 Tigard, Oregon 97220, ▪ is storing carpet in their back storage area. Per Contract Furnishings, carpet will be stored on racks, not over 20 feet. Per hydraulic sticker, on the existing riser, this system was calculated at a density of 0.495gpm, over 2000 sq. ft. by the first fire sprinkler system installer. The existing upright sprinkler heads are laid out in a 9' -0" X 10' -0" pattern, (90sgft per head). Sprinkler pipe center lines, are at 23' -6" at lowest area of ceiling. Using NFPA 13: 2002 edition: Section 5 -6: Commodity Classification: (title of section) Per Table A.5.6.3: Carpet tiles, group A plastic. Section 12.3: Protection of Commodities Stored on Racks. Per Section 12.3.1.2.2: Protection criteria for Group A plastics shall be permitted for the protection of the same storage height and configuration of Class I, II, III, and IV commodities. RECEIVE[ OCT 2 7 2P[ 1 CITY OF TIGARD BUILDING DIVISIC!N Per Section 12.3.2: Protection Criteria for Rack Storage of Class I through Class IV Commodities Stored Up to and Including 25 ft. (title of section) Per Section 12.3.2.1.1: Ceiling sprinkler water demand shall be determined in accordance with 12.3.2.1.2 for single- and double -row racks or 12.3.2.1.3 for multiple racks. Per Section 12.3.2.1.2: states to use table 12.3.2.1.2. Using table 12.3.2.1.2: (over 12ft up to and including 20 ft Class IV) non - encapsulated (see section 3.9.8), no in rack sprinkler, use figure 12.3.2.1.2(d). • Using figure 12.3.2.1.2(d): chart E (286 degree temp. 8 ft. aisles), density to use for calculations shall be, 0.495gpm over 2000 sq. ft. Per hydraulic sticker, on the existing riser, this system was calculated at a density of 0.495gpm, over 2000 sq. ft. by the first fire sprinkler system installer. The existing upright sprinkler heads are laid out in a 9' -0 "X 10' -O" pattern, (90sgft per head). Section 12.3.1.2 Sarinkler Protection Criteria: (title of section). Per Section 12.3.1.3: Hose connections shall not be required for the protection of Class I, II, III, and IV commodities stored 12 ft. or less in height. (Racks over 12 ft. need a fire hose connection installed.) Section 8.16.5 Hose Connections: (title of section) Per Section 8.16.5.1: Small (1 1 /2) Hose Connections: Per Section 8.16.5.1.1: Where required by chapter 12, small (1 1/2) hose lines shall be available to reach all portions of the storage area. Per Section 8.16.5.1.2: The hose connections shall not be required to meet the requirements of Class II hose systems defined by NFPA 14. 2 Per Section 8.16.5.1.3: Hose connections shall be supplied from one of the following: (2) A separate piping system for small hose stations. (The current system was set up with a separate hose connection line.) Cascade Fire Protection Company, will be installing two (2) one and one -half (1'/2) hose valve connections. Central Model A97 with cap and chain. One hose valve connection front area of storage. One hose valve connection back area of storage. Piping for these hose connections, will connect to existing hose connection line, with 1'/2 inch pipe with a 1 inch pipe drop to hose connection. Per hydraulic sticker on riser, this system was calculated at a density of 0.495gpm over 2000sq.ft. The existing upright sprinkler heads are laid out in a 9'- 0"X10'-0" pattern, (90sgft per head). This should be sufficient coverage of the storage area. Sincerely, 1 IJt , / Karon O'Donnell Cascade Fire Protection Co. 24023 N.E. Shea Ln. #110 Wood Village, Or. 97060 3 ----- , , [IENTRAL r_ 6 • 4 gtW4 °T. a z b, 6- F r �' �: x- fit >?. 300 PSI Working Pressure „„...,,,..a..,..,„,. , ., - -...t.43,z-4. , , , v0i-,2 _,..,..;v_, ---r7.-It-t,&,,,,--14-e.::. $ - r Y ,. 4 ma y ^ i.r i ; s Y g p , fi � R i- -' „ ,;ii . µ1{ Central Sprinkler Company �4 � ' t � '; " 451 North Caririon.Avenue, Lansdale, Pennsylvania 19446 - ,, _, Product t , ' . . Technical . � � : � a � ' � Mt. O Description y y * r: • The Central Modet A97 and A97H Model: A97 or A97H �` r- . Hose Valves are designed for use as Style: Male Hose Thread Outlet or -� s - _. te.t a fire department outlet connection or Female Hose Thread Outlet Y !�t . i-r7 - for use in a fire hose rack assembly.. Size: 2'/2" or 11/2" or 2'/2" with 1'/2" e ` , . ' y-. RA The Hose Valves are available in 1 /2" Reducing Adapter 1' f :n: or 21/2" sizes male or female national Approvals: UL, FM - hose thread by female national pipe Max. Working Pressure: 300 psi thread". Standard Finish: Cast Brass Mfg. Source: non - domestic The Central Model A97/A97H Hose Valves are UL Listed and FM Ap- proved. The Central Model A97/A97H Hose ei Valves provide positive shut off and (E) ill of Materials suitable for cold water service Q as _ r.-,_- e-- - - -1 Item Description Material only. They are rated at 300 psi I , � � �� working pressure. 0 1 Hand Wheel Ductile Iron 2 _ Packing Nut Brass Rod B16 The hand wheel is manufactured 0 1:1 � I % 3 Bonnet Brass B584 from high strength ductile iron, giving _ 4 Body Brass 8584 extra resistance to breakage. O s Stem Brass Rod 816 The Central Model A97/A97H Hose c' ev� �' 6 Lock Nut Brass Rod B16 Valves are tested twice, both times � =' 1&r 7 Set Screw Brass Rod B16 with air under water, to ensure 0 , 8 Holder Brass B584 consistent quality. Options available 0 , 9 Seat Seal Natural Rubber include cap (plug for the A97H) and O 1i ■� 10 Clamping Rin g Brass Rod 816 chain for both sizes and 2/z � " x 1 /2 � • " l 1 11 Clamping Nut Brass Rod 816 E as . ��� brass adapters to allow transition to 0 ''-- 1 +'`1► 12 Wheel Nut Mild Steel • 1' /z" hose lines. 1! � - A 13 Wheel Washer Mild Steel al 14 O -Rina Natural Rubber The Model A97 and A97H are not • Model A97 shown, Model A97/l pressure reducing hose valves and has a female hose connection. cannot be used as such. * The Model A97 has a mate hose thread outlet and the A97H has a female hose thread outlet. Both models have national pipe thread inlets. lw 00 4 C • • i Nom. . Dimensions In Inches Approx. Part ' . — art - - .1 s 3 /8° Size A B C D E Net. Wt. (Ibs) # ' - �"` •� I 1 Y2" 6.12 5.08 3.92 2.44 1 Y2" 5.0 22460 F 1 2 7.68 5.90 4.92 3.35 2W 11.5 22461 � 2 A = Open ---- E T read B = Closed i = � gLWA Care & • ordering J L ,` Mai nance =I Information `� ___ ��� 1 1/2° = 2.00 The Model A97 and A97H' must be Ordering Information: When 'D' 2 1/2° = 2.75 maintained in accordance with placing an order, indicate the full a ME0 NFPA 25 Standard entitled, product name. Please specify the "Inspection, Testing andMainte- quantity and model. z Thread —• nance of Water -Based Fire Protec- tion Systems". Availability and Service: Central sprinklers, valves, accessories, and ° other products are available throughout the U.S. and Canada; and internationally through a network of Central Sprinkler distribution centers. • Available Options You may write directly to Central Sprinkler Company or call (215) 362- /— for the distributor nearest you. Cap and Chain (for the A97H) Reducing Adaptor Guarantee: Central Sprinkler 11/2" or 2'/2" 21/2" x 11/2" (Part #41206) Company will repair and/or replace (1'/2" Part #41205, or 2W Part #41204) any products found to be defective in -- material or workmanship within a period of one year from the date of ,�' = � ' �' shipment. Please refer to the current /' Price List for further details of the r 1 II 1 111 warranty. Patents: Patents are pending. Conversion Table: 1 inch = 25.400 mm Note: Order 2W or 11/2° plug for use 1 foot = 0.3048 m with A971 female outlet 1 pound = 0.4536 kg (2'/2° Part #22451, 1W Part #22450)' 1 foot pound = 1.36 Nm 1 psi = 6.895 kpa = 0.0689 bar = 0.0703 kg/cm2 1 U.S. gallon = 3.785 dm3 ° LENT = 3.785 liters Conversions are approximate. �/ Central Sprinkler Company © 1994 Central S rinlder Company 451 North Cannon Avenue, Lansdale, PA 19446 P P y Phone (215) 362 -0700 Printed in U.S.A. FAX (215) 362 -5385 A97/A97H.0