October 25, 2005
CITY OF TIGARD
OREGON
Norlift of Oregon
Brian Ferrich
7373 SE Milwachie Exp
Portland, OR 97222
RE: RACK STORAGE @ CONTRACT FURNISHINGS
Project Information
Building Permit: BUP2005 -00565 Construction Type: 5 B
Tenant Name: Contract Furnishings Occupancy Type: S1
Address: 14160 SW 72 Place #110 Occupant Load: NA
Sprinklers: YES Hazard: Ordinary Group
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
2004 edition; and 2004 Oregon ire Code (OFC) as amended by TVF &R. The submitted
plans are approved subject to the •llowing conditions.
1. Specia • - • ection is req ' - , ' o , al lorage of storage rac - • - . or greater in
height (per 1 i OSS 1 . • ecial inspecti�y. . - cy of record shall furnish
inspection reports to : -. � er of R - • : , , :.. - : al Contractor, and the City of
Tigard, Building % ivis . • "' i;; . i . a W , 'ns. • discrepancies shall be brought to
the immediat . tt - . ion .4 • - gen.. a 1 1: „ , ection. The special inspector shall • submit a fin. ■. -,; • - •ort statin• • ' - t t iring special inspection was, to
the best of th - • - 's knowled:: 1 , ,, • with . • roved plans and
speci 'ons and the applicable workmanship • • sions of the col e. 1704 OSSC
2. Sprinkler System Analysis: A sprinkler system analysis shall be submitted to the City of
Tigard, Building Division prior to the request for final inspection. The analysis shall
provide hydraulic calculations verifying that the existing sprinkler system has the required
flow for the commodity being stored.
3. Provide 2 -A rated fire extinguisher as required per table 906.3 (1) of OFC the extinguisher
shall be located so that no usable space has a distance greater than 75 feet to the
extinguishers. OFC 906.3
4. The clearance between the deflector and the top of storage shall be 18 in. or greater.
NFPA 13 8.5.6.1
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
5. Flue spaces shall be provided and maintained in accordance with OFC table 2308.3.
6. The racks shall display in one or more conspicuous locations a permanent plaque not less
than 50 square inches in area, showing the maximum permissible unit load in clear
legible print. OSSC 1603
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respect y
al Henzel,
Senior Plans Examiner