Correspondence 6t)(7 2C:1,8:101" fr5"-- October 25, 2005 CITY OF TIGARD OREGON Norlift of Oregon Brian Ferrich 7373 SE Milwachie Exp Portland, OR 97222 RE: RACK STORAGE @ CONTRACT FURNISHINGS Project Information Building Permit: BUP2005 -00565 Construction Type: 5 B Tenant Name: Contract Furnishings Occupancy Type: S1 Address: 14160 SW 72 Place #110 Occupant Load: NA Sprinklers: YES Hazard: Ordinary Group The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and 2004 Oregon ire Code (OFC) as amended by TVF &R. The submitted plans are approved subject to the •llowing conditions. 1. Specia • - • ection is req ' - , ' o , al lorage of storage rac - • - . or greater in height (per 1 i OSS 1 . • ecial inspecti�y. . - cy of record shall furnish inspection reports to : -. � er of R - • : , , :.. - : al Contractor, and the City of Tigard, Building % ivis . • "' i;; . i . a W , 'ns. • discrepancies shall be brought to the immediat . tt - . ion .4 • - gen.. a 1 1: „ , ection. The special inspector shall • submit a fin. ■. -,; • - •ort statin• • ' - t t iring special inspection was, to the best of th - • - 's knowled:: 1 , ,, • with . • roved plans and speci 'ons and the applicable workmanship • • sions of the col e. 1704 OSSC 2. Sprinkler System Analysis: A sprinkler system analysis shall be submitted to the City of Tigard, Building Division prior to the request for final inspection. The analysis shall provide hydraulic calculations verifying that the existing sprinkler system has the required flow for the commodity being stored. 3. Provide 2 -A rated fire extinguisher as required per table 906.3 (1) of OFC the extinguisher shall be located so that no usable space has a distance greater than 75 feet to the extinguishers. OFC 906.3 4. The clearance between the deflector and the top of storage shall be 18 in. or greater. NFPA 13 8.5.6.1 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 5. Flue spaces shall be provided and maintained in accordance with OFC table 2308.3. 6. The racks shall display in one or more conspicuous locations a permanent plaque not less than 50 square inches in area, showing the maximum permissible unit load in clear legible print. OSSC 1603 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respect y al Henzel, Senior Plans Examiner