Correspondence 0 p 2u 6 c cl 7%1
/Grtnil:Illp;,ilJ� , ;
September 30, 2005 '=
CITY OF TIGARD
•
OREGON
Iselin Architects, P C
Todd Iselin
• 1307 Seventh St.
Oregon City, OR 97045 - -
RE: CONTRACT FURNISHINGS MART - TENANT IMPROVEMENT - REVIEW
Project Information
Building Permit: BUP2005-00474 Occupancy Type: B, S1
Tenant Name: Contract Furnishing Mart Construction Type: _ 5- B- Sprinklered
Address: 14160 SW 72 Bldg E #110 Occupant Load: 169
Area: 30,999 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF&R. The submitted plans are
approved subject to the following conditions.
1. Exits and exit access doors shall be marked by an approved exit sign readily visible from any
direction of egress travel. Access to exits shall be marked by readily visible exit signs in
cases where the exit or the path of egress travel is not immediately visible to the occupants.
2. Where not all means of egress are accessible, directional signs shall be provided at
non- accessible exits to indicate the route to the nearest accessible exit or area of rescue •
assistance. 1107.5 OSSC
3. All exit doors shall be openable from the inside without the use of a key or any special
knowledge or effort. 1008.1.8 OSSC
4. Exit signs shall be illuminated at all times and shall be provided with a second source of
power that will provide 1 '/z hours of illumination in case of primary power loss. 1006.3
OSSC FYI Additional exit signs may be required by the city field inspector to clearly
indicate the path of egress.
5. Safety glazing including but not limited to: the following locations: Each unit of
glazing shall be permanently identified by the manufacturer. Sec. 2406. Some of these
locations are as follows:
a. Glazing in ingress and means of egress doors.
b. Glazing in storm doors.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
c. Glazing in an individual fixed or operable panel adjacent to a door where the nearest
vertical edge is within a 24" arc of the door in a closed position and whose bottom
edge is less than 60" above the floor or walking surface except when there is an
intervening wall or other permanent barrier between the door and the glazing.
6. American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC, which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of conduction. 106.3.1 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the Building
Official has issued a certificate of occupancy 110.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings
in such a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
. Res Z i r e P
Val Henze
Senior Plans Examiner