Correspondence CkCg6 - 0/e7 ittk April 11, 1996 CITY OF TIGARD OREGON Oregreen Electric Construction Co., Inc. Attn: Bill Charles 10260 SW Nimbus Avenue, Suite M -12 Tigard, OR 97223 Project: TECH POULSON COMPANY 14140 SW 72nd Avenue, Suite 100 Tigard, Oregon Subject: ELECTRICAL PLAN REVIEW The plans submitted were reviewed for conformity with the 1993 National Electrical Code (NEC) and the State of Oregon Electrical Specialty Code. The following was noted: 1. The 1993 NEC is the minimum electrical requirement. 2. The rebar (UFER) shall be used as the grounding electrode for both the main service disconnect and the separately derived service connect. 3. The service equipment will be rated according to the available fault current (PGE 2/20/96). 4. There will be signs to warn of second service or additional source of current. Please contact Michael Rudd at 503 - 639 -4171, ext. 356, to discuss the electrical notes. Thank you for your cooperation, 7/1-e-leaj Michael Rudd Electrical Inspector e1c96- 0187 \oregreen.doc 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 CITY OF TIGARD BUILDING INSPECTION NOTICE Inspection Line: 639 -4175 Business Phone: 639 -4171 Footing Rain Drain Cover /Service FINAL: Foundation Water Line Ceiling - Plumb. Post/Beam Mech. Shear /Sheath Framing -Mech. PIbg.Und /FIr /Slab Plbg. Top Out Insulation - Elect. Post/Beam Struct. Mech. Rough -in Gyp. Bd. -Bldg. San. Sewer Gas Line Appr /Sdwlk Reins. Other: Date: 1 '— /. " 'f A.M. , P.M. Entry: Address:1 4- 11 41Z) Sz '7 Tenant: /-e CA- Rc. c{ / -1 Ste: MST: BUP: Con /Own: re_ G rime � y Fray.A MEC: PLM: ELC: THE FOLLOWING CORRECTIONS ARE REQUIRED: ELR: J ` ,k, -- S -.2111.� ...P i1 - c,s, Mir �/f` / Inspector: /��/ I e– L j42 , ( R c id Date:, P7 // APPROVED _ DISAPPROVED /CALL FOR REINSP. 4110 CO