Loading...
Plans (715) 1 4a I wiwt elms w. I F rr r1 %a • SYSTEMS — GE1.. RAL ? %? 1. Exceptions (Section 1813) 0 No HVAC. The building plans do not call for an HVAC system. Skip to Item 12 below. Exceptions 0 Exception. The building or part of the building qualifies for an exception from the code HVAC See a discussion of requirements. The applicable code exception is: Section 1313, Exception . Portions of the qualifying exaep- building which qualify: dons on p. 4-14 Seep 4-14 fora 2. Simple or Complex Systems (Section 1313.2) discussion of simple 0 Simple System. The planned HVAC system qualifies as a Simple System. If true, complete this vs. comPlex form (4a) and equipment effidency worksheets as required. Form 4b is not required. Complex System. The planned HVAC system is a Complex System. Complete this form (4a), Form 4b and equipment effidency worksheets as required. Exceptions 3. Economiser Cooling (Section 1313.1.2) x Systems 0 No Cooling. The building plans do not call for a new fan system with mechanical cooling. exceptions maY the same Complies. The new fan system has an air economizer capable of modulating outside air and a5o"ed for Simple Systems, return dampers to provide up to 85 percent of the design supply air as outdoor air. dons s three exceP 0 Exception - Simple Systems. The new fan system qualifies for an exception. The applicable Section 1313.12 code exception is: Section 1313.1.2, Exception , or Section 1313.2.1. Portions of the Seep. 4-15 fora building which qualify: discussion of these ❑ Exception - Complex Systems. The new fan system qualifies for an exception. The applicable exceptions. code exception is: Section 1313.1.2, Exception , or 1313.3.1, Exception _ Portions of the building which qualify: 4. Economiser Cooling - Overpressnrizing (Section 1313.1.2) 0 No Economizer. The building plans do not call for a new fan system with an economizer. Complies. The drawings specifically identify a pressure relief mechanism for each fan system that will exhaust the extra air introduced by the economizer, and the economizer system is capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the load. 5. System and Zone Controls (Sec. 1313.1.3.1 & 1313.1.3.2) ad Complies. All new HVAC systems include at least one temperature control device responding to tempreatures within the zone. 4: 0 Exception. The new HVAC system qualifies for an exception from the zone control require - Exceptions ments. The applicable code exception is: Section 1313.1.3.2, Exception 1 and 2. Portions of the - See a discussion of building which qualify: qualifying excep- dons on p. 4-16. 6. Control Capabilities (Sec. 1313.1.3.2.1) J8i Complies. Zone thermostats are capable of being set to the temperatures described in Sec. 1313.1.3.2.1. Where used to control both heating and cooling, zone controls shall be capable of providing a temperature range or dead band of at least 5 degrees F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. Exceptions 0 Exception. The building qualifies for an exception to the dead band requirements. The appli- See a discussion of cable code exception is: Section1313.1.3.2.1, Exception qu- lifYNg exoep- lions on p. 4 -16. (119 Forms & Worksheets 4-1 fpm 4a (cont.) • •v w v. ...n••.v. SYSTEMS - GENb1tAL P ..' 7. Off -hour Controls - HVAC Systems (Section 1313.1.3.8) Rfl Compiles. All new HVAC systems are capable of automatic setback or shutdown during periods of non -use or alternate use of the space served by the system. ❑ Exception. Equipment has full load heating demands of 2 kW (6,826 Btu/hr) or less and is controlled by a readily accessible manual off -hour control. 8. Off - hour Controls – Supply and Exhaust Systems (1318.1.3.3) gl Complies. Plans require that outdoor air supply and exhaust systems have a means of auto- matic (either motorized or gravity damnper) volume shutoff or reduction during periods of non- use or alternate use of the space served by the system. ❑ Exception. The building qualifies for an exception to the requirement for automatic shutoff or reduction. The applicable code exception is Section 1313.1.3.1, Exception • 9. Heat Pump Controls (Section 1313.1.3.4) fill No Heat Pump. The plans/specs do not call for a new heat pump. ❑ Complies. All new heat pumps equipped with supplementary heaters are controlled as required in Section 1313.1.3.4. 10. Equipment Performance (Section 1313.1.4) ❑ No New HVAC Equipment. The building plans do not call for new electrical HVAC equipment, combustion heating equipment or heat - operated cooling equipment. IN Complies. All new HVAC equipment has efficiencies not less than those required by the code. The following equipment efficiency worksheets are attached yo. 11. Duct Insulation (Section 1313.2.2 & 1313.3.2) ❑ No Ducts. The building plans/specs do not call for new HVAC ducts or plenums. ❑ Simple System: Complies. The plans/specs call for a Simple System, and all exterior supply/ retum air - handling ducts and plenums and all outside air ducts are insulated as required by Sec. 1313.2.2. JS Complex System: Complies. The building plans/specs call for a Complex System, and all air - handling ducts and plenums are insulated as required by Sec. 1313.3.2. 12. Piping Insulation (Section 1314) Exceptions ❑ No New Piping. The building plans/specs do not call for new piping serving a heating or cooling system or part of a circulating service water heating system. See a discussion of Q ( uas "COP" T I Complies. All new piping serving a heating or cooling system or part of a circulating service eons on n p. 4-17. water heating system complies with the requirements of the Code, Section 1314.1. ❑ Exception. New piping qualifies for the following exception: Section 1314, Exception — . 13. Service Water Heating (Section 1315) ❑ No New Water Heating. The building plans/specs do not call for new water heaters, hot water storage tanks, service hot water distribution systems, swimming pools or spas. Exceptions 2 Complies. All new water heaters, hot water storage tanks, service hot water distribution sys- See a discussion of tams, swimming pools or spas comply with the requirements of the Code. queuf)Ug exceP- ❑ Exception. The applicable code exception is, Section , Exception . Portions lions on P• 4-18. of the building which qualify: 42 Systems (1/96) /or sneei .Hs. . w wv% I vas a w. 1 K8etN c,c.G . "a" INITARY AIR COalITIONER - AIR I.n r DLED %gnipment (a) (b) ( (d) (e) es p. 4-19 era Proposed iscusslon of Performance ,tet ratings Cooling Seasonal Compliance ndequipntent Capacity Steady or Part Schedule Wirt/dons. Equip. ID Model Designation (Btu/h) State Load (A-E) A.0 -1 ws 1 N\ (45;090 aft EEL Q•S liti C 4C-2- IDS T'or.l /u,600 AS eia. a g ipti rr. AC- 3 10s Tats! ; i38, um S egg qs/ru G FCr 1 Two 34. Bore) /.: s - , • C -1 - r -r1 3r000 �o,zs EZ $ 1. Does the proposed equipment meet the required equipment efficiency? 1� Enter 'Y' if yes. l 2. Check boxes to indicate the source of information: 0 ARI Unitary Directory, Section AC (Enter the page number) 0 ARI Applied Products Directory, Section ULE (Enter the page number; til Product data (Attach data furnished by the equipment supplier) Cooling Capacity (Btu/h) Minimum Rating ante - But not Steady Seasonal or ance y Schedule Equipment Type Over over - State Part Load Single Package 0 65,000 na 9.7 SEER A Without a 65,000 135,000 8.9 EER 8.3 IPLV Heating Section 135,000 760,000 8.5 EER 7.5 ILPV 760,000 - 8.2 EER 7.5 IPLV Split System 0 65,000 na 10.0 SEER B Without a 65,000 135,000 8.9 EER 8.3 IPLV Heating Section 135,000 760,000 8.5 EER 7.5 IPLV 760,000 - 8.2 EER 7.3 IPLV Single Package 0 65,000 na 9.7 SEER C With a 65,000 135,000 8.9 EER 8.3 IPLV Heating Section 135,000 760,000 8.3 EER 7.3 IPLV 760,000 - 8.0 EER 7.3 IPLV Split System 0 65,000 na 10.0 SEER D With a 65,000 135,000 8.9 EER 8.3 IPLV Heating Section 135,000 760,000 8.3 EER 7.3 IPLV 760,000 - 8.0 EER , 7.3 IPLV E Condensing Unit Only 135,000 - 9.9 EER 11.0 IPLV 4-4 Systems • (1 196) • • • Forth 4b ! Project Name: "r M opiticE Page: COMPLEX HVAC SYSTEMS pa>z.14.1ec 1. Simple or Complex System (Sections 1318.2 as 1313.8) Note: This form is required for complex systems only. if your plans qualify as a simple system as defined by the code, you can skip this form. 2. Simultaneous Heating and Cooling (Section 1313.3.3.1) ❑ No Cooling. The building plans/specs call for a heating -only system. J3 Complies. Temperature and humidity controls are capable of operating in sequence the supply of cooling and heating energy to the zone as required by the code. Controls for this purpose are Exceptions detailed in the plans/specs on: J p F � / A c o T i v C / q - c. ❑ Exception. The building or part of the building qualifies for an exception from the code. The See a discussion of applicable code exception is Section 1313.3.3.1, Exception: . Portions of the building quallfYing DeP' which qualify: dons on p. 4-20. 3. Humidity Controls (Section 1313.3.3.2) SI No Moisture Added to Building. The building plans do not call for a means to add moisture to maintain specific humidity levels. ❑ Complies. All new humidity control systems are equipped with a humidistat as required by code. Air Transport 4. Air Transport Energy (Section 1313.3.4.2 as Table 13 -N) Energy ❑ Compiles. The energy demand of all HVAC fan systems meets code requirements. Complete sea Table 13.11, p. the form below. See Table 13 -N, reproduced at end of chapter, for max. allowed horsepower. 4-24, for maximum (a) (b) (c) (d) (e) (f) (g) • (colum n O. allowed horsepower Fan VAV or Design Motor Max. m System Description Constant Airflow HP Allowed Where noted in ID Volume? (CFM) HP plans /specs J Exception. The applicable code exception is Section 1313.3.4.2, Exception: Z, . Portions of the building which qualify: 6. Motor Efficiency (Section 1313.3.6 as Table 13 -0) Ja Not Regulated. There are no NEMA Design A & B squirrel cage, T frame induction, perma- nently -wired polyphase motors of one horsepower or more which serve built -up HVAC systems (regulated motors). Exceptions ❑ Complies. The efficiency of all regulated motors meets code requirements. See a discussion of ❑ Exception. The applicable code exception is Section 1313.3.4.2, Exception: . Portions of the qualifying excep- building which qualify: tons on p. 4 -22. 6. Variable Speed Drives (Section 1313.3.6.1) ❑ Not Regulated. The building plans/specs do not call for fan and pump motors 25 horsepower and greater which serve variable -flow air or liquid systems. / CI Compiles. All fan and pump motors 25 hp and greater which serve variable - flow air or liquid • systems are controlled by a variable speed drive. (yam Forme & Worksheets 4 Worksheet 4j Project Name: Page: FURNACES 8s UNIT HEATERS — GAS 8s OIL -FIRED Equipment ( (b) (c) (d) (e) Proposed Equip. ID Model Designation Heating Compliance Capacity E (Max.) Et (Min.) AFUE Schedule (Btu/h) (A — E) AC— I • /O %6 / Rz 82% 8 Z'�� — ittiC -1 /DS" / r✓ 8t co $Z% 02% — 4 14C y' /Os r/ S� app o z% �; z'/ — A Compli- Minimum Performance ance Equipment Type Over But not Steady Steady State Part Load Schedule over State Max. Min. Rating (AFUE) Rating (Et) (Et) A Gas -Fired Warm -Air 0 225,000 na na 78% Furnaces & Combination 225,000 — 80% 78% na Furnace /AC B Oil-Fired Warm -Air 0 225,000 na na 78% Furnaces & Combination 225,000 — 81% 81% na Furnace /AC C Gas -Fired Duct Furnaces 0 — 78% 75% na D Gas -Fired Unit Heaters 0 — 78% 74% na E Oil-Fired Unit Heaters 0 — 81% 81% na (1/96) Forms & Worksheets 4 -13