Loading...
Specifications (9) -coo.rl RECEIVED SEP 302010 �, C'arrce °r CITY OFTIGARD t > a BUILDING DIVISION SUBMITTAL Project Triangle Point Shell Larry Goodroe Table Of Contents Project: Triangle Point Shell 09/09/2 010 Prepared By: 0411PM VAV-2-1 5 Unit ''---� 6 Certified Drawing ---' 7 Performance Summary -'-'-�---�' -�-� --- 8 Acoustic Summary — 9 VAV-2-2 -- 10 Unit Report ............. ----- — --- . 11 Certified Drawing ' 12 Performance Summary 13 Acoustic Summary 14 VAV-2-3 ''- ----' ....................... --....... 15 Unit Report 16 Certified Drawing 17 Performance Summary 18 Acoustic Summary 19 VAV-2-4 20 Unit Report 21 Certified Drawing 22 Performance Summary 23 Acoustic Summary 24 VAV-2-5 25 Unit Report 26 Certified Drawing 27 Performance Summary - 28 Acoustic Summary 29 VAV-2-6 --- --� 30 Unit Report 31 Certified Drawing 32 Performance Summary. ' ' - ' - - '----- - ' ' '-- - ' - --�' ' - 33 Acoustic Summary 34 VAV'2-8 35 Unit Report 36 Certified Drawing - ' - �---' 37 Performance Summary _ � - '----' - �'--'--- - � - 38 Acoustic Summary .......... — 39 VAV-2-9 40 Unit Report 41 Certified Drawing - 42 Performance Summary 43 Acoustic Summary 44 VAV-2-10 45 Unit Report - 48 Certified Drawing 47 Performance Summary '' 48 Acoustic Summary 49 VAV-241 50 Unit Report 51 Certified Drawing 52 Performance Summary ----'- -.53 Acoustic Summary --� 54 VAV-2-12 55 Unit Report -----' 56 Certified Drawi — 57 Performance Summary --' 58 Acoustic Summary 59 VAV'2' 3 60 Unit Report ' - 61 Certified Drawing --' 62 Performance Summary 63 Acoustic Summary -- - ---� - � - ''-- 64 VAV ---' --� 65 Air Terminals Builder 1.09e Page 2 of 169 Table Of Contents Project: Triangle Point Shell 0809/2010 Prepared By: 0411PK4 Unit Report 66 Certified Drawing 67 Performance Summary ' -- - � - �' ' --------- - ' ---' Acoustic Summary - - Og VAV '�'' - �' - -� '--' ---�-----� — ' — ���0 Unit Report 71 Certified Drawing 72 Performance Summary 73 Acoustic Summary 74 VAV 75 Unit Report 76 Certified Drawing -''--''' ---- - ' ' - -- 77 Performance Summary 78 Acoustic Summary 79 VAV '' 80 Unit 81 Certified Drawing 82 Performance Summary 83 Acoustic Summary ' 84 VAV 85 Unit Report ----'86 Certified Drawing -'--- - 87 Performance Summary 88 Acoustic Summary -' -'' 89 VAV _ _ . 90 Unit Report 91 Certified D 92 Performance Summary 93 Acoustic Summary S4 VAV _ — _--- 95 Unit Report 96 Certified Drawing 97 Performance Summary ----'gO Acoustic Summary 99 VAV 100 Unit Report 101 Certified Drawing 102 Performance Summary 103 Acoustic Summary 104 VAV '----. - 105 Unit Report 108 Certified Drawing 107 Performance Summary 108 Acoustic Summary 109 VAV 110 Unit Report 111 Certified Drawing 112 Performance Summary - 113 Acoustic Summary 114 VAV 115 Unit Report 116 Certified Drawing 117 Performance Summary 118 Acoustic Summary -- --- -11S VAV 120 Unit Report ' 121 Certified Drawing 122 Performance Summary -- ----- 123 Acoustic Summary _'- ' '-' 124 VAV 125 UnitRoport --- -- 126 Certified Drawing 127 Air Terminals Builder 1.09e Page 3 of 169 Table Of Contents Project: Triangle Point Shell 0909D010 Prepared By: 0411PK8 Performance Summary 128 Acoustic Summary 129 VAV ---. ... '---.......... 130 Unit Report 131 Certified Drawing 132 Performance Summary ' 133 Acoustic Summary 134 VAV - '' - � - � --- -- 135 Unit Report '-� ' 136 Certified Drawing 137 Performance Summary 138 Acoustic Summary 139 VAV 140 UnitRaport - -' 141 Certified Drawing -' ' 142 Performance Summary -' 143 Acoustic Summary 144 VAV 145 Unit Report 146 Certified Drawing -� 147 Performance Summary 148 Acoustic Summary 149 VAV 6 - ' -- '---------��� Unit 151 Certified Drawing 152 Performance Summary _ 153 Acoustic Summary — 154 VAV 155 Unit Report - --_ 156 Certified Drawing - 157 Performance Summary - 158 Acoustic Summary 159 VAV - - 160 Unit Report -- --��'-- — 161 Certified Drawing ' 162 Performance Summary ' 163 Acoustic Summary 164 VAV 165 Unit Report 166 Certified Drawing 167 Performance Summary '- 168 Acoustic Summary ' 169 Air Terminals Builder 1.09e Page 4 of 169 VAV -2 -1 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -1 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 5 of 169 Unit Report For VAV-2-1 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM ‘1111 $ '1ZT Ihv 1 Unit Parameters Tag Name* VAV Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type* 4190: VAV with DCV Unit and Inlet Size: 6 Inch Part Number 35NC1C000L0606419000000S0000400020002000052 Insulation Lining: Standard (1/2 inch dual density f/g liner) Outlet* 6.9x6.9 Dimensions Unit Depth 35.9 in Unit Width 32.2 in Unit Height 8.9 in Unit Operating Weight • 31 lb *** Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L060641900000 35N Dual Duct Terminals 1 060000400020002000052 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 6 of 169 Certified Drawing for VAV -2 -1 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM C CE ,ra ccaxes 00EPKIFOITV a 903135 v 1KSa DIALDU 1VARIABLE Carrier GR♦e1CCFFCMRN Q"' MDisCHE ED ` T 1T .ANK 0,-- c DE epAFS9 Dcib1 IN COES POT fAbTNE CFCCNSINIMCIINE CATxocu A united Technologies Company ,°NEa HavaeR 1 f CF CR EILENWCHIONEER 35NBASEUNrr- wrFurnw1Nrfta Cf s CHARM:TAMEN:SON NCLiD6NETADAPTER ALLOA141LEA.Sr 24161 FaranNas CO L Er1)F S l■—" H d. li_ i ORS i I i I � is ' c a N4 ___ E 1 I W / F N.Er 4 0 {. /41 D I Li 1 iiil —1- Ili 61152)TYP 1E !? -- HANGERBRACKER4FLCS) SEECP1ENALFEATLRESEELCW INLET VIEW TOP VIEW DISCHARGE VIEW SENSOR- Lheamliplepoilaitomarsoris CASING- s ardcnah.nts sbalatarnsaErnetatakemiEdartgadekado LINER- 12' (Arad P$ trd Y 1yyi > ry5 (1.491 (Pa)Ps.} bs 11(24I gt 3 ).Thistrirgisccetedtopmentarcim, . Op6mat 23ga gasaarizedsleelmaig. 181ar1d■FPAa4 . Ogg Blanscomspsnel • ca 1125rrrn DAMPERS- be hstessnkicharerAiecIpoStityenloangasketa . Opttnt Steireinstiansysiam1316ticktgl liiekgetrouptetrtpsrdEsetenTActurivi isr/akin ,edgessealed CFMarelA9Pa • UNITACCESSOMES- et Notertisdatasystrnwercitrred . Ogashargetradet . Cp6ortat 12 Ogcnst tbiarrapalalecfnstiitn NOTE 1. Sensors ares (nwnin inlet and discharge, butare • available in both inlets. 2 Pneumaticeontrols shown, electronic areavailable. 3 Dimensions are shown as inches (mm). MET - NONMMX OISCHARCE SIM CFM(L!s) L W H A D E F G 4 255(106) 321i8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 9906(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 8 450(212) 321/8(816) 21518(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 36518(931) 275/8(702) 107/8(276) 33/8(86) 67/8(175) 159 97/8(251) 91/4(235) 8 800(377) 365 275/8(702) 107/8(276) 3318(86) 77/8(200) 159 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 335 /8(855) 127/8(352) 33/8(86) 87/8(225) 199116(497) 127/8(327) 113/4(298) 10 1350(637) 4458(1134) 335/8(855) 127/8(352) 33/8(86) 97/8(251) 199116(497) 127/8(327) 113/4(298) 12 2100(991) 505/8(1287) 39518(1007) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 06(1183) 181/8(460) 338(86) 137/8(352) 261/2(673) 167/8(429) 169 18 4030(1 S87) 649116(1640) 469 /16(1183) _ 181/8(480) 33/8(86) 1578(400) 2612(673) _ 167/8(429) _ 169 PRODUCTINFORM4110NISSUBJECTTOCHANGEWT (HOUTNOTICE 1/16/2()02 OWNE .030/4021 I.CCATON CRNVGw4®1 LUKE WK. ' B 1 OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 7 of 169 Performance Summary For ~1 Project: Triangle Point Shell 0909/2010 Prepared By: 0411PM Unit Parameters Tag Name VAV-2-1 1 Model Type: ...... ..... '-........ - VAV - CCN Model -'--- -- ' 35N Dual Duct Terminals Control Type - 4190: VAV with DCV CoId Inlet Size: - 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L060641900000080000400020002000052 Outlet: - ' - ------ 6.9x6.9 Unit Performance Altitude' 0 ft CoId Max. Airflow 400.0 CFM Cold Min. Airflow 200.0 CFM Hot Max Airflow 200.0 CFM Hot Min Airflow 52.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure .20 in wg Minimum Static Pressure Drop .44 in wg Note* Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual denmityf/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow CoId Inlet 400.0 CFM Safety Factor CoId Inlet 23 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet 200.0 CFM Safety Factor Hot Inlet 62 % Unit uwm/H 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 1OE watts • ' ~° Cold Max. Airflow 400.0 CFM Hot Max Airflow 200.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (PwI) 61 57 47 42 40 35 ^ Total Attenuation 17 18 20 23 25 26 ^ Room Sound Level (SpI) 44 39 27 19 15 <1O 27 Discharge Sound Primary Sound (PwI) 65 63 57 50 44 37 ^ Total Attenuation 29 30 41 53 55 41 ~ Room Sound Level (SpI) 36 33 16 <1O <1U <1O 20 Notes: 1. Room sound Ievels shown Include attenuatlon transferfunctlons shown above. 2. Data were obtalned from tests conducted In accordance wlth ARI Standard 880-90. 3. Sound power levels are in decibels, 10A-12 watts. *. Dash (-)m space indlcates sound andlorNC value is Iess than 10. ^^ Sound calculatlons are based on Iargest Iniet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporaton accepts no Iiability for the adequacy of any resulting design or installation. All data subject tou`unoowimv"tnot/co. Air Terminals Builder 1.09e Page 8 of 169 Acoustics Summary For VAV -2 -1 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -1 Quantity: 1 Model Type: ......... ... . ........ .... VAV - CCN Model 35N Dual Duct Terminals Control Type: ... 4190: VAV with DCV Cold Inlet Size:.. 6 Inch Hot Inlet Size 6 Inch Part Number: .. 35NC1C000L0606419000000S0000400020002000052 Outlet 6.9x6.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow Cold Inlet 400.0 CFM Safety Factor Cold Inlet 23 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet:.........__......._ .... 200.0 CFM Safety Factor Hot Inlet 62 % Unit LxVVxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 400.0 CFM Hot Max Airflow: .... _._ .. . 200.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 61 57 47 42 40 35 * Total Attenuation 17 18 20 .. _. 23 25 26 Room Sound Level (Spl) 44 39 27 19 15 < 10 27 Discharge Sound Primary Sound (Pwl) 65 63 57 50 44 37 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 36 33 16 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from testa conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) in space Indicates sound and /or NC value is less than 10. ** Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 9 of 169 VAV -2 -2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -2 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 10 of 169 Unit Report For VAV -2 -2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM 1 164W . • Unit Parameters Tag Name ..... " _ VAV -2 -2 Quantity' 1 • Model Type:.. VAV - CCN Model' 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Unit and Inlet Size' 10 Inch Part Number 35NC1C000L1010419000000S0001448070007000145 Insulation Lining' Standard (1/2 inch dual density fig liner) Outlet .. 9.9x9.9 Dimensions Unit Depth' 48.6 in Unit Width: ............... in Unit Height' 13.9 in Unit Operating Weight : 61 lb •'• Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L101041900000 35N Dual Duct Terminals 1 OS0001448070007000145 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 11 of 169 Certified Drawing for VAV -2 -2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM COM 0 ma do¢Aea arKpR ie y a< ae SIC.1 of 1ESE DUALDUCMA IABLE Carrier CVRlFACCFiOMR)1MDIS CELNEPEO SPNAINGS '`� °'o`mIS uv. 11E EXPRESS COMM ..s C ES for MOW! Q�6D�NRQLNE CAThLOC# A United Technologies Company C++� cR ,C EPT C 113meallIV1ITH Lea %mar oawoaroaear�um�n oamrcT O.13 YmzER 35NBASEUNIT W1H:3 CHARTEDWOMNSDN 4 FaLDFSNSZAD4PIER AL LOAA1LEAST 241610)CLEARAME O S L 1 BOTHS I ES H Idi 1 ii�i i IOAS !P- c a NET ■ 411 ° -› I E ' W F ''il ° ';'• II _ II I ( u oz 61,52) yp 11': mi f I-ANGERBRACKETAPLCS SEECPTIONALFEA1LIRESSELON INLET •VIEW TOP VIEW • DISCHARGE VIEW • SENSOR- Limannutplecoitirfcwsensais CASING - stadaidortaAr LINER- 12' (13mO P tick dua ctssatyi ort hi abodydtrs101 b .. (1.494Da)Pal be/014241On 3 ).ThiskirgiscoaIadtopmerteroEicn, . Cricnat 20ga. ga`variaadsb3elcasiv. artreetteagierrErtdJL181ariTPAglk g g COrrat Tern DAMPERS - . Cplortat Stetinertelalionsystam13/15tidaicjd /octiorrital i alarm a gesss a)ed CFMal6'(1.49Pa)Ps ifs. UNITACCESSORIES- at Noi aitntfutsyslerT> etnoiletrI . Cpbanaltart3abradaats. P . Cgcnst 12'biatapslateirala6on . Cp:crat l'Icie rapstabdra/a6orL NOTE 1. Sensorsareshown in inlet and discharge, but are available in both inlets. 2 Pneumaticcantrols shown, elearonicare available. 3 Dimensions are shown asitches(mm). INLET NCMNMAX DISCHARGE SI E CFMNs) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(203) 71/4(184) 6 350(165) 321/8(816) 21 5/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 27518(702) 107/8(276) 33(8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 10'0(495) 445/8(1134) 335/8(855) 127/8(352) 33 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 445/8(1134) 335/8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2100 (931) 505 395 /8(1007) 157/8(403) 33/8(86) 117/8(302) 239116(598) 147/8(387) 141/4(362) 14 3203 (1510) 589/16(1488) 469 /16(1183) 181/8(460) 33/8(86) 137/8(352) 2612(673) 167/8(429) 169/16(420) 18 4000(1887) 649 /16(1640) _ 469/16(1183) 181/8(460) 33/8(86) 157/8(403) 261/2(673) 167/8(429) 169/16(420) PRODUCTINFORMAT10NISSUBJECTTOCF4WGEWTTHOUrNOTICE 1/162002 .®wwE dHI■Hii CRAMS OUREe1 EWER ate. Rsvg. B 'E 1 OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 12 of 169 • Performance Summary For VAV-2-2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM Unit Parameters Tag Name VAV-2-2 Quantity .... 1 Model Type: VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Part Number.. ......... . ...... . . .35NC1C000L1010419000000S0001448070007000145 Outlet ..9.9x9.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,448.0 CFM Cold Min. Airflow 700.0 CFM Hot Max Airflow 700.0 CFM Hot Min Airflow 145.0 CFM Inlet Static Pressure: 1.00 in wg Downstream Static Pressure .... .20 in wg Minimum Static Pressure Drop* .94 in wg Note* Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining:.. Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet* 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,448.0 CFM Safety Factor Cold Inlet Maximum Airflow Hot Inlet: .......... . 1,448.0 CFM Design Airflow Hot Inlet .... . ..... . 700.0 CFM Safety Factor Hot Inlet 52 % Unit LxVVxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E-12 watts ** Cold Max. Airflow 1,448.0 CFM Hot Max Airflow* 700.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 64 60 55 51 49 44 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 47 42 35 28 24 18 31 Discharge Sound Primary Sound (Pwl) 62 62 59 56 51 45 • Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 33 32 18 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880-90. 3. Sound power levels are In decibels, re 10A-12 watts. 4. Dash (-) in space indicates sound and/or NC value Is less than 10. ** Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 13 of 169 Acoustics Summary For VAV -2 -2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name .. VAV -2 -2 Quantity .. _ . 1 Model Type VAV - CCN Model' 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001448070007000145 Outlet 9.9x9.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet:. 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,448.0 CFM Safety Factor Cold Inlet Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 700.0 CFM Safety Factor Hot Inlet 52 % Unit LxWxH:..... 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 1,448.0 CFM Hot Max Airflow 700.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 64 60 55 51 49 44 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 47 42 35 28 24 18 31 Discharge Sound Primary Sound (Pwl) 62 62 59 56 51 45 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 33 32 18 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) in space indicates sound and /or NC value is less than 10. ** Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 14 of 169 VAV -2 -3 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -3 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 15 of 169 Unit Report For .3 Project: Triangle Point Shell 0009/2010 Prepared By: 0411PM fe ~~ ' Unit Parameters Tag Name: VAV Quantity -- 1 Model Type VAV - CCN Moue/ 35N DuaI Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 12 Inch Part Number 35NC1C000L121241900000080001890090009000209 Insulation Lining: Standard (1/2 inch dual density fig liner) Outlet 11.9x11.$ Dimensions Unit Depth 51.9 in Unit Width 46.2 in Unit Haight 15.9 in Unit Operating Weight 80 |b ~~ Weights and Dimensions are approximate. Weight does not indude curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts OnIy Warranty Ordering Information Part Number Description Quantity Base Unit 35wC1C000L121241900000 35m Dual Duct Terminals 1 080001890090009000209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 16 of 169 Certified Drawing for VAV -2 -3 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM ' aarE TM =AMU mmn a sass(, oc MEM DJALD..CIVARAS.E i Carrier aJiiERZFRMECNNO 13 L81ED a""°" f at COMMITS lDW 11E SMLN �>Q, w PEES W ORIAME OlaU61ANR1011VE 35N CATALOG# A Unites Technologies Company at ar 5 r a TEMPIN. NN111H mrsvamaNmemaert EMMET EIDCNCOVNEER 35NBASEUN]T- wrFcprmetuvrAccEssows CHARTECA 6CN NIXLD6NLETADAPTER ALLOIMILEAST 24'(610)CL EARANCE 0 � FC�� OJIS L i gE H I E I W C F NLET , 11461 I c o iii Q. 5'(152)TYP E j 1J HA ERBRAaKETOPLCS) S FEATL CIN INLET VIEW TOP VIEW DISCHARGE VIEW SENSOR- LhearrraplecoilailloNsersoris CASING- sta ria darghris LINER- 12' (13mi P9$ • fridtdEIdadyialatgrt5thabodydenst1d1S (1.491(Pa)Psl . bsiculG4Vn ').itiskingiscoatecItoprewrterosion, . alt/ Z. 181adhFPP93k . q edlonsxmcoml. . Worst 1 "(25mn )hichalafaimeefrgspeofca- DAMPERS - 1QSabae . Cgrnat State is s m13r16Utidar d /oahonilal haita> edgers aced CF Mat6'(1.48Pa Ps UNITACCESSORIES- . cEt No6rair 6orti9ystmAt miles al . OpOonshargabrad paerfarckratm. . Cprmet 12 NOTE 1. Sensors are shown in inlet and discharge, but are available in both inlets. 2 PnernaticcaMrols shown, eleWVnicareavalable. 3 Dimensions are shown asilches(mm). NLET NOMMAX Of5CHl RGE St2E CFM(Us) L W H A D E F G 4 255(106) 321/8(816) 21 5/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(85) 57/8(149) 99/16(243) 77/8(203) 71/4(184) 7 650(307) 365/8(931) 275/8 (702) 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8(702) 107/8(276) 33/8(86) 77/8(203) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 33508(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 44518(1134) 335 /8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 11314(298) 12 2103 (991) 505/8(1287) 3958(1007) 1578(403) 33/8(86) 11 7/8(302) 239/16(598) 1478(387) 141/4(362) 14 3200(1510) 589/16(1488) 469 /16(1183) 181/8(450) 33/8(86) 1378(352) 261/2(673) , 167/8(429) 169 16 _4C00(1887) 649/16(1640) _ 469/16(1183) _ 1818(460) 338(86) 1578(403) 261/2(673) _ 167/8(429) 169/16(420) PRODUCTINFORMATIONISSUBJECTTOCHANG EWTHOUTNOTICE 1/162002 ZENME MINMM1 :COWEN aWVLWrMSc1 EWER dnER• 4EVMEN B '� 35N -202 -1 1 O 1 Air Terminals Builder 1.09e Page 17 of 169 Performance Summary For VAV-2-3 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM Unit Parameters Tag Name VAV-2-3 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type ..... ...... 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size 12 Inch Part Number . .. ...... . 35NC1C000L1212419000000S0001890090009000209 Outlet 11.9x11.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,890.0 CFM Cold Min. Airflow 900.0 CFM Hot Max Airflow: 900.0 CFM Hot Min Airflow 209.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure .20 in wg Minimum Static Pressure Drop:... .65 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,890.0 CFM Safety Factor Cold Inlet 9 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet: 900.0 CFM Safety Factor Hot Inlet' 57 ok Unit LxVVxH: . ................. . .51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E watts *" Cold Max. Airflow: 1,890.0 CFM Hot Max Airflow . . 200.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (PwI) 75 68 61 58 55 52 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 58 50 41 35 30 26 43 Discharge Sound Primary Sound (PwI) 66 61 60 56 50 43 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 37 31 19 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880-90. 3. Sound power levels are In decibels, re 10A•12 watts. 4. Dash (-) In space indicates sound and/or NC value Is less than 10. " Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 18 of 169 Acoustics Summary For VAV -2 -3 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -3 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type ....... ........ 4190: VAV with DCV Cold Inlet Size: .... ...... . 12 Inch Hot Inlet Size 12 Inch Part Number:.... 35NC1C000L1212419000000S0001890090009000209 Outlet ........ ....... ....... 11.9x11.9 Insulation: Other Information: Lining Standard (1/2 Inch dual density f/g liner) Maximum Airflow Cold Inlet: 2,085.0 CFM Attenuator: .......... No Design Airflow Cold Inlet 1,890.0 CFM Safety Factor Cold Inlet :.................... .............................. % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet 900.0 CFM Safety Factor Hot Inlet 57 % Unit LxWxH: 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 1,890.0 CFM Hot Max Airflow 900.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 75 68 61 58 55 52 Total Attenuation 17 18 20 23 25 26 * _ Room Sound Level (Spl) 58 50 41 35 30 26 43 Discharge Sound Primary Sound (Pwl) 66 61 60 56 50 43 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 37 31 19 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) in apace Indicates sound and /or NC value is less than 10. ** Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 19 of 169 VAV -2-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2-4 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 20 of 169 Unit Report For VAV-2-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM s•ie - .41 fit Unit Parameters Tag Name VAV-2-4 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals • Control Type 4190: VAV with DCV Unit and Inlet Size: . 8 Inch Part Number 35NC1C000L080841900000050000620031003100093 Insulation Lining: Standard (1/2 inch dual density f/g liner) Outlet 8.9x8.9 Dimensions Unit Depth 39.2 in Unit Width 36.2 in Unit Height 10.9 in Unit Operating Weight • 42 lb *** Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L080841900000 35N Dual Duct Terminals 1 0S0000620031003100093 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 21 of 169 Certified Drawing for VAV -2-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM °g ,, "'- nas amaert s 1MOiS ( v a< sa,Ssw a >e Qom. WPRIABLE 17 � °' �% ' Carrier CANER �EQNIC1MDI5HN dYMOGSCA�AB1IS S N1 tEYN 11E EXPRESS aCPGICN IV CCES 'Cr a?SRM1RE 1JYE CATALOGp nEmrte+ISUUat®nLEED Plat FERFCR CE A United Technologies Company OR USED wear CNRER CA IDCEPrMCE a lERIVINALINMITH � �p��� CFPCSNvanwrla�rt CCNIRCT BLENONCCHWEER q 5NBAsEuNr - Vin-CFMNALLNTACCESJl f s CHARTEDWCIVENSCN NCLUCE NL ETADAFTER ALL ONA1LEAST 241610)Ct.EARANCE FCFCONITCLS L 9711-6C H d 0 Ilia: I 1 ,111l1 % o I D Imts* E I W 1 I 0 . . NLET ►fai i I E o Ill kirfli 61152)TYP II -- 7 HANC { r{4PLCS) SEECIPTCNALFEATURESEELON INLET VIEW TOP VIEW . DISCHARGE VIEW SENSOR- CASING - stardardcnahrds. LINER- 12' (13Th) pews Eefilrg$Q°/ tidcctaldensOaktulwihaboVensljal15 . . (1.491dd)PS1 bskni 4l k i '1• i� d a. gaSanizedstelcashg. attreatenactierrertdUL181adNFPA934 . cd BlorreccesTEret . OrknEt 1 "(25mn DAMPERS - EathmknchsemEgastetlarrpEr . Word �m13/161tidagd /DaFrnirml i>stt35al edgessealed CFMaa6'(1.49Pa )Ps BPS UNITACCESSORIES NoinetialatowtmAtricilernEd k1 ' Oprrnahnerbadels PAL .d 12 . Opfionat 1' NOTE 1. Sensors are shown in inlet and discharge, but are available in both inlets. 2 Pnetmaticconttolsshavn , electronic areavailable. 3 Dimensions are shown asildies(mm). INLET NOMMAX 06Q41RGE SIZE CFM(L/s) L W H A D E F G 4 255(106) 321/8(816) 2158(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 3658(931) 275/8(702) 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8(702) 107/8(276) 338(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 4458(1134) 335/8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 4458(1134) 335/8(855) 127/8(352) 338(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2103(991) 50 518(1287) 3958(1007) 157/8(403) 338(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 /16(1183) 181/8(460) 338(86) 137/8(352) 261/2(673) 167/8(429) 169/16(420) 16 4000(1887) 649 /16(1640) 469/16(1183) 181/8(460) , 3316(86) 157/8(403) 261/2(673) 167/8(429) 169/16(420) PRODUCT64FORMATICNI SSUBJECTTOCHANGEWTH0UTNO110E • 1/162002 .08803E .®NMffJi {(YAId1 CRvoarst AEER SOS. Rte. B '.` 1 OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 22 of 169 Performance Summary For VAV-2-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM Unit Parameters Tag Name VAV-2-4 Quantity 1 Model Type VAV - CCN Model:.. 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size: 8 Inch Hot Inlet Size 8 Inch Part Number 35NC1C000L0808419000000S0000620031003100093 Outlet 8.9x8.9 Unit Performance Altitude 0 ft Cold Max. Airflow' 620 0 CFM Cold Min. Airflow: 310.0 CFM Hot Max Airflow: 310.0 CFM Hot Min Airflow .23.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure: .20 in wg Minimum Static Pressure Drop .30 in wg Note* Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet: 927.0 CFM Attenuator No Design Airflow Cold Inlet: 620.0 CFM Safety Factor Cold Inlet. ... ok Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot Inlet 310.0 CFM Safety Factor Hot Inlet. 67 ok Unit LxVVxF1' . 39.2 x 36.2 x 10.9 Acoustic Summary: • Sound Power Levels, dB re 10E ** Cold Max. Airflow: . .... 620.0 CFM Hot Max Airflow* 310.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 67 63 55 52 51 51 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 50 45 35 29 26 25 34 Discharge Sound Primary Sound (Pwl) 67 63 58 52 45 38 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 38 33 17 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880-90. 3. Sound power levels are In decibels, re 10A-12 watts. 4. Dash (-) in space Indicates sound and/or NC value Is less than 10. "' Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 23 of 169 Acoustics Summary For VAV -2-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -24 Quantity 1 Model Type: VAV - CCN Model: 35N Dual Duct Terminals Control Type: ........ . .. . 4190: VAV with DCV Cold Inlet Size 8 Inch Hot Inlet Size 8 Inch Part Number 35NC1C000L0808419000000S0000620031003100093 Outlet .. 8.9x8.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 927.0 CFM Attenuator . No Design Airflow Cold Inlet 620.0 CFM Safety Factor Cold Inlet 33 % Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot Inlet: 310.0 CFM Safety Factor Hot Inlet 67 % UnitLxWxH .. 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow: 620.0 CFM Hot Max Airflow: 310.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 67 63 55 52 51 51 ` Total Attenuation 17 18 20 23 25 26 _ Room Sound Level (Spl) 50 45 35 29 26 25 34 Discharge Sound Primary Sound (Pwl) 67 63 58 52 45 38 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 38 33 17 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10 " -12 watts. 4. Dash ( -) in space indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 24 of 169 VAV -2 -5 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -5 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 25 of 169 Unit Report For VAV-2-5 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM - - " TO' Unit Parameters Tag Name VAV Quantity 1 Model Type: VAV - CCN Model 35N Dual Duct Terminals Control Type' ................. . 4190: VAV with DCV Unit and Inlet Size 8 Inch Part Number 35NC1C000L0808419000000S0000620031003100093 Insulation Lining' Standard (1/2 inch dual density f/g liner) Outlet* 8.9x8.9 Dimensions Unit Depth' 39.2 in Unit Width' 36.2 in Unit Height 10.9 in Unit Operating Weight • 42 lb *** Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L080841900000 35N Dual Duct Terminals 1 0S0000620031003100093 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 26 of 169 • Certified Drawing for VAV -2 -5 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM C M Da CCOA.e1r 61146RSORrf CF mammy cc vae C IAL°UC1VAfaABLE 0 Carrier � ' � "O'MOIS ). D °"""1GSOROR TS LP MECCNOMALLMNEELECLOSED PMT 1E ,a p?BRNE acmstemauvE 35N CAT L # A United Technologies Company o/+ iFt> AVg on oca6r6 16a4NALLN1 MTH owvatoawne+case/r mawcT BLEICKCHOMEER 35NBASEUNfr NATFCFr1CNNLLIMTPCCE59L 5 Q ART AUNBNW4 NaLCESPLETADAPTER ALLOAATLEAST 241810)CLFARANCE 0 FCFCCNTICLS L B3TF6 I BS � H Ate o i I i I -l] ' c N:ET ILLS. 1 1 E I w Imo/ F Nir IAl II iii 1 E o Yr 6 1 152 TrYP 117 OW ---- FANGERBRAO(EroPum) ON INLET VIEW TOP VIEW DISCHARGE VIEW . SENSOR- Livarrrafpleccintaillowsensais CASING - Sandardatalutls LINER- 12' (13mi P - olhafxdycliarstiorT 5 (1.491(Pa)Ps4 . 6skult(24n '). adreattoxpiemarisctil81artINFPA9X . OptrEt BcricrrIXCESSIBIel . Cpta12t 1'7511 rt DAMPERS - talsatne . Cp5mat SbaTrlerhaki nsysiml3/16Uidagd /ooFnnit2l halakrktit3cedcnaisbeatireide,eigessBalEd CFMalT(1.49Pa)PP UNITACCESSORIES- . Orford isiolnairialafaisisErnAtt Likuial add, pmeriantrEdat . Cp6slat 12 NOTE 1. Sensors are shzw ,in inlet and discharge, butare available in both inlets. 2 Pneunaticcattrols shown, etedronicare available. 3 Dimensiorts are shown asildres(mm). NET NOMMAX DISCHARGE SZE CFAA(Us) L W H A D E F G 4 255(106) 321/8(816) 21518(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(164) 5 350(165) , 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321)8(816) 21518(550) 87/8(225) 33/8(88) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 36518(931) 27518(702) 107/8(276) 33/8(86) 67/8(175) 159 97/8(251) 91/4(235) 8 800(377) 365 27518 (702) 107/8(276) 33/8(86) 77/8(203) 159/16(395) 97/8(251) 91/4(235) 9 1050(496) 445 3358(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(837) 445 33516(855) 127/8(352) 33/8(86) 9718(251) 199/16(497) 127/8(327) 113/4(298) 12 2100 (991) 50518(1287) 395 /8(1007) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 /16(1183) 181/8(460) 336(86) 137/8(352) 261/2(673) 167/8(429) 169/16(420) 18 4000 (1887) 649/16(1640) 469 /16(1183) 1818(460) 33/8(86) _ 1578(403) 261/2(673) 1678(429) 169/16(420) PRODUCT INFORMATIONIS SUBJECTTOCHANGEwTHOUrNOTICE 1/16200 aeNAVE .aarwea+ L+ri+v+ rnAwcn„ew ahER EL E • Fe V8.6 B 10F 1 35N -202 -1 Air Terminals Builder 1.09e Page 27 of 169 Performance Summary For ~5 Project: Triangle Point Shell 0909D010 Prepared By: 0411PM Unit Parameters Tag Name: -' VAV-2-5 Quantity 1 Model Type VAV'CCN Model - -- — ���� --'__—_- — 35N Dua Duct Terminals Control Typo 4190: VAV with DCV CoId Inlet Size: 8 Inch Hot Inlet Size ' --' 8 Inch Part Number 35NC1C000L0808419000000S0000620031003100093 Outlet 8.9x8.9 Unit Performance Altitude 0 ft Cold Max. Airflow 620.0 CFM Cold Min. Airflow 310.0 CFM Hot Max Airflow 310.0 CFM Hot Min Airflow 93.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure: .20 inwg Minimum Static Pressure Drop .30 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dua% density flg liner) Maximum Afrflow Cold Inlet 927.0 CFM Attenuator No Design Airflow CoId Inlet 620.0 CFM Safety Factor CoId Inlet 33 % Maximum Airflow Hot Inlet - 927.0 CFM Design Airflow Hot |nlet: -- - 310.0 CFM Safety Factor Hot Inlet 67 % UndLxVVxM 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E watts °° Cold Max. Airflow 620.0 CFM Hot Max Airflow 310.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (PwI) 67 63 55 52 51 51 ~ Total Attenuation 17 18 20 23 25 26 ^ Room Sound Level (SpI) 50 45 35 29 26 25 34 Discharge Sound Primary Sound (PwI) 67 63 58 52 45 38 ° Total Attenuation 29 30 41 53 55 41 ^ Room Sound Level (SpI) 38 33 17 <1O ^1O <1O 20 Notes: 1. Room sound levels shown includa attenuation transfer functlons shown above 2. Data were obtained from tests conducted in accordance with ARI Standard 880-90. 3. Sound power levels are in decibels, 10A-12 watts. 4. Dash space sound and/or wc value w less than 1o. ~ Sound calculations are based on Iargest Inlet slze. The results af this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. Al/uau,"bjectmchmnov~m`outnot/co. Air Terminals Builder 1 .09e Page 28 of 169 Acoustics Summary For VAV -2 -5 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name _..... . ...... .. .... .._......._ .... ._ _.. VAV -2 -5 .............. .... .... Quantity 1 Model Type .VAV - CCN Model:........_ ..._ .. .... 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 8 Inch Hot Inlet Size: 8 Inch Part Number 35NC1C000L0808419000000S0000620031003100093 Outlet :................ _ _.__. ... 8.9x8.9 Insulation: Other Information: Lining: ...Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet: 927.0 CFM Attenuator No Design Airflow Cold Inlet 620.0 CFM Safety Factor Cold Inlet... ...... 33 ok Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot Inlet 310.0 CFM Safety Factor Hot Inlet:.. ... 67 Unit LxWxH 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts "* Cold Max. Airflow: ..... .. .......................... CFM Hot Max Airflow 310.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 67 63 55 52 51 51 Total Attenuation 17 18 20 23 25 26 . Room Sound Level (Spl) 50 45 35 29 26 25 34 Discharge Sound Primary Sound (Pwl) 67 63 58 52 45 38 Total Attenuation 29 30 41 53 55 41 * Room Sound Level (SpI) 38 33 17 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) in space Indicates sound and /or NC value is less than 10. ** Sound calculations are based on largest Inlet slze. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 29 of 169 VAV -2 -6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -6 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 30 of 169 Unit Report For VAV -2 -6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Sr' 41I N, • � Unit Parameters Tag Name VAV -2 -6 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type . ._ . 4190: VAV with DCV Unit and Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0001610080008000209 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet ...... . 11.9x11.9 Dimensions Unit Depth 51.9 in Unit Width 46.2 in Unit Height 15.9 in Unit Operating Weight • 80 lb -' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L121241900000 35N Dual Duct Terminals 1 OS0001610080008000209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 31 of 169 Certified Drawing for VAV -2 -6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM com Tie 0a Je4r RTEFWsi1Y 6 ascn1 is .0E WALD.CIVAR)AIBLE Carrier CAROEAEIIiOMTCNNO1ef CE °`" 1 p S P01 r n''e11 / c T£ OCF ES4 COMM ,a cOE4 10r Oa6TT11E CATS# A United Technologies Company �� al rc+�r g 0 IBRIVINIALINIWTH E E '�41p���` 07iIIMMSNmBS1TSBR o]1Pif.T LMMI ,� 391BASEu�- WTFI.PrEN �LL.ivra A4scsEs �awV.� CW1RTEDAMENSI0N NgADESMEfADAPIB2 FROVEEDONSIZIESMS ALJ UI ATLEALST 241610)CAF.ARANCE FCFCCNIFCLS O L BO HSC H Ide liji 1 i I11.fiS Ipi ' c o NLET E I W .// F ,,�1 I IN �i I E o Q 6 1 1 ii •-: 4 - 7 HAWER T{4FL ) SEECFRONALFENRRESEB.DAI - INLET VIEW • TOP VIEW DISCHARGE VIEW . SENSOR- Livarrattlerxentaitomrsais CASING - standardonakris LINER- 12' r tick teddereValakrunthatoVe al015 . . . (1.499 cPa)Ps} .... _ Ioslhii(24471 3 ).11151ringsmatedbpr onion, . OpkrEt 20ga gak.alizedsleelcaseg. 181ax1TPA904 . c g • Cplonzt 1" 5m DAMPERS - . Cp6)Irt Staieinablionsyslem13/151tidaigid /aoFmi i habfrniltacedonaisbearmade,edgessasded CFMalF(1.49Paps tanaisbearrwttheetnettz-5#3s. UN1TACCESSORIES- • CcOmt WhatalaftnEysternwItnonen31 . COcnaF>argerbradels . Cptn t 12tierxalalaledrs/aki. . Cpfi)ret 1'fuiarxapstatedrala6on NOTE 1. Sensors are shown in inlet and discharge, butare available in both inlets. 2 Pneunaticmntots shown, eledror/care available. 3 Dimensions are shownashches(mm). INLET NORM AX MCI-LARGE SIZE CFM(Us) L W H A D E F G 4 255(106) 321/8(816) 21 5/8(550) 87/8(225) 53/8(137) 37/8(98) 9916(243) 778(200) 71/4(184) 5 350(165) 321/8(816) 21 5/8(553) 87/8(225) 53/8(137) 47/8(124) 9916(243) 77/8(200) 71/4(154) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 9916(243) 778(200) 71/4(184) 7 650(307) 365/8(931) 275 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 27518(702) 107/8(276) 33/8(86) 77/8(200) 15 9/16(395) 97/8(251) 91/4(235) 9 1050(495) 4458(1134) 33518(855) 127/8(352) 33/8(86) 87/8(225) 199 1278(327) 113/4(298) 10 1350(637) 4458(1134) 33518(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 1278(327) 113/4(298) 12 2100 (991) 5058(1287) 395/8(1007) 1578(403) 33/8(86) 11 7/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 46916(1183) 181/8(460) 33/8(86) 137/8(352) 261/2(673) 167/8(429) 169/16(420) 16 4000(1887) 64916(1640) 469 /16(1183) _ 181/8(460) 338(86) 1578(403) 2612(673) 167/8(429) 169/16(420) PROOUCTINFORMATIONISSUBJECTTOCHANGEVNTHOUTNOTICE 1/162002 .03.1-E XEINAMS■ LCCATCN wwvcwEER EWER FEVOCI4 B 9E` 10F 1 35N -202 -1 Air Terminals Builder 1.09e Page 32 of 169 • Performance Summary For VAV-2-6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM Unit Parameters Tag Name VAV-2-6 Quantity 1 Mod& Type VAV - CCN Model 35N Dual Duct Terminals Control Type* 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0001610080008000209 Outlet .. 11.9x11.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,610 0 CFM Cold Min. Airflow* 800.0 CFM Hot Max Airflow ... 800.0 CFM Hot Min Airflow 209.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure .20 in wg Minimum Static Pressure Drop* .47 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,610.0 CFM Safety Factor Cold Inlet 23 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet 800.0 CFM Safety Factor Hot Inlet 62 % Unit LxVVxH: 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E watts *" Cold Max. Airflow:...... ....... ...... . ........... 1,610.0 CFM Hot Max Airflow* 800.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 74 67 60 57 54 52 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 57 49 40 34 29 26 41 Discharge Sound Primary Sound (Pwl) 65 61 59 54 49 42 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 36 31 18 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880-90. 3. Sound power levels are in decibels, re 10"-12 watts. 4. Dash (-) In space Indicates sound and/or NC value Is less than 10. " Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 33 of 169 Acoustics Summary For VAV -2 -6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -6 Quantity 1 Model Type ... VAV - CCN Model:. 35N Dual Duct Terminals Control Type: 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0001610080008000209 Outlet 11.9x11.9 Insulation: Other Information: Lining:... Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,610.0 CFM Safety Factor Cold Inlet 23 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet: 800.0 CFM Safety Factor Hot Inlet 62 % Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 1,610.0 CFM Hot Max Airflow 800.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 74 67 60 57 54 52 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 57 49 40 34 29 26 41 Discharge Sound Primary Sound (Pwl) 65 61 59 54 49 42 ' Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 36 31 18 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from testa conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) in space Indicates sound and /or NC value is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 34 of 169 VAV -2 -8 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -8 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 35 of 169 Unit Report For VAV-2-8 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM spj 4, 4 el -% Unit Parameters Tag Name ................... . ...... . .. . ... VAV Quantity 1 Model Type VAV - CCN Model' 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size .. 10 Inch Part Number: 35NC1C000L1010419000000S0001300065006500145 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet' 9.9x9.9 Dimensions Unit Depth .. .... 48.6 in Unit Width' 40.2 in Unit Height' 13.9 in Unit Operating Weight • 61 lb ••• Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty • Ordering Information Part Number Description Quantity Base Unit 35NC1C000L101041900000 35N Dual Duct Terminals 1 060001300065006500145 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 36 of 169 Certified Drawing for VAV -2 -8 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM OSE na mOABR 6REROPERIY 6 mamma, a 11ESE I.AALDU IVARIABL Carrier DIAREN ECAR0ND15BHEED MNZ g i sw nE Eat oarnv+ ,a PAW wr mmm/E LIVE 35N CATALOGO A United Technologies Company �� oR ACCEir 0 1HiW46LN1WIH J�1\ ELBENXHOMIR 6NBA EUN11- .M CHARTE 7AUNBJSICN NCLLOESNE/ADOPTER ALLOAA1LPAST 241810)CLEARANCE O S L 9°Tf6LES r— H d� 7 1i� { i I i I .r !r. MET c ❑ D wit* E I W F N-ET IA i ° ! II Illi --f � I E o W rower. 1l-; im Ha ACKErte SEOPI1CNALFF.ATLI CW INLET VIEW TOP VIEW DISCHARGE VIEW SENSOR- Lieamulplaccintadonsensais CASING - starOardonah LINER- 12' Pm) P D / tidvidth tyisl wihabodyd dl5 (1.49 cPa)Ps.} bskult(241®1n 3 ).1histringiscoalEdtormerterosim, • gtr 20ga 9 181ad•FPA9X . co Et gig • Cgicnt 1 " Ian DAMPERS - . curet S rin3bsUaliansysbrnl3/15Uidagd LedevtrouptelrrpaidesshareVolicnind tedaraktitacedortarshearmide,edgessedad CFMar(1.49NPs UNITACCESSORIES- • Word Noixremitonsystrn al . gionaFgrgatradcfs Prmetaorriasef n . Wart 12 . gT6agt 1'ldal taledi9t/a6on NOTE 1. Sensors are shown in inlet and discharge, butare available in both inlets. 2 Pneumaticcontrols shown, electronicareavailable. 3 Dimensisnsare stomas itches(mm). NET NDMMAX DISCHARGE SIZE CFM(Us) L W H A D E F G 4 255(106) 321/8(816) 2158(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 32118(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 33/8(85) 67/8(175) 159/16(395) , 97/8(251) , 91/4(235) 8 800(377) 365/8(931) 2758(702) 107/8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 4458(1134) 335 /8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) ,127/8(327) 113/4(298) 10 1350(637) 445/8(1134) 335/8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 21W(991) 5058(1287) 3958(1007) 157/8(403( 338(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 /16(1183) 181/8(460) . 338(86) 137/8(352) 2612(673) 167/8(429) 169/16(420) 18 4000(1887) 649/16(1640) 469/16(1183) 181/8(460) 338(86) 1578(403) 2612(673) 167/8(429) 169/16(420) PRODUCT)N FORMATICNISSUBJECTTOCHANGEWfTHOUTNoT10E 1/162002 auaE JWNA1BEt =ATM CAANDNABEt 3,13,' M"E"' B E 1OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 37 of 169 Performance Summary For ~8 Project: Triangle Point Shell 0909/2010 Prepared By: 04:11PKU Unit Parameters Tag Name VAV-2-8 Quantity 1 Model Type VAV'CCm Model 35N DuaI Duct Terminals Control Type —' 4190: VAV with DCV Cold Inlet Size -- — 10 Inch Hot Inlet Size 10 Inch Part Number - 35NC1C0000010419000000S0001300065006500145 Outlet* 9.9x9.9 Unit Performance Altitude 0 ft Co|dMax.AirUmw 1 CFM Cold Min. 650.0 CFM Hot Max Airflow 650.0 CFM Hot Min Airflow 145.0 CFM Inlet Static Pressure 1.00 inwg Downstream Static Pressure .20 in wg Minimum Static Pressure Drop: .76 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual denmity0g liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow CoId Inlet 1.300.0 CFM Safety Factor CoId Inlet 10 96 Maximum Airflow Hot Inlet 1,448.0 CFM DeoignAirDmwHct|n|et 650.0 CFM Safety Safety Factor Hot Inlet 55 % UnitLxVVx* 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E watts ** � CoMax.Airflmw 1,300.0 CFM • Hot Max Airflow: 650.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (PwI) 63 59 54 50 48 43 ^ 'Tota|Attenuodon 17 18 20 23 25 26 ~ Room Sound Level (SpI) 46 41 34 27 23 17 29 Discharge Sound PrimorySound<PwV 61 62 58 55 50 r 44 ^ Total Attenuation 29 , 30 41 53 55 41 ^ Room Sound Level (Spl) 32 32 17 ^1U <1O <1U 19 Notes: 1. Room 8ound Ievels shown Include attenuation transfer functions shown abov . 2. Data were obtalned from tests conducted in accordance wlth ARI Standard 880.90. 3. Sound power levels In decibels, 10A-12 watts. 4. Dash (.) In epace Indicatee Sound and/or NC value is Iess than 10. ~ Sound calculations are based on Iargest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Camer Cor accepts no Iiability for the adequacy of any resulting design or installation. All data subject to cl,ange without notice. Air Terminals Builder 1 .09e Page 38 of 169 Acoustics Summary For VAV -2 -8 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name: VAV -2 -8 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001300065006500145 Outlet 9.9x9.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,300.0 CFM Safety Factor Cold Inlet 10 % Maximum Airflow Hot Inlet... CFM Design Airflow Hot Inlet 650.0 CFM Safety Factor Hot Inlet 55 % Unit LxVVxH• 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts " Cold Max. Airflow 1,300.0 CFM Hot Max Airflow 650.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 63 59 54 50 48 43 * Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 46 41 34 27 23 17 29 • Discharge Sound Primary Sound (Pwl) 61 62 58 55 50 44 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 32 32 17 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from testa conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) In space indicates sound and /or NC value is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 39 of 169 VAV -2 -9 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -9 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 40 of 169 Unit Report For VAV -2 -9 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM to Unit Parameters Tag Name' .... . .. ..........._...... .. . . ... -2 -9 ........................... ............................... ............. .................... .. ........... . Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0001580075007500209 Insulation Lining .. Standard (1/2 inch dual density f/g liner) Outlet 11.9x11.9 Dimensions Unit Depth ............ .51.9 in Unit Width 46.2 in Unit Height 15.9 in Unit Operating Weight • _.. 80 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L121241900000 35N Dual Duct Terminals 1 OS0001580075007500209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 41 of 169 Certified Drawing for VAV -2 -9 Project Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM CCCE aaa °ca ea IST1EPIRCFVflY a sasssso1 or mem DUN.DUC VNIAB E Carrier ` �'t�I MC 13 �l =WAS i tFE a,s�ss maul , mu MDT re 1lVE CATALoca A United Technologies Company 0, USED w.cur ur a 181WAINIVAMI p ACC ,p �BAsEUN11 - wn CHARIEDWDIVEN4ON PIQLOPSN.ETADAFTER M1QAR►TLFASr 241610)CLEARNJCE FCFCCNIRCLS 0 L 1 BOIFECE5 H 13 - 7 o Iij.i I 1 • I A I ' c PLEr ■ ° II E 1 W I c u... /� 1 iii I E o aro c11slTVP IE =i T ter , SEECIPTICNALFEATURESEELON I NLET VIEW TOP VIEW DISCHARGE VIEW-. . . SENSOR- Liearmitiapoirtaitwsensais CASING - starda Imakrils LINER- 12' (1310 P t ' QidWaiderttyisiarrnmfiabodydaslyd15 _ ... ... (149da)Ps1 tatut124101 3 ).1biskingiscoaledtcprmenterstn, . C)p6or>at 20ga gakertizedstelcastIg. 181axf•FPA934 - • 1' tae rn DAMPERS- EacthancteavigEgestettxrpar . Cprmat Sterfnarhalalimsystrn13161hthrigid LIEEkagEtni.4012darrceislmstrertrAoharkel esJafrOcifacedmaisbearnEktolgess3alscl CFMa16 (1.48Pa)Ps • UNIT ACCESSORIES - . Ctnet NoInerirdafreplern,wil sciCu4 . pre atcldasarn . COxist 12biErapsilatthatfal. . Op6 n t 1"biei 05ps6113:616a3 al, NOTE 1. Sensors are s)ownin inlet and discharge, but are available in both inlets. 2 Pneunaticmdr olsshown,eledlonicareavailable. 3 Dimensiaysareshownasitdtes(mm). N.ET NOMMAX DISCHARGE SIDE CFM(Us) L W H A D E F G 4 255(106) 321/8(816) 21518(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 9:/16(243) 77/8(200) 71/4(184) 7 650(307) 3658(931) 275/8(702) 107/8(276) 3318(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 3658(931) 275/8 (702) 107/8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 4458(1134) 335/8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 1D 1350(637) 4458(1134) 335/8(855) 12718(352) 33/8(86) 97/8(251) 195/16(497) 1278(327) 113/4(298) 12 2103(991) 5058(1287) 3958(1007) 1578(403) 338(86) 11 7/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 /16(1183) 181/8(460) 338(86) 137/8(352) 2612(673) 167/8(429) 169/16(420) 16 . 4000 (1887) 649 469/16(1183) 181/8(460) 33/8(86) 1578(403) 2612(673) 16 7/8(429) 169/16(420) PRODUCTINFORMATICNISSUBJECTTOCWWGEWTHOUTNOT10E 1/162002 .0.4r- cep LQ'.w,C■ rnAvNara,rea: BUYERS EWER REVS. B 10F 1 35N -202 -1 Air Terminals Builder 1.09e Page 42 of 169 Performance Summary For ~9 Project: Triangle Point8ha| 0909/2010 Prepared By: 0411PM Unit Parameters Tag Name VAV-2-9 Quantity 1 Model Type VAV - CCN Model 35N DuaI Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size 12 Inch Part Number 350C1C000L1212419800000S0001580075007500209 Outlet' 11.9x11.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,580.0 CFM Co|dW1in.AJrOmw 750.0 CFM Hot Max Airflow 7500 CFM Hot Min Airflow 209.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure P�uune� 20 in wg Minimum Static Pressure Drop .46 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other information: Lining Standard (1/2 Inch dual density f/Q|inwr) Maximum Airflow Cold Inlet 2.085.0 CFM Attenuator No Design Airflow CoId Inlet 1,580.0 CFM Safety Factor Cold Inlet 24 % Maximum Airflow Hot Inlet 2,085.0 CFM • DeeignAirDmwHot|n|et 750.0 CFM Safety Factor Hot Inlet 64 % UnbLxVVxH 51.9 x 46.2 x 15.$ Acoustic Summary: Sound Power Levels, dB re IOE watts ^^ Cold Max. Airflow 1.580.0 CFM Max 750.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (PwI) 73 67 60 56 54 52 ^ Total Attenuation 17 , 18 20 23 25 26 Room Sound Level (SpI) 56 49 40 33 29 26 40 Discharge Sound Primary Sound (Pwl) 65 60 59 54 49 , 42 ^ Total Attenuation 29 . 30 41 53 ' 55 41 ~ Room Sound Level (SpI) 36 30 18 <10 <1O <10 16 Notes: 1. Room Sound levais Shown Include attenuatlon transfer functlons shown above. 2. Data were obtalned from tests conducted in accordance wlth ARI Standard 880-90. 3. Sound power levels are in decibels, 10A-12 wafts. 4. Dash (-) in s u"°mm*°mu,ounuanum,wC^wm*Is/m,omuv1o. ~ Sound calculatlons are based on Iargest inlet size. The res /ts of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no Itability for the adequacy of any resulting design or tnstallation. Alt data subject to change without notice. Air Terminals Builder 1.O9e Page 43 of 169 • Acoustics Summary For VAV -2 -9 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -9 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0001580075007500209 Outlet: 11.9x11.9 Insulation: Other Information: Lining: ..Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,580.0 CFM Safety Factor Cold Inlet 24 Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet 750.0 CFM Safety Factor Hot Inlet 64 % Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts "" Cold Max. Airflow 1,580.0 CFM Hot Max Airflow .750.0 CFM Octave Bands (dB) • Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 73 67 60 56 54 52 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 56 49 40 33 29 26 40 Discharge Sound - Primary Sound (Pwl) 65 60 59 54 49 42 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 36 30 18 < 10 < 10 < 10 16 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) In space indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 44 of 169 VAV -2 -10 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -10 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 45 of 169 Unit Report For VAV-2-10 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM Unit Parameters Tag Name VAV-2-10 Quantity' 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 10 Inch Part Number 35NC10000L1010419000000S0001200060006000145 Insulation Lining Standard (1/2 inch dual density fig liner) Outlet 9.9x9.9 Dimensions Unit Depth 48.6 in Unit VVidth 40.2 in Unit Height' 13.9 in Unit Operating Weight 61 lb *** Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L101041900000 35N Dual Duct Terminals 1 OS0001200060006000145 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 46 of 169 • Certified Drawing for VAV -2 -10 • Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM ttCE 3a tm&ea enecrosEptre a -maxim a name DUAL UCIVN30BLE 0 Carrier C D #C 3 CRAAI PM ww 7)E mmw ,a mES ar �sm araysomairE 355 CATALOGe A United Technologies Company a+ MECOMMALIACIIEDECLOSED CP yr a H JJI\ oasvatvavme+naert orvrta BLEMIDDIWEER 35NSASEUNrr WO-CFMNALINIACCESSCFES CHARIffiALIVENSOJ 14DLCE'SKETADAPIER ALLW1 ILEAST 241610)CLEARANZE O S L B°IF6[ES r-- H 1 I OAS 1 MET ■ r O]l D E I W Imo / P iii. l' —f !r I E o W 6 Ow': e ter, ON • INLET VIEW TOP VIEW DISCHARGE VIEW SENSOR- LiearmUlpleixelaitwsensais CASING- st rdardorduis LINER- ThetesarlisInEdvvthstarrlard12' (L'trrli pere4e/ tick,dadEnslynalla1vAt 1.5 (1.49da)PS.1 bskutG4Igto 1. 9 tit 181artFPA9d■ . OrtaEt BatrrixoEsprEt • Cpinrlat 1" (7amn )thiliskiarneefrgspealca- DAMPERS - EathsancteehsgEwstednpEr (mane. tviessrdokhores4riectxtphylenefoangazigerg. . Opionet SterireinsUaforsyst3n1316liciaigid LethagistrcuptledarpotilessitEn2Yootarind isfaon edges stad CFMa16'(1.49Pa)P5 s14:6• UNITACCESSORIES- • Wort Isioinatalaknoistrn,wiroilemal . OpficroForgabadels. pemtadassiJL . Want 12 . 07634 1' NOTE 1. Sensors are shown in Het and discharge, butare available in both inlets. 2 Pnematiccontrols shown, eledonicareavailable. 3 Dmeruiortsareshownasinches(mm). MET NDAAIAAX DISCHARGE SIZE CFOA(Us) L W H A D E F G 4 255(106) 321/8(816) 21518(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 21518(550) 87/8(225) 53/8(137) 4718(124) 9916(243) 7718(200) 71/4(184) 6 450(212) 321/8(816) 21 5/8(550) 87/8(225) 3318(86) 57/8(149) 99116(243) 77/8(200) 71/4(184) 7 650(307) 3658(931) 2758(702) 107/8(276) 3318(86) 67/8(175) 15916(395) 97/8(251) 91/4(235) 8 800(377) 36518(931) 2756(702) 107/8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 3358(855) 127/8(352) 33x8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 4158(1134) 335/8(855) 127/8(352) 33(8(86) 97/8(251) 199/16(4971 ,1278(327) 113/4(298) 12 2100(991) 505/8(1287) 3958(1007) 1578(403) 33/8(86) 1178(302) 239/16(598) 1478(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469x16(1183) 1818(460) 33/8(86) 137/8(352) 2612(673) 167/8(429) 169(16(420) 18 4000 (1887) 649/16(1640) 469x16(1183) 181/8(460) 33/8(86) 1578(403) 261/2(673) 167/8(429) _ 169/16(420) PRODUCT INFORMATION ISSUBJECTTOCHPNGEWTHOUfNOTICE 1/16(1002 AIWA.E .ID&WfEi =CM CWANNOPU11[Ei B I ' .. 1OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 47 of 169 • Performance Summary For -10 Project: Triangle Point Shell 0809/2010 Prepared By: 0411PM Unit Parameters Tag Name VAV-2-10 Quantity 1 Model Type VAV - CCN Moue/* 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size* 10 Inch Hot Inet Size 10 Inch Part Number 35NC1C000L1U1041g00Q00OS0001200060006000145 Outlet 9.9x9.9 Unit Performance Altitude* 0 ft Cold Max. Airflow 1,200.0 CFM Co|dkAin.Aj�ow* 600.0 CFM Hot Max Airflow 600.0 CFM Hot Min Airflow 145.0 CFM Iniet Static Pressure 1.00 in wg Downstream Static Pressure* .20 in wg Minimum Static Pressure Drop .64 in wg Note Inlet Static Pressure Includes downstream pressure drop. Insulation: Other Information: Lining. Standard (1/2 inch dual density flg liner) Maximum Airflow Cold Inlet 1.448/0 CFM Attenuator No Design Airflow CoId Inlet' 1,200.0 CFM Safety Fo�orCo|d Inlet 17 % Maximum Airflow Hot Inlet 1,448.0 CFM OeuignAirDmwHot|n|et 600.0 CFM Safety Factor Hot Inlet 59 % Unit LxVVxM 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E-12 watts ^^ Cold Max. Airflow 1,200.0 CF k� Hot Max Airflow 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (PwI) 62 59 53 49 47 42 ^ Total Attenuation 17 18 20 23 25 26 ~ Room Sound Level (SpI) 45 41 33 26 22 16 29 Discharge Sound Primary Sound (PwI) 61 61 57 54 50 43 ~ Total Attenuation 29 30 41 53 55 41 ^ Room Sound Level (SpI) 32 31 16 «1O «1O «1U 18 Notes: 1. Room sound levels shown Include attenuation uvo°m,mnou*o shown above. 2. Data were obtained from tests conducted In accordance wlth ARI Standard 880.90. 3. Sound power levels are In decibels, re 10A-12 watts. 4. Dash (-) In spac Indicates Sound and/or NC value 18 Iess than 10. Sound calculations are based en largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Camer Corporation accepts no Iiability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1 .09e Page 48 of 169 Acoustics Summary For VAV -2 -10 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name .... VAV -2 -10 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L101041900000050001200060006000145 Outlet 9.9x9.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow Cold Inlet: ..... 1,200.0 CFM Safety Factor Cold Inlet 17 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 600.0 CFM Safety Factor Hot Inlet 59 % Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts Cold Max. Airflow 1,200.0 CFM Hot Max Airflow 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 62 59 53 49 47 42 * Total Attenuation 17 18 20 . 25 26 Room Sound Level (Spl) 45 41 33 26 22 16 29 Discharge Sound Primary Sound (Pwl) 61 61 57 54 50 43 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 32 31 16 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from testa conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) In space Indicates sound and/or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 49 of 169 VAV -2 -11 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -11 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary • Air Terminals Builder 1.09e Page 50 of 169 Unit Report For .11 Project: Triangle Point Shell 09X09Q010 Prepared By: 0411Pk8 e Unit Parameters Tag Name VAV-2-11 Quantity — 1 Mode Type* VAV - CCN Model 35N DuaI Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 10 Inch Part Number 3sNC1C00oL1p1041900p0006qQ01310p600U6000145 Insulation Lining Standard (112 inch dual density f/QUnmr) Outlet 9.9x9.9 Dimensions Unit Depth 48.6 in Unit Width 40.2 in Unit Height 13.8 in Unit Operating Weight • 61 |b ~~ Weights and Oimensions are approximate. ight does not indude curbs and accessones. Approximate te dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty information 1 Year Parts Ony Warranty • Ordering information Part Number Description Quantity Base Unit 35NC1C000L101041900000 35N Dual Duct Terminals 1 DS0001310060006000145 4190: VAVwibh DCV Hangers Accessories Air Terminals Builder 1.DBe Page 51 of 169 Certified Drawing for VAV -2 -11 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM COM no mamba snKPFOvrn CF sa®c„+ of nESE DUA LDUC1VA 4A E Carrier 1I.€ e i OR I u +a. WE mates ,a does la COMMIE LJVE c.�Ta oca ,cmJfa TSWUOr� FART MP:roma A United Technologies Company OR USED woan Ceeeet oR uacsvrxg m lEFINNALLNIVIIIH q��p��� . mavaTVavmam�rt mRrrx 5NBASEUMT wri- FIION�LLM. Y�7 O4ARTEDADNENEpN NQ UCESPLETALMPIER ALLONATLEAST 241610)CLEARANCE FCFOZNIRDS Q L { EOTHMES H d0 Iiali I I .RS 1 e 0 !� NAT I h �I�I D E ' W �!�� D NET mto CF 61' r IE' T HAfJr, SEEOPTCNALFECURESEELON INLET VIEW TOP VIEW DISCHARGE VIEW. . SENSOR- Lhearrnatileixiladmvs3rsais CASING - sdrdadortaksta LINER- 12' 0 P Q , paraolAndYon S (1..4914 a)Ps� bskut241a�h1 3 ). ' . t Iioret 20ga gEkariaids4aelaaseg. 181arth PA904 el • Watt 1 "Q5mrn DAMPERS- . Cilonat 131154idaicyci /oohariel ir>sUaUor> edgessealed CFlvvar(1.49Pa)Ps GPs UNITACCESSORIES - . Cgrnat NoinEftedafrnsyalartvwtrn rlal • CpknEtertatradeh paerlorderslicn. . Cp6anat . 12 . Opkret 1' NOTE 1. Sensors are shownin inlet and discharge, butare available in both inlets. 2 Pneunaticcontols shown, elearonicare available. 3 Dimensions are shown asinches(mm). NLET NOMMAX DISCHARGE S2E CFM(L/s) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99(16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 8 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 338(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8(/02) 107/8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 335 /8(855) 127/8(352) 358(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(837) 4458(1134) 335/8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 11314(298) 12 2103(991( 5056(1287) 395/8(1007) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 /16(1183) 181/8(460) 3318(86) 137/8(352) 261/2(673) 167/8(429) 169/16(420) 18 _ 4000 (1887) 64516(1640) 469 /16(1183) 181/8(460) 336(86) 157/8(403) 2612(673) 167/8(429) 169/16(420) PRODUCTNFORMA710NISSUBJECTTOC- 6gNGEWTMOUTNOTICE 1/162002 WV. %nER• B '� 1OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 52 of 169 Performance Summary For VAV-2-11 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM Unit Parameters Tag Name VAV-2-11 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type ....4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001310060006000145 Outlet 9.9x9.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,310.0 CFM Cold Min. Airflow ........ . .. 600.0 CFM Hot Max Airflow 600.0 CFM Hot Min Airflow 145.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure .20 in wg Minimum Static Pressure Drop .77 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator: No Design Airflow Cold Inlet 1,310.0 CFM Safety Factor Cold Inlet 10 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 600.0 CFM Safety Factor Hot Inlet 59 % Unit LxVVxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E-12 watts — Cold Max. Airflow 1,310.0 CFM Hot Max Airflow 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (PwI) 63 59 54 50 48 43 Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Sp() 46 41 34 27 23 17 29 Discharge Sound Primary Sound (PwI) 61 62 58 55 50 44 Total Attenuation 29 30 41 53 55 41 • Room Sound Level (Spl) 32 32 17 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880-90. 3. Sound power levels are In decibels, re 10 watts. 4. Dash (-) In space Indicates sound and/or NC value is less than 10. ** Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 53 of 169 Acoustics Summary For VAV -2 -11 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -11 Quantity 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size* 10 Inch Part Number 35NC1C000L1010419000000S0001310060006000145 Outlet 9.9x9.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator . No Design Airflow Cold Inlet 1,310.0 CFM Safety Factor Cold Inlet 10 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 600.0 CFM Safety Factor Hot Inlet 59 % Unit LxWxH: 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts " Cold Max. Airflow 1,310.0 CFM Hot Max Airflow* 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 63 59 54 50 48 43 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 46 41 34 27 23 17 29 Discharge Sound Primary Sound (Pwl) 61 62 58 55 50 44 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 32 32 17 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 54 of 169 VAV -2 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -12 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 55 of 169 Unit Report For VAV -2 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV - - Quantity 1 Model Type VAV - CCN Model* 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0002070100010000209 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet 11.9x11.9 Dimensions Unit Depth 51.9 in Unit Width 46.2 in Unit Height 15.9 in Unit Operating Weight . 80 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L121241900000 35N Dual Duct Terminals 1 OS0002070100010000209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 56 of 169 Certified Drawing for VAV -2 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM CCCE na maAe f m wresTY o =10AS-• v erg WILLfl IVAtF E 0- Carrier C ne 1 O3 w ° IAIN uw mmw mEe ra '� oae�mre aaosomaiPSE 3 5 N CATALOGS A United Technologies Company �� OR ACtEVr o I 35N msv+.nvarnrtemrsen mmecr EILEPCIN3NOMEER 35NBASEUNrT VIITHCPrOOLINTPOCESSCRES CHARTEDADIVBSICN NCII LETADAPTER ALLCMAG EAST 24'(610)CLEARANCE O FMS L 1 I6?► E ES H d I I A s I c NET ■ E ' VV F II I E o iii 6 YI52)TYP u i : +w Fwr{4PI.C5) SEECFMNALFEAVIUREEEELON . I NLET VIEW TOP VIEW DISCHARGE VIEW SENSOR- Liearniddapilaifone9risoris CASING - sEndadonaluts steiSsemaaernectErtalfiesfacIenigaletdo LINER- 12' (13mi) P $ tid y 1 . 5 - (1.4E+PAPs4 .. . n 3 ).Thisiriviscoatecttopmeriettdco, • Cp6or>at 20p. gakerieedstelcadv. 181a N PA904 . Cpbia gig • Cpfaxt r rrm DAMPERS - . OpSmat StdreresJalimsyslem13161icklicfi LeekagehoultEdErrpathsshsrOkairtni191 hsUa6on edgessealed CFME0(1.48Paps. GPs. UNITACCESSORIES- Ogcret Noierh tJ knsysiimm frcelari . COm9hErgatradets peek J L . giorEt 12 a 1'bierrapsttalydrsl.ltaim NOTE 1. Sensors are shown ininletand discharge, blare available in both inlets. 2 Pneunaticcormolsshawn ,elearonicareavailable. 3 Dimensions areshownasichos(mm). MET NOMMAX DISCHARGE SE CFM(Ua) L W H A D E F • G • 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99 77/8(200) 71/4(184) 6 450(212) ' 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99 77/8(200) 71/4(184) , 7 650(307) 365/8(931) 275 /8(702) 107/8(276) 3318(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8(702) 107/8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 335/8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 445/8(1134) 335 /8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2100(991) 505/8(1287) 3958(1007) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200(1510) 589 /16(1488) 469 /16(1183) 181/8(460) 338(86) 137/8(352) 2512(673) 167/8(429) 169/16(420) 19 4000 (1887) 649/16(1640) 469 /16(1183) 1818(460) _ 33/8(86) 1578(403) 2612(673) 167/8(429) 169/16(420) PRODUCTP4FORI4ATICNISSUBJECTTOCWWGEVEHO UTNOT10E 1/1&20D2 Joen•s .caaeest :trino+ wA.vew+EER EWER ELME. `E0IS°6 B 1OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 57 of 169 Performance Summary For VAV -2 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -12 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size:. 12 Inch Part Number ..... 35NC1C000L1212419000000S0002070100010000209 Outlet 11.9x11.9 Unit Performance Altitude 0 ft Cold Max. Airflow 2,070.0 CFM Cold Min. Airflow 1,000.0 CFM Hot Max Airflow 1,000.0 CFM Hot Min Airflow 209.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure' 20 in wg Minimum Static Pressure Drop 78 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining:.... Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 2,070.0 CFM Safety Factor Cold Inlet 1 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet 1,000.0 CFM Safety Factor Hot net 52 % Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: • Sound Power Levels, dB re 10E -12 watts ** Cold Max. Airflow 2,070.0 CFM Hot Max Airflow 1,000.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 76 69 62 58 55 52 * * Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 59 51 42 35 30 26 44 Discharge Sound Primary Sound (Pwl) 66 62 60 56 51 44 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spi) . 37 32 19 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from testa conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) in space indicates sound and /or NC value is less than 10. ** Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 58 of 169 Acoustics Summary For VAV -2 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -12 Quantity: .... 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size .... 12 Inch Hot Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0002070100010000209 Outlet 11.9x11.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 2,070.0 CFM Safety Factor Cold Inlet 1 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet 1,000.0 CFM Safety Factor Hot Inlet 52 % Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 2,070.0 CFM Hot Max Airflow 1,000.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 76 69 62 58 55 52 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 59 51 42 35 30 26 44 Discharge Sound • Primary Sound (Pwl) 66 62 60 56 51 44 Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) _ 37 32 19 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) In space indicates sound and /or NC value Is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 59 of 169 VAV -2 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -13 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 60 of 169 Unit Report For VAV -2 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM l Unit Parameters Tag Name VAV -2 -13 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001300060006000145 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet 9.9x9.9 Dimensions Unit Depth ...........48.6 in Unit Width .. 40.2 in Unit Height 13.9 in Unit Operating Weight • 61 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L101041900000 35N Dual Duct Terminals 1 OS0001300060006000145 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 61 of 169 Certified Drawing for VAV -2 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM °CCE ma osucke STIEMTERTY a SAMSON Cr nrg Ol eLDIX VARIABLE C arrier CAMM1 Ml[NN CtDM ��ED QYNe T XLMNTS 35N uw ee EA SUCI WES ran R:0 M1 E OfDQbTANRR]11VE CATALOG* A United Technologies Company CR y3E0 nUT CF lH TERIMPLIMMI ELEICKaiNVIEER 35NBIASEUNrr w THYDCNoLLMaocESSCFaES CHARTE7A0m2Ns C 4 NCLJ.DBEPLETADAP(ER ALll ARTLEAST 241610)CL EARANCE Q L---{ B01F6[ES 1 --- H d• 1 I ..i I i I -A IS 1 c NIET E I W 101 NET mito iii I t 1 ----- MAMERERACHET+IPLCS) SEEC1 FEA I INLET VIEW TOP VIEW DISCHARGE VIEW • • - SENSOR- LhearatitilepoilailawsEnsais CASING- darrOrdc ahrtls LINER- 12' (13m1 pe.ErtEicagdc2%atrroirundEctibmg6" trickdu j'r aT,wihabodyder*:(15 (1.4Pfla)P51 • bsicultp4Igtn et 20ga gduaizedstedcashg. adnagEteKtiernelEdJL181adTPA904 . ClicrEt g • 1'(25m DAMPERS - 6orsabDke . Op6oret Steiteri tsklatrorlsysfern13115'Uidaicjd Ledcagetniciltelsmerdasstenrhaltainsi hd iatn, edgessealed CFMa0(1.484 UNRACCESSORIES- • CgicrEt NoinstralatnsystaiNt rtoiand . C 6ortat almbradata pe a tmdasa6Ql . Ccfionat 12tiebdrstlatlon. . Cpknat ttiEncapalatedrisiabon. NOTE 1. Sensors are shown in inlet and discharge, but are available in both inlets. 2 Pnetmaticowtrols shown, electronicareavailable. 3 Dimensions areshown as r hes(mm). INLET NOAMMX DISCHARGE St2E CFM(Us) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 4718(124) 99/16(243) ' 77/8(200) 71/4(184) 6 450(212) 321 /8(816) 215/8(550) 87 /8 (225) 33/8(86) 57/8(149) 99/16(243) 77 /8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107 /8(276) 33/8(86) 67 /8(175) 159/16(395) 97 /8(251) 91/4(235) 8 800(377) 365/8(931) 275/8 (702) 107/8(276) 33/8(86) 77 /8(200) 159/16(395) 97 /8(251) 91/4(235) 9 1050(495) 445/8(1134) 335/8(855) 127 /8(352) 33/8(86) 87 /8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 445,8(1134) 335 /8(855) 127 /8(352) 33/8(85) 97 /8(251) 199/16(497) 127 /8(327) 113/4(298) 12 2100 (991) 5058(1287) 395 /8(1007) 157 /8(403) 33/8(86) 117 /8(302) 239/16(598) 147 /8(387) 141/4(352) 14 3200 (1510) 589/16(1488) 469 /16(1183) 181/8(460) 3303(86) 137 /8(352) 261/2(673) 167 /8(429) 169/16(420) 16 4000(1887) 649 /16(1640) _ 469/16(1183) 181/8(460) 3303(86) 157 /8(403) 261/2(673) 167 /8(429) 169/16(420) PRODUCT INFORMATION ISSUBJECTTOCHANGEWrr }KWTNOTICE 1/162002 .GewWE .03NME1 LCGCCN GtiWtO4J* aNEI. censo4 B 'E` 1 OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 62 of 169 Performance Summary For VAV -2 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -13 Quantity 1 Model Type VAV - CCN Model: 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size* 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001300060006000145 Outlet 9.9x9.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,300.0 CFM Cold Min. Airflow 600.0 CFM Hot Max Airflow* 600.0 CFM Hot Min Airflow 145.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure .20 in wg Minimum Static Pressure Drop .76 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining:..... Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,300.0 CFM Safety Factor Cold Inlet 10 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 600.0 CFM Safety Factor Hot Inlet 59 % Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E -12 watts ** Cold Max. Airflow 1,300.0 CFM Hot Max Airflow' 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 63 59 54 50 48 43 Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Spl) 46 41 34 27 23 17 29 Discharge Sound Primary Sound (Pwl) 61 62 58 55 50 44 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 32 32 17 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from testa conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) in space Indicates sound and/or NC value Is Tess than 10. Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 63 of 169 Acoustics Summary For VAV -2 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -13 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Pan`. Number 35NC1C000L1010419000000S0001300060006000145 Outlet 9.9x9.9 Insulation: Other Information: Lining Standard (112 inch dual density fig liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,300.0 CFM Safety Factor Cold Inlet 10 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 600.0 CFM Safety Factor Hot Inlet 59 % Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 1,300.0 CFM Hot Max Airflow 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 63 59 54 50 48 43 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Sp» 46 41 r 34 27 23 17 29 Discharge Sound Primary Sound (Pwl) 61 62 58 55 50 44 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 32 32 17 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10" -12 watts. 4. Dash ( -) in apace indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 64 of 169 • VAV -2 -16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -16 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 65 of 169 Unit Report For VAV-2-16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM IIP. ke we ‘ Nt i&_ ....4 ..,.., i vit .... Unit Parameters Tag Name VAV-2-16 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size' 6 Inch Part Number 35NC1C000L0606419000000S0000220011001100052 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet' 6.9x6.9 Dimensions Unit Depth 35.9 in Unit Width' 32.2 in Unit Height 8.9 in Unit Operating Weight . 31 lb "* Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L060641900000 35N Dual Duct Terminals 1 0S0000220011001100052 4190: VAV with DCV Hangers Accessories • Air Terminals Builder 1.09e Page 66 of 169 Certified Drawing for VAV -2 -16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM a:CE tll4 L1nl.BR 611EPR:FOR'I CF StH.SSQ/ OF 11E°E DUALDUCIVAF3AEILE 0 Carrier GWNER06RMID.NOgCRAVED °""C''°'°°CURMS 116 ,a COD 'CT E N E 35N CATALOGS* A United Technologies Company DR oA RODEFTIVOE CF 1HRVNAiUNIWIH msvIROOARnewaee COMO' BJMNOCHOIVEER 35NBASEUNfr vun-cFnctounrpoomscRE CHARTEDIAUIVBrSON 4 NC LLJDESMETADAPf94 ALLlAA1 EAST 24 1�� 0 S Ils O I 1 I *IS I � ' C NET r�l D milo I - ,,' E I W F NET , II I e o Ili W. r't152)TYP ii - I - T ) SEECPnoNatEanrEseaoN . . • INLET VIEW TOP VIEW DISCHARGE VIEW • . . SENSOR- Lhearrnitleixilaitonraensais CASING- Thabasantaxnst slarlacknalunla LINER- Thete5eritaracMalisIatlard12' ( p ez tldcgkeldaValatr> :11.5 (1.49d'a)Psl bskuN2414m 1elattFPA904. rt BotmaxEsscati. • Op6orEt 1 "R DANIPERS- . Opoora Ste riterits(la6msystem13r161tidagd Le3legEtrittliedarpailEssterekincnted filar edgessealed CFMa1511.49Paps UNITACCESSORIES- • Cgfiorlat NbIrehattraYstm,w1hriceterrl . Cpfior'at>argabradaEts. peatnrldasa6ul. . Ogcrat 12 . Opkret 1' NOTE 1. Sensors are shown in inlet and discharge, but are available in both valets. 2 Pneurnaticcontrols sho «n,elearanicare available. 3 Dimensionsareshownas inches (mm). • .LET NON MAX DISCHARGE Sri CFM(Ll81 L W H A D E F G _ 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(203) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 338(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(7021 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(2351 8 800(377) 365/8(931) 275/8(702) 107/8(276) 338(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 445 335/8(855) 127 /8(352) , 33/8(86) 87 /8(225) 199/16(497) 127 /8(327) 113/4(298) 10 1350(637) 445/8(1134) , 335/8(855) 127 /8(352) 33/8(86) 97 /8(251) 199/16(497) 127 /8(327) 113/4(298) 12 2100 (9911 505/8(1287) 395 157 /8(403) 33 117 /8(3021 239/16(598) 147 /8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469/16(1183) 181 /8(460) 33/8(86) 137/8(352) 2612(673) 167 /8(429) 169116(420) 16 4030 (1887) 649 469/16(1183) 181 /8(460) _ 33(8(86) 157 /8(403) 261/2(673) 167 /8(429) 169/16(420) PRODUCTPIFORMATIONISSUBJECTTOCKANGE /W1'HOUTNOTICE 1/162002 16.41E .03.401 .0001 CRA M'L1661 ELM RAMAN 4.004 B '¢` 105 1 35N -202 -1 Air Terminals Builder 1.09e Page 67 of 169 Performance Summary For VAV -2 -16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -16 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000220011001100052 Outlet 6.9x6.9 Unit Performance Altitude 0 ft Cold Max. Airflow 220.0 CFM Cold Min. Airflow 110.0 CFM Hot Max Airflow' 110.0 CFM Hot Min Airflow* 52.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop .13 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow Cold Inlet 220.0 CFM Safety Factor Cold Inlet 58 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet 110.0 CFM Safety Factor Hot Inlet 79 % Unit LxWxH' 35.9 x 32.2 x 8.9 Acoustic Summary: • Sound Power Levels, dB re 10E 12watts ** Cold Max. Airflow* 220.0 CFM Hot Max Airflow 110.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 55 51 42 37 36 33 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 38 33 22 14 11 < 10 20 Discharge Sound Primary Sound (Pwl) 59 58 52 45 39 33 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 30 28 11 < 10 < 10 < 10 14 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) in space indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 68 of 169 Acoustics Summary For VAV -2 -16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -16 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000220011001100052 Outlet 6.9x6.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow Cold Inlet 220.0 CFM Safety Factor Cold Inlet: 58 °A) Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet 110.0 CFM Safety Factor Hot Inlet 79 Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts **Cold Max. Airflow 220.0 CFM Hot Max Airflow 110.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 55 51 42 37 36 33 Total Attenuation 17 18 20 23 25 _. 26 _ Room Sound Level (Spl) 38 33 22 14 11 < 10 20 Discharge Sound Primary Sound (Pwl) 59 58 52 45 39 33 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 30 28 11 < 10 _ < 10 < 10 14 Notes: 1. Room sound Levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 ^ -12 watts. 4. Dash ( -) In space indicates sound and/or NC value Is leas than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 69 of 169 • VAV -2 -17 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -2 -17 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 70 of 169 Unit Report For VAV-2-17 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM :tr e t 'v .4, MI. o'll A Unit Parameters Tag Name VAV-2-17 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Unit and Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000200010001000052 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet 6.9x6.9 Dimensions Unit Depth , ....... 35.9 in Unit VVidth 32.2 in Unit Height 8.9 in Unit Operating Weight • 31 lb *** Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L060641900000 35N Dual Duct Terminals 1 0S0000200010001000052 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 71 of 169 Certified Drawing for VAV -2 -17 • Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM °g nn oonAea o,1eitw CF Aa�GR a DIME DLJI4JDLx1VARIAELE Carrier 1°R"a IS ®" °""'GS 010°°''O''B N wa+ ne e4t ES.R mans+ va aces Ear =BEAM 1NE cnra oca TME0° °'�0® PPM �WRCE �m_uu 1 -�w.. A Unitee T e ch nologies Company OE USED vow DAFFIER OR A PTTh ! 1�•.�1•-1H 6 p���11 FFERRESm AieD7aeR oORACt ELEICyy�u 35NBASEUNFr- wn- cprosAuiirA /�..�1 CHARTEDADF/E SIGN NCLICESILETADAPfER ALLL AA1LEAST 24%610)CLEARANCE KFCCNITCLS 0 L---.{ BOIF6CE5 r-- H d � , Hai: I i I AkiN: ‚i E o l D 1 40' NEr ■ E 1 ' W 0:- 7 t !`u 1 o IN w. 611521TYP I E i 6 • HANGERBRAIaErS) SEECPIICNALFFATURESEELOIN INLET VIEW TOP VIEW DISCHARGE VIEW SENSOR- Lisamitlepcilailowsersoris CASING - stincJardorehris LINER- 12' (13mi P$ wdabadydaniyd15 (1.49a)Ps.4 _ . 181ardNFPA934 el • glad T7mrl DAMPERS - trsaho+e . Cptrlat Slaiiaitsaabornyslern13164idaigd dtnrital isfa_orl e:19 s eedEd CFMaE6'(1.49Pa)Ps. UNITACCESSORIES- . ()Ant NoiiaiEdarr syslarnwltnoiEntit prealoorl krEdr t . OgorEt 12tienimpstkitdralabl. . Wont ttiencapsialednilakri. NOTE: 1. Sensors areshownin Het and discharge, but are available in both inlets. 2 Pneurnaticcontrols shown,eledronicareavailable. 3 Dimensions areshownas inches (mm). MET NDNIMA)( DISCHARGE WE CFM(L/s) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 21518(550) 87/8(225) 53,8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 8 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 7718(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 33/8(86) 6718(175) 159/16(395) 9718(251) 91/4(235) 8 800(377) 36518(931) 275/8(702) 107/8(276) 33/8(86) 77/8(203) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 4458(1134) 335 /8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 4456(11341 33 518(8551 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2100 (991) 5)5/8(1287) 3958(1007) 157/8(403) , 3318(86) 117/8(302) 239/16(598) 1478(387) 141/4(362) 14 3200 (1510) 589116(1488) 469 /16(1183) 181/8(460) 338(86) 137/8(352) 2612(673) 1678(429) 169/16(420) . 18 _ 4000 (1887) 64816(1640) 469 /16(1183) 18118(460) 33/8(86) 157/8(403) 2612(673) 1678(429) 169/16(420) PRODUCTINFOR4AT) ONISSUBJECTTOCWWGEVKTHOUTNOTICE 1/162002 Wasp 1ENAtEER '. iern fAiNNpHAe331 aAER EVER. RF/BpV B 9EEr IOF 1 35N -202 -1 Air Terminals Builder 1.09e Page 72 of 169 Performance Summary For VAV -2 -17 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -17 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 6 Inch Hot Inlet Size' 6 Inch Part Number 35NC1C000L0606419000000S0000200010001000052 Outlet 6.9x6.9 Unit Performance Altitude* 0 ft Cold Max. Airflow 200 0 CFM Cold Min. Airflow 100 0 CFM Hot Max Airflow 100 0 CFM Hot Min Airflow:. 52 0 CFM Inlet Static Pressure* 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop' .11 in wg Note* Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (112 inch dual density f/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator:. No Design Airflow Cold Inlet 200.0 CFM Safety Factor Cold Inlet 62 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet 100.0 CFM Safety Factor Hot Inlet 81 cYo Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E -12 watts " Cold Max. Airflow 200.0 CFM Hot Max Airflow 100.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 54 51 41 36 35 32 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 37 33 21 13 10 < 10 20 Discharge Sound Primary Sound (Pwl) 57 57 52 44 38 32 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 28 27 11 < 10 < 10 < 10 13 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value Is less than 10. Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 73 of 169 Acoustics Summary For VAV -2 -17 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -2 -17 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L060641900000080000200010001000052 Outlet 6.9x6.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow Cold Inlet 200.0 CFM Safety Factor Cold Inlet 62 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet 100.0 CFM Safety Factor Hot Inlet 81 % Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 200.0 CFM Hot Max Airflow 100.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 54 51 41 36 35 32 ' Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 37 33 21 13 10 < 10 20 Discharge Sound Primary Sound (Pwl) 57 57 52 44 38 32 ' Total Attenuation 29 30 41 53 55 41 ' Room Sound Level (Spl) 28 27 11 < 10 < 10 < 10 13 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) In apace Indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 74 of 169 VAV -3 -1 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -1 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 75 of 169 Unit Report For VAV -3 -1 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM - s Unit Parameters Tag Name VAV -3 -1 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size' 8 Inch Part Number 35NC1C000L0808419000000S0000760035003500093 Insulation Lining' Standard (1/2 Inch dual density fig liner) Outlet 8.9x8.9 Dimensions Unit Depth' 39.2 in Unit Width 36.2 in Unit Height 10.9 in Unit Operating Weight • 42 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for - • - • - shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L080841900000 35N Dual Duct Terminals 1 050000760035003500093 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 76 of 169 • Certified Drawing for VAV -3 -1 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM CCtE 1149 mniaa lsTERCPERn' a 51a.64on CP 'WEE DUALDUCNAF3/IBLE Carrier N MC S N D w Druisns i C CC wa aE S mmw ,a t ror arammeauvE 35N CATALOGS A United Technologies Company �� 7‘ ARiPr Q7 1 H 35N CCFFQ OLFISA iTTENCO ea CCIVIR CT aB V Z 3 NBN S U�- w�A •.m CHARTB3ATIVE SICK NCLIXESNETADAPTER W.LOAKILEAST 2 1 1 FCRINIFELS 0 L i BI31 H ive, Iiii; I 1 I OBS I D -� E I nil I W ,/ F ° 1 !4.I I E o iii Crii rosrep U '411•1;1 HAN ro t.cs) SEEoPnadA<FEAn.RESBaav fNLET VIEW TOP VIEW DISCHARGE VIEW _ SENSOR- Lilearrteipkapoilaitwsersais CASING- slandi rda>ah LINER- 12' tickci dery mitanyttiabodyda (1.4%Pa)Pal L4kgtn Trhisfringiscoateitoprekrterosion, . Cgasst g 181a11i'FPA904 g 131t.nexEsvrEt . glad 1 "(a*n DAMP JiS- treabae . OpforEt St9rinsirsiarrnsystm13 161Fidagd /ac+furea1 hationtitscEdcraistreenrside,edlyssesied C a16'(1.48Pa UNITACCESSORIES- Ple.etadereatn . Cpfioret 12 . Opecnet 1"bierlmpsfatelnalaion NOTE 1. Sensors are shown in irdetand discharge, but are available in both inlets. 2 Pnetmaticmrttrnlssh wn,electronicareavailable. 3 Dimensiansareshownasiches(mm). P&Er NCMMAX DISCHARGE SIZE CFM(Us) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 2758(702) 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 2758(702) 107/8(276) 336(86) 778(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 4458(1134) 3358(855) 1278(352) 33/8(86) 878(225) 199/16(497) 127/8(327) 113/4(298) . 10 1350(637) 4458(1134) 3358(855) 127/8(352) 3318(86) 978(251) 199/16(497) 1278(327) 113/4(298) 12 2100(991) 5058(1287) 3958(1007) 1578(403) 33/8(86) 1178(302) 239/16(598) 147/8(387) 141/4(362) 14 3200(1510) 58916(1488) 469 /16(1183) 1818(460) 33/8(86) 137/8(352) 2612(673) 1678(429) 16916(420) 18 _ 4000(1887) 649/16(1640) 469/16(1183) _ 181/8(460) 33/8(86) 1578(403) _ 2612(673) 167/8(429) 169/16(420) PRODUCTINFORMATIONISSUBJECITOcHANGEWRHOUTNOTICE 1/162002 B.NER a,' `EVSLN B I 10F 1 359/ -202 -1 � Air Terminals Builder 1.09e Page 77 of 169 Performance Summary For VAV -3 -1 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -1 Quantity* - 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 8 Inch Hot Inlet Size' 8 Inch Part Number 35NC1C000L0808419000000S0000760035003500093 Outlet .8.9x8.9 Unit Performance Altitude* 0 ft Cold Max. Airflow 760 0 CFM Cold Min. Airflow 350 0 CFM Hot Max Airflow' 350.0 CFM Hot Min Airflow* 93.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop' .46 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 927.0 CFM Attenuator No Design Airflow Cold Inlet 760.0 CFM Safety Factor Cold Inlet 18 % Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot Inlet' -' 350.0 CFM Safety Factor Hot Inlet 62 % UnitLxWxH 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts - ** Cold Max. Airflow' 760.0 CFM Hot Max Airflow' 350.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 69 65 57 54 53 52 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 52 47 , 37 31 28 26 37 Discharge Sound Primary Sound (Pwl) 69 64 59 53 47 39 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 40 34 18 < 10 < 10 < 10 21 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10" -12 watts. 4. Dash ( -) in space Indicates sound and/or NC value Is less than 10. ** Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 78 of 169 Acoustics Summary For VAV -3 -1 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -1 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 8 Inch Hot Inlet Size 8 Inch Part Number 35NC1C000L0808419000000S0000760035003500093 Outlet 8.9x8.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 927.0 CFM Attenuator No Design Airflow Cold Inlet 760.0 CFM Safety Factor Cold Inlet 18 % Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot Inlet: 350.0 CFM Safety Factor Hot Inlet 62 % Unit LxVVxH 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts " Cold Max. Airflow 760.0 CFM Hot Max Airflow 350.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 69 65 57 54 53 52 * Total Attenuation 17 18 . 20 . - 23 25 26 _ Room Sound Level (Spl) 52 47 37 31 28 26 37 Discharge Sound Primary Sound (Pwl) 69 64 59 53 47 39 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 40 _ 34 18 < 10 < 10 < 10 21 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) In space Indicates sound and/or NC value Is less than 10. Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Cartier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 79 of 169 VAV -3 -2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -2 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 80 of 169 Unit Report For VAV -3 -2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM f.! CIO ft Unit Parameters Tag Name VAV -3 -2 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 10 Inch Part Number' 35NC1C000L1010419000000S0001110055005500145 Insulation Lining Standard (1/2 Inch dual density fig liner) Outlet 9.9x9.9 Dimensions Unit Depth 48.6 in Unit Width 40.2 in Unit Height 13.9 in Unit Operating Weight • 61 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L101041900000 35N Dual Duct Terminals 1 OS0001110055005500145 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 81 of 169 Certified Drawing for VAV -3 -2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM OXE 0 3* non►ear sr are a aaASSon a MESE WALDUCIVARIAaE Carrier R €„ON NO tetd °CR 3bN I,n+ E Qm av+ .a DM KR =awe CATPLOG# A United Technologies Company a TEROALLNIWT1H �e��pA ART EIENMOCH t 391 1B 1SEuN 1 - wn-cenavauricassams CWIRTE50'ADNBNSIO 4 NalEESNETADAPTER AL LOM L EAST 241610cLE RA E FCROCNITCIS 0 L- E301}5C r". H d• ilia: I 1 I -RS I ■ E 1 ' W I F I/ NET • ell 117 .� ----- - O T4 SEEDPnCNN,FEATU O N INLET VIEW :. TOP VIEW . :.. DISCHARGE VIEW. . . SENSOR- LheaniklecdntailaysEnsais CASING- Sar>dardmedir s . tid LINER- >� t 4 S. .... .. (1 - . . b in '). B 181ar1dsFPA904 gig • OptnEt 1125rrm • DAMPERS- . Op5orlat Sl iirlailsttatonsystrn13/161tidagd /oofnrritel halakn edgessealed CRAsierl 48Pa)Ps funaishearnwitsheetrnetalz-sbts. UNITACCESSORIES- • Cprmst NoIneriationsyskernAdhnoilernal . Op o shargertradels pmatiordasaBn . Op6Q1at 12'biarwsfat•idrstitton . Wont T'foiarapalatsdrtskion NOTE 1. Sensors are sham ininlet and discharge, but are available in both inlets. 2 Pnetmaticcontrolsshownt, electronicare available. 3 Dimensions we shown ashches(mm). INLET NOMAtAX DISCHARGE SUE CFNI(Us) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 5303(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 8 450(212) 321/8(816) 215/8(550) 87/8(225) 3318(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 36518(931) 275/8(702) 107/8(276) 33/8(85) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8(702) 107/8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 4458(1134) 335 /8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) , 445/8(1134) 335/8(8551 127/8(352) 3318(26) 9718(251) 199/16(497) 127/8(327) 113/4(298) 12 2100 (991) 505/8(1287) 395 /8(1007) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 /16(1183) 181/8(460) 33/8(86) 137/8(352) ' 2612(673) 167/8(429) 169/16(420) 16 4000(1887) _ 649/16(1640) _ 469/16(1183) 181/8(460) _ 33/8(86) 157/8(403) 261/2(673) 167/8(429) 169/16(420) • PRODUCTI FOF2V1ATicNISSUBJECTTOCW NGEVNn4OUTNOTICE 1/16/2002 191MIE .091014061 IQRaA *AW.CNJ SPIER EWE . RM.. B air I OF 1 36N -202 -1 Air Terminals Builder 1.09e Page 82 of 169 Performance Summary For VAV -3 -2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -2 Quantity 1 Model Type: VAV - CCN Model .._ ................_..... 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 10 Inch Hot Inlet Size: 10 Inch Part Number: 35NC1C000L1010419000000S0001110055005500145 Outlet 9.9x9.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,110.0 CFM Cold Min. Airflow' 550.0 CFM Hot Max Airflow 550.0 CFM Hot Min Airflow 145.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure .20 in wg Minimum Static Pressure Drop' .55 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,110.0 CFM Safety Factor Cold Inlet 23 % Maximum Airflow Hot Inlet 1,448.0 CFM - Design Airflow Hot Inlet 550.0 CFM Safety Factor Hot Inlet' 62 % Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts Cold Max. Airflow 1,110.0 CFM Hot Max Airflow' 550.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) , 62 58 53 48 46 42 Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Spl) 45 40 33 25 21 16 28 Discharge Sound Primary Sound (Pwl) 60 61 57 53 49 42 • Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 31 31 16 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 wafts. 4. Dash ( -) In space Indicates sound and/or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 83 of 169 Acoustics Summary For VAV -3 -2 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -2 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001110055005500145 Outlet 9.9x9.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator• No Design Airflow Cold Inlet 1,110.0 CFM Safety Factor Cold Inlet 23 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 550.0 CFM Safety Factor Hot Inlet 62 % Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts "` Cold Max. Airflow .1,110.0 CFM Hot Max Airflow 550.0 CFM • Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 62 58 53 48 46 42 Total Attenuation 17 18 20 23 25 26 ` Room Sound Level (Spl) 45 40 33 25 21 16 28 • Discharge Sound Primary Sound (Pwl) 60 61 57 53 49 42 ` Total Attenuation 29 30 41 53 55 41 ` Room Sound Level (Spl) 31 31 16 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10 " -12 watts. 4. Dash ( -) In space Indicates sound and/or NC value is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 84 of 169 VAV -3 -3 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -3 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 85 of 169 Unit Report For VAV -3 -3 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM -= Unit Parameters Tag Name* VAV -3 -3 Quantity 1 Model Type VAV - CCN Model* 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0001965095009500209 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet 11.9x11.9 Dimensions Unit Depth 51.9 in Unit Width 46.2 in Unit Height. 15.9 in Unit Operating Weight • 80 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L121241900000 35N Dual Duct Terminals 1 OS0001965095009500209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 86 of 169 • Certified Drawing for VAV -3 -3 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM CCCE 1H5 CCCueir emeiomtr a aacea+ a t1EM DlYY.CNA N3LE I Carrier GVi61 33 NO leORNeED CRAMS CO UI g sn n U 33514 LICE DE E EODIESC oaatw is CCtl DOT Q�016DYrM1 CATALOG# A United Technologies Company 01 w ■zaBTt a 1ERN Nj..NIWTH Wi0inW9Wnem6dR CHAR1EETAUNE3JSIa4 tK71.CESTLETADAPIEft ALLO A1LFASr 241610/CLEARANCE ID L { Saila:ES H alit Ma: I / I ,OAS I 161 NIET c ❑ E 1 I W Iii F NIET ' PSI D i lli IN6 1 Q 6'(152)TYP u1_•; eow -- HAN3EFEIRACKEN4PLCS) SEECFMCWLLFEATLFES93-Oly INLET VIEW TOP VIEW DISCHARGE VIEW • SENSOR- lixernaplepcintaibmensais CASING- sfaldatda athis. steaarneartanalarbskselxiErrigailetdo LINER- Thetesanlidnactaislaniadla Puri 1 P Qi kita!76r1styi arrnyttatcdyderstyarl5 (• • tstutt241tt 1• • Chat 181ad•FPA904 st gc07Tga g 1 1n DAMPERS - 4rrsahD.e . COrnEt SatEr sda6onsyste n13h51Fidapd /aatartel iisJa6or> CFM1611.49Paps UNITACCESSORIES- a Nolnetalagonsysism, . Optor>ahanpatracJets P . Cpfortat 12 . CrOonat 1' NOTE: 1. Sensors are shown in inlet and discharge, but are available in both inlets. 2 Pneuriaticcatrolsshoom eledronicareavailable. 3 Oimensionsareshownas tees (mm). NET NONIMAX DISCHARGE ST2E CFMNs) L W H A D E F G 4 255(106) 32118(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 8 350(165) 321/8(816) 215/8(550) 87/8(225) 5318(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 32118(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 36518(931) 275/8(702) 107/8(276) 3318(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 36518(931) 275/8(702) 107/8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 335 /8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) _ 113/4(298) 10 1393(637) 445/8(1134) 335 /8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 2 2100(991) 505/8(1287) 3958(1007) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469116(1183) 1818(460) 338(86) 137/8(352) 261/2(673) 167/8(429) 169/16(420) 18 4000(1887) 649/16(1640) 469/16(1183) 1818(460) 33/8(86) 1578(403) 261/2(673) _ 167/8(429) 169/16(420) PRODUCTNFORMAT10NGSUBJECTTOCHANGEVNTHOUTNOT10E 1/162002 101.YE .03114$t - IA.T04 CEDDERWAB37 M"°' 1 DEMON B 'EE` 10F 1 35N -202 -1 Air Terminals Builder 1.09e Page 87 of 169 Performance Summary For VAV -3 -3 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -3 Quantity' 1 Model Type' VAV - CCN Model' 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 12 Inch Hot Inlet Size' 12 Inch Part Number 35NC1C000L1212419000000S0001965095009500209 Outlet 11.9x11.9 Unit Performance Altitude' 0 ft Cold Max. Airflow 1,965 0 CFM Cold Min. Airflow 950 0 CFM Hot Max Airflow 950 0 CFM Hot Min Airflow' 209.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure .20 in wg Minimum Static Pressure Drop .70 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining:.... Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet:. 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,965.0 CFM Safety Factor Cold Inlet 6 % Maximum Airflow Hot Inlet' 2,085.0 CFM • Design Airflow Hot Inlet: - .. 950.0 CFM Safety Factor Hot Inlet:. 54 % Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: • Sound Power Levels, dB re 10E - 12 watts - " Cold Max. Airflow 1,965.0 CFM Hot Max Airflow 950.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 75 69 62 58 55 52 * Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 58 51 42 35 30 26 43 Discharge Sound Primary Sound (Pwl) 66 61 60 56 51 44 Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 37 31 19 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10" -12 watts. 4. Dash ( -) In space Indicates sound and/or NC value is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 88 of 169 Acoustics Summary For VAV -3 -3 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -3 Quantity 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 12 Inch Hot Inlet Size: 12 Inch Part Number 35NC1C000L121241900000050001965095009500209 Outlet .... ..11.9x11.9 Insulation: Other Information: Lining' Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,965.0 CFM Safety Factor Cold Inlet' 6 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet 950.0 CFM Safety Factor Hot Inlet' 54 % UnitLxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts " Cold Max. Airflow 1,965.0 CFM Hot Max Airflow' 950.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 75 69 62 58 55 52 * Total Attenuation 17 18 20 23..._ .25_ . 26 * Room Sound Level (Spl) 58 51 42 35 30 26 43 Discharge Sound Primary Sound (Pwl) 66 61 60 56 51 44 Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 37 31 19 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, is 10A -12 watts. 4. Dash ( -) In space indicates sound and/or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 89 of 169 VAV -3-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3-4 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 90 of 169 Unit Report For VAV -3-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3-4 Quantity 1 Model Type VAV - CCN Model: 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000400020002000052 Insulation Lining: Standard (1/2 inch dual density f/g liner) Outlet 6.9x6.9 Dimensions Unit Depth 35.9 in Unit Width 32.2 in Unit Height 8.9 in Unit Operating Weight • 31 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L060641900000 35N Dual Duct Terminals 1 050000400020002000052 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 91 of 169 • Certified Drawing for VAV -3-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM °OM ,HS anJerz anE>wre+n s sasscer cn nESE DLJALD CTVARAa.E Carrier OMER CCRPCRATCHMO IS f33hEFED OR CCO eta L nE EXPRESS mina ,a mES Par tasmJE 35N CATALOG# A United Teohnorogies Company C r CF 1ERNWILLNMIIH carycapisanarnacsaert 35NBASEUNFT- wri-cFnaolusruccEsscfEs CHART37ALIMIE SCN NQL.OESMETADAP1ER ALL041AIL EAST 3T(610)CLEARANCE 0 S L-y BUF6CF5 H I13" E D lip: I OA I c I C aril I W Wal d 1 D r 0 7 I E o ill Q VII 52rTP u1=: *I? ter) SE fTMALFEA7lJ DW • . INLET VIEW TOP VIEW DISCHARGE VIEW • SENSOR- LhearnitieccirtarbNa3nsoris CASING - stardardonstr LINER- 12' (KiTn1 R% tickglEicierslyirr. aR si yo[1 b - (1,481 Pa )Pal . - bsl4(241*n 3 ).Thishiviscoatedtopraerterostn, . 1 Ell adsFPA934 . Cpl B el • Walt 1 'p5mn DAMPERS . Cticnat Sbrinerisdakonsyslem13/1Ulticlvgd /a0iwrirel haticntiltcedmaisteansidaedgesseabd CFMlalF(1.49Pa)PS itrnashearrmAhsheellnetiz-shta UNITACCESSORES- • Opfro Ncirshaktcrsysian,wItnoilemal . OficrEterge6rada palid031i3182807L . Cp(cret 12tienwalaB station . Wart 1bisicapsdabdiaMon NOTE 1. Sensors are shown ininletand discharge, butane avai la ble in both inlets. 2 Pnetmaticconfrolsshown ,electonicareavaileble. 3 Dimensions areshawnasiidtes(mm). INLET NOMMAX DrSIHARGE S(TE CFM(Us) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(203) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99116(243) 77/8(200) 71/4(184) 7 , 650(307) 3658(931) 2758(702) 107/8(276) 336(86) 67/8(175) 159/16(395) 978(251) 91/4(235) 8 800(377) 3658(931) 27518(702) 107/8(276) 33/8(86) 778(203) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 4498(1134) 335/8(855) 127/8(352) 33x8(86) 87/8(225) 199/16(497) 1278(327) 113/4(298) 10 1350(537) 445 3358(855) 1278(352) 33x8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2100(991) 5056(1287) 395/8(1007) 1578(403) 33x8(86) 117/8(302) 239/16(598) 1478(387) , 141/4(362) 14 3200(1510) 589/16(1488) 469 /16(1183) 1818(460) 33x8(86) 137/8(352) 261/2(673) 1678(429) 169/16(420) 18 4000 (1887) 649/16(1640) 46906(1183) 181/8(460) _ 33/8(86) 1578(403) 2612(673) 167/8(429) 169/16(420) PRODUCT INFORMATION ISSUBJECTTOCHANGEWT HOUTNO110E 1/162002 a4SE .GBN.Ya'it {COCCN CRS WIW B I . 1 OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 92 of 169 Performance Summary For VAV -3-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3-4 Quantity 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type: 4190: VAV with DCV Cold Inlet Size: ...... .__ .__.. 6 Inch Hot Inlet Size' 6 Inch Part Number 35NC1C000L0606419000000S0000400020002000052 Outlet' 6.9x6.9 Unit Performance Altitude' 0 ft Cold Max. Airflow' 400.0 CFM Cold Min. Airflow 200.0 CFM Hot Max Airflow' 200.0 CFM Hot Min Airflow' 52.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop' . .44 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining:... Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow Cold Inlet' 400.0 CFM Safety Factor Cold Inlet' 23 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet' 200.0 CFM Safety Factor Hot Inlet' 62 % Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow' 400.0 CFM Hot Max Airflow' 200.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 61 57 47 42 40 35 * Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 44 39 27 19 15 < 10 27 Discharge Sound Primary Sound (Pwl) 65 63 57 50 44 37 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 36 33 16 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 93 of 169 Acoustics Summary For VAV -3-4 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name* VAV -3-4 Quantity' 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size' 6 Inch Hot Inlet Size' 6 Inch Part Number 35NC1C000L0606419000000S0000400020002000052 Outlet 6.9x6.9 Insulation: Other Information: Lining' Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow Cold Inlet 400.0 CFM Safety Factor Cold Inlet* 23 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet 200.0 CFM Safety Factor Hot Inlet 62 Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow' 400.0 CFM Hot Max Airflow' 200.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 61 57 47 42 40 35 Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 44 39 27 19 15 < 10 27 Discharge Sound Primary Sound (Pwl) 65 63 57 50 44 37 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 36 33 16 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) In space Indicates sound and/or NC value Is less than 10. ** Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 94 of 169 VAV -3 -5 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -5 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 95 of 169 Unit Report For VAV -3 -5 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM ‘li C Unit Parameters Tag Name' VAV -3 -5 Quantity' 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Unit and Inlet Size' 6 Inch Part Number 35NC1C000L0606419000000S0000280010001000052 Insulation Lining* Standard (1/2 inch dual density fig liner) Outlet 6.9x6.9 Dimensions Unit Depth' 35.9 in Unit Width' 32.2 in Unit Height 8.9 in Unit Operating Weight . 31 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L060641900000 35N Dual Duct Terminals 1 0S0000280010001000052 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 96 of 169 Certified Drawing for VAV -3 -5 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM oOM MR CGQABR en4r1 a aaeecn CF ,te Dlt4LDUCIVARIPE E 0 Carrier CARER CC CRU N ENDED NDED tRYY 01 69 CO3.143431 vw 3.3 EIWES3 oamw ,a Coca NM oasvenE Q�as�NM1atNE 3 CATALOG?, A United Technologies Company � OR rrgvr v tNMI1H JJI, ccapcomnesearrecaesee• COMIC,' ••E 35MBASEUM wn T- w navtusrr CHARTEDROIVENSCN NCLUDESILETAMPIER 2C(610)CLEARANCE . 0 S L 1 B Th6 1-..— H d ❑ I *is I I NET c E I W ' F r 1�1I' NET (1 E o 611StireP am' +, I SEECPICNALMATUFESEELON INLET VIEW TOP VIEW DISCHARGE VIEW • SENSOR- LileartniplepitaifonsErsoris CASING- serdardonal nle LINER- 12' (Gni r $Q tibciad yi kahsbodydaslyafl5. (1.49cPa)Ps.4 • _ .. • adreethascliernaleciJL181attsFPPECIA I t Ettrrecomspret • Op6onat 1 DAMPERS - rate ae . Wont Stednerialalbnsyrsern13167idagd /ooturks1 eigessealed CFMarY14EPa Ps UNITACCESSORIES- . Cpbonst Noherhalafonsysta>w rtef . Opetnatergetralets paetarldastal . Op evt 12 . Wart Ttiencapmiaixtralatort NOTE 1. Sensorsareshcmnininletanddischarge , butare available in both inlets. 2 Pneunaticmntrols shown, etearonicareavailable. 3 Diner >sionsare shown as inches (mm). MET Nd 8 X DISCHARGE S2E CFMNS) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 32118(816) 215/8(550) 87 /8(225) . 53/8(137) 47 /8(124) 99/16(243) , 77 /8(200) 71/4(184) 6 450(212) 32118(816) 215/8(550) 87 /8(225) 33/8(86) 57 /8(149) 99116(243) 77 /8(200) 71/4(184) 7 650(307) 36518(931) 275/8(702) 107 /8(276) 33/8(86) 67 /8(175) 159/16(395) 97 /8(251) 91/4(235) 8 800(377) 365/8(931) 275/8(702) 107 /8(276) 33/8(86) 77 /8(200) 159/16(395) 97 /8(251) 91/4(235) 9 1050(495) 445/8(1134) 335 /8(855) 127 /8(352) 3343(86) 87 /8(225) 199/16(497) 127 /8(327) 113/4(298) 10 1350(637) 445/8(1134) 335/8(855) 127 /8(352) 33/8(86) 97 /8(251) 199/16(497) 127 /8(327) 113/4(298) 12 2103(991) 505/8(12871 39518(1007) 157 /8)403) 33/8(86) 117 /8(302) 239/16(598) 147/8(387) 141/4(362) 14 3270(1510) 589/16(1488) 469/16(1183) 181 /8(460) 3303(86) 137 /8(352) 2612(673) 167 /8(429) 169/16(420) 16 4000 (1887) 649/16(1640) 469 /16(1183) _ 181 /8(460) 33/8(86) 157 /8(403) 2612(673) 167 /8(429) . 169/16(420) PRODUCTINFORMATIONISSUBJECTTOCH NGEWTHOUTNOT)CE 1/162002 -SAYE °WAR ii tCGVW QtWNGNO3331 RASA • ' " new B I 10F 1 35N-202 -1 Air Terminals Builder 1.09e Page 97 of 169 Performance Summary For VAV -3 -5 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -5 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000280010001000052 Outlet 6.9x6.9 Unit Performance Altitude' 0 ft Cold Max. Airflow 280 0 CFM Cold Min. Airflow 100 0 CFM Hot Max Airflow 100 0 CFM Hot Min Airflow' 52.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure' 20 in wg Minimum Static Pressure Drop' .22 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet' 521.0 CFM Attenuator No Design Airflow Cold Inlet 280.0 CFM Safety Factor Cold Inlet 46 % Maximum Airflow Hot Inlet' 521.0 CFM Design Airflow Hot Inlet 100.0 CFM Safety Factor Hot Inlet 81 % Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E -12 watts " Cold Max. Airflow' 280.0 CFM Hot Max Airflow' 100.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 57 54 44 39 37 34 * Total Attenuation 17 18 20 23 25 26 " Room Sound Level (Spi) 40 36 24 16 12 < 10 24 Discharge Sound Primary Sound (Pwl) 61 60 54 47 41 34 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 32 30 13 < 10 < 10 < 10 16 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10 " -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value Is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 98 of 169 Acoustics Summary For VAV -3 -5 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -5 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000280010001000052 Outlet .... 6.9x6.9 Insulation: Other Information: Lining Standard (1/2 Inch dual density fig liner) Maximum Airflow Cold Inlet: 521.0 CFM Attenuator No Design Airflow Cold Inlet 280.0 CFM Safety Factor Cold Inlet: 46 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet 100.0 CFM Safety Factor Hot Inlet 81 % Unit LxWxH: 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 280.0 CFM Hot Max Airflow 100.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 57 54 44 39 37 34 ` Total Attenuation 17 18 20 23 25 .26 Room Sound Level (Spl) 40 36 24 16 12 < 10 24 Discharge Sound Primary Sound (Pwl) 61 60 54 47 41 34 Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 32 30 13 < 10 < 10 < 10 16 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 "42 watts. 4. Dash ( -) In space Indicates sound and/or NC value Is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Cartier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 99 of 169 VAV -3 -6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -6 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 100 of 169 Unit Report For VAV -3 -6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM - s Unit Parameters Tag Name" VAV -3 -6 Quantity" 1 Model Type" VAV - CCN Model" 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Unit and Inlet Size" 8 Inch Part Number 35NC1C000L0808419000000S0000655030003000093 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet" 8.9x8.9 Dimensions Unit Depth" 39.2 in Unit Width" 36.2 in Unit Height 10.9 in Unit Operating Weight . 42 lb "• Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L080841900000 35N Dual Duct Terminals 1 050000655030003000093 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 101 of 169 Certified Drawing for VAV -3 -6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM ttCE „o IID6!@R one r v sa®on CF n� DilN t>tlCNAf E 0- Carrier fM131 CCFREFV3133 N13 1e0E1NEED 1313313333tliO3:u434a uw of EItRE59 =MOH l/a OOE3 Wf vwVITP.QL . 35N 13ECCRE339MUNTMEDECLOSED ANN CAT# A United Technologies Company 7 a 7lRMAILN1 WOH CCFFERVIENTWORTOCCFEENT * Z p��� 36NBASEUNrT- Na-cFna44LLNrp CHARTECOAAIVENSCN NCLLTADAPTER ALLOMTLEAST 2410)CLEARANCE FOFCCNIFCIS L--y EIC+)F H 1 0 7 o I I c lb E 1 ' W -// oral D ii,' N.ET W roszyrrp u1- 46 : r HAN3ERBRACKETOPLCE0 EEECFMCN41FEATh W INLET VIEW TOP VIEW DISCHARGE VIEW. SENSOR- Livarmultixdribilmsensoris CASING - sdrdadonalria LINER- 12' fide, ctEldaal*a.lafiorvAthabodytdanlyaf15 _ _ . ( )mil . .. .. . t>s WI:24101n 1. ThisIringiscoaledtopawrtercsicn, . Optnit 20ga gasfiriaxIstelmeh8 arinalshaEqiernalscLL181adsFPA934 . OptrEt gig . • Ctknat 11:25rnm )tiftatafareirgspeaka- DAMPERS- . Opionat Sterfiatalafonystm13/611idagd LasemetaxthhadErrpethsstenThattorrirel hakficrktifacalavitearmeitle,edgessealzd CFMa1611.4.EPd)Ps UNITACCESSOWES- • OpborEt Notlai>slabo►tsystrr4V rcitar>al . Cp(creFargerbades. pmetmdasa6an . Cpworlat 12Toiatcapslabednsion . C::onst 1'iaferxaps fak3dis/ NOTE 1. Sensors are shown in inletand discharge, butare available in both inlets. 2 Prseunaticoxdrelsshom, elecLnnicareavailable. 3 Dimensions are shwmas inches (mm). NJ:T NOMMAX 015CWIRGE Sly CFM(Us) I W H A D E F G 4 255(106) 321/3(816) 215/8(550) 87/8(225) 53/8(137) 37/8(981 99/16(243) 7718(200) 7114(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 518(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99(16(243) 77/8(200) 71/4(184) 7 650(307) , 3658(931) 27508(702) 107/8(276) 336(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 36518(931) 275/8(702) 107/8(276) 33x8(86) 7718(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 4458(1134) , 335/8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 12718(327) 113/4(298) 10 1350(637) 4458(1134) 335 /8(855) 127/8(352) 33/8(86) 9718(251) 199/16(497) 127/8(377) 11314(298) 12 2198(991) 5058(1287) 395/8(1007) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 14718(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 /16(1183) 1816(460) 33/8(86) 137/8(352) 2612(673) 167/8(429) 169/16(420) 19 4000(1887) 649/16(1640) 469/16(1183) 181/8(460) 336(86) 157/8(403) 2612(673) 167/8(429) 169/16(420) PRODUCTINFORMAT1p 4SSUBJECTTOCHANGEWTHOUTNOT ICE 1/1620 0 ARRAN 2913•3313 ICON N O pneaRE FFEEt . B I 1 35N -202 -1 Air Terminals Builder 1.09e Page 102 of 169 Performance Summary For VAV -3 -6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -6 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 8 Inch Hot Inlet Size 8 Inch Part Number 35NC1C000L0808419000000S0000655030003000093 Outlet 8.9x8.9 Unit Performance Altitude 0 ft Cold Max. Airflow 655 0 CFM Cold Min. Airflow 300 0 CFM Hot Max Airflow 300 0 CFM Hot Min Airflow:... 93.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure 20 in wg Minimum Static Pressure Drop .34 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 Inch dual density f/g liner) Maximum Airflow Cold Inlet 927.0 CFM Attenuator No Design Airflow Cold Inlet 655.0 CFM Safety Factor Cold Inlet 29 % Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot Inlet 300.0 CFM • Safety Factor Hot Inlet 68 % Unit LxWxH 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts Cold Max. Airflow' 655.0 CFM Hot Max Airflow 300.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 67 64 56 52 52 51 Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Spi) 50 46 36 29 27 25 35 Discharge Sound Primary Sound (Pwl) 68 63 58 52 46 38 ' Total Attenuation 29 30 41 53 55 41 ' Room Sound Level (Spl) 39 33 17 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) in apace Indicates sound and /or NC value Is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 103 of 169 Acoustics Summary For VAV -3 -6 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -6 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 8 Inch Hot Inlet Size' 8 Inch Part Number 35NC1C000L0808419000000S0000655030003000093 Outlet' 8.9x8.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 927.0 CFM Attenuator No Design Airflow Cold Inlet 655.0 CFM Safety Factor Cold Inlet 29 % Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot Inlet 300.0 CFM Safety Factor Hot Inlet 68 % Unit LxWxH 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 655.0 CFM Hot Max Airflow' 300.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC • Primary Sound (Pwl) 67 64 56 52 52 51 * Total Attenuation 17 18 20 23 25 26 - Room Sound Level (Spl) 50 46 36 - 29 27 25 35 Discharge Sound Primary Sound (Pwl) 68 63 58 52 46 38 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 39 33 17 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 wafts. 4. Dash ( -) In space indicates sound and/or NC value is less than 10. ** Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Cartier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 104 of 169 VAV -3 -7 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -7 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 105 of 169 Unit Report For VAV -3 -7 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM It,' °I N, a.A Unit Parameters Tag Name VAV -3 -7 Quantity* 1 Model Type* VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 12 Inch Part Number* 35NC1C000L1212419000000S0001795085008500209 Insulation Lining* Standard (112 inch dual density fig liner) Outlet 11.9x11.9 Dimensions Unit Depth 51.9 in Unit Width 46.2 in Unit Height 15.9 in Unit Operating Weight • 80 lb '•• Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L121241900000 35N Dual Duct Terminals 1 OS0001795085008500209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 106 of 169 Certified Drawing for VAV -3 -7 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM °g ne =ABC enes+are v a SUMMER a nrE DIIAIDUCNARABE 0 Carrier 9Yy@1 CCROM1174/IO IS CeMSFED Ot ORME= O we ,a WES ror A OO�ownc uNE 35N CATPLOG# A United Technologies Company ER c occEprotre a lEFIIIIYALLINIVVIH msvamawmemREIR m7r7 B,BWVB32 35NBASEUNEr- wt novul nrrc CHARTEDAAIVE '1 ICLI ESNETACAPTER ALLOAlk115 241610)CLEARANCE R 0 CMriQS L ECM4SCE+S r— H t ive l i. i ; I I -r IM NET o D E I W 10- F NET /]I II II iii I E o 9 sr li -; i - I 14 SECFMNALFEMUREEEELON INLET VIEW • TOP VIEW •DISCHARGE VIEW SENSOR- Lilearnlitleixiriairlonsensoris CASING - siardardonalrts • LINER- 12' (13mi) 1 P 4° � tslor4wdta tidc,aliensi todydad dl.5 (• . • bsku4241071 • Oricnd 20ga gaSaizedsMaelcasirg. 181ati■FPA934 d B±rrecaseparel • Qtd 1 "(25mn DAMPERS - . O SBediaisJabonsystrnl3/151fidayd /aafuri e hulattntikedonaisheamitlexdgEssealal CFMalet1A9Pa)Ps, UNITACCESSORIES- . Optad Notretialalionsgiarn d . Ogcna arga6radel paertxr dasatn. . Ogtost 12 . Oplmet liencapablecfraisicrt NOTE 1. Sensorsare shown in inlet and discharge, but are available in both inlets. 2 Pneunaticcontrolsshown ,elecronicareavailable. 3 Dimensions are shownasnches(mm). NET NOlYMAX 019CHARGE S2E CFMNa) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275 /8(702) 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8(702) 107/8(276) 33/8(86) 77/8(203) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 335 /8(855) 127/8(352) 3318(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 4458(1134) 335 /8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2100 (991) 5056(1287) 3958(10)7) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 /16(1163) 181/8(460) 33/8(86) 137/8(352) 2612(673) 167/8(429) 169/16(420) 16 4000(1887) 649116(1640) 469/16(1183) 181/8(460) 33/8(66) 157/8(403) 2612(673) 167/8(429) 169/16(420) PRODUCTPIFORAM110NISS UBJECTTOCHANGENTHOUTN0110E 1/16/2002 a."7 BREW. REVS.. B I 1 35N -202 -1 Air Terminals Builder 1.09e Page 107 of 169 Performance Summary For VAV -3 -7 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -7 Quantity' 1 Model Type' VAV - CCN Model* 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size* 12 Inch Hot Inlet Size' 12 Inch Part Number 35NC1C000L121241900000050001795085008500209 Outlet' 11.9x11.9 Unit Performance Altitude' 0 ft Cold Max. Airflow' 1,795.0 CFM Cold Min. Airflow' 850.0 CFM Hot Max Airflow' 850.0 CFM Hot Min Airflow' 209.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop' .59 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet' 2,085.0 CFM Attenuator No Design Airflow Cold Inlet' 1,795.0 CFM Safety Factor Cold Inlet' 14 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet* 850.0 CFM Safety Factor Hot Inlet 59 % Unit LxWxH' 51.9 x 46.2 x 15.9 Acoustic Summary: • Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow' 1,795.0 CFM • Hot Max Airflow' 850.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 74 68 61 57 55 52 * Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 57 50 41 34 30 26 41 Discharge Sound _Primary Sound (Pwl) 66 61 59 55 50 43 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 37 31 18 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from teats conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) in space Indicates sound and /or NC value Is less than 10. •• Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Cartier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 108 of 169 Acoustics Summary For VAV -3 -7 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -7 Quantity 1 Model Type VAV - CCN Model' 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0001795085008500209 Outlet 11.9x11.9 Insulation: Other Information: Lining:... Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,795.0 CFM Safety Factor Cold Inlet 14 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet 850.0 CFM Safety Factor Hot Inlet 59 % Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 1,795.0 CFM Hot Max Airflow 850.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 74 68 61 57 55 52 Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Spl) 57 50 41 34 30 26 41 Discharge Sound Primary Sound (Pwl) 66 61 59 55 50 43 Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 37 31 18 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 wafts. 4. Dash ( -) In space Indicates sound and /or NC value Is less than 10. *" Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 109 of 169 • VAV -3 -8 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -8 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 110 of 169 Unit Report For VAV -3 -8 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -8 Quantity' 1 Model Type' VAV - CCN Model' 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Unit and Inlet Size' 8 Inch Part Number:.... 35NC1C000L0808419000000S0000720035003500093 Insulation Lining: Standard (1/2 inch dual density fig liner) Outlet 8.9x8.9 Dimensions Unit Depth' 39.2 in Unit Width 36.2 in Unit Height' 10.9 in Unit Operating Weight . 42 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimansiors are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty - Ordering Information Part Number Description Quantity Base Unit 35NC1C000L080841900000 35N Dual Duct Terminals 1 050000720035003500093 4190: VAV with DCV ,Hangers Accessories Air Terminals Builder 1.09e Page 111 of 169 Certified Drawing for VAV -3 -8 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM CCCE 0- Carrier no commaa eni ry D* SMARM O. nrg DUYLLDUC1VANA6LE Carrier CM1 I9 ®NEFED 6WNfS OR RII/.Bn9 �+ E t COCIE t MR CCE9 NA 0:N51mlE 1JVE 35N CATPLGG# A United Technologies CompanyCR Lea WMA 0, Ac CF 35NBASEUNFT Vf1 LLNfP0CES9CfiES CHARTEDAUNE SCN NOLLCESNETADAPTER ALl OMMEAST . 24*(610JCLEARANCE 0 S L B dIFC ES H d e lii i 1 r s I I . ' I o i�Er E I W loll NLEr II ! b D iii `( i 1 l E o cz g1 ' Ii�1 �� r HA r{4PLJ i SEEoP CNA FFAnFE ON . INLET VIEW TOP VIEW . DISCHARGE VIEW. SENSOR- Livarrnfpecoitadomenscris CASING- slardadc alnas LINER- 12' 113»ll P *G% fidcdteld aslyonala.ortwihabodydersiyo..S ... .. ._. . (1.491Pa si . _ . .. 41gn 181ar topr • Wort 0pfaxt 1 5mn . �- Bordrr>a�Jere! . Op6met SfarinerFsUadionsyslEm13 161tidaicjd /aoharrial haJafalbifaceJonaisbeanside,edgEsseakl CFMa6(1.49Pa)Ps fanaistearrwlhateetmelEiz-shts. UNRACCESSORIES- • qtr . CptnsitergahradEis. paelardasatn . Cgcnat 12 . Walt l'bbnapatatacfnalaton NOTE 1. Sensors are shown in inlet and discharge , balers availablein both inlets. 2 Poe= afic controls shawl, eleWOnic are available. 3 Dimerubre are shown as etches (mm). MET NOMMAX - 019CM1RGE SZE CRM(L) L W H A 0 E F G 4 255(106) 321/8(816) 215/8(550) 8718(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 6 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 9916(243) 77/8(200) 71/4(184) 8 450(212) 321/8(816) 215/8(550) 87/8(225) 3318(85) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 36518(931) 2758(702) 107 /8(276) 33/8(86) 6718(175) 159/16(395) 97 /8 (251) 91/4(235) 8 800(377) 365/8(931) 275/8(702) 107 /8(276) 33/8(86) 77 /8 (200) 159/16(395) 97 /8(251) 91/4(235) 9 1050(495) 445/8(1134) 3358(855) 127 /8(352) 3318(86) 87 /8 (225) 199/16(497) 127 /8(327) 113/4(298) 10 1350(637) 445/8(1134) 335 /8(855) 127 /8(352) 33/8(86) 97 /8 (251) 199/16(497) 127 /8(327) 113/4(298) 12 2103(931) 505 /8(1287) 395/8(1007) 157 /8(403) 33/8(68) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469 /16(1183) 181 /8(460) 33/8(86) 137 /8(352) 2612(673) 167 /8(429) 169/16(420) 18 4000 (1887) 649/16(1640) 469 /16(1183) 181 /8(460) 33/8(86) 157 /8(403) _ 2612(673) 167 /8(429) 169/16(420) PRODl1CTIN FORMAT) ON /8SUBJECTTOCHANGEWITHOUrNOT10E 1 /162032 .01AUME .00.0461 =RCN OURRGINLORWR 'ice` 10F 1 35N -202 -1 B Air Terminals Builder 1.09e Page 112 of 169 • Performance Summary For VAV -3 -8 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3-8 Quantity 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 8 Inch Hot Inlet Size 8 Inch Part Number 35NC1C000L0808419000000S0000720035003500093 Outlet' 8.9x8.9 Unit Performance Altitude' 0 ft Cold Max. Airflow:.... .. 720 0 CFM Cold Min. Airflow 350 0 CFM Hot Max Airflow 350 0 CFM Hot Min Airflow 93 0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop' .41 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 927.0 CFM Attenuator No Design Airflow Cold Inlet 720.0 CFM Safety Factor Cold Inlet 22 % Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot Inlet • 350.0 CFM Safety Factor Hot Inlet' 62 % Unit LxVVxH 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts •• Cold Max. Airflow' 720.0 CFM Hot Max Airflow' 350.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 69 65 57 53 53 52 • Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Spl) 52 47 37 30 28 26 37 Discharge Sound Primary Sound (Pwl) 69 64 59 53 46 39 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 40 34 18 < 10 < 10 < 10 21 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) In space Indicates sound and/or NC value Is less than 10. •• Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 113 of 169 Acoustics Summary For VAV -3 -8 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -8 Quantity* 1 Model Type' VAV - CCN Model* 35N Dual Duct Terminals Control Type* 4190: VAV with DCV Cold Inlet Size' 8 Inch Hot Inlet Size' 8 Inch Part Number 35NC1C000L0808419000000S0000720035003500093 Outlet 8.9x8.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet' 927.0 CFM Attenuator No Design Airflow Cold Inlet 720.0 CFM Safety Factor Cold Inlet:. 22 % Maximum Airflow Hot Inlet' 927.0 CFM Design Airflow Hot Inlet' 350.0 CFM Safety Factor Hot Inlet 62 % Unit LxWxH 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts " Cold Max. Airflow 720.0 CFM Hot Max Airflow' 350.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 r 7 NC Primary Sound (Pwl) 69 65 57 53 53 52 * Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 52 47 37 30 28 26 37 Discharge Sound Primary Sound (Pwl) 69 64 59 53 46 39 • Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 40 34 18 < 10 < 10 < 10 21 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) in space Indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 114 of 169 VAV -3 -9 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -9 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 115 of 169 Unit Report For VAV -3 -9 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM 4.'1 0 Unit Parameters Tag Name' VAV -3 -9 Quantity' 1 Model Type' VAV - CCN Model' 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Unit and Inlet Size' 12 Inch Part Number 35NC1C000L1212419000000S0001780085008500209 Insulation Lining' Standard (1/2 inch dual density f/g liner) Outlet 11.9x11.9 Dimensions Unit Depth' 51.9 in Unit Width' 46.2 in Unit Height 15.9 in Unit Operating Weight * 80 lb "' Weights and Dimensions are approximate. Weight does not include curbs • and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L121241900000 35N Dual Duct Terminals 1 OS0001780085008500209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 116 of 169 Certified Drawing for VAV -3 -9 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM °g no coaster anEr n a aanma cr rase DIJALDI.TVARTAB.E Carrier C 033'03‘10/.0 13 °YI^•G5 net comas w pm ea 006171.33 aloosvwnaLrlE qe „ CATALOGS l A United Technologies Company �+�C OR 0 1EiaVNAl1NIWTH �1\ 07s31‘1136MR17FPCM6@If =MR BJEKINXHOMER 394aAsEVN11 - vvnizfircivsturrAcoasscRES CHARTETJAMENEld'1 ICUXE3N.ETADAP ER ALLOAINI E ST 241610)CLEARANCE 0 FLR17VrRaS L� BOIFSCFS H MET e k e I � 10 0> C D C:1 ar�1 I E W F FUT I 01 ►• , I E o IIMI • 1 MI.GEFERAOCE144PLLS INLET VIEW TOP VIEW DISCHARGE VIEW SENSOR- CASING- slandallonal is LINER- 12' Prrrt) % tid k rlwlhabcdfien lycf15 ( • )P teiaitip4Igtn glad v. 181ad&FPA9:14 . qnst Bolorrecilexerel . CrfcrEt 1'T(25mn DAMPERS - trsabae . Opfonat Slein3resUabonsisi2m13161lidetlid LaskageticultedarmetiEssitrrinditxriA halafalfoltacecknaistream-side,eclgessealed C '(1.4EPa)Ps UNITACCESSORIES- . Worst N Iner alla>sjsimp tnokt rated . Oplizsitenpbadels pe einrldasatn. . Spam l2 NOTE 1. Sensors are shownin inlet and discharge, Oa/tare available in both inlets. 2 Pneunaticoontrolsshowr >,electronicare available. 3 Dimensions ereshownas etches (mm). N.ET NDNA AX DISCHARGE WE CR/8L/) , L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99116(243) 77/8(2001 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 9916(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99116(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 33 67/8(175) 159116(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275 /8(702) 107/8(276) 3318(86) 77/8(200) 159116(395) 97/8(251) 91/4(235) 9 1050(495) 44518(1134) 335/8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 445/8(1134) 335 /8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2100(991) 50518(12871 395 157/8(403) 33/8(661 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(14881 469116(1183) 181/8(460) 33/8(86) 137/8(352) 2612(673) 167/8(429) 169116(420) 16 4000(1887) 649116(1640) 469/16(1183) 181/8(460) _ 33(8(86) _ 157/8(403) 2612(673) 167/8(429) 169/16(420) PROD) CTINFORMAT10NGSUBJECTTOCHANGEV4T HOUTNOTICE 1/162002 -GMAYe IswTa ow•owrst t EWER. B I s 10F 1 35N -202 -1 Air Terminals Builder 1.09e Page 117 of 169 Performance Summary For VAV -3 -9 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -9 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size' 12 Inch Part Number 35NC1C000L1212419000000S0001780085008500209 Outlet 11.9x11.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,780.0 CFM Cold Min. Airflow' 850.0 CFM Hot Max Airflow 850.0 CFM Hot Min Airflow 209.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop' .58 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet' 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,780.0 CFM Safety Factor Cold Inlet 15 % Maximum Airflow Hot Inlet' 2,085.0 CFM Design Airflow Hot Inlet 850.0 CFM Safety Factor Hot Inlet 59 °Ao Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E -12 watts **Cold Max. Airflow 1,780.0 CFM Hot Max Airflow' 850.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 74 68 61 57 55 52 * Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 57 50 41 34 30 26 41 Discharge Sound Primary Sound (Pwl) 66 61 59 55 50 43 ` Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 37 31 18 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with AR! Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 118 of 169 Acoustics Summary For VAV -3 -9 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -9 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 12 Inch Hot Inlet Size' 12 Inch Part Number 35NC1C000L1212419000000S0001780085008500209 Outlet 11.9x11.9 Insulation: Other Information: Lining Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,780.0 CFM Safety Factor Cold Inlet 15 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet' 850.0 CFM Safety Factor Hot Inlet 59 % UnitLxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts " Cold Max. Airflow 1,780.0 CFM Hot Max Airflow 850.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 74 68 61 57 55 52 * Total Attenuation _ 17 18 20. , 23 25 26 - Room Sound Level (Spl) 57 50 41 34 30 26 41 Discharge Sound Primary Sound (Pwl) 66 61 59 55 50 43 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 37 31 18 < 10 _ < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10" -12 watts. 4. Dash ( -) In space Indicates sound and/or NC value Is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 119 of 169 VAV -3 -10 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -10 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 120 of 169 Unit Report For VAV -3 -10 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM .. eil (.,,, 410 Unit Parameters Tag Name VAV -3 -10 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001200060006000145 Insulation Lining Standard (1/2 inch dual density fig liner) Outlet 9.9x9.9 Dimensions Unit Depth 48.6 in Unit Width 40.2 in Unit Height 13.9 in Unit Operating Weight • 61 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primaliiy for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L101041900000 35N Dual Duct Terminals 1 OS0001200060006000145 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 121 of 169 Certified Drawing for VAV -3 -10 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM • CCCE INS aoaae+r mTERC Fnn CF SAMSON CF TIME Q1W. NARde$E Carrier W WRIER OSIINi[)INDIe�NOEd CAW= O1=WPM 3 C uw DE EXPRESS cQdRN NC Cosa POT o>`BOME U VE // crnr IBivI.M CE CATALOGS United Technologies Company J /nee 6 lERYNALLNINTH ELEKNECHONEER 35141BASEUNIT- oin-cFroouNrAcamsows O1ARTED'AteENsoN NCLIX SNMADAPTER ALLOWLE0ST 24'(610)cLEARANCE FCFCCNIFCLS Q L--.{ EORT r.-- H id", Iiiii I I *IS 1 I� NET c E 1 I W - F I �,/ D '•* , �i1 1 E o iiii • - I - HANGERERACKETOPLCS) SE TCNAIFEATI ON INLET VIEW .. - TOP VIEW DISCHARGE VIEW SENSOR- Linearratipapoirtailaysersais CASING - standardona4nis. seaSzereatinethaireiallo LINER- 12' 03Tn1 pmenbacayttrhalrtroilarrrAdarbACT tickdualdalsValafiorr neEtodydaslyOf15 .... . ...... (1.4S4 . ...... . tekulf24101 $ 181ad'FPA934 . Cgut BOtirreCOMEME4 . O � s bs a 11;25nrn DAMPERS- . C goret Slairerhalafiarrsysbam13 /151Fidvijd /dcfiomeel halaficntitamdcnaisbeEnwile,edgessBabd C Maffi (1.4EPa Ps UNITACCESSORIES- . qfa at Noi>eli 6or n . calba inaitmENtarektalarcriamarniendedto pe,a ontrise JL . . Ogmat 12'bierrdpalabe alatn. - . Op(tnat T'biawpstabdralafion NOTE 1. Sensors are shown in inletand discharge, but are available in both inlets. 2 Pneurnaticmntols shown, eleCtrcnicareavailable. 3 Dimensionsare shown asixhes(mm). PLE7 NDMMAX DISCHARGE S ZE CFM(L/s) L W H A D E F G 4 255(106) 321 /8(816) 21518(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 21 5/8(550) 87/8(225) 5318(137) 47/8(124) 99(16(243) 77/8(200) 71/4(184) 6 450(212) 32118(816) 215/8(550) 87/8(225) 33(8(86) 57/8(149) 99 7718(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 10718(276) 33/8(86) 67/8(175) 159 97/8(251) 91/4(235) 8 800(377) 365/8(931) 27518(702) 107/8(276) 33/8(86) 77/8(200) 159(16(395) 97/8(251) 91/4(235) 9 1050(495) 445+8(1134) 335/8(855) 12718(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 1() 1350(637) 445/8(1134) 3356(855) 127/8(352) 3318(86) 9718(251) 199(16(497) 127/8(327) 113/4(298) 12 2100(991) 505/8(1287) 3958(1007) 157/8(403) 33/8(66) 11 7/8(302) 239(16(598) 147/8(387) 14114(36'1) 14 3200(1510) 589/16(1488) 469116(1183) 1818(460) 33/8(66) 1378(352) 261/2(673) 167/8(429) 169/16(420) 18 4000(1887) 649/16(1640) 469(16(1183) 1818(460) 33/8(86) 1578(400) 2612(673) 167/8(429) 169(16(420) PROOUCTINFORMAT1ONISSUBJECTTOCHANGEW THOUnNOT10E 1/162002 ZENWE .02N/1H8i IC'A1[N CFUI.OrUI.®t EJVet alnEi• REV1934 ' B E` IOF 1 . 35N -202 -1 Air Terminals Builder 1.09e Page 122 of 169 Performance Summary For VAV -3 -10 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -10 Quantity* 1 Model Type' VAV - CCN Model* 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size* 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001200060006000145 Outlet' 9.9x9.9 Unit Performance Altitude' 0 ft Cold Max. Airflow' 1,200.0 CFM Cold Min. Airflow* 600.0 CFM Hot Max Airflow* 600.0 CFM Hot Min Airflow' 145.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop .64 in wg Note: Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet:... 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,200.0 CFM Safety Factor Cold Inlet' 17 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 600.0 CFM Safety Factor Hot Inlet' 59 % Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts " Cold Max. Airflow' 1,200.0 CFM Hot Max Airflow 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 62 59 53 49 47 42 • Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Spl) 45 41 33 26 22 16 29 Discharge Sound Primary Sound (Pwl) 61 61 57 54 50 43 Total Attenuation 29 30 41 53 55 41 • Room Sound Level (Spl) 32 31 16 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) In apace Indicates sound and/or NC value Is less than 10. •' Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 123 of 169 Acoustics Summary For VAV -3 -10 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -10 Quantity 1 Model Type* VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size' 10 Inch Part Number 35NC1C000L1010419000000S0001200060006000145 Outlet 9.9x9.9 Insulation: Other Information: Lining Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow Cold Inlet' 1,200.0 CFM Safety Factor Cold Inlet 17 % Maximum Airflow Hot Inlet' 1,448.0 CFM Design Airflow Hot Inlet' 600.0 CFM Safety Factor Hot Inlet 59 % Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts " Cold Max. Airflow' 1,200.0 CFM Hot Max Airflow' 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 62 59 53 49 47 42 * Total Attenuation 17 18 20 23 25 26 Room Sound Level (Spl) 45 41 33 26 22 16 29 Discharge Sound Primary Sound (Pwl) 61 61 57 54 50 43 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 32 31 16 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from teats conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Cartier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 124 of 169 VAV -3 -11 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -11 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 125 of 169 Unit Report For VAV -3 -11 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM ......i..", r VIZ _- Unit Parameters Tag Name VAV -3 -11 Quantity 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 10 inch Part Number 35NC1C000L1010419000000S0001310060006000145 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet 9.9x9.9 Dimensions Unit Depth 48.6 in Unit Width 40.2 in Unit Height 13.9 in Unit Operating Weight • 61 lb "' Weights and Dimensions are approximate. Weight does not include curbs • • and accessories. Approximate dimensions are provided primarily for . shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L101041900000 35N Dual Duct Terminals 1 060001310060006000145 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 126 of 169 Certified Drawing for VAV -3 -11 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM oaZ w tzaAeir sTEPpo W y a a9Geon a mesa ClUALDUCIVARABLE 6- Carrier OYAER OMiW MD is ®n 010:QA Tn uoi ne a�a sa deer b. aa'sm archsrmauvE CATALOG!! A United Technologies Company OR LREOsNa1 Cn R CP IERRMINIWIN NAT FORSINCE 35N p��+� aRVOCNWENemae vaw rt C¢r EILEICINDNONEER 35N6'ASEUN T- f CHART137ALWENS CN NCIICESKETACAPIER ALLQ 1411EAST 24161 FCFCCNIFIZIS 0 L--.1 BQTF$GE.S H o S E I W ' KU I , ., II o i E o ii Qj 61t54TYP UM: wwcE na�T#P CS1 T SEECPIENALFEATLFESEELON INLET VIEW TOP VIEW DISCHARGE VIEW . SENSOR- LinearrnAtiemetailbnearsoris CASNG- sTardadar LINER- 12' 03111 P $ 4idccIalder ,siyialabor>Ahitodydaniyf1.5 (1.494 4$n 8 achealsteafjerretclUL181atisFPA934 . glad . Ocibiat 11251tm DAMPERS - EaitelnchacmgEgasketlarpar . Opfiatat StEdratalaficnsAem13161hiciaijd LarkgivaqttEdarparigestanachrreel ia13631 ed9esseedd CFM9611.48Pa)Ps UNRACCESSORIES- • CpEcnst Nolnethaisionsisk2nw1frnikrtsi . CpBudrrabtalaalel5. pmertartnedm. . Opbrt 12 . Waist l'bien NOTE 1. Sensorsare shown in inletand discharge, butare available in both inlets. 2 Pneunaticcatrols shown, elearonicareavailable. 3 Dimertsioreareshownasechos(mm). LET - NOMMAX - - - E SIZE CR/?(L) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) S 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8(702) 10718(276) 33/8(86) 77/8(200) 15 W16(395) 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 335/8(855) 127/8(352) 3343(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 44543(1134) 335/8(855) 127/8(352) , 3318(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2103 (991) 505/8(1287) 395 /8(1007) 157/8(403) 33/8(56) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1488) 469/16(1183) 18118(460) 33/8(86) 137/8(352) 2612(673) 167/80429) 169/16(420) 16 4000(1887) 649/16(1640) i 469/16(1183) _ 18118(460) 33/8(86) 157/8(403) 2612(673) 167/8(429) _ 169/16(420) PRODUCTWFORMATIONISSU (3JECTTOCH4NGEWRHOUTNO110E 1/162002 A3N510 dRNMeW taGL+ CRw.oaaie SET B I 10F 1 `N -202 -1 Air Terminals Builder 1.09e Page 127 of 169 Performance Summary For VAV -3 -11 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -11 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L101041900000080001310060006000145 Outlet* 9.9x9.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,310.0 CFM Cold Min. Airflow 600.0 CFM Hot Max Airflow 600.0 CFM Hot Min Airflow 145.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure 20 in wg Minimum Static Pressure Drop .77 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,310.0 CFM Safety Factor Cold Inlet 10 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 600.0 CFM Safety Factor Hot Inlet 59 oh Unit LxVb H• 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts - Cold Max. Airflow 1,310.0 CFM Hot Max Airflow 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 63 59 54 50 48 43 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (SpI) 46 41 34 27 23 17 29 Discharge Sound Primary Sound (Pwl) 61 62 58 55 50 44 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 32 32 17 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880-90. 3. Sound power levels are In decibels, re 10 * -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value is less than 10. '• Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Cartier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 128 of 169 Acoustics Summary For VAV -3 -11 Project: Triangle Point Shell • 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -11 Quantity .... 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size ... ......... _ 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001310060006000145 Outlet_ ................... ........._..................... _ ...... 9.9x9.9 Insulation: Other Information: Lining: Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator .. No Design Airflow Cold Inlet 1,310.0 CFM Safety Factor Cold Inlet 10 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet: 600.0 CFM Safety Factor Hot Inlet 59 ok Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E -12 watts ** Cold Max. Airflow 1,310.0 CFM Hot Max Airflow 600.0 CFM • Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 63 59 54 50 48 43 * Total Attenuation 17 18 20 23 .. 25 26 Room Sound Level (Spl) 46 41 34 27 23 17 29 Discharge Sound Primary Sound (Pwl) 61 62 58 55 50 44 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 32 32 17 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Cartier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 129 of 169 VAV -3 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -12 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 130 of 169 Unit Report For VAV -3 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM fA <r - Unit Parameters Tag Name VAV -3 -12 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0002060100010000209 Insulation Lining Standard (1/2 Inch dual density fig liner) Outlet 11.9x11.9 Dimensions Unit Depth 51.9 in Unit Width 46.2 in Unit Height 15.9 in Unit Operating Weight • 80 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L121241900000 35N Dual Duct Terminals 1 OS0002060100010000209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 131 of 169 Certified Drawing for VAV -3 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM °g na maaen enorakxrr o aansw cc n DJAL UCIVAIaAeLE Carrier CORM 0TiOMi01MOISCRAM" °""'321CR 3 1.1.0.4 714 cocoas 1. mes TOT awmure OiDU 6QINM1aLJYE CATA# A U Ile d Technologies Company CR USW M.:Ur . C c 1 14AUMIWIH 35NBA\SEUNTr- va-cFrovaffr/ cHARTEDAMENE CN I/If LIXE.SMETALAPTER ALLOAATLEAST 241610)CLEARANCE FCRCOJIRa3 O L j B11-ECES H de Hail I I .r I 2 ii. O W Er l D ~ I - j E I W ' F Oa D ■11 NET U II 51,E iE-" 40 - 1 - HANGERERACHER4PLCS) .. _ • INLET VIEW TOP VIEW DISCHARGE VIEW • - SENSOR- Lhearrnitlep3kiladcwsirscris CASING - sardonak LINER- Thebasantigretntrisndard12' Prni P Q tidgd(LaldallyieJafrn,m` ?sbodydat koll5 ( • tstuft(244m 1• 8 • 181artdsFPA904 . Opkrat gig . Opkutat 1 "(25mn )tiltaisfonmeefrgspedca- DAMPERSS- trsabote . Opkmat Ssdneri>stlatonsyslan131 1Itagd /eohonia itsLta _ P's edge sealad OFMar UNITACCESSORIES- . 01*xat Nolroisilaknsyskarrtwencilenal . CpSzratargattadasts Pre ondensa>In . c onat 12131En aceiA kulaio . . Opkmat 1' NOTE 1. Sensorse estawn n inlet and discharge, butane available in both inlets. 2 Pne<maticcaWolsshavr elearonicareavailable. 3 Dimensions are shown as inches (mm). PSEr NOrYI a cesco e ST2E CFA(Us) L W H A 0 E F G 4 255(106) 321/8(816) 2198(550) 87/8(225) 53/8(137) 37/8(98) 99'16(243) 77/8(203) 71/4(184) 6 350(165) 321/8(816) 215)8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 7718(200) 71/4(184) 8 450(212) 321/8(816) 21518(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 7718(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 10718(276) 3318(86) 67/8(175) 159/16(395) 9718(251) 91/4(235) 8 800(377) 3698(931) 2758(702) 107/8(276) 33/8(86) 77/8(203) 159/16(395) 9718(251) 91/4(235) 9 1050(495) 445/8(1134) 335 /8(855) 127/8(352) 33/8(66) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(537) 445/8(1134) 335 /8(855) 127/8(352) 33/8(66) 97/8(251) 199/16(497) 12718(327) 113/4(298) 12 2100(991) 505 3958(1007) 157/8(403) 3318(86) 117/8(302) 239/16(598) 14718(387) 141/4(352) 14 3200 (1510) 589/16(1488) 469116(1183) 181/8(460) 398(86) 137/8(352) 2612(673) 1676(429) 169/16(420) 16 4000(1887) 649116(1640) 469/16(1183) _ 181/8(460) _ 3318(66) 157/8(403) 261/2(673) 16718(429) 169/16(420) PRODUCTINFO/8 A11oNISSUBJECTTOCHANGEv4TH(JTNOT10E 1 /162000 ASA. ,CEIPAREGI =RCP owwaw.37 PIPER 'R'°°' I B ' I OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 132 of 169 Performance Summary For VAV -3 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -12 Quantity 1 Model Type* VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0002060100010000209 Outlet 11.9x11.9 Unit Performance Altitude 0 ft Cold Max. Airflow 2,060.0 CFM Cold Min. Airflow 1,000.0 CFM Hot Max Airflow* 1,000.0 CFM Hot Min Airflow 209.0 CFM Inlet Static Pressure* 1.00 in wg Downstream Static Pressure* 20 in wg Minimum Static Pressure Drop 77 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 2,060.0 CFM Safety Factor Cold Inlet 1 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet 1,000.0 CFM Safety Factor Hot Inlet 52 % Unit LxWxH• 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts • ** Cold Max. Airflow 2,060.0 CFM Hot Max Airflow 1,000.0 CFM Octave Bands (dB) • Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 76 69 62 58 55 52 • Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Spl) 59 51 42 35 30 26 44 Discharge Sound Primary Sound (Pwl) 66 62 60 56 51 44 • Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 37 32 19 < 10 _ < 10 < 10 19 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value is less than 10. Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 133 of 169 Acoustics Summary For VAV -3 -12 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -12 Quantity* 1 Model Type* VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size* 12 Inch Hot Inlet Size' 12 Inch Part Number 35NC1C000L1212419000000S0002060100010000209 Outlet 11.9x11.9 Insulation: Other Information: Lining* Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 2,060.0 CFM Safety Factor Cold Inlet 1 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet 1,000.0 CFM Safety Factor Hot Inlet 52 % Unit LxWxH 51.9 x 46.2 x 15.9 • Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 2,060.0 CFM Hot Max Airflow* 1,000.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 76 69 62 58 55 52 . Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 59 51 42 35 30 26 44 Discharge Sound Primary Sound (Pwl) 66 62 60 56 51 44 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (SpI) 37 32 19 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10 watts. 4. Dash ( -) in space indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 134 of 169 VAV -3 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -13 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 135 of 169 Unit Report For VAV -3 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM iw Unit Parameters Tag Name' VAV -3 -13 Quantity' 1 Model Type' VAV - CCN Model' 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Unit and Inlet Size' 12 Inch Part Number 35NC1C000L1212419000000S0001070050005000209 Insulation Lining: Standard (1/2 inch dual density fig liner) Outlet' 11.9x11.9 Dimensions Unit Depth' 51.9 in Unit Width' 46.2 in Unit Height' 15.9 in Unit Operating Weight • 80 lb "' Weights and Dimensions are approximate. Weight does not include curbs - and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L121241900000 35N Dual Duct Terminals 1 OS0001070050005000209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 136 of 169 Certified Drawing for VAV -3 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM 0:17E NS corer nn w a as�oH a TES: DUALDUCTVARYIB.E Carrier � -°3"O° ° °R°°° ^° ICY M' 35N i ua4 11E owrEss .i.O 5 ,.c xv Mt msnue VwV V��Kaa CA7AiOGe A united Technologies Company cRThewaiN9n1N3181usm wilar GwiEm I ff COECIIMPISAS 35NBASEUNIT- WTHCPTUNALINTACOESSIZFES Q ARTffiAME SIGN Ng1lETADAPIEi ALlAMALEAST 241810)CLEARAME O F'QJIAQS L BOIF6CE5 H d0 1 I I BS 1 71 t 2 o NET E I W ' F NET ILt I Q eVeZfrYP Ii•- - 7 HoICERBRACKETOPUM4 SEECPTICINKFEAILRESEELON INLET VIEW TOP VIEW DISCHARGE VIEW.. SENSOR- LivermuVlepoitaitomerrioris CASLNG- stardardoro LINER- 12' (13ml Pte • etke lJatl rxiLynaJakn abodydet4,c415 (1.491cd)Ps1 ... tsehi6(2410) '). . OptrEt 20ga 9a\aizedsleelcas8 181adTPA904 gpyrlgg . C tcnst 1'125rrn DAMPERS- . 01:6Q)at 13116Uidayd /oot alnal hstatalttfacatnaisbeansdeolg358eakd CFMate 1.4EPa)Ps UNITACCESSORIES- • Op6a>at IstinatislatnsyslErnwIrcitma . C pram rgatradals. imErtaidemelka . 00311 12 . C licnat TToierapstadi Edatal NOTE 1. Sensasare shown in inkstand discharge, butare available in both inlets. 2 Pnessnaticcontolsshown, electronicareavailable. 3 Dimenstnsareshownasnches(mm). NIT 98 X DISCHARGE SUE CFiNPls) L • W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 8778(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 7114(184) 8 450(212) 321/8(816) 21518(550) 87/8(725) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 7114(184) 7 650(307) 365/8(931) 275 /8(702) 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8(702) 107)8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1063(495) 445/8(1134) 335 /8(855) 127)8(352) 33/8(86) 8718(225) , 199/16(497) 127/8(327) 113/4(298) V 1350(637) 44518(1134) 335/8(855) 127)8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 11314(298) 2 2100 (991) 50518(1287) 39543(1007) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200 (1510) 589/16(1468) 469 /16(1183) 181/8(460) 33/8(86) 137/8(352) 261/2(673) 167/8(429) 169/16(420) IS 4000(1887) 649/16(1640) _ 46916(1183) 181/8(460) 33/8(86) _ 157/8(403) 261/2(673) 167/8(429) 169/16(420) PRODUCTINFOR ATIONSSUSJECTTOCHANGEWTHOUTNOTICE 1/162002 LEWES .03K ILU1[N pwannwnEEl ,. B l'� 10F 1 35N -202 -1 AMA Air Terminals Builder 1.09e Page 137 of 169 Performance Summary For VAV -3 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -13 Quantity' 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 12 Inch Hot Inlet Size' 12 Inch Part Number 35NC1C000L1212419000000S0001070050005000209 Outlet 11.9x11.9 Unit Performance Altitude' 0 ft Cold Max. Airflow' 1,070.0 CFM Cold Min. Airflow' 500.0 CFM Hot Max Airflow* 500.0 CFM Hot Min Airflow 209.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop' .21 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (112 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,070.0 CFM Safety Factor Cold Inlet 49 % Maximum Airflow Hot Inlet 2,085.0 CFM • Design Airflow Hot Inlet 500.0 CFM Safety Factor Hot Inlet 76 % Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: • Sound Power Levels, dB re 10E 12•watts - ** Cold Max. Airflow' 1,070.0 CFM • Hot Max Airflow* 500.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 70 65 57 54 53 51 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 53 47 37 31 28 25 37 Discharge Sound Primary Sound (Pwl) 64 59 56 52 46 39 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 35 29 15 < 10 < 10 < 10 15 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, to 10 watts. 4. Dash ( -) In space indicates sound and /or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Cartier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 138 of 169 Acoustics Summary For VAV -3 -13 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -13 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size: 12 Inch Hot Inlet Size' 12 Inch Part Number 35NC1C000L1212419000000S0001070050005000209 Outlet 11.9x11.9 Insulation: Other Information: Lining Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,070.0 CFM Safety Factor Cold Inlet' 49 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet' 500.0 CFM Safety Factor Hot Inlet 76 % Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow' 1,070.0 CFM Hot Max Airflow 500.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 70 65 57 54 53 51 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 53 47 37 31 28 25 37 Discharge Sound Primary Sound (Pwl) 64 59 56 . 52 46 39 Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 35 29 15 < 10 < 10 < 10 15 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10" -12 wafts. 4. Dash ( -) In apace Indicates sound and/or NC value Is less than 10. Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 139 of 169 VAV -3 -14 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -14 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 140 of 169 Unit Report For VAV -3 -14 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Vir Unit Parameters Tag Name' VAV -3 -14 Quantity 1 Model Type: VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size:. 10 Inch Part Number 35NC1C000L1010419000000S0001200060006000145 Insulation Lining' Standard (1/2 inch dual density f/g liner) Outlet' 9.9x9.9 Dimensions Unit Depth' 48.6 in Unit Width' 40.2 in Unit Height' 13.9 in Unit Operating Weight . 61 lb •" Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L101041900000 35N Dual Duct Terminals 1 OS0001200060006000145 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 141 of 169 Certified Drawing for VAV -3 -14 Project: Triangle Point Shell 09/09/2010 • Prepared By: 04:11 PM • °XE T maaee spesece xn o 90650+ CF , WALDUCIVAR IA�E Carrier ^°° MD1e ° ° °CR 35N L he LOAM domes .a CM KIT dssmue CIiDQ6DYII{OIJVE CATS, A United Technologies Company v+� cot eccaimece or lERVINALLNIMI1H CCFFCR 06MimFNbfieR dMYGr ENyyy 35NBASEUNIT- �1,IVr ��M '.m G4WRTE7AU MENSI N 1CUXESNLETAGAPIER AL OAR1LEAST 241610)CLEARANCE FCRXNITCLS 0 L--.1 E71F6CES � H I r ' 2 o E 1 OM I W 0 W Er , ill !'.=1 E o TT SEEOP 1ONALFEi►nJ�nAI INLET VIEW . • TOP VIEW DISCHARGE VIEW . SENSOR- Lilearrnows2riscris CASING- sta rla ckna4n15 LINER- 12' . tlidcAtaldensiyiutladawalhE odyde l5. (1.4 a)Psl . n Et >; arkreettaaliErretd-L181adTPA934 . W g iel . C 1Q crEt 1'(Zrxlm DAMPERS- . Cpfa neritalabonsystem13rt64ick c1 Issicaxihn#itedarpatkeetrinrActicrtirel isidori edgesseebd CFMal6'(1.48Pa)Ps. UNRACCESSORIES- . OpecrEt NoF>aiata6oroisarr,wfiroitmal . CitonEirrgettadefs. peat xr dasa6ort . Cpiortat 12 . Cp crt# 1bia capalaBdralaliort NOM 1. Sensors are shown in inlet and discharge, but are available in both inlets. 2 PneumaticconWlsshwm ,elemmieareavailable. 3 Dimensions we shown asiidies(mm). P&Er NDMMAX - DISCHARGE SL1= CFM(L.) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 6 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 8 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 803(377) 365/8(931) 275 /8(702) 107/8(276) 318(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 335/8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 445/8(1134) 335 /8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2100 (991) 50513(1287) 395/8(1007) 157/8(403) 33/8(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200(1510) 589/16(1488) 469116(1183) 181/8(460) 33/8(86) 137/8(352) 2612(673) 16718(429) 169/16(420) 18 4000 (1887) 649/16(1640) 469/16(1183) 181/8(460) 33/8(66) 157/8(403) _ 2612(673) 167/8(429) 169/16(420) PRODUCTINFORMAT) ONISS LJBJECTTOQ4ANGEWTHOUTNOT)CE. 1/16/2002 , 3.0.4 , EIKAOM Lcu,a■ rnsmAKIWwEER OPER ate. 9EVISCro B I OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 142 of 169 Performance Summary For VAV -3 -14 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -14 Quantity 1 Model Type VAV - CCN Model* 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Part Number 35NC1C000L1010419000000S0001200060006000145 Outlet 9.9x9.9 Unit Performance Altitude 0 ft Cold Max. Airflow 1,200.0 CFM Cold Min. Airflow 600.0 CFM Hot Max Airflow 600.0 CFM Hot Min Airflow 145.0 CFM Inlet Static Pressure* 1.00 in wg Downstream Static Pressure 20 in wg Minimum Static Pressure Drop .64 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining:..... Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,200.0 CFM Safety Factor Cold Inlet 17 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 600.0 CFM Safety Factor Hot Inlet 59 ok Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts • ** Cold Max. Airflow 1,200.0 CFM Hot Max Airflow 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 62 59 53 49 47 42 • Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Spl) 45 41 33 26 22 16 29 Discharge Sound Primary Sound (Pwl) 61 61 57 54 50 43 ` Total Attenuation 29 30 41 53 55 41 • Room Sound Level (Spi) 32 31 16 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10" -12 wafts. 4. Dash ( -) In space Indicates sound and/or NC value is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 143 of 169 Acoustics Summary For VAV -3 -14 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -14 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 10 Inch Hot Inlet Size 10 Inch Part Number 35NC10000L1010419000000S0001200060006000145 Outlet 9.9x9.9 Insulation: Other Information: Lining Standard (1/2 Inch dual density f/g liner) Maximum Airflow Cold Inlet 1,448.0 CFM Attenuator No Design Airflow Cold Inlet 1,200.0 CFM Safety Factor Cold Inlet 17 % Maximum Airflow Hot Inlet 1,448.0 CFM Design Airflow Hot Inlet 600.0 CFM Safety Factor Hot Inlet 59 % Unit LxWxH 48.6 x 40.2 x 13.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 1,200.0 CFM Hot Max Airflow 600.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 62 59 53 49 47 42 * Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 45 41 33 26 22 16 29 Discharge Sound Primary Sound (Pwl) 61 61 57 54 50 43 Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 32 31 16 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) In space Indicates sound and /or NC value Is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 144 of 169 VAV -3 -15 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -15 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 145 of 169 Unit Report For VAV -3 -15 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM a Unit Parameters Tag Name VAV -3 -15 Quantity 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 6 Inch Part Number* 35NC1C000L0606419000000S0000380016001600052 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet* 6.9x6.9 Dimensions Unit Depth 35.9 in Unit Width' 32.2 in Unit Height 8.9 in Unit Operating Weight • 31 lb "• Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty • Ordering Information Part Number Description Quantity Base Unit 35NC1C000L060641900000 35N Dual Duct Terminals 1 050000380016001600052 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 146 of 169 • Certified Drawing for VAV -3 -15 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM o:CE t* ooaAe+r oTt TV a susea01 a heie CUALCUCIVAFIABLE 0 Carrier a+RImww,w MO lb ®Maim o.A,. C 11 C ,a � SHE 351 CATS# A United Technologies Company v+ w ,035 a IERNWII + tfliOMll? n SNgB10?a@ OAK.T !r O a e a se ® �BASEUMT wTFCPrK vainfracca9J CHARTE4ADIVBJ9:14 NCUXESPLETADAPIER ALLQM1LEAST 241610)CLEARANCE 1120 FMS L —•1 BOIF6[65 H d0 i: i I .r is I NE c E I W LT° F NET ��i l o -e r %�� yr 6 1 152 ITVP IE " 41IMI — I - FAAG r44PLCSt sr ECIFIE ALFFAnREEeaOW • . . I NLET VIEW . . TOP VIEW DISCHARGE VIEW . SENSOR- Livarrnapepcirtaittwsensais CASING - LINER- 2' It P fiidCdua nalyralaawallabodyda>,styafl5 t 1 . 181actsFPP804 g Blxraccessparel. . Op6orx# 11pErrm ' ' DAMPERS - . Wart Stedratialarionsystrni3tlettlagid UsekagEtgultEdErrpedslasshsrekkrrinsl hation,folkedcriaistrearmsdaedgassaatad CF v 1.49Pa Ps UNITACCESSORIES- . Opkinat NDUehalaforsOnvwthr oi, rnd . OgrnatErgabrackela pme,mmder a crt . Cp6arEt 12 . Cpfialat 1' NOTE 1. Sensorsare shown in inlet and discharge, butane available in both inlets. 2 Pneunaticoon6O ls sham, elecaonicare available. 3 Dimensions areshownasiches(mm). INLET NOAMMX DISCHARGE Std CFM(1./6) L W H A 0 E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 6 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99116(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 33/8(86) , 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275 /8(702) 107 /8(276) 33/8(86) 77 /8(200) 159/16(395) 97 /8(251) 91/4(235) 9 1050(496) 445/8(1134) 335 /8(855) 127 /8(352) 33/8(86) 87 /8(225) 199/16(497) 127 /8(327) 113/4(298) 10 1350(537) 445 335 /8(855) 127 /8(352) 33/8(86) 97 /8(251) 199/16(497) 127 /8(327) 113/4(298) 12 2100 (991) 505/8(1287) 395 /8(1007) 157 /8(403) 338(86) 117 /8(302) 239/16(598) 147 /8(387) 141/4(362) 14 3200(1510) 589/16(1488) 469116(1183) 181 /8(460) 33/8(86) 137 /8(352) 261/2(673) 167 /8(429) 169/16(420) 18 _4000(1887) 649 . 469116(1163) _ 181 /8(460) 33/8(86) 157 /8(403) 261/2(673) 167 /8(429) 169/16(420) PROCJCTPJ FORM4 TIONISSUBJEC7TOCWWGEVUrr HOUTNOTICE 1/16/2032 -02244ts .00.031 =Atw oary awry �' eASS PEww B BEST 1OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 147 of 169 Performance Summary For VAV -3 -15 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -15 Quantity' 1 Model Type VAV - CCN Model' 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 6 Inch Hot Inlet Size' 6 Inch Part Number 35NC1C000L0606419000000S0000380016001600052 Outlet 6.9x6.9 Unit Performance Altitude 0 ft Cold Max. Airflow' 380.0 CFM Cold Min. Airflow' 160.0 CFM Hot Max Airflow' 160.0 CFM Hot Min Airflow' 52.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure' .20 in wg Minimum Static Pressure Drop' .40 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining:.... Standard (1/2 Inch dual density f/g liner) Maximum Airflow Cold Inlet' 521.0 CFM Attenuator No Design Airflow Cold Inlet' 380.0 CFM Safety Factor Cold Inlet 27 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet' 160.0 CFM Safety Factor Hot Inlet 69 % Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: • Sound Power Levels, dB re 10E - 12 watts - " Cold Max. Airflow' 380.0 CFM Hot Max Airflow' 160.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 61 56 46 42 40 35 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 44 38 26 19 15 < 10 26 Discharge Sound Primary Sound (Pwl) 65 62 57 50 44 36 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 36 32 16 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) in space indicates sound and/or NC value is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 148 of 169 Acoustics Summary For VAV -3 -15 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -15 Quantity 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size ...... _....... 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000380016001600052 Outlet' 6.9x6.9 Insulation: Other information: Lining' Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet' 521.0 CFM Attenuator No Design Airflow Cold Inlet:......... 380.0 CFM Safety Factor Cold Inlet' 27 % Maximum Airflow Hot Inlet' 521.0 CFM Design Airflow Hot Inlet 160.0 CFM Safety Factor Hot Inlet 69 Unit LxVb H' 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts • " Cold Max. Airflow' 380.0 CFM Hot Max Airflow' 160.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 61 56 46 42 40 35 * Total Attenuation 17 18 20 . 23 25 26 Room Sound Level (Spl) 44 38 26 19 15 < 10 26 Discharge Sound Primary Sound (Pwl) 65 62 57 50 44 36 * Total Attenuation 29 30 41 53 55 41 • Room Sound Level (Spl) 36 32 16 < 10 < 10 < 10 19 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10 " -12 watts. 4. Dash ( -) In space Indicates sound and/or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 149 of 169 VAV -3 -16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -16 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 150 of 169 Unit Report For VAV -3 -16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -16 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 12 Inch Part Number 35NC1C000L1212419000000S0001905095009500209 Insulation Lining Standard (1/2 inch dual density fig liner) Outlet 11.9x11.9 Dimensions Unit Depth 51.9 in Unit Width 46.2 in Unit Height 15.9 in Unit Operating Weight • 80 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessorios. Approximate dimensions are provided primarily tor shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L121241900000 35N Dual Duct Terminals 1 OS0001905095009500209 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 151 of 169 • Certified Drawing for VAV -3 -16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM °xE no calmer aneseescrcarr a 9.svmS01 a NM CIIALD.C7VAR AB.E Carrier WRIER Ot5VMtICN Sec °'""` °°`om"B"a 3 i Isw 11•E aware C01:1101 1Q C MM 1.01' COMMIE CADUSOaNnALIIUE CATALOG*/ A United Technologies Company co Lea yaw C C 7 •TH p��� ART B Z 'µ 3 BASEuN 1- vin-cmclueiM/ CHARTED'ADIVB45 1 PCU-CIESNESICAPTER • ALLOAFO EAST 210)CLEARANCE O R FCCINIFCLS L R6 B7C r __ H ix I I IN sI D I c Pl ET ml■, - / /' E 1 11111111 W / �� D NET II I E o Q! 611S2)TNP ii- S®oPTENALFE4nl:E9BaCW - . INLET VIEW . . TOP VIEW ..... - DISCHARGE VIEW SENSOR- livarrnSplepoetaibmensais CASING - sfandardona4 LINER- 12' (13 rj peafetwatt Vo lickdrltiatyF ionvatabodydast of15 . .... _ (1.49a)Ps1 . .. .. . • 4Igtn 23ga. gtatstlstaelcasing. 181arldsFPA904 . glint • glint 1'(25nin DAMPERS . c rtr at tsrlatE uysten13'164idvigd LeelegataicnliedarptisiastEn2Yatirrint hsUatn,fleamikle,edgessealscl CFM316'(1.48Pa)Ps. its. UNITACCESSORIES- . glint t Nbilaislafor romIh nits al . Oginal>agalbradcts. preaa'bondasabt . glint 12 . Optcn t 1' NOTE 1. Sensors are & nininletanddischarge,butare available in both inlets. 2 Pnet maticcormis shown, electronit:areavailable. 3 Dimensionsaeshownas inches (mm). INLET , 1X PSC:MARGE S2E CRA(L/s) L W H A 0 E F G 4 255(106) 321/8(816) 215/8(550) 87/8 225) 53/8(137) 37/8(98) 99/16(243) 77/8(200) 71/4(184) 8 350(165) 321/8(816) 215/8(550) 87 /8(225) 53/8(137) ' 47/8(124) 99/16(243) 77/8(200) - 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 33/8(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275 /8(702) 107/8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) , 91/4(235) 9 1050(495) 445/8(1134) 335 /8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(537) 445/8(1134) 335 /8(855) 127/8(352) , 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2100 (991) 505/8(1287) 395/8(1007) 157/8(403) 3318(86) 117/8(302) 239/16(598) 147/8(387) 141/4(362) 14 3200(1510) 589/16(1488) 46916(1183) 181/8(460) 33/8(86) 137/8(352) 261/2(673) 167/8(429) 169116(420) 18 4W0(1E87) 649/16(1640) 469/16(1183) 181/8(460) 33/8(86) 157/8(403) 261/2(673) 167/8(429) 169/16(420) PRODUCTINFORMATICNISSUBJECTTOCHANGEN THOUTNOTICE 1 /16=2 -MORE .0.0.637 =RCM CRAPR.C.REER ewe B I OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 152 of 169 Performance Summary For VAV -3 -16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -16 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 12 Inch Hot Inlet Size 12 Inch Part Number 35NC1C0000212419000000S0001905095009500209 Outlet' 11.9x11.9 Unit Performance Altitude' 0 ft Cold Max. Airflow 1,905 0 CFM Cold Min. Airflow' 950.0 CFM Hot Max Airflow 950.0 CFM Hot Min Airflow 209.0 CFM Inlet Static Pressure 1 00 in wg Downstream Static Pressure' 20 in wg Minimum Static Pressure Drop' 66 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,905.0 CFM Safety Factor Cold Inlet 9 % Maximum Airflow Hot Inlet 2,085.0 CFM Design Airflow Hot Inlet' 950.0 CFM Safety Factor Hot Inlet 54 % Unit LxWxH 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB to 10E - 12 watts ** Cold Max. Airflow 1,905.0 CFM Hot Max Airflow' 950.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 75 68 61 58 55 52 * Total Attenuation 17 18 20 23 25 26 Room Sound Level (SpI) 58 50 41 35 30 26 43 Discharge Sound Primary Sound (Pwl) 66 61 60 56 50 43 Total Attenuation 29 30 41 53 55 41 * Room Sound Level (SpI) 37 31 19 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10 " -12 watts. 4. Dash ( -) in space Indicates sound and /or NC value is less than 10. Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 153 of 169 Acoustics Summary For VAV -3 -16 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -16 Quantity 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size 12 Inch Hot Inlet Size' 12 Inch Part Number 35NC1C000L1212419000000S0001905095009500209 Outlet' 11.9x11.9 Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 2,085.0 CFM Attenuator No Design Airflow Cold Inlet 1,905.0 CFM Safety Factor Cold Inlet' 9 % Maximum Airflow Hot Inlet' 2,085.0 CFM Design Airflow Hot Inlet 950.0 CFM Safety Factor Hot Inlet 54 % Unit LxWxH• 51.9 x 46.2 x 15.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 1,905.0 CFM Hot Max Airflow 950.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 75 68 61 58 55 52 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 58 50 41 35 30 26 43 Discharge Sound Primary Sound (Pwl) 66 61 60 56 50 43 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 37 31 19 < 10 < 10 < 10 18 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from teats conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) In apace Indicates sound and /or NC value is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 154 of 169 VAV -3 -17 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM , VAV -3 -17 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 155 of 169 Unit Report For VAV -3 -17 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM 2 r .- 4 Unit Parameters Tag Name' VAV -3 -17 Quantity:. 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Unit and Inlet Size 6 Inch Part Number 35NC1C000L060641900000050000400020002000052 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet 6.9x6.9 Dimensions Unit Depth 35.9 in Unit Width 32.2 in Unit Height 8.9 in Unit Operating Weight . 31 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions we provided primarily for - . . shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L060641900000 35N Dual Duct Terminals 1 0S0000400020002000052 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 156 of 169 Certified Drawing for VAV -3 -17 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM °XE nn =mar anon a= stoma. or new DUALDUZIVARaaHE 0- ne Carrier CARIO SFOra CtDh .QED °'"""S°'° IJI Q SDWI601JVE 35iV ewe v dames ,a PORT ,m oM DECCNIEMVALLICREEXCLOSED PORT GTPLOGC United Technologies Comoany Q a BJENMNOWEER 35NBASEUNIT- va urrrA • CHARIIDAAIOB/6D4 NOLDEINETADAPTER AILOAM-EAST 241610)CLEARANCE R 0 Lam F024TPaS { B011-SEES � H d I • lijii I i I.ill G , c o I D NFT ■ E I W ' F NET r -:171 I .�I o iii • ------ HANGERERACKET4IFICS) FEAT ow • • INLET VIEW .. 1QP VIEW DISCHARGE VIEW . SENSOR- LreamuTplepoitaitwsensais CASING - standardonalvd LINER- 12' (t3Trtl PZh triti cix asVisIablwdt3'ao tstre orl5 (1.4 a)Psl . bskutr24161tn 1• . Cpeavt 20cp gekrizettelmtg. auneatshasTiErnertalli181axisFPA934 . (fig a. gisl . Ogcret 1125rrrn )tbdrs.1957mEefruspedca- DAMPERS- famine. hsAessEctinecross#1693:44Verieb3rgasleirg. . 0Anst S inerialafarysterrr131161Fidagd /doflari>31 isaisfal edgessealed C IAW(1A8Pa)Ps UNITACCESSORIES- • Walt Niolretaltonsydrn,wtrcelarel . (p6orshagertradet pmerlincimmtm . OgEret 12 . C)p6 nst l'biErrapatdecfraiaban NOTE 1. Sensors are sFwmin inlet and discharge, but are available in both inlets. 2 Pneumabccontrolsshown, elecironicareavailable. 3 Dmerubreereshownas itches (mm). NET NONWYIX DISCHARGE CFIN(L/s) L W H A 0 E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99016(243) 77/8(293) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(203) 71/4(184) 6 450(212) 321/8(816) 215/8(550) 87/8(225) 330(86) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 355/8(931) 275/8(702) 107/8(276) 338(86) 67/8(175) 15316(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 27518(702) 107/8(276) 33(8(86) 77/8(200) 15316(395) 97/8(251) 91/4(235) 9 1050(495) . 4458(1134) 335/8(855) 127/8(352) 33(806) 87/8(225) 19316(497) 127/8(327) 113/4(298) 10 1333(637) 4456(1134) 335/8(855) 127/8(352) 3318(861 97/8(251) 19316(497) 1270(327) 113/4(298) 12 2100(991) 5058(1287) 3958(1007) 157/8(403) 3318(86) 117/8(302) 23316(598) 147/8(387) 141/4(351) 14 3200 0 5101 56916(1488) 469/16(1183) 181/8(460) 33/8(86) 137/8(352) 2612(673) 167/8(429) 169/16(420) 16 4000 (1887) 649/16(1640) 469/16(1183) 181/8(460) 33,8(86) 157/8(403) 2612(673) 167/8(429) _ 169/16(420) PRODUCTINF0F8v14T10MSSUaJECTTOCHANGE (AKTHOUTNOIICE 1/162002 .are .ca. + LCGC04 rnrawwe9+ 8,131 ate• B I 1 35N -202 -1 Air Terminals Builder 1.09e Page 157 of 169 Performance Summary For VAV -3 -17 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name' VAV -3 -17 Quantity 1 Model Type' VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000400020002000052 Outlet 6.9x6.9 Unit Performance Altitude' 0 ft Cold Max. Airflow' 400.0 CFM Cold Min. Airflow' 200.0 CFM Hot Max Airflow 200.0 CFM Hot Min Airflow' 52.0 CFM Inlet Static Pressure' 1.00 in wg Downstream Static Pressure: .20 in wg Minimum Static Pressure Drop' .44 in wg Note' Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining' Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet' 521.0 CFM Attenuator No Design Airflow Cold Inlet 400.0 CFM Safety Factor Cold Inlet 23 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet' - — 200.0 CFM • Safety Factor Hot Inlet' 62 % Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts •• Cold Max. Airflow' 400.0 CFM Hot Max Airflow' 200.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 61 57 47 42 40 35 • Total Attenuation 17 18 20 23 25 26 • Room Sound Level (Spl) 44 39 27 19 15 < 10 27 Discharge Sound Primary Sound (Pwl) 65 63 57 50 44 37 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 36 33 16 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 wafts. 4. Dash ( -) in space Indicates sound and/or NC value is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 158 of 169 Acoustics Summary For VAV -3 -17 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM • Unit Parameters Tag Name* VAV -3 -17 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type* 4190: VAV with DCV Cold Inlet Size 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000400020002000052 Outlet 6.9x6.9 Insulation: Other Information: Lining Standard (1/2 Inch dual density f/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow Cold Inlet 400.0 CFM Safety Factor Cold Inlet 23 % Maximum Airflow Hot Inlet 521.0 CFM Design Airflow Hot Inlet 200.0 CFM Safety Factor Hot Inlet 62 % Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 400.0 CFM Hot Max Airflow 200.0 CFM Octave Bands (dB Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 61 57 47 42 40 35 • Total Attenuation . 17 18 20 23 . . 25. _ 26 • Room Sound Level (Spl) 44 39 27 19 15 < 10 27 Discharge Sound Primary Sound (Pwl) 65 63 57 50 44 37 • Total Attenuation 29 30 41 53 55 41 • Room Sound Level (Spl) 36 33 16 < 10 < 10 < 10 20 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted In accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10 ^ -12 watts. 4. Dash ( -) In apace indicates sound and/or NC value Is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 159 of 169 VAV -3 -18 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -18 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 160 of 169 Unit Report For VAV -3 -18 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -18 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Unit and Inlet Size 8 Inch Part Number 35NC1C0001_080841900000050000760035003500093 Insulation Lining Standard (1/2 inch dual density fig liner) Outlet 8.9x8.9 Dimensions Unit Depth 39.2 in Unit Width 36.2 in Unit Height 10.9 in Unit Operating Weight 42 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L080841900000 35N Dual Duct Terminals 1 0S0000760035003500093 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 161 of 169 Certified Drawing for VAV -3 -18 • Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM OXE nes ceases' Rn FPFCCOn a asestaow cc 1143E DULLaUCNARYIELE Carrier � 'C 1°JNO18 ®"°eD Ot=.€II 0- trot 714 ova' MOM =OTOS w ones tar cassava U 1NE 35N CATALOG# A Unites Technologies Company co L4E0 W.G C m te � v IH 35NBASEUNrr- WTHCFPCNIUNTACCESSCWS CHARTED'ADIVE 6ON FICLL OESINE rADAPIER AULQM11.EAST 241610)CLEARMICE F OITROS 0 L--.{ B71F6 I� � H &40, i I f �i I 1 I -RS I c a IdET ■ E 1 I D I % 1111111 W F iii , /� , D NET II !'' I y I E o Qt 611 II": H4NGERBPACK:T(4PLCS) SEECIPRONALFEATURESBEIDAI ' INLET VIEW TOP VIEW . _ DISCHARGE VIEW . • SENSOR- Lilearrnitlepoirtailbfisensais CASING - stattlardmakris LINER- Thebasetrithstlw1h5tardard10 tidgialEnay alablvAhabodyda�yof1.5 fGTT� ... . (?.49P9 s1 .• _ t lu1124l. n 3 ).Thislringiscoab3dtcpmfrterosim, . 181arl•FPA934 . Opirnat gig . Opfar12t f fare )tikkialabrxeritgfealica- DAMPERS - . Opimet S9erinerialdionsystrn13/1Th(g d kerInie halafakfolraaxionaisbearn4cle,edgessealed C ilal6'(1.49Pa )Ps GPs. UNITACCESSORIES- . Opfonst Noineriaitas,rs rtwitroi real . Cp5onahrgertrakals. . Opfionet 1 . Wart 1'Toierraralaberst.la6on NOTE 1. Sensors are shownin inlet and discharge, butare available in both inlets. 2 Pne tmaticcantrols shown, elechOnicareavailable. 3 Dgnensions are shovel asildtes(mm). NET NOMMAX DISCHARGE SZE CFMO./a) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 9:/16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 21 5/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77)8(200) 71/4(184) 8 450(212) 321/8(816) 215/8(550) 87/8(225) 33 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(3071 365/8(931) 275/8(702) 10718(276) 33/8(86) 67/8(175) 159/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8 (702) 107/8(276) 3308(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) 9 1050(495) 445/8(1134) 335 /8(855) 127/8(352) 33/8(86) 87/8(225) 199/16(497) 127/8(327) 113/4(298) 10 1350(637) 4458(1134) 335 /8(855) 127/8(352) 33/8(86) 97/8(251) 199/16(497) 127/8(327) 113/4(298) 12 2100(991) 505/8(1287) 395/8(1007) 157/8(403) 33/8(86) 11 7/8(302) 239/16(598) 147/8(387) 141/4(36'1) 14 32C0(1510) 589/16(1488) 469/16(1183) 1818(460) 3348(86) 137/8(352) 261/2(673) 1678(429) 169116(420) 16 4000(1887) 649/16(1640) 469/16(1183) _ 1818(460) _ 33/8(86) 157/8(403) 2612(673) 1678(429) 169/16(420) PRODUCTINFORMA1 )ONISSUBJECTTOCWWGEWTHOUTNOTICE 1 /16/2002 _census JWNARM LC RW CRaWSCIEEi arvER RASA. `e`HO" B 'E• IOF 1 35N -202 -1 Air Terminals Builder 1.09e Page 162 of 169 Performance Summary For VAV -3 -18 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name* VAV -3 -18 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 8 Inch Hot Inlet Size 8 Inch Part Number 35NC1C000L0808419000000S0000760035003500093 Outlet' 8.9x8.9 Unit Performance Altitude 0 ft Cold Max. Airflow 760.0 CFM Cold Min. Airflow 350.0 CFM Hot Max Airflow 350.0 CFM Hot Min Airflow 93.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure* .20 in wg Minimum Static Pressure Drop .46 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 927.0 CFM Attenuator No Design Airflow Cold Inlet 760.0 CFM Safety Factor Cold Inlet 18 % Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot inlet 350.0 CFM Safety Factor Hot Inlet 62 % Unit LxVVxH 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E watts " Cold Max. Airflow 760.0 CFM Hot Max Airflow 350.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 69 65 57 54 53 52 Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 52 47 37 31 28 26 37 Discharge Sound Primary Sound (Pwl) 69 64 59 53 47 39 * Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 40 34 18 < 10 < 10 < 10 21 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) In space indicates sound and /or NC value is less than 10. Sound calculations are based on largest inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 163 of 169 Acoustics Summary For VAV -3 -18 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -18 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 8 Inch Hot Inlet Size' 8 Inch Part Number 35NC1C000L0808419000000S0000760035003500093 Outlet 8.9x8.9 Insulation: Other Information: Lining:.... Standard (1/2 inch dual density fig liner) Maximum Airflow Cold Inlet 927.0 CFM Attenuator No Design Airflow Cold Inlet 760.0 CFM Safety Factor Cold Inlet 18 % Maximum Airflow Hot Inlet 927.0 CFM Design Airflow Hot Inlet 350.0 CFM Safety Factor Hot Inlet 62 Unit LxWxH 39.2 x 36.2 x 10.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 760.0 CFM Hot Max Airflow 350.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 69 65 57 54 53 52 * Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 52 47 37 31 28 26 37 Discharge Sound Primary Sound (Pwl) 69 64 59 53 47 39 Total Attenuation 29 30 41 53 55 41 * Room Sound Level (Spl) 40 34 18 < 10 < 10 < 10 21 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10A -12 watts. 4. Dash ( -) In space Indicates sound and/or NC value Is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. • Air Terminals Builder 1.09e Page 164 of 169 VAV -3 -19 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM VAV -3 -19 Tag Cover Sheet Unit Report Certified Drawing Performance Report Acoustic Summary Air Terminals Builder 1.09e Page 165 of 169 Unit Report For VAV -3 -19 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11PM to Unit Parameters Tag Name' VAV -3 -19 Quantity' 1 Model Type' VAV - CCN Model' 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Unit and Inlet Size' 6 Inch Part Number 35NC1C000L0606419000000S0000240012001200052 Insulation Lining Standard (1/2 inch dual density f/g liner) Outlet' 6.9x6.9 Dimensions Unit Depth' 35.9 in Unit Width 32.2 in Unit Height 8.9 in Unit Operating Weight • 31 lb "' Weights and Dimensions are approximate. Weight does not include curbs and accessories. Approximate dimensions are provided primal :i' for shipping purposes. For exact dimensions, refer to certified drawings. Warranty Information 1 Year Parts Only Warranty Ordering Information Part Number Description Quantity Base Unit 35NC1C000L060641900000 35N Dual Duct Terminals 1 050000240012001200052 4190: VAV with DCV Hangers Accessories Air Terminals Builder 1.09e Page 166 of 169 Certified Drawing for VAV -3 -19 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM O ma mesa isn1ccetn o samm+ a ,� CUALDUCWARIME C Carrier .0 O+ � 1i8 D °'""""° ar CAOasomRDi rE 35N CATALOG* vAwr s JJI A United Technologies Company CR USED lb49 B IH 391BASEUNET VVri-CPTIONALINIACZES9CRES O4ARTEDAtf(' SIGN NCLICESIKETADAPTER ALLUI1 MEAST 241 O FL7COJISC S d• li�i I i I Or I I � NET Cl n , 7 D � ET E . W PL ��, D itii IMI Q• et 11-'- f HO r{4 LCS► INLET VIEW TOP VIEW DISCHARGE VIEW SENSOR- LhearmUttlepcintaitwamscris CASING - 5ardador>alutls LINER- 12' (13m4 pae' 8$ -frinkeladensiyeetfolwfiabodydasty115 (1.49cPa)Psl . • Wad artmettsegiernsrisill8lartFPASOk . Wart Bctnlaccmspensi . Ortoret 1 'V:7rrrl DAMPERS - . Cflortat StedherhsJaficns,d6m13161tidcrigid 1.66kazghtultEclarperkiesztEnNoharivi insUaraltitacecknaksbearn6iie,eigaseesded OlvIat6X1A8Pa)Fs UNITACCESSORIES- . Walt rsottai ors r>, trcilarrel . giort6tErg3bradels. plawrtu(13E n . 01:6311 12 . Wad 1' NOTE 1. Sensorsare shawl in inlet and discharge, but are available in both inlets. 2 Pnetmaticaontrolsshavn ,eledronicareavailable. 3 Dimensionsa eshownasinches(mm). POET NDAMMX Dom E SIZE CFM(L/s) L W H A D E F G 4 255(106) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 37/8(98) 99x16(243) 77/8(200) 71/4(184) 5 350(165) 321/8(816) 215/8(550) 87/8(225) 53/8(137) 47/8(124) 99/16(243) 77/8(200) 71/4(184) 6 450(212) 321/8(8161 215/8(550) 87/8(25) 3318(66) 57/8(149) 99/16(243) 77/8(200) 71/4(184) 7 650(307) 365/8(931) 275/8(702) 107/8(276) 33/8(66) 67/8(175) 15:/16(395) 97/8(251) 91/4(235) 8 800(377) 365/8(931) 275/8 (702) 107/8(276) 33/8(86) 77/8(200) 159/16(395) 97/8(251) 91/4(235) a 1050(495) 445/8(1134) 335 /8(855) 127/8(352) 33/8(86) 87/8(225) 199/18(497) 127/8(327) 113/4(298) 10 1350(637) 445/8(1134) 335 /8(855) 127/8(352) 33/8(66) 97/8(251) 199116(497) 127/8(327) 113/4(298) 12 2100(991) 505/8(1287) 395/8(1007) 157/8(403) 33/8(86) 117/8(302) 239116(598) 147/8(387) 141 /4(362) 14 3200 (1510) 589/16(1488) 469 /16(1183) 181/8(460) 33/8(66) 137/8(352) 2612(673) 167/8(429) 169/16(420) 16 4000(1887) 649 /16(1640) _ 469116(1183) , 181/8(460) _ 33/8(86) 157/8(403) 261/2(673) _167/8(429) _ 169(16(420) PRODUCTPIFORMAnONISSUBJECTrO wTHOUTNOTICE 1 /162002 .03..8 .OBNARE7 iQCRON 'O ssnOLAW EUcei ENS. 4 B 51.W• I OF 1 35N -202 -1 Air Terminals Builder 1.09e Page 167 of 169 Performance Summary For VAV -3 -19 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -19 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type 4190: VAV with DCV Cold Inlet Size 6 Inch Hot Inlet Size 6 Inch Part Number 35NC1C000L0606419000000S0000240012001200052 Outlet 6.9x6.9 Unit Performance Altitude 0 ft Cold Max. Airflow 240.0 CFM Cold Min. Airflow 120.0 CFM Hot Max Airflow 120.0 CFM Hot Min Airflow 52.0 CFM Inlet Static Pressure 1.00 in wg Downstream Static Pressure .20 in wg Minimum Static Pressure Drop .16 in wg Note Inlet Static Pressure includes downstream pressure drop. Insulation: Other Information: Lining Standard (1/2 inch dual density f/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow Cold Inlet 240.0 CFM Safety Factor Cold Inlet 54 % Maximum Airflow Hot Inlet 521.0 CFM • Design Airflow Hot Inlet - -120.0 CFM Safety Factor Hot Inlet 77 % Unit LxWxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts ** Cold Max. Airflow 240.0 CFM Hot Max Airflow 120.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 56 52 42 38 36 33 ` Total Attenuation 17 18 20 23 25 26 * Room Sound Level (Spl) 39 34 22 15 11 < 10 21 Discharge Sound Primary Sound (Pwl) 60 58 53 46 40 33 * Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 31 28 12 < 10 < 10 < 10 14 Notes: 1. Room sound levels shown include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are in decibels, re 10A -12 watts. 4. Dash ( -) In space indicates sound and/or NC value Is less than 10. " Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 168 of 169 Acoustics Summary For VAV -3 -19 Project: Triangle Point Shell 09/09/2010 Prepared By: 04:11 PM Unit Parameters Tag Name VAV -3 -19 Quantity 1 Model Type VAV - CCN Model 35N Dual Duct Terminals Control Type' 4190: VAV with DCV Cold Inlet Size' 6 Inch Hot Inlet Size' 6 Inch Part Number 35NC1C000L0606419000000S0000240012001200052 Outlet' 6.9x6.9 Insulation: Other Information: Lining:..... Standard (112 inch dual density f/g liner) Maximum Airflow Cold Inlet 521.0 CFM Attenuator No Design Airflow Cold Inlet 240.0 CFM Safety Factor Cold Inlet' 54 % Maximum Airflow Hot Inlet' 521.0 CFM Design Airflow Hot Inlet 120.0 CFM Safety Factor Hot Inlet 77 % Unit LxVVxH 35.9 x 32.2 x 8.9 Acoustic Summary: Sound Power Levels, dB re 10E - 12 watts "" Cold Max. Airflow' 240.0 CFM Hot Max Airflow' 120.0 CFM Octave Bands (dB) Radiated Sound 2 3 4 5 6 7 NC Primary Sound (Pwl) 56 52 42 38 36 33 * Total Attenuation 17 18 20 23 , 25 26 * Room Sound Level (Spl) 39 34 22 15 11 < 10 21 Discharge Sound • Primary Sound (Pwl) 60 58 53 46 40 33 • Total Attenuation 29 30 41 53 55 41 Room Sound Level (Spl) 31 _ 28, 12 < 10 < 10 < 10 14 Notes: 1. Room sound levels shown Include attenuation transfer functions shown above. 2. Data were obtained from tests conducted in accordance with ARI Standard 880 -90. 3. Sound power levels are In decibels, re 10 " -12 watts. 4. Dash ( -) In space indicates sound and /or NC value Is less than 10. Sound calculations are based on largest Inlet size. The results of this program are only an aid to the designer, and are not a substitute for professional services. Carrier Corporation accepts no liability for the adequacy of any resulting design or installation. All data subject to change without notice. Air Terminals Builder 1.09e Page 169 of 169