PC #: 11-43c .BUP#: 98 -0048
Page #2
B. Copies of all special inspection reports shall be filed with this office continually
during construction [OSSC, Section 3305].
C. A final signed report must be on file before an occupancy certificate will be issued
[OSSC, Section 3318].
In addition to Building Department plan review comments, you will find a copy of
comments from one or all of the following departments: Engineering, Water, and Planning,
referencing deficiencies in that departments requirements for your site.
If you have questions regarding their comments, please call or respond to them
personally.
All corrections, including those from the building department shall be incorporated in your
revised plans.
A site permit will not be issued until all corrections have been made and approved by the
respective department, therefor it is paramount that you reply expeditiously.
Contact Stewart Davis, Senior Engineer, Tualatin Valley Water District, P.O. Box 745,
Beaverton, OR, 97075, 503 -848 -3025.
7. The storm drainage plan shall adequately address the number of catch basins required to
handle the parking lot and hard surface runoff. The Uniform Plumbing Specialty Code
[UPSC, Section 1108] allows a maximum 6" outlet on each catch basin, and Table 11 -2
limits the maximum surface area one catch basin can serve to 7,133 squ feet at 1%
slope of the horizontal line from the catch basin. Additional catch basins are required to
adeq serve the area.
A. Sizing of all storm drain piping is determined by OPSC, Table 11 -2. If an
engineered system is to be used in lieu of a table 11 -2, two sets of plans
stamped by an engineer licensed in Oregon and the hydrodynamic calculations
must be submitted for review and approval. iv 1 A
& The 62 I.f. of 10" s.d. pipe at the NE parking lot is undersized. / S v� ,,
2. The 200, 54 and 209 I.f. of 12" s.d. pipe along the SW and South building I Q n /l A
perimeter are undersized.
✓3. The volume of drainage area exceeds the capacity of the 205 if. of 15" y r 1
s.d. pipe south lateral.
V 4. The volume of drainage area exceeds the capacity of the catch basin in
the south parking lot. Provide additional catch basins as determined by S `'~
the Oregon Plumbing Specialty Code, Section 1108 and Table 11 -2.
✓
5. The 57 I.f. of 15" s.d. pipe continuing to M.H. "A" is undersized. — 2, w A
V B. Provide the engineering calculations for s.d. M.H. "A" and piping to the outfall..... 1 i, " ,-
1/C- How does the pert pipe behind retaining structures connect to the S.D system
and has that piping been sized for its volume?
• . Cleanouts are required on all drainage piping every 100 linear feet and at each aggregate
change of direction exceeding 135 degrees [OPSC, Section 707.4 and 707.5]. Show
/, location of clean outs on the plans.
r.. Submit revised plans with details and specifications for the Lynch -type catch basin. The
design shall be in accordance with OPSC, Section 1108 requirements. Catch basins shall
be trapped by using the inverted one - quarter bend or welded baffle. Provide catch basins
)
• Eagle Hardware Site Plan Review
• • PC#: 11-43c BUP#: 98-0048
Page #3
constructed to OPSC, Section 1108 specifications. Flow through catch basins are not
permitted.
'40 The installation of piping from the city vault, and the backflow device shall be installed by
.a licensed plumber. Installation, inspection and test shall be in accordance with NFPA 13.
t.1 / No building shall be constructed, altered, enlarged, moved or repaired in a manner that by
• reason of size, type of construction, number of stories, occupancy or any combination � ---
thereof, creates a need for a fire flow in excess of 3,000 gallons per minute at 20 psi
residual or exceeds the available fire flow at the site of the structure [UFC, Section 903.3].
i L fil ��� Provide Fire Flow Testing pursuant to NFPA 291 using the enclosed "Hydrant
d'' Flow Test Report Form." Hydrant flow test reports shall be submitted to the City
_. f7 Building Department prior to commencing construction of the building.
Complete the enclosed "Fire Flow Work Sheet' and retum to the City of Tigard,
attention Plans Examiner.
Note: These documents shall be on file before a building permit will be issued.
I ACCESSIBILITY" I
u Curb ramps. Curb ramps shall have detectable wamings which shall extend the full
V t P width and depth of the curb ramp, including the flairs, complying with Section 1109.16
V c 4,.O r (OSSC, Section 1103.2.3.1). Details of the curb ramp design shall be incorporated in
V°' ' revised plans.
/
V Slope. The running slope of the accessible sidewalk route shall not exceed 1 unit vertical
in 20 units horizontal (5% slope). Cross slopes shall not exceed 1 unit vertical in 50 units
horizontal (2% slope).
Handrails are not required on walks with a slope of 1 unit vertical in 20 units horizontal
(5% lope), or Tess (OSSC, Section 1103.2.4.3).
Slope of the sidewalk segments between the 5.5 ft. landings of the 5.5 sidewalk
and the sidewalk route from 72nd Avenue to the East Plaza area exceeds 1 in 20.
to/
Provide handrails in accordance with OSSC, Section 1109.7.6.
Provide a detail of the accessible route from the East Plaza monument to the floor
level of the store. Provide landings and handrail in accordance with OSSC,
Section 1109.7.
Accessible parking stalls for the disabled shall have signs and pavement markings of the
3. e
intemational symbol of accessibility clearly visible and designated to standards adopted
by the Oregon Department of Transportation [OSSC, Se ' . n 1104.1 and ORS 447.233].
Correct elevation of accessible parking sign from 48" 40) detail sheet 8/9.
Development requirements for Building A will include an accessible route to the public
way. Why are you not showing the proposed accessible route connecting to SW
Beveland?
Provide an accessible route connecting all exterior doors, designated as exit doors, along
5. g
the north and west building perimeter to the public way (OSSC, Section 1106.2.4).
•
• Eagle Hardware Site Plan Review
• PC#: 11-43c BUP#: 98-0048
Page #4 .
I FIRE ND LIFE SAFETY I
Provide the location of the Fire Department Connection (FDC) and a detail of design.
Provide 4 ports on the six inch riser/lateral.
A. FIRE HYDRANT /FIRE DEPARTMENT CONNECTION: A fire hydrant shall be
located within 70 feet of a fire department connection (FDC). Fire hydrants and
FDC's shall be located on the same side of the fire apparatus access roadway.
(UFC Sec. 903.4.2.5) FDC locations shll be approved by the building official.
(1998 Oregon Structural Specialty Code, Sec. 904.1.1)
B. FIRE DEPARTMENT CONNECTIONS ON BUILDINGS: Fire department
connections shall not be located on the building that is being protected. (UFC Sec
903.4.2.5)
ISTRUCTURAL I
0 Provide the engineering calculations for the keystone wall. Design details specified by the
Geo- technical engineer shall be incorporated on Sheet c5/9 or an additional sheet.
Rockery retaining walls shall be designed by an engineer licensed in the state of Oregon.
0 2. The design's engineering shall address intemal forces as well as shear and overturning.
Design details specified by the Geo-technical engineer shall be incorporated on sheet
c5/9 or an additional sheet
,
EXCEPTION: Rock walls constructed to the design specification of the Associated
Rockery Contractors standards. Publication dated 12/2/92.
Provide the engineering calculations for CMU and concrete walls exceeding 4 feet in
height.
V Provide the engineering calculations for the triangle monument.
r Every page of each set of plans containing drawings and specifications required to be
prepared by a State of Oregon licensed engineer must be stamped and signed with the
expiration date of that engineer's license written below his or her signature [OAR 820 -10-
620 and ORS 672 -020(2)].
A. One set of revised plans, specifications and engineering shall have a
fresh stamp and signature.
i. Provide plans and specifications stamped appropriately/
I/. Deferred submittals are defined as those portions of the design not submitted at the time
of the application [OSSC, Section 106.3.4.2].
A. The architect or engineer of record shall list the deferred submittals on the plans.
B. Each deferred submittal shall be first submitted to the architect or engineer for
their review and then forward them to the plans examiner with a notation that
each of the deferred submittals has been reviewed and that they have been found
to be in conformance with the design of the building [OSSC, Section 106.3.4.2].
Eagle Hardware Site Plan Review
•
PC#: 11-43c BUP#: 98 -0048
Page #5
NOTE! The deferred submittal item[s] shall not be installed until the design and submittal
documents have been approved by the City Building Department's Plans Examiner.
Please submit three copies of revised submittal documents and a letter indicating your response
to the above comments for review. Please call me at (503) 639 -4171 if you have any questions.
Sincerely,
Jim Funk
PLANS EXAMINER
oC„� DOC
SITE PLAN REVIEW 40
COMMENTS
CITY OF TIGARD
Community (Development
Shaping Better Community
Date: la-3-9$
Staff Person Commenting: v � tdak--
Department f Iq n p
Phone Number /Extension: 63 '- y/ $ y o7
Project Name: 6 j/ W roit-Ave lk GQ
Site Permit Noy SD4 98 -v oO ' /PD 2 9 3 - .szq 9s- o/L
Land Use Case File No[sle
THE PROPOSED PLANS SUBMITTED FOR A SITE PERMIT HAVE BEEN REVIEWED BY
OUR DEPARTMENT AND WE HAVE THE FOLLOWING COMMENTS:
❑ Plans are approved. All land use conditions related to this department have been
satisfactorily met.
Plans are generally consistent with the land use approval, but there are still land use •
conditions that must be met prior to release of the site and /or building permit,
or prior to a final building inspection.
Specifically,
All or fvrf - ;ols or earien . Ca1dIions (I- /7) ev ale S b / 01 dig
P /e4se. aged p /v,,s JS#iow eqe.4 Cfinel ,n ls4'teA L*4 4 sud.,2, '
acv, s d f /41 s . rks e....w rsv - e Mole r � ravi g w of 60404 itt o lom 144
❑ Plans are NOT consistent with the land use approval and must be revised.
Specifically,
•
❑ Revised plans are approved.
NOTE: IF THE PERMIT APPLICANT HAS ANY QUESTIONS WITH REGARD TO THE COMMENTS ABOVE,
THEY MUST CONTACT THE STAFF PERSON SPECIFIED AT THE TOP OF THE PAGE.