Form 4a Project Name: Eagle Hardware Page: 1
SYSTEMS - GENERAL
Exceptions 1. Exceptions (Section 1313)
Discussion of CI No HVAC. The building plans do not call for an HVAC system. Skip to Item 12 below.
qualifying excep- ❑ Exception. The building or part of the building qualifies for an exception from HVAC code
Lions on page 4-14 requirements. The applicable code exception is Section 1313, Exception . Portions of the
building that.qualify:
See page 4-14 for a 2. Simple or Complex Systems (Section 1313.2 or 1313.3)
discussion of simple El Simple System. The planned HVAC system qualifies as a Simple System. If true, complete this
vs comp /ex form (4a) and equipment efficiency worksheets as required. Form 4b is not required.
systems.
❑ Complex System. The planned HVAC system is a Complex System. Complete this form (4a),
Form 4b and equipment efficiency worksheets as required.
Exceptions 3. Economizer Cooling (Section 1313.1.2)
Comp /ex Systems ❑ No Cooling. The building plans do not call for a new fan system with mechanical cooling.
may claim the same ❑ Complies. The new fan system has an air economizer capable of modulating outside -air and
exceptions a/ /owed retum -air dampers to provide up to 85 percent of the design supply air as outdoor air.
for Simple Systems,
plus three excep- ❑ Exception — Simple Systems. The new fan system qualifies for an exception. The applicable
dons allowed code exception is Section 1313.1.2, Exception , or Section 1313.2.1. Portions of the
Section 1313.12 building that qualify:
See page 4-15 fora
discussion of these ❑ Exception — Complex Systems. The new fan system qualifies for an exception. The applicable
exceptions. code exception is Section 1313.1.2, Exception , or 1313.3.1, Exception . Portions of
the building that qualify:
4. Economizer Cooling - Overpressurizing (Section 1313.1.2)
❑ No Economizer. The building plans do not call for a new fan system with an economizer.
El Complies. The drawings specifically identify a pressure relief mechanism for each fan system
that will exhaust the extra air introduced by the economizer, and the economizer system is
capable of providing partial cooling even when additional mechanical cooling is required to meet
the remainder of the load.
5. System and Zone Controls (Sec. 1313.1.3.1 & 1313.1.3.2)
El Complies. All new HVAC systems include at least one temperature control device responding to
temperatures within the zone.
❑ Exception. The new HVAC system qualifies for an exception from the zone control require -
Exceptions ments. The applicable code exception is Section 1313.1.3.2, Exception 1 and 2. Portions of the
Discussion o/ building that qualify:
qua //fy /ng excep-
tions on page 4-16. 6. Control Capabilities (Sec. 1313.1.3.2.1)
al Complies. Zone thermostats are capable of being set to the temperatures described in Sec.
1313.1.3.2.1. Where used to control both heating and cooling, zone controls shall be capable of
providing a temperature range or deadband of at least 5 degrees F within which the supply of
heating and cooling energy to the zone is shut off or reduced to a minimum.
❑ Exception. The building qualifies for an exception to the deadband requirements. The applicable
code exception is Section1313.1.3.2.1, Exception
(10/98) Forms & Worksheets 4
Form 4a (cont.) Project Name: Eagle Hardware Page: 2
SYSTEMS - GENERAL
7. Off -hour Controls - HVAC Systems (Section 1313.1.3.3)
Cpl Complies. All new HVAC systems are capable of automatic setback or shutdown during periods
of non -use or altemate use of the space served by the system.
❑ Exception. Equipment has full load heating demands of 2 kW (6,826 Btu/hr) or less and is
controlled by a readily accessible manual off -hour control.
8. Off -hour Controls - Supply and Exhaust Systems (1313.1.3.3)
❑ Complies. Plans require that outdoor air supply and exhaust systems have a means of auto-
matic (either motorized or gravity damper) volume shutoff or reduction during periods of non -use
or altemate use of the space served by the system.
❑ Exception. The building qualifies for an exception to the requirement for automatic shutoff or
reduction. The applicable code exception is Section 1313.1.3.3, Exception
9. Heat Pump Controls (Section 1313.1.3.4)
❑ No Heat Pump. The plans /specs do not call for a new heat pump.
❑ Complies. All new heat pumps equipped with supplementary heaters are controlled as required
in Section 1313.1.3.4.
10. Equipment Performance (Section 1313.1.4)
❑ No New HVAC Equipment. The building plans do not call for new electrical HVAC equipment,
combustion heating equipment or heat - operated cooling equipment.
eh Complies. All new HVAC equipment has efficiencies not less than those required by the code.
The following equipment efficiency worksheets are attached: 4a, 4j
11. Duct Insulation (Section 1313.2.2 & 1313.3.2)
❑ No Ducts. The building plans and specifications do not call for new HVAC ducts or plenums.
• Simple System: Complies. The plans and specifications call for a Simple System, and all
exterior supply /return air - handling ducts and plenums and all outside air ducts are insulated as
required by Section 1313.2.2.
❑ Complex System: Complies. The building plans /specs call for a Complex System, and all air -
handling ducts and plenums are insulated as required by Sec. 1313.3.2.
12. Piping Insulation (Section 1314)
Exceptions ❑ No New Piping. The building plans and specifications do not call for new piping serving a
heating or cooling system or part of a circulating service water heating system.
Discussion of
qua /dying excep- a Complies. All new piping serving a heating or cooling system or part of a circulating service
bons on page 4-18 water heating system complies with the requirements of the Code, Section 1314.1.
❑ Exception. New piping qualifies for the following exception: Section 1314, Exception .
13. Service Water Heating (Section 1315)
❑ No New Water Heating. The building plans and specifications do not call for new water heaters,
hot water storage tanks, service hot water distribution systems, swimming pools or spas.
Exceptions a Complies. All new water heaters, hot water storage tanks, service hot water distribution sys-
Discussion of tems, swimming pools or spas comply with the requirements of the Code.
qualifying excep- ❑ Exception. The applicable code exception is Section , Exception . Portions
dons on page 4-18 of the building that qualify:
(10/98) Forms & Worksheets 4-2
Worksheet 4a Project Name: Eagle Hardware Page: 3
UNITARY AIR CONDITIONER - AIR COOLED
Equipment (a) (b) ' (c) (d) (e)
Discussion of Proposed Performance
equipment ratings
and equipment Cooling Seasonal Compliance
definitions on page Capacity Steady or Schedule
¢19 Equip. ID Model Designation (Btu/h) State Part Load (A -E)
AC -1 thru Trane YCD - 300 - 1C4H 275,236 9.7 EER 9.8 1PLV C
AC -8
AC -9 Trane YCD - 211 - C4L 209,887 11.0 EER 12.0 1PLV C
AC -10 Trane YCD - 048 - C4L 45,717 - 10.0 SEER C
AC-11 59 ¥CD - 060 - C4L ,71 - 10. SEER C
Required Indicate source of information
Documenta- ARI Unitary Directory, Section AC, page :
tloII ARI Applied Products Directory, Section ULE, page :
--L_ Product data (Attach data furnished by the equipment supplier, i.e., cut sheets')
Code Compli- Cooling Capacity (Btu/h) Minimum Rating
Required ance Equipment Type
Efficiencies Schedule Over But not Steady State Seasonal or
over- Part Load
0 65,000 na 9.7 SEER
This schedule of
Single Package Without a 65,000 135,000 8.9 EER 8.3 IPLV
equipment efficien A g g
cies was refomratted Heating Section 135,000 760,000 8.5 EER 7.5 IPLV
from the code, Table 760,000 - 8.2 EER 7.5 IPLV
13 - G.
0 65,000 na 10.0 SEER
B Split System Without a Heating 65,000 135,000 8.9 EER 8.3 IPLV
Section 135,000 760,000 8.5 EER 7.3 IPLV
760,000 - 8.2 EER 7.3 IPLV
0 65,000 na 10.0 SEER
C Single Package With a Heating 65,000 135,000 8.9 EER 8.3 IPLV
Section 135,000 760,000 8.3 EER 7.3 IPLV
760,000 - 8.0 EER 7.3 IPLV
0 65,000 na 10.0 SEER
D Split System With a Heating 65,000 135,000 8.9 EER 8.3 IPLV
Section 135,000 760,000 8.3 EER 7.3 IPLV
760,000 - 8.0 EER 7.3 IPLV
E Condensing Unit Only 135,000 - 9.9 EER - 11.0 IPLV
(10/98) Forms & Worksheets 4 -4
Worksheet 4j Project Name: Eagle Hardward Page: 4
FURNACES as UNIT HEATERS — GAS as OIL -FIRED
Equipment (a) (b) (c) (d) (e)
Proposed
Discussion of Heating Compliance
equipment ratings
and equipment Equip. Capacity E E Schedule
definitions onpage ID Model Designation (Btu/h) (Max.) (Min.) AFUE (A - E)
4-19
UH -1 Trane GCND - 010 100,000 80 80 - D
UH -2 Trane GCND - 010 100.000 80 80 - n
AC -1 thrL Trane YCD - 300 - C4H 400,000 1 80.8 80.8 - A
AC -8
AC -9 Trane YCD 211 - C4L 250,000 81.0 81.0 - A
AC -10 Trane YCD - 048 - C4L 90,000 - - 81.0 A
AC -11 Trane YCD - 060 - C4L 90,000 - - 81.0 A
Required Indicate source ofinfonnation
Documenta- GAMA Consumer Directory, page :
tion _x__ Product data (Attach data furnished by the equipment supplier, i.e., 'cut sheets')
Code Capacity (Btu/h) Minimum Performance
Required Compli- Steady Steady
Efficiencies ance But Not State Max. State Min. Part Load
This schedule of Schedule Equipment Type Over Over Rating (E) Rating (E (AFUE)
equipment eflcien- Gas -Fired Warm -Air
cies was reformatted 0 225,000 na na 78%
from the code, A Fumaces & Combustion
Table 13 -1 Fumace/AC 225,000 - 80% 80% na
Oil-Fired Warm -Air 0 225,000 na na 78%
B Fumaces & Combustion
Fumace /AC 225,00 - 81% 81% na
C Gas -Fired Duct Fumaces 0 - 78% 75% na
D Gas -Fired Unit Heaters 0 - 78% 74% na
E Oil -Fired Unit Heaters 0 - 81% 81% na
(10/98) Fofms & Worksheets 4 -13