Sconzo /Hallstrom Architects
919 - 124th Avenue NE, Suite 101
Bellevue, WA 98005
RE: Eagle Hardware Building Plan Review
12615 SW 72nd
PC#: 11-44c BUP #: 98 -0520
Occupancy: M Construction 5N (fully sprinklered)
Allowable Area: Unlimited (OSSC, Section 505.2)
Future Occupancy: Unknown at this time. Please note property lines for this
proposed use will be based on OSSC, Section 503.3.
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1998 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
ENERGY COMPLIANCE
A , - Provide all information required on the enclosed Oregon Non - Residential Energy Code
'N' Compliance forms.
1 FIRE AND LIFE SAFETY I
1. / Your door schedule conflicts with the size of the impact doors. Please review
b,/ and adjust your door schedule as required.
2. Exit door #9 enters room 003 which is an intervening room, and the occupant
D1 load subsequently enters a second intervening room. This is not allowed,
OSSC, Section 1004.2.2. Provide details on how you will eliminate this situation.
3. b Drawing A7.02, detail 4. As shown the 1 hour requirement doesn't comply with
/ 1003.3.3.9, unless the suspended ceiling is a rated assembly, provide details.
4. Show on architectural plans the following egress identifications:
A. Path of exit travel - OSSC, Section 1003.2.8.2.
B. Graphics, illuminations - OSSC, Section 1003.2.8.3, 4 and 5.
C. Illumination - OSSC, Section 1003.2.9.1, 2 and 10.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
' Eagle Hardware Building Plan Review
PC #: 11-44c BUP#: 98 -0520
Page #2
5. Provide 2 A10 BC fire extinguishers every 75 feet. Tualatin Valley Fire
°% Department requirement - provide details on plans.
6. Small hose connections only - provide small hose connections at the following
locations. UFC, Section 8102.9.1 - provide details.
�1 A. Line A -5 on the wall adjacent to exit door #18. y
/ " B. Line D -1 on the wall adjacent to exit door #12. A - - w"
6 C. Line G -5 on the wall adjacent to exit door #8.
D. Line E -10 on the wall adjacent to exit door #71. 1-4
E. On a column near the intersecting aisles at housewares and storage
systems.
a Provide HVAC shutoff for smoke control in accordance with OMSC, 608, and
0 shall be interconnected with the alarm system. Provide details.
'HAZARDOUS MATERIAL QUANTITIES I
1. Provide quantities of stock on hand of the following:
A '� � r A. Flammable and combustible liquids.
B. Aerosols.
1 ' C. Oxidizers.
D. Corrosives.
'DEFERRED SUBMITTALS I
6 1 Greenhouse
0 Greenhouse shaded cloth area.
3. High piled storage.
1STRUCTURAL I
j Provide truss drawings.
6 Provide snow calculations for shaded cloth area over greenhouse.
l % Demonstrate compliance with OSSC, Section 1633.2.4.
,4D Provide name of testing agency for special inspection.
ACCESSIBILITY I
1 The main floor area requires 728 inches of exit width. Under the provisions of
0 OSSC, Section 1106.2.4(3) we interpret that all exits shown with the main floor
6
area shall be accessible. Provide details on how you will comply with the
Eagle Hardware Building Plan Review
PC #: 11-44c BUP#: 98 -0520
Page #3
required accessible route, crosswalks, curb ramps, walks and passing space.
OSSC, Section 1103.2, provide details.
0 #_ 2. Stairs require handrails on both sides, OSSC, Section 1109.8.6, provide details.
O lt 3. Provide an accessible locker. OSSC, Section 1108.4.6, provide details.
® (L4. The sink in the lunchroom shall be accessible. OSSC, Section 1108.4.11,
provide details.
Please submit three copies of revised documents to include the following:
1. Site plan.
2. Full structural.
3. Full architectural.
Please call me at (503) 639 -4171 if you have any questions.
Sincerely,
Ro ert Poskin, CBO
SENIOR PLANS EXAMINER
MAPRMSYS\D000MENT1BUP98 05.20\PC1144C.DOC