JUL 1 0 2000 Moisture - Density Relationship
Permit No.: 2000 - 00018
•
B nc - Andy Cartales 07/05/00
Project: Delta Fire Retaining Wall - Const Monitoring Job Number: G0001590
Material Type: Native Light Brown Silt Location: On - Site (Bottom of Cut)
Test Method: ASTM D -1557 A, C -136, D -2216 Date Sampled: 06/28/00
Sample Method: ASTM D -75 Date Tested: 06/29/00
Preparation Method: Moist Oversized Material: Removed
Compacting Method: Manual Hammer Type: Circular
107
•
•
106
105
104
c ,
p 103
102
101
100
15 16 17 18 19 20 21 22
Moisture Content ( %)
Zero Air Voids Line = 2.600
Optimum Moisture: I 17.9% I Max. Dry Density: I 104.5 I Ibs /ft'
Percent Passing #4 Sieve: 98.7%
cc: City of Tigard - Robert Poskin
Reviewed By:
Our reports pertain to the material tested /inspected only. Information contained herein! of to be
reproduced, except in full, without prior authorization.
06/30/00 FRI 11:08 FAX 503 670 9147 CARLSON TESTING ``1 0 0001
J ` -)00 /,/
C arlson Geotechnical Mein office Salem Office Bend Office
P.O. Box 23814 4060 Hudson Ave,, NE P.O. BoX 7918
A Division of Carlson Testing, Inc. Tigard, Oregon 97281 Salem, OR 97301 Bend, OR 97708
Geotechnical Consulting Phone (503) 684 -3460 Phone (503) 589 -1252 Phone (541) 330 -9155
Construction Inspection and Related Tests FAX (503) 670-9147 FAX (503) 589 -1309 FAX (541) 3.30 - 9163
uric 30, 2000
CGT No. G0001590
Permit No. 2000-000
FIELD OBSERVATION REPORT
PROJECT: Delta Fire
ADDRESS: 14795 SW 72 Tigard
BY: Jeanne M. Niemer, PE
WEATHER: Sunny and Warm
PURPOSE OF VISIT: Construction Monitoring
Arrived on site at 1000, per the request of Don of Anderson Construction. Met with the earthwork contractor on
site. While on site, I observed the condition of the subgrade for the proposed retaining wall. The subgrade
consisted of stiff to hard native silt. I probed the subgrade using a one -half inch steel rod, and was unable to
penetrate the subgrade more than about 1 /2 inch in any location.
Based on the results of my observations, the retaining wall subgrade has been prepared in accordance with the
plans, specifications and our recommendations.
Left site at 1015
J - - ne M. Niemer, P.E.
Prin •pal Geotechnical Engineer
• •te: Our reports pertain to the locations observed at the time of our visit only. Information contained herein is
not to be reproduced, except in full, without prior authorization from this office.
DISTRIBUTION
Andy Cartales, Delta Fire: 620.1058
City of Tigard: 684.7297
doc id: delta fireffr063000
C arlson Geotechnical _ Main Office Salem Office Bend Of/ice
P .O. Box 23814 4060 Hudson Ave., NE P.O. Box 7918
A Division of Carlson Testing, Inc. Tigard, Oregon 97281 Salem, OR 97301 Bend, OR 97708
Geotechnical Consulting Phone (503) 684 -3460 Phone (503) 589 -1252 Phone (541) 330 -9155
Construction Inspection and Related Tests FAX (503) 670 -9147 FAX (503) 589 -1309 FAX (541) 330 -9163
August 14, 2000
FILE C�P
Andy Cartales
Delta Fire, Inc.
PO Box 4101
Tualatin, Oregon 97062 -4010
Geotechnical Letter of Compliance
Delta Fire Retaining Wall
14795 SW 72n Avenue
Tigard, Oregon
CGT Proj: G0001590
Carlson Geotechnical has served as geotechnical engineer of record for the retaining wall at the
Delta Fire site in Tigard, Oregon. As geotechnical engineer of record, Carlson performed
footing subgrade observations, and observation and testing of backfill compaction during
construction. Based on the results of our observations, all earthwork was completed in general
accordance with the plans, specifications, and our recommendations. We provided field reports
to the design and construction team, as well as to the City of Tigard during construction.
Additional copies of our reports are available in our office, if needed.
Please contact us if you have any questions.
Sincerely,
CARLSON GEOTECHNICAL
;4\)_Pfifikei;
. - 1' - #156484
Jean e M. Niamer, •.E. :
Prin pal Ge echnical Engineer �?� ���
I OTIKS: t2.3t . co 1
Doc. ID: Delta Fire /comp letter