Specifications l` e FACP BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255 -9488 Office, (503) 255 -1966 Fax L ��® S E P 1 2 2007 JOB NAME: Dartmouth Square „� JOB ADDRESS: 11935 SW 70th Ave. Tigard, OR 97223 DATE: 9/5/2007 CITY t IGA D w PANEL DESCRIPTION: SK 5820XL FACP BY: Dan WiIso B1AI" PIpl'SION DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE DESCRIPTION QUANTITY CURRENT CURRENT CURRENT CURRENT FACP INTERNAL COMPONENTS 0.00000 0.000000 Silent Knight Model 5820XL FACP 1 0.140 0.14000 0.260 0.260000 5860 Remote Annunciator 1 0.020 0.02000 0.025 0.025000 5815XL SLC Expander 0.055 0.00000 0.055 0.000000 5496 Addressable Power Module 0.010 0.00000 0.010 0.000000 0.00000 0.000000 INITIATING DEVICES SD500 -PS Addressable Manual Station 1 0.000055 0.00006 0.000055 0.000055 Spklr Flow Switch w/ SD500 -MIM 1 0.000055 0.00006 0.000055 0.000055 Spklr Supv Switch w/ SD500 -MIM 2 0.000055 0.00011 0.000055 0.000110 Elev ST Pwr Monitor w/ SD500 -MIM 1 0.000055 0.00006 0.000055 0.000055 SD505 -APS Photo Smoke Detector, Spot 5 0.000055 0.00028 0.000055 0.000275 SD505 -AHS Heat Sensor 2 0.000055 0.000110 0.000055 0.000110 SD505 -ADH Duct Det. Housing W/ Photo Det 12 0.000055 0.000660 0.000055 0.000660 , OUTPUT DEVICES SD500 -ARM Relay Module (Elev Recall) 3 0.000055 0.00017 0.000055 0.000165 SD500 -ARM Relay Module (HVAC Shutdown) 1 0.000055 0.00006 0.000055 0.000055 SD500 -ARM Relay Module (FSD Control) 1 0.000055 0.00006 0.000055 0.000055 SD500 -ARM Door Release Control 3 0.000055 0.000165 0.000055 0.000165 SD500 -ARM Relay Module (Elev ST) 1 0.000055 0.00006 _ 0.000055 0.000055 I/O Number 1 Outside Sprinkler Flow Alarm 0.00000 0.000 Wheelock ASWP- 2475W -FW Outside H/S (H) 1 0.168 0.168 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 I/O 1 Alarm Total 0.168 I/O Number 2 Floor 1 Shell 0.00000 0.000 Wheelock AS- 24MCW -FW 110 Cd H/S (M) 0.253 0.000 Wheelock AS- 24MCW -FW 75 Cd H/S (M) 1 0.190 0.190 Wheelock AS- 24MCW -FW 30 Cd H/S (M) 0.110 0.000 Wheelock AS- 24MCW -FW 15 Cd H/S (M) 4 0.074 0.296 Wheelock RSS- 24MCW -FW 75 Cd Strobe 0.165 0.000 Wheelock RSS - 24MCW -FW 30 Cd Strobe 2 0.092 0.184 Wheelock RSS - 24MCW -FW 15 Cd Strobe 1 0.060 0.060 0.00000 0.000 0.00000 0.000 I/O 2 Alarm Total 0.730 Dartmouth, FACP (NAC1.0) Batt Calc.xls 5820XL Batt Caic FACP BATTERY CALCULATIONS I/O Number 3 Floor 2 Shell 0.00000 0.000 Wheelock AS- 24MCW -FW 110 Cd H/S (M) 1 0.253 0.253 Wheelock AS- 24MCW -FW 75 Cd H/S (M) 0.190 0.000 Wheelock AS- 24MCW -FW 30 Cd H/S (M) 0.110 0.000 Wheelock AS- 24MCW -FW 15 Cd H/S (M) 4 0.074 0.296 Wheelock RSS- 24MCW -FW 75 Cd Strobe 0.165 0.000 Wheelock RSS - 24MCW -FW 30 Cd Strobe 2 0.092 0.184 Wheelock RSS - 24MCW -FW 15 Cd Strobe 0.060 0.000 0.00000 0.000 0.00000 0.000 I/O 3 Alarm Total _ 0.733 I/O Number 4 Floor 3 Shell 0.00000 0.000 Wheelock AS- 24MCW -FW 110 Cd H/S (M) 0.253 0.000 Wheelock AS- 24MCW -FW 75 Cd H/S (M) 0.190 0.000 Wheelock AS- 24MCW -FW 30 Cd H/S (M) 0.110 0.000 Wheelock AS- 24MCW -FW 15 Cd H/S (M) 4 0.074 0.296 Wheelock RSS - 24MCW -FW 75 Cd Strobe 0.165 0.000 Wheelock RSS - 24MCW -FW 30 Cd Strobe 2 0.092 0.184 Wheelock RSS - 24MCW -FW 15 Cd Strobe 0.060 0.000 0.00000 0.000 0.00000 0.000 I/O 4 Alarm Total 0.480 I/O Number 5 24VDC Constant Power 0.00000 0.000 0.00000 0.000 FSD Control Relay: MR101 3 0.015000 0.04500 0.000 0.00000 0.000 Door Holder: ESL 3 0.015000 0.04500 0.000 0.00000 0.000 0.000000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 I/O 5 Alarm Total 0.000 I/O Number 6 0.00000 0.000 0.000000 0.000000 0.00000 0.000 0.000000 0.000000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 0.00000 0.000 I/O 6 Alarm Total 0.000 Dartmouth, FACP (NAC1.0) Batt Calc.xls 5820XL Batt Calc FACP BATTERY CALCULATIONS STANDBY TOTAL CURRENT: I 0.251815 I STANDBY HOURS: 24 STANDBY AMP HOURS: 6.04356 ALARM TOTAL CURRENT: ( 2.398 ALARM MINUTES: 5 ALARM AMP HOURS: 0.1998 TOTAL CALCULATED AMP HOURS 6.243 NAC TOTAL CURRENT: I 2.111 APPLIED SAFETY FACTOR 1.10 MINIMUM AMP HOURS REQURED 6.868 SELECTED BATTERY SIZE 1 2 EACH 12 VOLT, 12 AMP HOUR BATTERIES Dartmouth, FACP (NAC1.0) Batt Calc.xls 5820XL Batt Calc NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255 -9488 Office it 03) 255 -1966 Fax Job Name: Dartmouth Square 'Job Address: 11935 SW 70th Ave. Tigard, OR 97223 Job Number: Prepared By: Dan Wilson Date: 9/5/2007 Panel Description: Silent Knight 5820XL FACP Panel No.: NAC 1.0 NAC Devices Mfg By: Wheelock ALARM OUTPUT TOTALS OUTPUT 1 0.168 AMPS OUTPUT 2 0.730 AMPS OUTPUT 3 0.733 AMPS OUTPUT 4 0.480 AMPS OUTPUT 5 0.000 AMPS OUTPUT 6 0.000 AMPS TOTAL 1 2.1111 AMPS WIRE LENGTH TOTALS OUTPUT # 1 WIRE LENGTH 1 GAUGE OUTPUT 1 160 14 OUTPUT 2 361 14 OUTPUT 3 358 14 OUTPUT 4 270 14 OUTPUT 4 0 14 OUTPUT 4 0 14 TOTAL 1 11491 FEET Dartmouth, FACP (NAC1.0) EOLv Calc.xls JOB INF SHEET NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255 -9488 Office 4503) 255 -1966 Fax Job Name: Dartmouth Square -.Job Address: 11935 SW 70th Ave. Tigard, OR 97223 Job Number: Conductor Wire Guage I 14 I Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) I 3.07 I Date: 9/5/2007 Cable Length In Feet (source to end of line) I 160 I Total Circuit Current I 0.168 I Nominal System Voltage I 20.4 I Panel Description: Silent Knight 5820XL FACP Minimum Device Voltage I 16 I Panel No.: NAC 1.0 Output No.: 1 Point To Point Method EOLv I 20.23 I Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv I 20.23 I Circuit Within Limits ? YES Load Centering Method EOLv I 20.32 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet ) 1 Outside Sprinkler Flow Alarm ASWP- 2475W -FR W/P H /S -H 75 Cd 0.168 160 20.23 2 20.23 3 20.23 4 20.23 5 20.23 6 20.23 7 20.23 8 20.23 9 20.23 10 20.23 11 20.23 12 20.23 13 20.23 14 20.23 15 20.23 16 20.23 17 20.23 18 20.23 19 20.23 20 20.23 Dartmouth, FACP (NAC1.0) EOLv Calc.xls OUTPUT 1 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255 -9488 Office 1503) 255 -1966 Fax Job Name: Dartmouth Square Job Address: 11935 SW 70th Ave. Tigard, OR 97223 Job Number: Conductor Wire Guage I 14 I Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) I 3.07 I Date: 9/5/2007 Cable Length In Feet (source to end of line) I 361 I Total Circuit Current I 0.73 I Nominal System Voltage 20.4 Panel Description: Silent Knight 5820XL FACP Minimum Device Voltage I 16 I Panel No.: NAC 1.0 Output No.: 2 Point To Point Method EOLv I 19.57 I Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv I 18.78 I Circuit Within Limits ? YES Load Centering Method EOLv I 19.59 I Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device (feet) 1 Floor 1, Shell RSS - 24MCW -FW (30) STB WHT 30 Cd 0.092 60 20.13 2 Floor 1, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 20 20.05 3 Floor 1, Shell RSS - 24MCW -FW (30) STB WHT 30 Cd 0.092 20 19.98 4 Floor 1, Shell AS- 24MCW -FW (75) H/S WHT -M 75 Cd 0.190 65 19.80 5 Floor 1, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 53 19.70 6 Floor 1, Shell RSS- 24MCW -FW (15) STB WHT 15 Cd 0.060 43 19.65 7 Floor 1, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 68 19.59 8 Floor 1, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 32 19.57 9 19.57 10 19.57 11 19.57 12 19.57 13 19.57 14 19.57 15 19.57 16 19.57 17 19.57 18 19.57 19 19.57 20 19.57 Dartmouth, FACP (NAC1.0) EOLv Calc.xls OUTPUT 2 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255 -9488 Office 1 255 -1966 Fax Job Name: Dartmouth Square - Job Address: 11935 SW 70th Ave. Tigard, OR 97223 Job Number: Conductor Wire Guage I 14 I Prepared By: Dan Wilson Ohms Per 1000 Ft © 75 Deg C (167 Deg F) I 3.07 I Date: 9/5/2007 Cable Length In Feet (source to end of line) I 358 I Total Circuit Current I 0.733 Nominal System Voltage ` 20.4 I Panel Description: Silent Knight 5820XL FACP Minimum Device Voltage I 16 I Panel No.: NAC 1.0 Output No.: 3 Point To Point Method EOLv I 19.62 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv I 18.79 I Circuit Within Limits ? YES Load Centering Method EOLv I 19.59 I Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet ) • 1 Floor2, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 35 20.24 2 Floor 2, Shell RSS- 24MCW -FW (30) STB WHT 30 Cd 0.092 31 20.12 3 Floor 2, Shell RSS - 24MCW -FW (30) STB WHT 30 Cd 0.092 30 20.01 4 Floor 2, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 35 19.91 5 Floor 2, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 45 19.80 6 Floor 2, Shell AS- 24MCW -FW (110)H /S WHT -M 110 Cd 0.253 60 19.68 7 Floor 2, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 122 19.62 8 19.62 9 19.62 10 19.62 11 19.62 12 19.62 13 19.62 14 19.62 15 19.62 16 19.62 17 19.62 18 19.62 19 19.62 20 19.62 Dartmouth, FACP (NAC1.0) EOLv Calc.xls OUTPUT 3 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255 -9488 Office t503) 255 -1966 Fax Job Name: Dartmouth Square gob Address: 11935 SW 70th Ave. Tigard, OR 97223 Job Number: Conductor Wire Guage I 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) I 3.07 I Date: 9/5/2007 Cable Length In Feet (source to end of line) I 270 I Total Circuit Current I 0.48 I Nominal System Voltage I 20.4 Panel Description: Silent Knight 5820XL FACP Minimum Device Voltage I 16 I Panel No.: NAC 1.0 Output No.: 4 Point To Point Method EOLv I 20.01 I Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv I 19.60 I Circuit Within Limits ? YES Load Centering Method EOLv I 20.00 I Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet ) • 1 Floor 3, Shell RSS - 24MCW -FW (30) STB WHT 30 Cd 0.092 45 20.27 2 Floor 3, Shell RSS - 24MCW -FW (30) STB WHT 30 Cd 0.092 28 20.20 3 Floor 3, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 36 20.14 4 Floor 3, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 46 20.07 5 Floor 3, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 25 20.05 6 Floor 3, Shell AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 90 20.01 7 20.01 8 20.01 9 20.01 10 20.01 11 20.01 12 20.01 13 20.01 14 20.01 15 20.01 16 20.01 17 20.01 18 20.01 19 20.01 20 20.01 Dartmouth, FACP (NAC1.0) EOLv Calc.xls OUTPUT 4 # INT ELLIKNIGH T FIRE ALARM CONTROL PANEL �� � . :mo _ _ - Intellii(night® Model 5820XL Addressable Fire Alan® Control System / tr a . ,,,,A4 . r tA ' .,. . . , The IntelliKnight System is the easy ,*. , , f ® way to make the most of fire alarm ' y 10 j technology. IntelliKnight is the first fire alarm system to provide you with the revolutionary value and performance of addressable sensing technology combined with exclusive, built -in digital communication, distributed intelligent power, a modular design and an expanded, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the IntelliKnight system, or to locate your nearest source, please call 1- 800 -446 -6444, or in Minnesota, call 763 -493 -6435. Desaltption • Two built -in Form C programmable _ _ The IntelliKnight 5820XL performs drift relays rated at 2.5 amps at 24 VDC. Y y • compensation and calibration checks Supports Sounder Bases. t — :� on each of the sensors in the system. SpedfcUI1Ons 1 f •, 11 The basic IntelliKnight 5820XL system Primary AC: 120 VRMS at 50 / 60 hz, ai can be expanded by adding modules 2.5A such as the Model 5860 Remote Total Accessory Load: 5A at 24 VDC _ -- Y r IW Annunciator, Model 5815XL Signalling 5 amps at 24 VDC of power - limited + Line Circuit Expander, the Model 5824 notification power r ' 3.1 ' ,. •— ,1 i iff Serial /Parallel Interface (for printing 1 { - ``t E +r! ; • I j Standby Current: 140 mA i r � ; , system reports), and the 5895XL - I. .. , ; , Intelligent Power Module. The Model Alarm Current: 260 mA ; 5820XL also features a powerful built -in Flexput'"" Circuits i'I^; dual line fire communicator that allows Six programmable circuits which can ."�` for reporting of all system activity to a be programmed individually as: i remote monitoring location. Notification circuits: 3 amps of Feaiures power - limited power per circuit at 24 i ` - • Up to 508 addressable points. VDC. ;; li 'L z _ • • Uses standard wire —no shielded or Auxiliary power circuits: 3 amps of i i twisted pair required. power - limited power per circuit at 24"� • Built -in digital communicator. VDC. • Central station reporting by Point or Initiation Circuits: 100 mA of power Approvals: by Zone. limited power per circuits at 24 VDC. UL Listing • Supports Class B (Style 4) and Mediankal Spedfications: NFPA 72- Central Station Class A (Style 6) configuration for Flush Mount - Remote Signalling SLC, SBUS, and Flexput circuits. Dimensions: -Local Protective • Distributed, intelligent power. - 14 -1/2 "W x 24 -3/4 "H x 3 -7/8 "D Signalling System • Drift compensation. (36.8 W x 62.9 H x 9.8 D cm) - Auxiliary Protected • FlexputTM' I/O circuits. Premises Unit • Eight pre - programmed output Overall Dimensions: cadences, (including ANSI - 3.41), 16 -1/8 "W x 26 -3/8 "H x 4 -1/8 "p -Water Deluge and 4 programmable outputs. (40.6 W x 67 H x 11.8 D cm) Releasing Service • Built -in annunciator with 80- Weight: 28 lbs. (12.8 kg) CFSM: 7165 -0559: 135 character LCD display. Color: Red MEA 429 -92 -E Vol. 9 • RS-485 bus provides communication Telephone Requirements: FM approved to system accessories. FCC Part 15 and Part 68 approved • Built -in RS -232 interface for Type of Jack: RJ31X (two required) programming via PC. "-'-'.- SILENT • Built -in Form C trouble relay rated at N KNIGHT 2.5 amps at 24 VDC. 0 ,k INTELLIKNIGHTFIREALARM ': CONTROL PANEL IntelliKnight Model 5820XL Addressable Fire Alarm 71) Control Panel Indicator Lights : enclosure is required for batteries dialing. The communicator is GENERAL ALARM (Red) - On for in excess of 17 amp hours. compatible with SIA and Ademco alarm Flexput circuits on the Model Contact ID. The format is 5820XL control can be individually selectable by account number. SUPERVISORY (Yellow) - On programmed to function as notifi- User Interface when a supervisory condition cation circuits, auxiliary power exists. The IntelliKnight's built -in outputs, or initiation circuits that annunciator with 80 character LCD SYSTEM TROUBLE (Yellow) - On support both 2- and 4 -wire smoke display and large easy -to -use when a trouble condition exists. detectors. tactile touchpad can be used for SYSTEM SILENCED (Yellow) - On The IntelliKnight system operates system operation, programming when an alarm, trouble or on non - twisted, unshielded cable supervisory condition has been and maintenance. It has five LEDs su P rY when wired in compliance with for alarm, supervisory, system silenced but not yet cleared. standard wiring practices as called trouble, system silenced and SYSTEM POWER (Green) - On out in the National Electric Code system power. System operations when power systems are 760 specifications for power - limited include silencing alarms and normal;flashes for AC or DC fire protective signalling cables. No troubles, resetting alarms and the failure. special wiring is required. display of alarm troubles and System Application The Model 5820XL provides seven memory. The system's non - volatile The IntelliKnight Model 5820XL preset notification cadence patterns event history buffer stores 1000 control panel has one built -in including ANSI 3.41 and four user events for viewing from the built -in Signalling Line Circuit (SLC) which programmable selections for fire or remote annunciator. System supports 127 devices. Three alarm notification. _ I additional loops can be added Two programmable general purpose Form C relay outputs are 1 P *a- using the 5815XL SLC expanders s,.,..a..: to increase overall capacity to 508 provided on the Model 5820XL a „*,•,�,,, FACP. — ;,..-.::,•;. - - devices. A.. �_, r . The Model 5820XL's SLC loops Additionally, the IntelliKnight support multiple device types: system features a built -in walk test at in Is A : 4 • Addressable photoelectric smoke and auto - programming. Its ii No ON 1 III. innovative, dead -front cabinet Es mg of in detector design allows for flush or surface Off OO MO • Addressable ionization smoke mounting. System maintenance is ",µ . detector easy to perform. • Addressable heat sensor Built-in i l C it Di aommuncator • Addressable duct smoke g operation can be initiated with a detector The IntelliKnight Model 5820XL mechanical firefighter's key or a • Contact module features a built -in UL listed digital valid 4- to 7 -digit operator's code. • Relay output module communicator for remote reporting Programming • Addressable notification module of system activity and system The IntelliKnight system offers The following advanced sensor programming. The communicator several options to simplify and capabilities are available using the has the ability to seize two speed up programming. The IntelliKnight Model 5820XL: telephone lines to report alarms JumpStartTM feature minimizes • Automatic drift compensation and troubles to a monitoring facility. programming required to start a The communicator supervises two new system. The built -in keypad • Maintenance alert phone Tines and will activate a and the 5860 Remote Annunciator • Built -in sensor test to comply trouble signal if a line failure is give on -site access to all with NFPA 72 calibration testing sustained for more than 45 programming. You can also requirements seconds. Other communication program remotely using the The IntelliKnight 5820XL features a features include: retry if communi- Windows Download Software. 5 amp power supply and maximum cation fails, two phone number battery charging capacity of 33 capability, download phone number amp hours. An additional cabinet capability and touchtone or rotary . INTELL•IKNIGHTFIREALARM CONTROL PANEL, IntelllKnight Model 5824X1. Addressable Flre Alarm Control Panel • I ntelliKnight 5820XL Addressable Fire Alarm System WWw3De *ad P•e:'Y ! j W.xm`3D3rn l ' R � tC9ra 1 SoVe3re d I . 9800 9500 wDS.m m nrrs. 17-1.P. Rac RN a41e1 .,Weera d�Dal e R.Yr+« 5895XL 5840X1. Imrprevvow 111g9.1e 1 :. { 3PVmCHHUlf JFwm �..rys 11 ::: ' :::- L_ 1 Evora Prate X - k Z . w v : • . - lt. e I ; .., � 5860 5824 ' , R.1990Arr'.n r P,aev.9R.'apY7:aC41 C Lnb 41uP.�T..m1t — 5615X1. 9 C E nbt $61$x1. l I I 9 � � L« 0 6 6 q FlexputTM FlexputT"' ti 8 .21.9rtbv .Moi l. aWliAC3 l 9 I •,,C, } k P A Cuban. Caw».nanr 9.3/;•41 Dou OCKI3/3 r I � _ � .. 1 1 � • 50505 -APS S 0505441 50505 -658 50505 -AHS 60505SQM AC1uu t. AM er• 9132.10, Data ACEreeLD:e N.M 24'.:33 • ; l:5. PbotoSct terCnn DS.Ces £mextePeal. ` t„ D•wnr D•bCer 5860 t r _I__ -i 1 Sbtl,e AnnuviaW ` , • 30505.325 H � � � . • Remo e _____ —1 � • ®1 0500 -ANM SD505 -6RB 5050541/3 S13505-6A8 I i' 5880 [ —♦� w t AGYr.mD'+ AaMeeafe Rr�9m trJaty .'DU•cfe8v. . LCD Darer 1 SD500 -LED 5 MC 11 NdJkGan am Dr . ' 1.63931. 4bdW I , ii j f I 'f I._� I _ tyil• I 6 1 I I T I_ - -ra°� I L --1111111111111111 ; f _ " ` ,- 5863 ci A i - - - r � RCry, a 88 3 3237. 4 S0505ADHR 50500 -PS 50505 -AOH 50500441M SD500 -ARM 50500-L11M Peau•s3.393. Cud Attam9a313 bdr•awl• Ws Coy Cod. A 41no SS4 Add39344 Iaaeoo Wfe Ka( Pull 231320 MC C.1ee.1 19a9113C3 Rory LbauN 1.1 fy On PnOaaottt Ka'm19 4X.634 More or P11e1f1s6r.1 ':ailk'M' r 58654 of 5865.3 I I Le•■,,4o4- 4 I Use he 5320 to control up to 4i_ _ 9319.1 gee„ 5583 Relay Interface Modules I J • INTELLIKNIGHTFIREALARM CONTROL PANEL 'nte'Igni System �� m ount on a 4 in square electrical 5860 Remote Fire g box. • Prov • i nd i cator LED to show Annunciator t _< output status and comes with a The 5860 features the ' P same 80 character ' 4 coverplate. I • 7= '' „y 3 I Model SD505 -ADH backlit LCD display ”' I gr Duct Housing. Detects smoke in HVAC keypad and firefighter's 1 ducts. keyswitch as the 5820. t -= The s stem can be full ro rammed • � 3 ti .r ,- Model SD50 - ADHR system y p g k 1- Duct detector base with relay. Provides and operated from any remote , annunciator. form C alarm contact. For use with ' 1 1 ; _ ^ SD505 -APS and AIS sensors. 5815XL Signal Line Circuit Expander Compatible with SD505 -DTS remote The SLC expander is used to add more test switch. addressable devices to the IntelliKnight - - Model SD505 -DTS system. The 5820XL can support three Compatible Devices Remote test switch. Used with SD505 5815XLs. Each 5815XL can support IntelliKnight's devices feature a low 127 devices. ADHR. Provides remote key operated profile design and EEprom addressing. test function and annunciation of 5895XL Intelligent Power Module EEprom addressing prevents water detector alarm. Adds 5 amps of power, 6 FlexputTm I/O intrusion problems via the back of the Model SD505 -6SB circuits and 2 Form C relay circuits to sensor and eliminates mechanical an IntelliKnight system. failures related to decade switches. Six-inch sounder base. Operates in Model SD505 -APS single and multi- station modes and /or 5880 LED/I0 Module Addressable photoelectric smoke as a system sounder. Used with Features 40 LED outputs, 8 normally detector. existing sensor and base. Requires 2 open dry contact inputs and one piezo additional wires for power. output. Model SD505 -AIS Model SD505 -61B 5865 -3 and 5865 -4 Addressable ionization smoke detector. Six inch isolator base. Used with Remote LED Annunciator Model SD505 -AHS existing base and the SD505 -APS, Features 30 Programmable LEDs (15 Addressable heat sensor. AIS, and AHS sensors. Provides red and 15 yellow) outputs and piezo Model SD505 -6AB isolation for style 7 circuits. sounder. The 5865 -4 adds a silence Six inch base designed for use with Model SD505 -6RB and reset switch to the package. detector head models SD505 -APS, Six -inch relay base. Used with existing 5883 Relay Board SD505 -AIS and SD505 -AHS. sensor and base. Provides one Form C Features 10 General purpose Form C Model SD505 -4AB contact. relays. Used with 5880 module. Four inch base designed for use with Model SD500 -SDM 5824 Serial /Parallel Gateway Module detector head models SD505 -APS, Two -wire detector input module. Allows Has one parallel and one RS -232 serial SD505 -AIS and SD505 -AHS. for the connection of conventional 2- port for connecting any standard IBM - Model SD500 -AIM wire detectors on the SLC loop. compatible printer to the IntelliKnight Dry Contact Input Module. Designed to Requires two additional wires for system. Interfaces with building control used with normally open dry contacts. power. system. Mounts in a 4 inch square electrical Model SD500 -LIM 5496 Intelligent Power Module box. It features an indicator LED to Loop Isolator Module. Provides The Model 5496 is a 6 amp.notification show alarm status and a coverplate. isolation for style 7 circuits. power expander that provides four Model SD500 -MIM Model SD500 -LED additional power - limited notification Mini Dry Contact Input Module. A An Addressable LED driver module that appliance circuit outputs. miniature version of the addressable connects to the SLC loop and is SKSS Silent Knight Software Suite input module which is designed to be capable of driving 80 LEDs. Up to 40 5660 Up Down Load Software used with pull stations and other SD500 -LED modules can be used SLC User - friendly, WindowsTM software for normally open dry contact inputs where loop with a maximum or 100 SD500- remote programming of the IntelliKnight a smaller size is desired. LED modules per system. panel using a PC. Model SD500 -ANM Model SD500 -PS 5670 Facility Management Software Addressable Notification Module Addressable Pull Station Powerful end -user software allows providing a single Class A or Class B S -BUS Accessories viewing of detector status and event notification circuit on the SLC. The following items listed are devices history via modem or direct connection. Model SD500 -ARM that connected to the IntelliKnight's RS- Addressable Relay Module. Features 2 485 Bus Form C output relays, designed to ilti SILENT KNIGHT MADE IN AMERICA FORM# 350210, Rev. 10/01 7550 Meridian Circle, Maple Grove, MN 55369 -4927 Copyright © 2001 Silent Knight 800-446 -6444 or in Minnesota 763 -493 -6435 FAX: 763 -493 -6475 IntelliKnight is a Registered Trademark of Silent Knight World Wide Web: http: / /www.silentknight.com Flexput is a Trademark of Silent Knight , INTELLIKNIGHT ACCESSORY � `_ 5 y 47 ; f ! Mo del 5860 - ' x ,�1 s: Remote Annunciator - it , i ;''' - 4 -- �''' Bring the power to control IntelliKnight® to every ' _ area within your facility. Now you can operate and program your IntelliKnight system from up to 8 locations throughout your facility. The Model 5860 Remote Annunciator provides the same advanced, easy -to -use interface found on the IntelliKnight panel's built -in annunciator. The 80- character display and ergonomically designed keypad allow for simple and error -free system operation. All operations — including reset, silence, detector status checking, fire drill, and programming —are identical. Access to the system is through a firefighter's key or an access code. For security, a special installation code is needed for programming functions. The 5860 connects to the IntelliKnight panel via the RS-485 system bus. Wire runs can be up to 6000 feet from the panel. Model 5860 Users identify themselves to the Remote �IIUI�O control panel by entering a code on . the annunciator or by turning the The 5860 is designed to look and firefighter's key. When a user w: operate exactly the same as the presses a button, the annunciator . IntelliKnight built -in annunciator. piezo beeps and the LCD prompts Features include an 80- character the user to enter a code or other UN backlit LCD providing easy -to- relevant information. understand system messages. The annunciator is ergonomically Multiple users can work at different 5860 Remote kmuadmor designed with over -sized buttons annunciators simultaneously for the most frequently used without affecting each other. Spedfications Operating voltage: 24 VDC features, like Reset and Silence. Features Standby Current: 20 mA In addition to status messages • 80- character display displayed on the LCD, there are Alarm Current: 25 mA • Tactile /audible feedback five LEDs for alarm, supervisory, Max. per system: 8 • trouble, silence, and AC power Accepts user codes or p firefighter's key Ambient Temperature: 32°F to 120°F status. (0 °C to 49 °C) • RS-485 interface to panel The annunciator is available in gray Can be flush or surface- Mounting: Surface or flush • to match virtually any decor and red mounted. Trim ring available for Wiring Distance from for applications where the surface- mounting. IntelliKnight panel: Up to 6,000 feet annunciator must stand out. The annunciator enclosure can be • Operation and appearance Dimensions: Height: 7 -3/8" identical to on -board annunciator Width: 1-1/2" surface or flush mounted. A trim Depth: 1 -1/2/2• " ring kit is available for surface • Supports simultaneous use by Colors: Lt. gray (5860) mounting. multiple users Red (5860R) Oxon • UL listed, complies with NFPA 72 • When the system is normal and CSFM Approved receiving AC power, the power LED • MEA Listed is lit and all other LEDs are off. Other LEDs turn on as the SILENT conditions occur. KNIGHT 1NTEL'LIKNIGHTACCESSORY` • Model 5860 Remote Annunciator Engineering Spedfaations The main control must have a built -in annunciator and must support up to eight remote annunciators. Remote annunciators shall have the same control and display layout so as to match the appearance of the built -in annunciator. Remote annunciators shall be available in two colors, red or light gray. Remote annunciators shall have identical functionality and operation as the built -in annunciator. All annunciators must have an 80- character LCD display and must feature five LEDs for: General Alarm, Supervisory, System Trouble, System Silence, and System Power. All controls and programming keys are silicone mechanical type with tactile and audible feedback. Keys have a travel of .040 inches. No membrane style buttons will be permissible. The annunciator must be able to silence and reset alarms through the use of a code entered on the annunciator keypad or by using a firefighter's key. The annunciator must have two levels of user codes that will limit the operating system programming to authorized individuals. The control panel must allow all annunciators to accommodate multiple user input simultaneously. 5860 Nods; Dlogr m IMO Up O Ocao fr.41 panct a • r Up lo 8 deMeE.;,et s±/: "ern. Tilt= t SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800 - 446 -6444 or in Minnesota 612 - 493 -6435 FORM# 350224, Rev. 01/00 FAX: 612 -493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2000 Silent Knight C' INTELLIKNIGHT ACCESSORY a 1 Addressable F,:: ,r Photoelectri Typ Smoke Detector Detect smoldering fires quickly and get help fast a 1 r. with IntelliKnight® photoelectric smoke detectors. ,; . ' # 1 IntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505 -APS photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds are wasted in determining location of an alarm. The SD505 -APS compensates automatically for contamination in the environment. And detector testing is simple —even from a remote site. Like other IntelliKnight detector models, the SD505 -APS offers a low profile for pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model SD505 -6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight smoke detectors —easy installation, stable operation, RF /transient protection, and vandal- resistant locking —and it adds up to a flexible solution for all your fire protection needs. Model SD505 -APS The light received is converted into Anal / Addressable an electronic signal. Under normal conditions, the status LED blinks Photoelectric Type approximately every 15 seconds, Smoke Detector indicating that the head is; a • The SD505 -APS is particularly communicating with the loop. The . LED lights continuously during the suited to detecting dense smoke typical of fires involving materials alarm period. such as soft furnishings, plastic, hectares foam or other similar materials • Low profile, 2 inches, including • w SDSOS-APS Smoke Detector hich tend to smolder and produce base large visible particles. Simple and reliable addressing ,,,�p,,,� • The detector features automatic without mechanical switches Specipcations compensation for contamination Operating Voltage: 17 -41 VDC com p Automatic compensation for and a simple detector calibration sensor contamination Current Consumption: test procedure that can be run from • Built -in fire test feature Standby: .55 mA the panel or remotely (using the Alarm: .55 mA • Simple detector calibration WindowsTM based downloading testing through the control panel Ambient Temperature: 32 °F to 100 °F software). or remotely through a (o °c to 50°C) Operation WindowsTM based computer Mounting: 4" Square, 4" OCT, software. Single gang mud The SD505 -APS units made up of ring an LED light source and a silicon • Vandal- resistance locking Relative Humidity: 85% photo diode receiving element. In a features noncondensing normal standby condition, the • Field cleanable Sensitivity: 0.88% - 3.57% FT receiving element receives no light • UL listed, meets NFPA 72 Ch 7 from the pulsing light source. In the requirements Air Velocity: 500 - 4000 FPM event or fire, smoke enters the • CSFM approved detector and light is reflected from MEA approved • the smoke particles to the receiving SILENT element. 4 4 KNIGHT INTELLIKNIGH.TACCESSORY • Model SD5O5 -APS • Addressable Photoelectric Type Smoke • Detector ' • Engineering Spedfiartions The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector Silent Knight SD505 -APS. The combination detector head, and twist -lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight 5820XL fire panel. The base shall permit direct interchange with Silent Knight SD505 -AIS Ionization Smoke Detector, or SD505- AHS Heat Detector. Base shall be the appropriate twist -lock base SD505 -6AB. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal- resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SD505 -APS shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. • tf Diameter = 5- 15/16" N Diameter = 3- 15/16" N o ea At � o I , ` Height = 2 inches, , including base ® Model SD505 -6AB Detector ease • Model SDsos -APS Moder Head (soot vlooi) (front view) • ti SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800- 446 -6444 or in Minnesota 612 -493 -6435 FORM# 350225, Rev. 01/00 FAX: 612- 493 -6475 Copyright ©2000 Silent Knight World Wide Web: http:JJwww.silentknight.com r�+ £ A. ` F INTELLIKNIGHT ACCESSORY r- .. . - Addressable Heat Detector 1 S ! ...% - ' ' r .,„,.‘ _ , , . . .., f .:. ALr' ,.■ IntelliKnight® addressable heat detectors combine t ' accurate heat detection with pin-point location ID. ' An essential combination for any installation. IntelliKnight heat detectors are an essential component in virtually any IntelliKnight installation. The IntelliKnight panel recognizes each detector by its specific address, so precious seconds are not wasted in determining location of an alarm. Like other IntelliKnight detector models, the SD505 -AHS offers a low profile for pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model SD505 -6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight detectors —easy installation, stable operation, RF /transient protection, and vandal- resistant locking —and it adds up to a flexible solution for all your fire protection needs. Model SDS0S -AHS If the temperature exceeds the trip Addressable Heat Detector point (programmed at the panel) an alarm occurs. The status LED The SD505 -AHS is a heat detector lights continuously during the alarm ' ;' `, suited to virtually any commercial period. I setting. The SD505 -AHS is an °, absolute temperature device. This Under normal conditions, the status means that it responds in alarm if LED blinks approximately every 15 the temperature goes above the seconds, indicating that the head is • trip point (programmed at the communicating with the loop. panel). • Features The SD505 -AHS provides accurate • Low profile, 2 inches, including SD505 -AHS Heat Detector temperature measurement data to base Scatlons the fire alarm control panel. This Absolute temperature device Operating Voltage: 17 to 41 VDC • heat detector is particularly suited to environments where smoke • Simple and reliable addressing Current Consumption: detectors cannot be used because • Uses digital communication Standby: .55 mA of the presence of steam or protocol Alarm: 55 mA cooking fumes, such as in a • The SD505 -AHS is UL Listed Detection Temperature kitchen. • Range: 135 °F to 150 °F and meets the requirements (57 °C TO 65 °C) t outlined in NFPA 72 Inspection Operation Ambient Temperature: 32 °F to 100 °F Testing and Maintenance, (o °C to 37 °C) The SD505 -AHS unit is made up of Chapter 7. an externally mounted thermistor Mounting: 4° SQR, 4" OCT with a specially designed cover that CFSM listed Single gang mud protects the thermistor while • MEA listed ring allowing maximum air flow. The Rated Spacing: 70' between thermistor reads the temperature sensors on smooth from the air it takes in. It then ceilings. transmits a signal representing the SILENT temperature to the IntelliKnight KNIGHT • panel. . 4/1 INTELLIKNIGHT`JACCESSORY • Model SD505 -ADH yF�� Z •FJi ' ,t --., Duct Smoke Detector iii ;'4 , Detect smoke in air handling systems and -1 _ 4' air handeling equipment with Silent Knight's addressable duct smoke detector The SD505 -ADH addressable duct smoke detector detects smoke and products of combustion present in air moving through an HVAC air handling system. The SD505 -ADH is a heavy duty metal housing with a pre - installed detector base. When smoke is detected in a duct, the unit communicates the condition to the IntelliKnight control panel. The panel, in tum, depending on programming and wiring, turns off fans, blowers, and other devices. The SD505 -ADH is designed to be used with Silent Knight's SD505 -APS Photoelectric Smoke Detector and SD505 -AIS Ionization Smoke Detector. Now there's even more power and flexibility available to the IntelliKnight family of products! . Model SD50S -ADH — - -. Spedpaalons Dud Smol® DMedor i _ • Included Parts: Metal housing with 7.5" The Model SD -505 ADH Duct i °�� exhaust tube Smoke Detector is a heavy duty '.-.---- x - '`' . SD505 4A8 detector base � metal detector housing with a pre- 'ti ; f #i Installation template installed detector base. The unit is 1 4 mounting screws compatible with Silent Knight's Accessory (parts not included with SD505 -APS photoelectric and models: SD505 -ADH) SD505 -AIS ionization smoke SD505-APS Photoelectric Smoke Det. detectors. , .=. SD505 -AIS Ionization Smoke Det. All features of the photoelectric ; SD500 -ARM Relay Module and ionization detectors are STS -2.5 Sampling tube for 6" to FeatUMS 2.5' duct width available, including automatic drift compensation for contamination • Two - wire connection to SLC STS -5.0 Sampling tube for 2.5' to com P 5.0' duct width and the automatic detector • LED alarm indication and STS -10.0 Sampling tube for 5.0' to calibration test. Detector calibration communication on sensor head 10.0' duct width can be checked from the panel or • Rugged steel backbox with clear (using the IntelliKnight plastic cover Current: (alarm mA remotely ( 9 9 P (alarm and standby) software with a WindowsTM based • Installation template included Computer). • Large terminal connection screws Air Velocity: 500 -4000 fpm (SD505 -APS) g 300 -4000 fpm (SD505 -AIS) Opendlon • Interchangeable "plug -in" Air sampling is accomplished by photoelectric or ionization heads Sensitivity: 1.1 (SD505 -APS) % obs two tubes which protrude into the • 3 standard tube lengths 0.8 (SD505 -AIS) % obs duct. An exhaust tube of one • UL listed, complies with NFPA 72 Ambient 32 °F to 100 °F standard length (7.5 ") is provided and 101 Temperature: (0 °C to 37 °C) with the detector housing. Intake • CSFM listed Humidity: 10 to 85% RH sampling tubes (ordered • MEAApproved 429 -92 -E, Vol 9 separately) are supplied in three • FM Approved Dimensions: 10" H x 8.25" W x 2.25^ D standard lengths. Duct mounting is SILENT Color Gray accomplished through a template and 4 sheet metal screws fel KNIGHT (provided). 4, 1 ' " IN TEL' LIKNIGHTO ACCESSORY Model SD505 -ADH Duct Smo k e Detector Engineering Spedficafons The air duct smoke detector shall be Silent Knight Model SD505 -ADH. The housing shall contain a detector base, Silent Knight model SD505 -4AB. The detector housing must be compatible with Silent Knight smoke detector head models SD505 -APS (photoelectric) and SD505 -AIS (ionization). One detector head must be used for each SD505 -ADH used. The detector head must perform an automatic sensitivity check every 3 hours. The duct detector housing shall be of metal construction. Complete mechanical installation must be able to be perforhied without removal of the detector cover. Terminal connections shall be screw type using a minimum of #6 screw. SD505.ADH Dimensions Front View Side View N O ® ® , Air 10" sampling tube 0000 �) • m 14 8.25" • • 2.25" 2.75" it SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800-446-6444 or in Minnesota 763 -493 -6435 FORM# 350216, Rev. 01/01 FAX: 763-493-6475 World Wide Web: http: / /www.silentknight.com Copyright © 2001 Silent Knight e 1 (KNIGHT ACCESSORY SD500 - PS and SD500 -PSDA • Addressable Pull- Station :_7 r IntelliKnight's addressable pull stations combine -- fast response with pin -point location ID. 1 The SD500 -PS and SD500 -PSDA are a single action or dual action addressable manual fire alarm pull station for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SD500 -PS /PSDA provides a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. The SD500 -PS /PSDA mounts to a single gang box and features a rugged metal construction that lasts and lasts. Combine all this with the features you've come to expect from Silent Knight - easy installation and stable operation - and it adds up to a flexible solution for all your fire protection needs. Model SD500 -PS & SD500 -PSDA • Reflective label makes it easier Addressable Pull Station to locate in low li -- OperaHon PULL .4. The SD500 -PS is a single action The SD500 -PS /PSDA single action a # addressable fire pull station, and pull stations are operated by a pull C.. the SD500 - -PSDA is a dual action i addressable fire pull station. The on the front pull cover of the station. A plunger switch, wired to SD500 -PS /PSDA feature rugged , 1 metal construction A terminal strip a self contained addressable : ► fa E on back of the pull station allows module, is released as the pull interconnection of the pull station to station opens to initiate the alarm. the SLC of an IntelliKnight control Once operated, the cover hangs panel. The SD500 -PS /PSDA is down and can be seen up to 100 FIR designed for indoor use in non- feet away. The pull station is reset explosive environments. The by returning the front cover to the .`z. `� . normally open initiating point normal upright position and contacts are gold - plated to avoid relocking the station with a reset ALARM key. The reset keys are the same risk of corrosion. The SD500 keys used on Silent Knight PS /PSDA has been tested by UL enclosures. for compliance to the requirements — II.E' i of the Americans with Disabilities The SD500 -PS /PSDA includes a ' VN 1Ci ACT (ADA). status LED which blinks, indicating y that the addressable module is Feahnes commun with the loop. The • UL Listed status LED lights continuously SD500 -PS • CSFM listed during an alarm. A dip switch on • ADA compliant the addressable module is used to • Key reset (Same key as Silent set the unique address. Knight enclosures) Spedfiaftions • Surface mount back box Operating Voltage: 24VDC available Standby Current: .55mA • Terminals - accept up to 14 Alarm Current: 55mA wire Ambient Temperature: 32 °F to 120 °F SILENT gauge 9 (0 °C to 49°C) • Extremely easy to operate Mounting: single gang T KNIGHT • Corrosion - resistant gold - plated box - contacts. Optional Red Surface Mount Box PS -SMBB • ! INTELLIKNIGHTACCESSORY • SD500 -PS and SD500 -PSDA r . • Addressable Pull- Station " 1. Engineering Sped cation Manual pull station shall be addressable Module SD500- PS /SD500 -PSDA. Equipment shall be made of 14 gauge C.R.S.(Cold Rolled Steel), painted with a red enamel . The label shall contain the words Fire Alarm and be made of a reflective material embossed text 3/8 inches tall. Operating instruction shall be clearly visible on the same label. Manual station Shall contain a key operated test and reset lock using a lock plate actuator, the key shall match the control panel. Manual station shall contain four terminal blocks with two connected to the addressable module and two connect to the SLC loop. Manual station shall provide data to the control panel with an ID address programmed by dip switch settings . Manual stations shall be Underwriters Laboratories Inc. listed and installed within the limits defined in the American Disabilities Act. �. _ ~ Y Win =A`rwr t` ~ � ~ ��^ 1 ` !P 1I 4 / IC IllU hl _ 1 1 ..,.._, M ` y ■ ,,,.,_ 9 , . - I• y - 1 _ f S. V! AN., `v ( f t i t ` 1/4..,, _ , ___ `� k 1 • I N N. 1Ai I - j `-,I Wiring j a e t— _ -- - - -e Mounting to Single Mounting to Optional - i -' Gang Electrical Box Surface Mount Box I , ii SD500 -PSDA 1 Ill UFT b Installing SD500 -LK Dimensions s - . iti SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800-446-6444 or in Minnesota 763 - 493 -6435 FORM# 350342, Rev. 09/02 FAX: 763 -493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2002 Silent Knight TJ INTELLIKNIGHT ACCESSORY tr'A P • !' ._: 1 Model SD500 -AIM - '' ! Addressable Input Module . 6 A�xA And ' ` Model SD500 -MIM Miniature Input Module .t �= `— IntelliKnight's addressable contact monitor modules ' • a, ,' ,, combine fast response with pin -point location ID. . A `: A combination that saves lives and property. The SD500 -AIM and SD500 -MIM are addressable input modules for use with Silent Knight's IntelliKnight fire control panel. The SD500 -AIM and SD500 -MIM are designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. The SD500 -AIM addressable input module mounts to a 4 "- square box. The SD500 -MIM mini input module fits inside a single gang box. The modules are supervised, single input contact monitors. Using an EOL resister, they monitor for alarm contact closures and for open circuit wiring fault conditions. The SD500 -AIM and SD500 -MIM offer a compact design for adaptability and pleasing aesthetics as well as easy installation and stable operation —a flexible solution for all your fire protection needs. Model SD500 -AIM and SD500-MIM Input Modules The addressable input modules _ expand the flexibility of the • — IntelliKnight system by allowing the ! use of contact type inputs. Typical - - applications include manual pull f Y . 0 0 rp 0 ... stations and water flow switches. Features _ - • Operates on Class A (Style 6 & Style 7) or Class B (Style 4)SLC Loop. U AIM 6738N - M1111 • Single contact monitor. Operation Specifications • Up to 127 modules per SLC loop. Each addressable input module is Operating Voltage: 24 VDC • SD500 -MIM mounts in a single programmed with a unique SLC Standby Current: 0.55 mA loop address. The module gang box. Alarm Current: 0.55 mA supervises the wiring to the contact • SD500 -AIM mounts in a with an End Of Line (EOL) resistor. Ambient Temperature: 32 °F to 120 °F 4 "- square or double gang If a fault occurs in the wiring, the (0 °C to 49 °C) electrical box, and has an module alerts the FACP. • Mounting: SD500 -AlM attractive ivory cover plate. double gang box or • SD500- AIM /MIM are DIP switch 4 "- square electrical box programmable. is up to 14 gauge wire. SD500-MIM • Acce ng P P 9 9 single gang box • Both modules UL 864 listed; comply with NFPA 72 SILENT • 2500 ft max. wiring distance from u ' input module to contact. ` KNIGi11 • CSFM listed. INTELLIKNIGHT ACCESSORY. Model SD500 -AIM and SD500 -MIM Addressable Input and Mini Input Modules Engineering Specifications nt The contractor shall furnish and install where indicated on the plans, addressable input modules Silent Knight SD500 -AIM or SD500 -MIM. The modules shall be UL listed and compatible with Silent Knight's IntelliKnight 5820XL fire panel. The SD500 -MIM shall fit inside a single gang electrical box. The SD500 -AIM shall be supplied with a plastic cover and shall be suitable for mounting to a 4 "- square or double gang electrical box. The SD500 -AIM addressable input module must provide a monitor LED that is visible from outside the cover plate. Model 8D5t -A71 FRONT'WEY* 8.111141,11E3h SIDE 4tEW r , r, L ll ' c am? s-ir ru.• Model 5O5U1941IM y . ' io i il) 1�1�1 tms'' II _12- 44 SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800 - 446 - 6444 or in Minnesota 612 -493 -6435 FORM# 350231, Rev. 01 /00 . FAX: 612 -493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2000 Silent Knight INTELLIKNIGHT ACCESSORY Model SD500 -ARM , • ' � .r Addressable Relay Module it • .` Place relay applications anywhere on the IntelliKnight loop with the SD500 -ARM Addressable Relay Module. The SD500 -ARM is an addressable device that adds great flexibility to the IntelliKnight system. Providing two Form C contacts rated at 2.0 amps @ 30 VDC or .6 amp @ 120 VAC. The SD500 -ARM allows you to control a wide variety of normally open and normally closed applications, including elevator recall, door closing, fan operation, and auxiliary notification. And, because the relay module is addressable, these applications can be located at any point in the signaling line circuit. Like other IntelliKnight SLC devices, the SD500 -ARM is compact for adaptability and pleasing aesthetics. Combine this with the features you've come to expect from Silent Knight fire protection devices —easy installation and stable operation —and it adds up to a flexible solution for all your fire protection needs. Model SD500 -ARM Features Addressable Relay Module • Two sets of Form C contacts. '. • The SD500 - ARM provides two The are rated at 2A @ 30 I VDC or.6A@ 120 VAC. a Form C contacts rated at 2A @ ( - 30 VDC or .6A @ 120 VAC. • Up to 127 relays can be used on I These contacts can be used for each SLC loop. virtually any normally open or • Relay programming is normally closed application. completely flexible — can be Model SD500 - ARM mapped to zone conditions. • Polling LED visible through Sp Gallons Operation cover plate. • UL listed, complies with NFPA Contact Rating: Form C Each relay module is 72. 2A @ 30 VDC programmed with a unique SLC • CSFM approved .6A @ 120 VAC loop address. When an event • MEA Approved, 429 - 92 - E, Vol. 9 that controls the relay module Standby Current: .55 mA occurs, the relay is triggered by Alarm Current: .55 mA the IntelliKnight panel. Ambient 32 °F to 120 °F Temperature (0 °C to 49 °C) ftvi SILENT Mounting 4- square electrical box KNIGHT • >rr INTELLIKNIGHTACCESSORY' Model SD500 -ARM Addressable Relay Module ZZ1 Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable relay modules, Silent Knight SD500 -ARM. The modules shall be UL listed compatible with Silent Knight's Intelliknight 5820XL fire panel. The relay module must provide two Form C dry contacts rated at 2.0 amps at 30 VDC or .6 amp at 120 VAC. The relay module must be suitable for mounting in a standard 4- square electrical box and must include a plastic cover plate. The relay module board must provide an LED that is visible from the outside of the cover plate. The relay must be fully programmable for such applications as are required by the installation. FRONT VIEW �,C 4 _ � 1. T 4 n ; r, : f I II 0 () 1l f i in id of 0 r 0 01 ! it dl ;� 4 -718" . 1/4" 1 Model SD500 -ARM Addressable Relay Module Dimensions fts SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800-446-6444 or in Minnesota 612 -493 -6435 FORM# 350218, Rev. 11/99 FAX: 612 -493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 1999 Silent Knight A rt ,. , whezlock ", y +-� .. e 1 ; : . SEA M ADA .. f k- - � '7 „ _ . Helping People Take Actions ' SERIES AS SINGLE & MULTI - CANDELA AUDIBLE STROBE APPLIANCES SERIES AH AUDIBLES Description . , FE t ” Wheelock's patented 2 -wire Series AS Audible Strobe e j R= : E _ Appliances and Series AH Audibles offer more features ";� l ; , with low current draw. x Strobe options for wall mount models include 1575cd or SERIES AS SERIES AH Wheelock's patented MCW multi - candela wall strobes with field selectable candela settings of 15/30/75/110cd, or the high intensity MCWH strobe with field selectable : - -. _~ 11. _ 135/185cd. i ' - '' = - - �' Ceiling mount models incorporate Wheelock's patented ( .:;: ' ' � -" =_._ - - • MCC multi - candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH Multi - Candela Indicator strobe with field selectable 115/177cd. (bottom of lens) The audible provides a selectable choice of either a Features continuous horn or temporal pattern (Code 3) when • Approvals include: UL Standard 1971, UL Standard 464 constant voltage from a Fire Alarm Panel (FACP) is New York City (MEA), California State Fire Marshal (CSFM), applied. Each tone has 3 dBA settings to choose from. Factory Mutual (FM), and Chicago (BFP). See approvals by model in Specifications and Ordering Information. When used with the Wheelock Series SM or DSM Sync • ADA/NFPA/UFC /ANSI Compliant Module or Wheelock PS - 12/24 - 8CP and PS - 12/24 - 8MP • Wall mount models are available with Field Selectable Power Supplies with Patented Sync Protocol, Candela Settings of 15/30/75/110cd or 135/185cd synchronization of the continuous horn tone provides the (Multi - Candela models) or 1575cd (single candela temporal (code 3) tone (mandated by NFPA 72) model) • Ceiling mount models are available with field selectable simultaneously for all audible appliances. This ensures a candela settings of 15/30/75/95cd or 115/177cd distinct temporal (code 3) pattern when 2 or more audibles (multi - candela ceiling models) are within hearing distance. If not synchronized the • Selectable Continuous Horn or Temporal (Code 3). temporal sound could overlap and not be distinctive. At • 3 Selectable dBA settings (99, 95 and 90 dBA) in both the same time the strobes will be synchronized. This tones provides the ability to comply with ADA guidelines • Patented 2 - Wire Audible Strobe Appliance. concerning photosensitive epilepsy and the NFPA • Patented Universal Mounting Plate standards when installing 2 or more visual appliances • Weatherproof models are available for outdoor use within the field of view all of this plus the ability to silence • Strobes produce 1 flash per second over the regulated the audible is achieved by using only 2 wire. • voltage range 12 and 24 VDC models with wide UL "Regulated Voltage Range" using filtered DC or unfiltered FWR input voltage • The strobes can be synchronized using Wheelock's sync modules or power supplies with built in sync protocol • Fast installation with IN /OUT screw terminals using For Weatherproof Series AS, See Datasheet S9004 #12 to #18 AWG wires Copyright 2004 Wheelock Inc. All rights reserved. :e• 1 NOTE: All CAUTIONS and WARNINGS are identified by the symbol A . All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR . APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION; WHICH COULD RESULT IN PROPERTY • DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. . General Notes • Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 (1999) specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • . Series AS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120° F (0° C to 49° C) and maximum humidity of 93% (± 2 %). • Series AH -24 horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • Series AH -24WP audible appliances are listed under UL Standard 464 for indoor /outdoor use with a temperature range of -31 °F to 150 °F ( -35 °C to 66 ° C) and.maximum humidity of 95 %. • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the terminology "Listed Voltage Range ". Table 1: Ratings Per UL 1971 Model Input Voltage VDC RRange egulated veDC/FWR Voltage Strobe Candela (cd) AS -24MCW 24 16.0 - 33.0 15/30/75/110 AS- 24MCCH 24 16.0 - 33.0 115/177 AS- 241575W 24 16.0 - 33.0 15 (75 on Axis) AS- 121575W 12 8.0 - 17.5 15 (75 on Axis) AS -24MCC 24 16.0 - 33.0 15/30/75/95 AS- 24MCWH 24 16.0. 33.0 135/185 ASWP -2475W 24 16.0 - 33.0 75 © -31T Table 2: dBA Ratings for 12 VDC and 24 VDC Series AS /AH 12 and 24 VDC Audible Description Volume Reverberant dBA Anechoic Per UL 464 @ 10 ft. dBA @10 f. High 91 99 Continuous Hom Medium 88 95 Low 83 90 High 87 99 Code 3 Hom Medium 84 95 Low 79 90 Table 3: Average RMS Current Audible Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models 24 VDC Models AH -24 AS- 241575W AS -24MCW AS- 24MCWH AS -24MCC AS- 24MCCH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.062 0.100 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320 High (99) dBA UL max* 0.080 0.121 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480 24 vdc 0.033 0.080 0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305 Med (95) dBA UL max* 0.043 0.107 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465 24 vdc 0.017 0.072 0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295 Low (90) dBA UL max* 0.021 0.100 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460 Audible Wall Mount 12 VDC Models Audible Strobe AH -12 AS-121575W * RMS current ratings are per UL average RMS method. UL max current 12 vdc 0.163 0.260 rating is the maximum RMS current within the listed voltage range (16- High (99) dBA i 4 3 3v for 24v units). For strobes the UL max current is usually at the UL max* 0.192 0.320 ) y minimum listed voltage (16v for 24v units). For audibles the max current 12 vdc 0.076 0.195 is usually at the maximum listed voltage (33v for 24v units). For unfiltered Med (95) dBA FWR ratings, see installation instructions. UL max* 0.108 0.275 • 12 vdc 0.039 0.175 Low (90) dBA UL max* 0.058 0.265 r 1 - ,' whe-eloCk / /� , To , . x ,tiy w ' :� r i i ' ,;;: 7 .4=4 4.4;r..: si i= pjl F " ADA © r - S }'S fE y Helping People Take Actions "' SERIES RSS & RSSP SINGLE & MULTI - CANDELA STROBES & STROBE PLATES .• F;1( FZ-,, DESCRIPTION <. _� Wheelock's patented Series RSS Strobe Appliances and t-%' "e I Series RSSP Strobe Plates have lower current draw while F� A E, j igt =-._.. 74 i maintaining outstanding performance, reliability and cost ; , effectiveness. These versatile appliances will satisfy F'RE virtually all requirements for indoor, wall or ceiling mount Series RSS RSS Round applications. Series RSSP Strobe options for wall mount models include 1575 or ,,--:'..,;, Wheelock's Patented MCW multi - candela strobe with field selectable candela settings of 15/30/75/110cd or the high ' • - - _° intensity MCWH strobe with field selectable 135/185cd. - :ti 1. y g,. � ' - Ceiling mount models include the patented MCC multi - candela ceiling strobe with field selectable intensities of Multi- Candela Indicator 15/30/75195cd or the high intensity MCCH strobe with (bottom of Strobe Lens) field selectable 115/177cd. • Features All models may be synchronized using the Wheelock • Approvals include: UL Standard 1971, New York City SM, DSM Sync Modules or the PS- 12/24 -8CP and (MEA), California State Fire Marshal (CSFM), Factory PS- 12/24 -8MP Power Supplies with Wheelock's Patented Mutual (FM), and Chicago (BFP) See approvals by Sync Protocol. Synchronized strobes can eliminate model in Specifications and Ordering Information possible restrictions on the number of strobes in the field • ADA/NFPA/UFC /ANSI compliant. Meets OSHA 29 of view. Wheelock's synchronized strobes offer an easy Part 1910.165 way to comply with ADA recommendations concerning • Wall mount Multi - Candela models are available photosensitive epilepsy as well as meeting the with Field Selectable Candela Settings of 15/30/ requirements of NFPA72. 75/110cd or 135/185cd. Single Candela models are available in 1575cd Wheelock's Series RSS Strobes employ a Patented • Ceiling mount Multi- Candela models are Integral Strobe Mounting Plate that can be mounted to a available with field selectable candela settings of ' single gang, double gang, 4" square, 100mm European 15/30/75195cd or 115/177cd. (Round or Square) backboxes or the SHBB surface backbox. If the flush • Strobes produce 1 flash per second over the backbox has side or top space between it and the finished regulated voltage range wall, the NATP (Notification Appliance Trimplate) may be • 12 and 24 VDC models with wide UL "Regulated used. It provides an additional .65" of trim for the Appliance. Voltage" using filtered (DC) or unfiltered VRMS input An attractive cover plate is provided for a clean, finished voltage appearance on all models. • Synchronize using Wheelock's sync modules or power supplies with built -in sync protocol The Series RSSP Multi - Candela Strobe Plates are a cost • Fast installation with IN /OUT screw terminals using effective way to retrofit required wall strobe appliances to #12 to #18 AWG wire bells, horns, chimes, multitones or speakers and easily mounts to standard 4" backboxes or for surface mount use with Wheelock's SBL2 surface backbox. For Weatherproof Series RSS See Datatsheet S9004 Copyright 2004 Wheelock, Inc. All rights reserved. 1 NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. • General Notes • • Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series RSS & RSSP Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32° F to 120° F (0° C to 49° C) and maximum humidity of 93% (± 2 %). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the terminology "Listed Voltage Range ". • • Table 1: Average RMS Current* RSS/RSSP RSS /RSSP - Wall Mount RSS - Ceiling Mount 24VDC 241575W 24MCW 24MCWH 24MCC 24MCCH Models 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 UL max" 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 RSS /RSSP RSS/RSSP RMS current ratings are per UL average RMS method. UL max current 24VDC Wall Mount rating is the maximum RMS current within the listed voltage range (16 -33v Models 121575W for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, UL max* 0.255 see installation instructions. Table 2: Audibles /Speakers for RSSP Strobe Plate Product Series Multitone Appliances AMT, MT Horns AH, NH, HS Motor Bells MB- G6 /G10 Speakers ET- 1010/1080, E70, ET70 Chimes CH70 A WARNING: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" AND "GENERAL INFORMATION" SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING: • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS. • ADDING, REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELA SETTINGS WILL AFFECT CURRENT DRAW. RECALCULATE CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCE OR FUSES. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR "REGULATED VOLTAGE RANGE ". • INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS. • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBES MAY NOT FLASH. • FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU ANDIOR OTHERS. • CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS. r when ock '7- :--:,, - ‘ r i.j . ' .':-.' - ; 1 4 1 ' 1 .. ' -;..- --" • F:- '' • ---.---.‘ ; -,4 • -,.---. - -.;•.•,-,--f.:.: , . '? l ADA `' v 6.. 4 E ,, i__ s„..1,44,.r.:... 3 �� t SYSTEM y 2 k L.::. -f a•. ., -r. 2 .. • Helping People Take Actions' DESCRIPTION: SERIES RSSWP, ASWP, AHWP, MTWP Wheelock's Weatherproof Strobe, Audible Strobe, Audible and MT -12/24 Horn and Multitone Strobe appliances have an extended temperature range of -31'F to 150'F ( -35'C to 66*C) that WEATHERPROOF STROBE will satisfy virtually all outdoor and severe environment WEATHERPROOF AUDIBLE STROBE applications. All strobes are Indoor /Outdoor UL Standard AND WEATHERPROOF AUDIBLES 1638 Listed and rated for 180 candela on axis @ 77 °F (25 *C) and 75 candela at -31 °F (35 °C) with low current draw.t tF' ` s.' ;_: ;, rf SERIES MTWP The Wheelock Weatherproof Appliances are designed for , • 104 I ° Mounted to IOB -R maximum performance, reliability, and cost effectiveness (�',f �, 1i while meeting or exceeding the latest requirements of I'+' ^R } �liigr " NFPA 72 (National Fire Alarm Code), UL Standard 1638 E • ,, t ai , (Standard for Visual Signaling Appliances), and UL tx Standard 464 (Standard for Audible Signaling Appliances). J F ' Series RSSWP Strobes, SeriesASWPAudible Strobes and SERIES RSSWP 1 .' ' .' - i Series AHWP Audibles may be synchronized when used Mounted to WPSBB -R , = '" in conjunction with the Wheelock SM and DSM Sync ., 1 s Modules or the PS- 12/24 -8CP and PS- 12/24 -8MP Power c i t ( , i 4if Supplies with Patented Sync Protocol. The Series MTWP 1411'ti � } 1 , 4' ; is a true 4 -wire appliance. The strobe portion can be ?,' (} I synchronized as stated above. The multitone portion P a ti = l i3 SERIES AHWP cannot, but it can be connected to a coded fire alarm ; 1 ` s ° qS Mounted to WBB -R ; V4� system. �I ; te ,a , t Weatherproof Strobe Series RSSWP - `f - . _ Is UL Standard 1638 approved for Indoor /Outdoor use. The appliances use a Xenon flashtube with solid state f " SERIES ASWP rL -,.. circuitry enclosed in a rugged Lexan® lens to provide f v ;. r, , .. Mounted to WPBS -R �.. J � maximum visibility and reliability for effective visual ;; iE.r _, signaling. The Series RSSWP mounts to a Series WPSBB ;= ` Weatherproof Backbox. Features Weatherproof Audible Strobe and Audible Series • Approvals include: UL Standard 1971, California State ASWP and AHWP Fire Marshal (CSFM) and New York City (MEA), Factory Is UL Standard 1638 and UL Standard 464 approved for Mutual (FM) and Chicago (BFP) See approvals by model Indoor /Outdoor use and offer a field selectable choice of ih Table 8 continuous horn or temporal pattern (Code 3) when • Designed to meet or exceed NFPA, /UFC /ANSI 117.1/ constant voltage from the Fire Alarm Control Panel (FACP) OSHA Part 29, 1910.165, and ADA requirements is applied. Additionally, the audible has three (3) selectable dBA settings of 99, 95, and 90 dBA in both tones and, • UL Standard 1638 and UL Standard 464 listed with when synchronized, may be silenced while maintaining extended temperature range of -31° to 150 °F ( -35 °C to strobe activation. The Series ASWP mounts to a WPBB 66 °C) Weatherproof Backbox while the Series AH mounts to a • 24 VDC with new UL "Regulated" Voltage Range: of WBB Weatherproof Backbox. 16 -33 VDC using filtered DC or unfiltered FWR voltage Weatherproof Multitone Strobe and Multitone Horn Note: The Series MT -12/24 voltage range is 10.5 - 15.6 Series MTWP and MT -12/24 VDC (for 12V) and 20 -31 VDC (for 24V) Is UL Standard 1638 and UL Standard 464 approved for • Sync /Non -Sync in each product. Note: The audible Indoor /Outdoor use and offers a field selectable choice • portion of the Series MTWP and MT -12/24 is non sync of 8 nationally and internationally recognized alerting only signals. Additionally, the audible has 2 installer selectable • Synchronize with Series SM, DSM Sync Modules or PS- sound output levels: Standard and high covering a range 12/24-8CP and PS-12/24-8MP Power Supplies with (depending on selected signal) of 76 -94 dBA reverberant. built-in patented sync protocol The Series MTWP is a true 4 wire appliance. The Strobe portion can be synchronized or non - synchronized. The • Selectable dBA settings multitone (audible) portion cannot be synchronized, but it • Selectable alert signals can be connected to a coded fire alarm system. The Series • IN and OUT wiring termination that accepts two #12 -18 MTWP and the MT -12/24 mount to a series 106 Backbox. AWG wires at each terminal • Inputs are polarized for compatibility with Copynght 2004 Wheelock, Inc. All rights resented. industry standard reverse polarity supervision D f NOTE: All CAUTIONS and WARNINGS are identified by the symbol 0 All WARNINGS are printed in bold capital letters. AWARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS, OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH • COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. • General Notes: • Wheelock UL Standard 1638 Strobes are designed to produce 30 -62 flashes per minute over the Regulated Voltage Range. If used in an indoor • application, UL Standard 1638 strobes must be operated at a minimum of 20 VDC to meet the NFPA -72 flash rate of 1 to 2 flashes per second and ADA Guideline flash rate of 1 to 3 flashes per second. • • Wheelock Weatherproof Appliances are designed to operate over an extended temperature range of -31'F to 150'F ( -35 to 66 and at candela ratings represent minimum effective strobe intensity based on UL Standard 1638. Maximum humidity of 93% RH ±2%. • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the terminology "Listed Voltage Range ". AWARNING: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" AND "GENERAL INFORMATION" SHEET (P82380) ON THESE PRODUCTS. THE INSTALLATION INSTRUCTIONS AREAS FOLLOWS: P84135 FOR SERIES RSSWP, P83957 FORSERIESASWP, P83641 FOR SERIESAH -WP, P84150 FOR SERIES MTWP AND P824671 FOR SERIES MT- 12/24 -R. THESE DOCUMENTSUNDERGO PERIODIC CHANGES. IT IS IMPORTANTTHATYOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING: • Total current required by all appliances connected to system secondary power sources. • Fuse ratings on notification appliance circuits to handle peak currents from all appliances on those circuits. • Adding, replacing or changing appliances will effect current draw. Recalculate current draw to insure that the total average current and total peak required by all appliances does not exceed the rated capacity of the power source or fuses. • Composite flash rate from multiple strobes within a person's field of view. • The voltage applied to these products must be within their "REGULATED VOLTAGE RANGE ". • Use strobe only on circuits with continuously applied operating voltage. Do not use strobes on coded or interrupted circuits in which the applied voltage is cycled on and off as the strobe may not flash. • Conductor size (AWG), length and ampacity should be taken into consideration prior to design and installation of these products, particu larly in retrofit installations. Table 1: Average Current' for Series RSSWP and Table 5: Average Current* (AMPS) for 24 V Series MTWP Strobe in MTWP Audible Strobe Avg. Current * Strobe 75 cd @ Regulated 24.0 VDC UL Max* 24.0 UL -31 °F ( -35 °C) Voltage Range 24.0 UL Tone VDC Max' • VDC Max* Standard High Standard High RSSWP-2475W-FR 16.0 - 33.0 VDC 0.094 0.138 Hom 0.033 0.074 0.044 0.108 Table 2: Average Current* (AMPS) For Series ASWP" Bell 0.018 0.040 0.024 0.053 High dBA Medium dBA Low dBA March Time 0.033 0.067 0.038 0.104 Voltage Setting Setting Setting Code 3 Hom 0.026 0.069 0.035 0.091 0.094 0.138 (99) dBA (95) dBA (90) dBA Code 3 Tone 0.026 0.061 0.035 0.075 24.0 VDC 0.128 0.105 0.098 UL Max' 0.168 0.155 0.150 Slow Whoop 0.028 0.069 0.037 0.098 "Audible and Visual combined. Siren 0.027 0.080 0.036 0.104 Table 3: Average Current* (AMPS) for Series AHWP Hi/Lo 0.020 0.044 0.026 0.057 Voltage AH -24WP Voltage AH -12WP -- - AH -24WP Hi/Med /Low AH -12WP Hi /Med /Low Table 6: dBA Ratings for Series MTWP and MT -12/24 24.0 VDC 0.062/0.033/0.017 12.0 VDC 0.163/0.076/0.039 Tone Standard MTWP MT UL Max' 0.080/0.043/0.021 UL Max* 0.192/0.108/0.058 s Heittigh 16.0 24.0 V 33.0 20.0 24.0 10.5 12.0 VDC DC VDC VDC VDC VDC VDC • Horn Standard 84 87 90 82 85 82 85 Table 4: dBA Ratings for Series ASWP & AHWP High Setting 89 92 94 I 88 I 91 88 91 Reverberant dBA Anechoic dBA Bell Standard 76 80 83 75 I 79 75 79 lion Volume Per UL 464 @ 10 ft. @ 10 ft. Description !High Setting 83 86 88 82 ( 85 82 85 24 VDC 24 VDC March Time Standard 80 84 87 79 I 82 79 82 High 91 99 _ Continuous Med 88 95 High Setting 86 89 91 85 I 88 85 I 88 • Horn Code 3 Hom Standard 79 83 I 86 75 • 79 75 I 79 • Low 82 90 High Setting 85 88 I 90 85 I 85 85 85 High 85 99 Code 3 Med 82 95 Code 3 Tone I Standard 76 80 I 82 75 I 75 75 75 Horn I High Setting 1 81 85 I 86 • 79 i 82 79 82 Low 75 90 Slow Whoop I Standard 81 85 I 87 82 I 82 82 I 82 RMS current ratings are per UL average RMS method. UL max current I High Setting 87 90 I 92 88 88 88 88 rating is the maximum RMS current within the listed voltage range (16- 33v for 24v units). For strobes the UL max current is usually at the Siren I Standard I 81 84 87 82 82 82 82 minimum listed voltage (16v for 24v units). For audibles the max current I High Setting 86 89 92 85 88 85 88 is usually at the maximum listed voltage (33v for 24v units). For unfiltered Hi /Lo I Standard 77 81 I 84 79 79 79 79 FWR ratings, see installation instructions. High Setting 83 86 I 89 82 85 82 85 • E S L P R O D U C T I N F O R M A T I O N B U L L E T I N t .� Electromagnetic -.c F . I Fire Door Holders 3 F �, �, �3 1 4ia '7 3 • ..e:*, _ ., , S , + a S . _ .4 k z q ro .prc .. - Ex '�r'' � LISTED rmvaoveD �va.a� d �rv.c � e Extremely low current draw. Only The DH Series Electromagnetic Fire Door Holders are 15 mA at 24 V lets you save on constructed of the finest materials available. Each power supplies and backup door holder is made of durable die -cast metal and batteries finished in a high lustre double chrome or brass New recessed mount for lowest plating for a high quality appearance. • profile look Standard dual voltage AC or DC inputs reduce stocking requirements with 12/24 V, 24/120 V, and • Dual voltage inputs in each unit 24/220 V models. The 24120 model draws a mere reduces stocking requirements 15 mA at 24 V AC or DC, helping you keep overall • Self- adjusting swivel catch -plate job costs to a minimum. reduces installation time and Installation is easy with ESL's DH Series adjusts to door alignment changes installation technique —an adhesive template assures alignment without secondary adjustments. • Optional extension rods make No brackets are required for recessed, flush or installation even faster surface mounting (the surface mounting box has • Low residual magnetism easily three conduit ready entries). Plus, the new catch releases even on new ADA low plate features two pivot points and two way pressure door closers adjustability to further ensure perfect alignment. Optional extension rods are also available for • Transient Protection is built -in providing the proper gap distance between the door and wall. (Recess mounted doorholder includes a 3" extension rod). The basic units offer superior reliability with built -in transient protection and low residual magnetism so they release easily even on new ADA low pressure door closers. continued Sentrol DH Series Electromagnetic Fire Door Holders Performance Data Terminal Diagram General Dimensions Model Voltage DC /mA AC /mA Terminals lbs. kg. Dual Voltage Surface Mount Back Box • DHX' -1224 12V 30 30 C &L 35 15.9 24V 30 30 C &H 35 15.9 O O i 1 ° DHX' -24120 24V 15 ' 15 C &L 35 15.9 (C.L) 3.3. 1 I 120V — 15 C &H 35 15.9 Louege 8.4a,, I 11 vn DHX' -24220 24V 15 15 • . C &L 30 13.6 , . Hi 2 8 1 O 220V — 15 C &H 30 13.6 04.610_,. .610 . _ (c +Me i o ' For all models, "X" represents either F (Flush Mount, ff R (Recessed), or S (Surface) 1 O 1.r L 3.0an- F 21' ..1 Extension Rod Applications Accessories io'5 1 5.2°" DH-ER1 'Itl) a')=1 1 . 0 " 2.54 cm Door Magnet � DH� -''��ER3 ) 1 • 4.7' 3.0" I 11.9 an ',. -<:. zz ' 7.62 cm ( Oy 3.3' -5 f ; % 8.3 rin . ,.._. -. • Ordering Information Product Selector Guide n Ordering Description Qty /pkg - Information • DHR-1 224C 12 or 24 V DC /AC, recess mount, chrome, with 3" Extension Rod 20 /case 2.8' 7.1 an ' 1.1• 0.95• DHR-1 224B 12 or 24 V DC /AC, recess mount, brass, with 3" Extension Rod 20 /case 2.8 «n 2.4 an DHR- 24120C 24 or 120 V DC /AC, recess mount, chrome, with 3" Extension Rod 20/case Catch Plate Assembly DHR-241 20B 24 or 120 V DC /AC, recess mount, brass, with 3" Extension Rod 20 /case DHR- 24220C 24 or 220 V DC /AC, recess mount, chrome, with 3" Extension Rod 20/case DHR- 24220B 24.or 220 V DC /AC, recess mount, brass, with 3" Extension Rod 20 /case DHF-1 224C 12 or 24 V DC /AC, semi -flush mount, chrome 20/case 2 Di 5 s:m DHF-1 224B 12 or24 V DC /AC, semi -flush mount, brass 20/c e 6.4 s un DHF- 24120C 24 or 120 V DC /AC, semi -flush mount, chrome 20 /case • DHF-241 20B 24 or 120 V DC /AC, semi -flush mount, brass 20 /case DHF- 24220C 24 or 220 V DC /AC, semi -flush mount, chrome 20 /case I-- 52' rn ~I DHF- 24220B 24 or 220 V DC /AC, semi -flush mount, brass 20 /case DHS-1 224C 12 or 24 V DC /AC, surface mount, chrome 20 /case DHS -12248 12 or 24 V DC /AC, surface mount, brass 20 /case DHS-241 20C 24 or 120 V DC /AC, surface mount, chrome 20 /case DHS- 241206 24 or 120 V DC /AC, surface mount, brass 20 /case DHS- 24220C 24 or 220 V DC/AC, surface mount, chrome 20 /case example: DHS-24220B 24 or220 V DC /AC, surface mount, brass 20 /case Extension Rods DHS- 24120C DH-ER1 C 1 " chrome DH ER16 • 1 " brass . DH = Door Holder DH -ER3C 3 "chrome 24120 = Model/Voltage DH -ER3B 3 "brass F = Flush Mount Accessories R = Recessed .. DHW Extension rod wrenches S = Surface Mount DH -BP Back Plate (Chrome or Brass) C = Chrome Plating B = Brass Plating SENTROL Sentrol reserves the right 12345 SW Leveton Dr., Tualatin, OR 97062 to change ticadona • wit thoouut notice. Tel.: 503.692.4052 Fax: 503.691.7566 J 5 LFJ T http: / /www.sentrol.com ©1999 Sentrol U.S. & Canada: 800.547.2556 Technical Service: 800.648.7424 E- 2930- FLG10K -0497 A PRODUCT OF SENTROL FaxBack: 1.800.483.2495 Printed on recycled paper • 1 . . , . . . . P 01 . . V -.: . fti,11 lualiini-ii : � . r MR1 MR2 ro -4. , - __ - = MR -100, 200 Series Relays Multi- Voltage Control Relays The MR Series Multi - voltage Control Relays offer SPDT or DPDT 10 Amp resistive contacts which may be operated by one of four input control voltages. A single relay may be energized from a voltage source of 24VDC, 24VAC, 120VAC or 230VAC by wiring to appropriate input terminals. Each relay position contains a red LED which indicates the relay coil is energized. Relays may be "snapped apart" from a standard 4 module assembly and used independently. These devices are ideal for applications where local contacts are required for system status, remote contacts for control of electrical loads and general purpose switching.They are suitable for use with HVAC,temperature control, fire alarm, security, energy management and lighting control systems. - --- = Standard Features: • Relays may be energized from a voltage source of 18 to 35VDC or VAC, 120VAC or 230VAC 1 } �: =1 '" II c • Each relay position contains a red LED, which -�— _ illuminates when the coil is energized.This ;�;.,, € provides a time saving device when checking an installed system — no metering is required • Single, dual or triple relay modules may be WIRING "snapped apart" from standard 4- position master (TYPICAL FOR ONE MODULE POSITION) • DC input is polarized for continuous duty use SPOT CONTACTS DPDT CONTACTS • Available in dust resistant enclosures with LED 10A RESISTIVE@ 10A RESISTIVE@ 120VAC 130VAC viewin port � 11I1 g I• NC C NO ' •N` C NO NC C "°•' • /C versions mounted in enclosures 1 loo 01 I 1100000NI I I RELAY I I RELAY ' - • /C /R versions with red covers for NYC and ENERGIZED y I. ENERGIZED —A I LED LED 1e other uses 1 0 I 1 0 I = , I o , • /T versions come complete with track mounting INPUT : I 0 0 0 0 l I INPUT I LD 0 0 0 l I CONTROL I. D 1n. 1,5 n" •I CONTROL 1 0 1 115 7 •I hardware which facilitates installation in VOLTAGE 1 1 1 1 VOLTAGE I I I 1 standard cabinets 24(18.35)VDC -1. mim 4 24(18.35)VDC- + ®nmei n 24 .23M0 24VAC -- =Me • UL recognized relays rated at 10,000,000 120VAC --* ©/ EM 120VAC—* MOM 230VAC- 0. Cle p 230VAC -1* mom mechanical operations TERMINAL STRIP CONECTNINS TERMINAL STRIP CONECTIONS • UL listed as Control Unit Accessory (MR -104) (MR -204) Building Control pI` (e:D Space Age Electronics, Inc. { S 09001 tits STATE OF S AT FIR 406 Lincoln Street EGI 9001 NFPA NEW YORK /11) -- ,� Marlboro, MA 01752 -2195 R www.1 sae.com 800.486.1 723 voice ©Space Age Electronics, Inc. 2003 508.485.0966) ED0313 LT10278 Rev. A Pg. 1/2 No Excuses Just Solutions! 508.485.4740 —fax Specifications ."'-' SPACE AGE is= Spacer Mounted s ELECTRONICS, INC. /T = Track Mounted -w;;r _ , x. #f . Tw r:. n? `-, "`- • IC = Metal Enclosure /R = Red Finish CONTACT TRACK ENCLOSURE UL' MEA CSFM .1 MODULE CONFIGURATION MOUNTED MOUNTED COVER FILE FILE FILE SAE PN# POSf110NS PER POSITION H X W X D i HXWXD MATERIAL S3403 73 -92 -E 7300 -1004 3.25" (82.6mm) SSU- MR -101/T 1 SPDT 2.125" (54mm) UOXX2 :106 1.5" (38.1mm) Grey SSU- MR -101/C 1 SPDT UOXX Vol. 14 :101 5.125" (130.2mm) Plastic 3.125" (79.4mm) UOXX2 2.5" (63.5mm) Red UOXX7 SSU.MR- 101/C/R 1 SPDT ABS -94V0 Vol. 22 :101 Plastic 3.25" (82.6mm) SSU- MR -104/T 4 SPDT 8.5" (215.0mm) UOXX2 :106 1.5" (38.1mm) Plated UOXX SSU- MR -104/C 4 SPDT 18ga UOXX2 Vol. 14 :101 5.125" (130.2mm) CRS UOXX7 9.5" (241.3mm) Red 2.5' (63.5mm) r SSU -MR- 104 /C /R 4 SPDT 18ga UOXX7 4 CRS 3.25" (82.6mm) SSU -MR -201 /T 1 DPDT 2.125" (54mm) UOXX2 :106 1.5" (38.1mm) Grey SSU- MR -201/C 1 DPDT ABS -94V0 UOXX Vol. 16 :101 5.125" (130.2mm) Plastic 3.125" (79.4mm) UOXX2 Red 2.5" (63.5mm) ABS -94V0 Vol. 22 :101 SSU•MR- 2011CIR 1 DPDT Plastic 3.25" (82.6mm) SSU -MR -204 /T 4 DPDT 8.5" (215.0mm) UOXX2 :106 1.5" (38.1mm) Plated UOXX SSU- MR -204/C 4 DPDT 5.125" (130.2mm) 18ga UOXX2 Vol. 16 :101 CRS UOXX7 9.5" (241.3mm) Red 2.5" (63.5mm) 18ga UOXX7 SSU- MR- 204/C/R 4 DPDT CRS COIL VOLTAGE: MR -100: 24(18- 35)VDC, 24(18- 35)VAC, 120VAC, 230VAC MR -200: 24(18- 35)VDC, 24VAC, 120VAC, 230VAC (Pull In Voltage: 75% of nominal max. @ 25 °C; Drop Out Voltage: 25% of nominal min. @ 25 °C) POLARIZED: DC input only ENERGIZED LED INDICATOR: One Per Module Position CURRENT REQUIREMENT: Per Module Position: MR -100 Series = 18mA / MR -200 Series = 40mA CONTACT RATINGS: 7A @ 28VDC / 10A (NO:1 /6HP, NC:1 /8HP) @ 120VAC / 7A @ 230VAC CONTACT CONSTRUCTION: Dry Form "C" AMBIENT TEMPERATURE: -58 °F to 185 °F ( -50 °C to 85 °C) © 85% RH, NON - Condensing WIRING: #14 to #22 AWG terminals /T VERSIONS: 3.5" wide, low profile plastic snap track provided with mounting screws /C VERSIONS: Backbox: 18ga CRS, plated with 1/2" conduit knockouts top and bottom "UOXX= Control Unit Accessories, System; 2= Component; 7= Certified for Canada NOTICE: The information contained in this document is intended only as a summary and is subject to change without notice. The products described have specific instructional/ installation documentation, which covers various technical, approval, code, limitation and liability information. Copies of this documentation along with any general product . _ x _ -.,. _,, - BUlldl t COrltfOl k warning and limitation documents, which also contain important information, are provided with the product and � "- . �, . , ,..9 ., l are also available from Space Age Electronics, Inc. The information contained in all of these documents should be considered before specifying or using the products. Any example applications shown are subject to the most Space Age Electronics, Inc. current enforced local /national codes, standards, approvals, certifications, and/or the authority having jurisdiction. p All of these resources, as well as the specific manufacturer of any shown or mentioned related equipment, should 406 Lincoln Street be consulted prior to any implementation. For further information or assistance conceming the products, contact Space MA , boro 01752 -2195 Age Electronics, Inc. Space Age Electronics Inc. reserves the right to change any and all documentation without notice. Marlboro, 1 ro MA 800.486.1723 -voice ©Space Age Electronics, Inc. 2003 508.485.0966) ED0313 LT10278 Rev. A Pg. 2/2 No Excuses Just Solutions! 508.485.4740 -fax 1 I ) 1 • g 6?s NP12 - 112h g r SEALED RE CHARGEABLE LFAD•ACID BATTERY � ; L: c ' r NP • �� � A ( r� .DwD.mD.wD i =ZUNIS O Pb Ditl.0 n ALAN WO UUremwtYm RI b �.mw., �""` Pb ENERS MAN IN CHOIA 8 8A0180. PA 1061E � .50fa NP 12 -12 NP12 -12FR Sealed Rechargeable —_ _ -__ Lead Acid Battery • 12V 12.0Ah • NOMINAL VOLTAGE: 12V • CHARGE RETENTION (shelf life) at 68 (20 • NOMINAL CAPACITY: 1 month 97% 20 hr. rate of 0.6A to 10.5V 12.0Ah 3 months 9196 . - o _ 10 hr. rate of 1.1Ato10.5V 11.OAh 6 months 8596 LV�I`GLILL�6Lii 5 hr. rate of 2.1A to 10.2V 10.5Ah 1 hr. rate of 7.2A to 9.60V 7.2Ah • LIFE EXPECTANCY: STANDBY USE 3 to 5 years .250x.004 110 • WEIGHT (approx.): 8.82 pounds CYCLE USE (approx.): r (4 kgs.) 10096 depth of discharge 250 cycles 5096 depth of discharge 550 cycles z■■ • ENERGY DENSITY (20 hr. rate): 30% depth of discharge 1200 cycles 1.70 m 1.70 WH /cubic inch (103.5 WH /liter) ° all - MM 7 j- • SEALED CONSTRUCTION: 0 • SPECIFIC ENERGY (20 hr. rate): Can be operated in any position " .310 7.90 16.3 WH /pound (36.0 WH /kg) without leakage. .250 6.35 .16 4.0 • INTERNAL RESISTANCE OF CHARGED • STANDARD TERMINAL .031 0.8 BATTERY: Quick Disconnect .250 or .031:.004 .020 0.5 16 mi(liohms (approx.) Optional .187 • • MAXIMUM DISCHARGE CURRENT • HOUSING MATERIAL: WITH STANDARD TERMINALS: ABS Resin 40 amperes • OPTIONAL: • MAXIMUM SHORT - DURATION Container and cover made from DISCHARGE CURRENT: Flame Retardant ABS a e Ill e L"Z S E G EI S 360 amperes (U194- VO /L.O.I.>28 %) • OPERATING TEMPERATURE RANGE: • Approved for shipping as Me CHARGE 5 ° F to 122 °F non - hazardous, nonspillable ( -15 °C to 50 °C) ' DISCHARGE -4°F to 140°F0 �i] �j (.20°C to 60°C) 151:1 98 :1 (5.95 .04) (3.86 •..04) .- 1 1 S a v ri V 4; ul m DIMENSIONS: MM (INCHES) UL listing pending - File No MH16464 E ney s. Power/Full Solutions '" Publication No: US- NP12 -12 -02 • February 2005 DISCHARGE CHARACTERISTIC TEMPERATURE EFFECTS IN RELATION CURVES AT 25 °C (77°F) TO BATTERY CAPACITY 2V 6V *V W (46) Battery NI' T.mper.he 25•C677 s 120 - � -- ao a - .m .B ...AI�=, -.�,,' _ . _- ..- �)iG =,1 \, a t ri u0. 1.0- 40 :;i . S`',, bilk � 1, 0` - - \.II� \ 1�1 a nn • 0- 36r d At 1111Pillillit to 2C . '1 M A A CS 60 li 0.4CA I■ eo .o - z r ■■1 111 / 1 A ■ ■111■ I ¢ 2 •'� 1 3CI` ■■ 11111111111110 d 0 a � 1 4 e e 10 20 40 m 2 4 e 00 20 -20 -10 0 10 20 30 40 50 ( °C) I, -- - rnn 1 e +( -24 14 32 50 He 86 104 122 PFI Dluhnq. T4re Temperature SELF DISCHARGE CHARACTERISTICS OPEN CIRCUIT VOLTAGE VS REMAINING CArA.CI`o Y ( %) (y) AT 25'C (77'F) 100 ' I I a 14.0 d ca \ =' a ca r v = v • 50 z: r-a 12.0 .. ..... 5 20'C (68'0) _ I i i 40'C 1 154.0 ) 30'C 186'0) 25 1 11.0 { - - -- - I i I W 0 L 10.9 I Ci 3 6 9 12 15 18 0 20 40 60 80 100 W STORAGE TIME (MONTHS) REMAINING CAPACITY (%) u 0 0 0 0 CYCLE SERVICE LIFE IPA RELATION FLOAT SERVICE LIFE c TO DEPTH OF DISCHARGE -5 TESTING CONDITIONS: DISCHARGE CURRENT: 0.17C AMP. (F.V. 1.7VICELL) m i E CHARGING CURRENT: 0.090 AMP. S TESTING CONDITIONS: FLOATING VOLTAGE 2.25 TO 2.30V/CELL �+ CHARGING VOLUME: 125% OF DISCHARGED CAPACITY a AMBIENT TEMPERATURE: 20'C TO on (64'0 TO 72'0) Z a (AN %) AMBIENT TEMPERATURE: 20% TO 25 (60'0 TO 777) a IAH %) 0 • 120 - - f_ 120 - - i �� _ a 100 . — aaa • 100 _—_— ca 69 C e. 90 0 60 - . 01 u. cro _ n -, —_ a v 40 X) a 6U 50%0.0.0. 30% DEPTH OF DISCHARGE 8- H = 100% O.O.D. W 20 • u 40 2 0 c 1 2 3 4 5 5.5 C a LIFE (YEARS) " 0 - 200 400 600 800 1000 1200 1400 0 3 NUMBER OF CYCLES -0 gi • N When the battery will be used by current in excess of 3C, consult with EnerSys prior to use. o N CHARGING METHODS (At 20 °C) Cycle use: Maximum charging current 3.0A ,Y Charging voltage 14.4 to 15.0V a Standby use: Float charging voltage 13.50 to 13.80V Z CAUTION •Avoid short circuit L.7 •Do not charge in a sealed container. 0 Z c ,o 0 V Z a EnerSys EnerSys EMEA Represented by: E nerSvS. P.O. Box 14145 Brussels, Belgium Reading, PA 19612 -4145 Tel: +32 (0)2 247 94 47 ` - "•' "— • USA EnerSys Asia Tel:+ 1- 610 - 208 -1991 Guandong, China + 1- 800 -538 -3627 Tel: +86 755 2689 3639 www.enersys.com © 2005 EnerSys. All Rights Reserved.