Site Review #1 Checksheet Response Application #: SIT2006 -00008
From Review dated: November 7, 2006
Date: 11.16.06
From: BRIAN FREY Work: 503 236 -6000
MYHRE GROUP ARCHITECTS
APPLICANT 700 SW TAYLOR ST., SUITE 400 Fax: 503 236 -7500
PORTLAND OR 97205 E -mail: brianfemvhregroup.com
To: PLANS VAL HENZEL Phone: 503.639.4171
EXAMINER E -mail: val @tioard- or.qov
cc: Mark Ferris Phone: 503.598.3440
OWNER Dartmouth Square, LLC Fax: 503.598.3450
7165 SW Fir Loop, suite 100
Tigard, Oregon 97223 E -mail: markf a(�.zimmler.com
CIVIL Scott Emmons Phone: 503.238.2097
LANPACIFIC E -mail: jseelanoacific.com
PROJECT INFORMATION
Street Address: 11935 SW 70` Avenue
Description of Work: NEW 3 -STORY OFFICE BUILDING WITH ABOVE GRADE PARKING.
The following assumptions were made while reviewing this project:
Occupancy group Construction Type Square Footage Stories Sprinklers Alarms Detection
B II -B - 38,830 3 Yes Yes Yes
PLAN REVIEW
Based on the plan review comments submitted, the following items have been addressed and are outlined herein:
Locatlo Code
Item # n on Section Clarification / Correction Required
plans
Fire Review
01 OFC 508 The submitted hydrant work sheet shows four hydrants required, the site
plan shows only three hydrants. Where is the fourth hydrant located?
The existing fire hydrant located across the street and has been approved as
the required fourth fire hydrant, see attached e-mail from John Dalby. dated
11.09.06 for approval of hydrant design and location.
02 Sheet C13 shows fire hydrant/ Sprinkler Vault / FDC located on private
property check with TWD for location requirements on private property and
provide copy of easement.
An easement is to be a deferred submittal.
Page 1
03 OFC 905 Provide approval from Fire Marshalls office on fire hydrant design and
location. Please contact John Dalby, Deputy Fire Marshal for these
requirements @ 503 - 356 -4723.
See attached e-mail from John Dalby, dated 11.09.06 for approval of hydrant
design and location.
_ I
04 OFC 503 Provide approval on site slope and access road entrance stating this meets
OFC 503. Contact John Dalby, Deputy Fire Marshal for these requirements
@ 503 -356 -4723.
See attached a -mall from John Dalby, dated 11.09.06 for approval of site
slope and access road entrance.
05 NFPA 24 Underground Fire Fighting Water Supply: Provide thrust blocking details
Section 4.1.3 including cut sheets and installation instructions for any mechanical joint
13:8 -1.1.1 c onnections. Provide supply pipe burial depth, piping ( 1 PP Y P�P P P�P� 9 sizes and materials,
valve equipment cut sheets, vault details, equipment in vaults, details for
hydrants and Fire Department Connection (FDC) location that are necessary
for the installation of the fire service. All valves shall be listed for use in a fire
service application.
Working plans shall be drawn to an indicated scale on sheets of uniform
size, with a plan of each floor, and shall include the following items that
pertain to the design of the system:
(1) The size and location of all water supplies
(2) The size and location of standpipe risers, hose outlets, hand hose,
monitor nozzles, and related equipment
(3) The following items that pertain to private fire service mains:
a. Size
b. Length
c. Location
d. Weight
e. Material
f. Point of connection to city main
g. Sizes, types, and locations of valves, valve indicators,
regulators, meters, and valve pits
h. Depth at which the top of the pipe is laid below grade
(4) The following items that pertain to hydrants:
a. Size and location, including size and number of outlets and
whether outlets are to be equipped with independent gate valves.
b. Whether hose houses and equipment are to be provided, and
by whom
c. Static and residual hydrants used in flow
(5) Size, location, and piping arrangement of fire department connections
Plan view and detail information for the above referenced information is
found on sheets C10, C11, C13 and C18 of the site civil construction plans.
06 1103.1 Clarify the accessible route to the public way as required by section 1103.1
OSSC OSSC.
The accessible route to the public way is from the access at Dartmouth
Street. The building is served by an elevator providing full accessibility
access to all floors. See attached e-mail from Brian Blaylock for approval.
dated 7.28.06.
Page 2
07 Section 1103 The accessible parking shown on sheet CO3 appears not to provide an
& 1104. accessible route from the access aisle to the proposed side walk to
(OSSC 106) structure. Provide site accessibility information as required per section 1103
& 1104. (OSSC 106)
Site accessibility is provided per OSSC Sections 1103 and 1104 as indicated
on sheets CO3 - Site Plan and C04 - Grading Plan. An at grade path of
travel is provided from all accessible parking stalls to the 2"`' floor lobby
building entrance and the number of stalls meet the requirements of 1104
Parking Facilities as indicated with 5 accessible stalls. one of which is van
accessible.
08 1103.2.4.3 Accessible walkways and routes shall not exceed a running slope of 1 unit
OSSC vertical in 20 units horizontal (5% slope). Cross slopes shall not exceed 1
unit vertical in 50 units horizontal (2% slope).
Accessible routes do not exceed 5% running slope and 2% cross slope as
indicated in sheet C04 — Grading Plan.
09 Accessible parking signs are required to be 84 inches to the bottom of the
sign. Provide sign detail.
Please see attached Rev 4 for revised Typical ADA parking Sign with
mounting heights as indicated.
Page 3
Page 1 of 2
Brian Frey
From: Scott Emmens Use @lanpacific.comj
Sent: Thursday, November 16, 2006 9:13 AM
To: Brian Frey
Subject: FW: Dartmouth Square Improvements
Here is John Dalby's response he sent last week. He also cc'd Val and Kim at the City.
Scott Emmens, PE
LanPacific, Inc.
1001 SE Water Ave., Suite 360
Portland, Oregon 97214
Ph: (503) 238 -2097
Fx: (503) 238 -2447
www.Ianpacific.com
From: Dalby, John K. [mailto:John.Dalby @tvfr.com]
Sent: Thursday, November 09, 2006 4:09 PM
To: jse @lanpacific.com
Cc: val @tigard- or.gov; Kim Mcmiilan
Subject: RE: Dartmouth Square Improvements
The submitted drawings and calculations are approved insofar as fire apparatus access and firefighting water
supplies are concerned. We trust this will clear the way for this project insofar as fire district regulations are
concerned.
John K. Dalby, Deputy Fire Marshal II
Tualatin Valley Fire & Rescue, North Division
14480 SW Jenkins Road
Beaverton, OR 97005 -1152
503 - 356 -4723
From: Scott Emmens [mailto:jse @Ianpacific.com]
Sent: Wednesday, November 08, 2006 4:38 PM
To: Dalby, John K.
Subject: FW: Dartmouth Square Improvements
Hi John,
I got your voice mail earlier. Thanks for calling back. Below is the email I sent you back the first week of
September. I understand your concern about the driveway grades coming off of 70'" Ave. Since my meeting with
you, I updated the driveway grades in the driveway. The driveway and sidewalk at the entrance is sloped down
and away from centerline at the same grade as the cross slope of the road (2.0 %). At back of walk, the driveway
drops down on a vertical to a maximum of 15% and then flattens to 8 %.
thanks
Scott Emmens, PE
LanPacific, Inc.
1001 SE Water Ave., Suite 360
Portland, Oregon 97214
11/16/2006
Page 2 of 2
Ph: (503) 238 -2097
Fx: (503) 238-2447
www.lanpacific.com
From Scott Emmens [mailto:jse@Ianpacific.com]
Sent Friday, September 08, 2006 10:08 AM
To: 'john.dalby @tvfr.com'
Subject Dartmouth Square Improvements
John,
1 met with you a few weeks ago regarding the Dartmouth Square commercial development. The site is located on
the northwest comer of Dartmouth St and SW 70"' Ave in Tigard. I've updated the plans since we last spoke. I've
attached three construction drawing sheets and the fire flow calc sheet for you to review.
Sheet C10 — Dartmouth public Improvements
Sheet C11 — 70s' Ave Public Improvements
Sheet C13 — Onsite water and sanitary sewer improvements
I would like to follow up with you by this aftemoon if you're available.
Thanks,
Scott Emmens, PE
LanPacific, Inc.
1001 SE Water Ave., Suite 360
Portland, Oregon 97214
Ph: (503) 238 -2097
Fx: (503) 238 -2447
www.lanpacific.com
11/16/2006
Brian Frey
From: Doug Strickler Idws@lanpacific.com]
Sent: Wednesday, June 28, 2006 9:56 AM
To: Scott Emmens; Brian Frey; 'Mark Ferris'
Cc: Erik Esparza; Brian Keefer
Subject: FW: Dartmouth Square conditions of approval
Hi Group - Here is the response I got regarding the Dartmouth Square accessibility issue.
T guess "On the nose!" is as clear an indication as we could ask for.
Regards, Doug S.
Doug Strickler, LEED
Senior Planner
LanPacific, Inc.
1001 SE Water Ave., Suite #360
Portland, OR 97214
Phone: 503.238.2097
Fax: 503.238.2447
Original Message
From: Brian Blalock Imailto:brianb @tigard- or.govI
Sent: Wednesday, June 28, 2.006 5:28 AM
To: dws@lanpacific.com
Subject: Re: Dartmouth Square conditions of approval
On the nose!
»> "Doug Strickler" <dws @lanpacific.com> 06/26 4:37 PM >»
Brian - I am the planner who wrote the application for the Dartmouth Square application,
and I was talking with Scott Emmens today about the Conditions of Approval for that
project, particularly #1 which concerned the project having an accessible route to both SW
Dartmouth Street and SW 70th Avenue.
It is my understanding, from discussions with Scott, that your concerns were based on your
review of a set of plans that apparently showed stairs at the Dartmouth Street entrance
and no elevator connecting all three floors.
It is
further my understanding that if plans are submitted that do not have stairs at the
Dartmouth Street entrance and that clearly show the presence of an elevator providing
access to all three floors, that your concerns regarding accessibility would he adequately
addressed.
Could you please advise me as to the whether my understanding of the situation is correct
and whether it would be helpful to sit down with you and a set of current plans to verify
the adequacy of the access that we are proposing for the building? I know it would be
helpful to us to have a high degree of confidence that our plans address your concerns
before developing them further.
I look forward to hearing from you regarding this matter.
Regards,
1
Doug Strickler, LEED
Senior Planner
LanPacific, Inc.
1001 SE Water Ave., Suite #360
Portland, OR 97214
Phone: 503.238.2097
Fax: 503.238.2447
2
Site Address: I R 3S Sw 70 r ' i✓L 14A/t t 0(2- ' t 7 Z23 - - -)
Letter of Transmittal
Building Division
C u f Ta
DATE RECEIVED:
T0: \ 1c, Ne./4ZC.L.
DEPT: BUILDING DIVISION
FROM: _get1l,J ri-L-Y
COMPANY: i'k'rt 620, A2cr1
PHONE NO.: (5 Z36 - '000 By;
RE S IT 6.- 00008 11935 Sw 70 Av6.
(Case number, site address, etc.)
OAfLTfrtDv H ovn-/LE
(Project name or subdivision name and lot number)
ATTACHED ARE THE FOLLOWING ITEMS:
I Copies: I Description: 1 Copies: Description:
Additional set(s) of plans. 9 ,. Revisions: 'L
Cross section(s) and details. Wall bracing and /or lateral analysis.
Floor /roof framing. Basement and retaining walls.
Beam calculations. Engineer's calculations.
1 Other(explain): SsrE i evic.' gerPo e
REIVIA.RKS: - Sire ,,cwe.w # 1 cmcc r2c5✓D,J5 tr
CaJFt2/'1A1 J f r1A.L • CoPiES
Ders%. r ?��t'rG!9 T;a titt,401c P flgly 4, GI`I
For Office Use Only:
1 Routed to Permit Technician: Date: 1 Initials:
Fees Due: $ _ Date: j Initials:
Re rint Permit ( er Plans Examiner : { Yes: _ _ 1 No:
— 1 Notified Applicant: Date: 1 Initials:
i:(3uildingTornacttcrTrmumitml dra 14'04
•
1'
ALUMINUM SIGN PLATE
3/8' 3/8. YVHITE BACKGROOND.
1 NIGH BLUE LETTERS
MO,..,, AND BORDER, BAKED ENAMEL.
aM OlOOLIO
NW Olt
MONO
MEM
WOO woe
awns. to
1 -31' 1.5'
GALVAN]ZED e ,
STEEL
POST
VAN HANDICAP SYMBOL WHITE
SIGN �9LE WITH BWE BACKGROUND sGN
04' MOUNT HEIGHT Q
2' -0' MW
t
TYPICAL HANDICAP PARKING SIGN
NOT TO SCALE