Correspondence (4) / 2c4, --b . July 31 2006 Y .�(l& co CITY OF TIGARD Myhre Group Architects Brian Frey OREGON 700 SW Taylor St. Suite 400 Portland, OR 97205 RE: DARTMOUTH SQUARE — SITE REVIEW #1 Project Information Building Permit STT2006 -00008 Construction Type: II -B Tenant Name: Dartmouth Square Occupancy Type: B Address: 11945 SW 70 Ave. Building Area: 3 story, 38,830 sq ft The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the Tualatin Valley Fire & Rescue Fire & Life Safety Requirements based on the 2004 Oregon Fire Code (OFC). The following information is required prior to the issuance of a Site Permit: FIRE REVIEW 1. The submitted hydrant work sheet shows Four hydrants required, the site plan shows only Three hydrants. Where is the Fourth hydrant located? OFC 508 2. Sheet C13 shows fire hydrant/ Sprinkler Vault / FDC located on private property check with TWD for location requirements on private property and provide copy of easement. 3. provide approval from Fire Marshalls office on fire hydrant design and location. Please contact John Dalby, Deputy Fire Marshal for these requirements @ 503-356-4723. OFC 905 4. Provide approval on site slope and access road entrance stating this meets OFC 503. Contact John Dalby, Deputy Fire Marshal for these requirements @ 503- 356 -4723. 5. Underground Fire Fighting Water Supply. Provide thrust blocking details including cut sheets and installation instructions for any mechanical joint connections. Provide supply pipe burial depth, piping sizes and materials, valve equipment cut sheets, vault details, equipment in vaults, details for hydrants and Fire Department Connection (FDC) location that are necessary for the installation of the fire service. All valves shall be listed for use in a fire service application. NFPA 24 section 4.1.3 for the items necessary for a plan review. 4.1.3 (13:8- 1.1.1) Working plans shall be drawn to an indicated scale on sheets of uniform size, with a plan of each floor, and shall include the following items that pertain to the design of the system: (1) The size and location of all water supplies (2) The size and location of standpipe risers, hose outlets, hand hose, monitor nozzles, and related equipment (3) The following items that pertain to private fire service mains: 13125 SW Hail Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 a. Size b. Length c. Location d. Weight e. Material f. Point of connection to city main g. Sizes, types, and locations of valves, valve indicators, regulators, meters, and valve pits h. Depth at which the top of the pipe is laid below grade (4) The following items that pertain to hydrants: a. Size and location, including size and number of outlets and whether outlets are to be equipped with independent gate valves. b. Whether hose houses and equipment are to be provided, and by whom c. Static and residual hydrants used in flow (5) Size, location, and piping arrangement of fire department connections ACCESSIBILITY 6. Clarify the accessible route to the public way as required by section 1103.1 OSSC. 7. The accessible parking shown on sheet CO3 appears not to provide an accessible route from the access aisle to the proposed side walk to structure. Provide site accessibility information as required per section 1103 & 1104. (OSSC 106) 8. Accessible walkways and routes shall not exceed a running slope of 1 unit vertical in 20 units horizontal (5% slope). Cross slopes shall not exceed 1 unit vertical in 50 units horizontal (2% slope). 1103.2.4.3 OSSC 9. Accessible parking signs are required to be 84 inches to the bottom of the sign. Provide sign detail. Please provide an item -by -item response. Deferred submittals such as Truss Joist Shop Drawings, Suspended ceiling system, Retaining wall design, etc. will be charged a deferred submittal fee based on the valuation of the portion of the work being deferred. The minimum fee shall be $200.00. This fee is in addition to the project plan review fee based on the total project value. OAR 918 - 050 -0150 `Documents for deferred submittal items shall be submitted to the registered design professional in responsible charge who shall review them and forward them to the building official with a notation indicating that the deferred submittal documents have been reviewed and been found to be in general conformance to the design of the building. The deferred submittal items shall not be installed until the design and submittal documents have been approved by the building off ciaL OSSC Section 106.3.4.2" Deferred Items: None Listed When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Val He el , Senio Plans Vxaminer RECEIVED JUL 1 4 2nn6 CITY OF TIGARD BUILDING DIVISION , ® Fire Marshal's Division Offices Tualatin Valley North - 14480 SW Jenkins Rd., Beaverton, OR 97005, (503) 356 -4700 Fire & Rescue South - 7401 SW Wash Ct., Tualatin, OR 97062, (503) 612 -7010 Fire Flow and Hydrant Worksheet 1 This worksheet is required to be submitted to and approved by the Authority Having Jurisdiction (AHJ) before any permits for new building construction, building expansion or fire hydrants will be issued by any building department within the TVF &R District. See the instructions for assistance completing this form or call one of the above numbers. Preparer Information 1 Preparer Name: (John Webster Phone: 1503- 236 -6000 1 Fax:1503- 236 -7500 1 Architect / Engineer of Record: (Brian Frey Phone:1503- 236 -6000 I Fax:1503- 236 -7500 1 General Building Information I Project Name: (Dartmouth Square 1 Project Address: 111945 SW 70th Avenue City: Tigard ( County:ITualatin 1 Zip:197223 1 Construction Type(s): Type IIB and IIIB Total Bldg Area: 1 38,830jsgft Total Fire Area: 1 38,8301sgft Bldg Fire Flow: I 4256IGallons Per Minute (Light Hazard) Describe Fire Area: (if more than one fire area, include an 81/2 x 11 or 11 x 17 drawing Indicating the various fire areas) 3 -story office building of non - comustable materials, fully sprinklered with NFPA 13 automatic sprinklers Type of Occupancy or Use of Building: (office building A. Occupancy Hazard Al Determine percent of each occupancy hazard in the fire area. Occupancy Hazard Class Fire Area 1 Total Fire Area Percent of Fire Area Light Hazard 38,830 SF / 1 38,830 SF x 100 = 100 % Ordinary Hazard Grp 1 0 SF / 1 SF x 100 = 0 % Ordinary Hazard Grp 2 0 SF / 1 SF x 100 = 0 % Extra Hazard Grp 1 0 SF / 1 1 SF x 100 = 0 % Extra Hazard Grp 2 0 SF / 1 SF x 100 = 0 % Total Must equal 100% ( 100 % I A2 Calculate Fire Flow Occupancy Hazard Class Factor Fire Area Fire Flow Bldg Fire Flow Light Hazard 1.0 • x 100 % x 4256 GPM = 4256 GPM Ordinary Hazard Grp 1 1.2 x 0 % x 4256 GPM = 0 GPM Ordinary Hazard Grp 2 1.3 x 0 % x 4256 GPM = 0 GPM Extra Hazard Grp 1 1.4 x 0 % x 4256 GPM = 0 GPM Extra Hazard Grp 2 1.5 x 0 % x 4256 GPM = 0 GPM A3 Required Fire Flow 1 4256 GPM I 1 B. Minimum Number of Fire Hydrants Required I Required Fire Flow 4256 = I 4 INo. of Hydrants Required I C. Reduction of Fire Flow - Reductions are based on the following: I C1 - Reduced by 25% for all Group R Occupancies without fire sprinklers (multiply by .75) C2 - Reduced by 25% for a NFPA 72 Fire Alarm System (multiply by .75) C3 - Reduced by 75% for NFPA 13 Automatic Sprinklers (multiply by .25) D. Required Fire Flow 1 D1 - Group R occupancy I No Ix 1 1 I = I 4256 GPM (Max. 3000 - Min. 1500 gpm) I D2 - Fire Flow 4256 GPM x 1 0.25 I = 1 1500 GPM (Max. 3000 - Min. 1500 gpm) E. Available Fire Flow to the Building I Test Results: I I GPM Manually enter available fire flow here. Please attach documentation of the flow test that was made. It shall include date, time, location of static /residual and flow hydrants, and the tester's name, phone number and address. Sitework Review I f 0�� \nod 4- c!tework Permit Review �✓ 1 -ci 1 Check for Fire De � � partment Access. Section 503 & 508 Fire Code. e • Check for Underground Fire Lines. NFPA 24. IA,' r ') Li- we �l 1 p N-v �"" \ � rJ` Check for any Retaining �. • C y Retainin Walls. Section 1806 & Chapter 16 Building Code e, • Check for Site Accessibility. Section 1103 & 1104 Building Code. L • Check for any special Soil conditions. Chapter 18 Building Code. v° �, Verify that the erosion control measures have been indicated. , 4j/ • Check the building for location on pro do (Point out re P perry. Table 602 Building Code. ��` quired rated exterior walls, opening protection, parapets etc...) Plumbing Site Utilities Review • Check Potable Water supply for meth ° d size and material. • Check Storm Drainage piping for method, slope, size &material. • Check Sanitary Sewer piping method, slope, size &material.