Loading...
Specifications (2) M Y H R E •GROUP p\,42 C ZUU i+GUSja a r c h i t e c t s T R A N S M I T T A L Project: Dartmouth Square Topic: Structural Calculation for Mechanical Curb Mounts Project No.: 053570 Date: 12.07.07 To: S.I. Grace From: Myhre Group Architects 11935 SW 70 Ave. 700 SW Taylor Street Tigard, Oregon 97223 Suite 400 Portland, Oregon 97205 Distribution: Joe Estes . Issued by: John Webster O � Sent Via: Courier Fox #: (503) 620 -7934 Phone #: (503) 519 -9347 Pages: See copy list Copies: Dated: Item: 3 12/4/07 Structural Calculation for Mechanical Supports Joe, Please find attached three (3) copies of the Structural Calculations for Mechanical supports for the Dartmouth Square project. Regards, • John Webster 700 SW Taylor Street, Suite 400. Portland, OR 97205. v 503.236.6000 f 503.236.7500 . www.mvhrearoup.com This transmittal may contain privileged and /or confidential information intended only for the use of the addressee. If you receive this transmittal by mistake, please notify Myhre Group Architects at the above number. GRACE vv v LLC • , '' GENERAL CONTRACTORS S.I. Grace, LLC CDPr h ° AIME_ [ TaL 7165 SW FIR LOOP, SUITE 100 TIGARD, OR 97223 PH (503) 620 -6553 FAX (503) 620 -7934 Attn: Ken McKinley DATE: 1 -3 -08 To: American Heating, Inc. 1339 SE Gideon Portland, Oregon 97202 From: RE: Dartmouth Square Bob Wilson WE ARE SENDING YOU: Attached 0 Under separate cover via ❑ Fax 0 Messenger ❑ Mail the following items: ❑ Shop drawings ❑ Prints ❑ Plans ❑ Samples ❑ Specification ❑ Copy of letter ❑ Change order ❑ Other 0 COPIES DATE NO. DESCRIPTION 2 @ 12 -3 -07 Structural Calcs for Mechanical Units from Architect /Engineers THESE ARE TRANSMITTED as checked below: ❑ For approval ❑ Approved as submitted ❑Re- submit copies for approval For your use ❑ Approved as noted ❑ Submit copies for distribution ❑ As requested ❑ Returned for corrections El Return corrected prints REMARKS: Ken; Here are the structural calcs for the Mechanical Unit supports from the engineer. Thank You, ' 4 ) 4)6 11 'i Bob Wilson SI Grace, LLC (503) 620 -6553 x110 COPY TO: SIGNED: file 71l C11) L':« T ....« T:.... «.7 C1D 07072 imilQ \Cn!■ /2==0 Dt. 1R4\Q \C0/1 7024 r.... !`!`D44 1 I " 2 I I Form 2a Project Name: Dartmouth Square Page: 1 SUMMARY Project 1. Project Name Dartmouth Square Office Building • 2. Project Address 11935 SW 70th Avenue 3. City/Town Tigard 5. County J Washington 4. Building, Gross Area (ft2) 6. No. of Floors 3 7. Construction Site Elevation Above 2,000 ft? ❑ YES ONO Attached Chapter Type ID Description Attach Forms and Building Envelope Form 3a Building Envelope - General ❑ Worksheets 3b Prescriptive Path - All Climate Zones ❑ * CodeComp Report for Simplified Trade -off ❑ * In lieu of 3b * Floppy disc with .occ CodeComp file ❑ Check boxes to Worksheet 3a Wall U- factor ❑ indicate attached 3b Roof U- factor ❑ forms and 3c Floor U- factor ❑ worksheets 3d Window /Skylight Schedule ❑ Systems Form 4a Systems - General U 4b Complex Systems p Worksheet 4a Unitary Air Conditioners - Air Cooled 4b Unitary Air Cond. - Water & Evap Cooled ❑ 4c Unitary Heat Pump - Air Cooled ❑ R ECEIVE® 4d Unitary Heat Pump - Water Cooled ❑ 4e Packaged Terminal A.C. - Air Cooled 4f Packaged Terminal Heat Pump - Air Cooled ❑ S E P 0 6 2007 4g Water Chilling Pkgs - Water & Air Cooled ❑ COFTI 4h Heat Rejection Equipment ITY TIMID ❑ B Ij 11 D U 4i Boiler - Gas -Fired and Oil -Fired ❑ 4j Furnace & Unit Heaters - Gas and Oil -Fired ❑ 4k Simultaneous Heating and Cooling 41 Air Transport Energy p 4m Natural Ventilation ❑ Lighting Form 5a Lighting - General LJ 5b Interior Lighting Power - Tenant Method ❑ 5c Int. Ltng. Power - Space -by -Space Method ❑ Worksheet 5a Lighting Schedule ❑ 5b Interior Lighting Power ❑ Applicant 7. Name Ken McKinley 10. Telephone 503 - 239 -4600 8. Company American Heating Inc 11. Date 09/04/07 9. Signature Attached No. of Pages Description of Documentation Document 44 Equipment Specifications ation �,vmpnanc a with v enecuve v vu uvv Form 4a Project Name: Dartmouth Square Page: 2 SYSTEMS - GENERAL Applicability Plans /Specs Discussion of qualifying Show compliance by including a drawing sheet, detail number, exceptions on paqe 4 -25 specification section and subparagraph. 1. Applicablity (Section 1317) Is this form required? o Form Required. Complete form if a new HVAC system is being installed, or components of an existing HVAC system are being replaced (I.e., equipment, controls, ductwork, and insulation.) ❑ Exception. The building or part of the building qualifies for an exception from HVAC code requirements. Applicable code exception is Section 1317.1. Portions of the building that qualify: Area: Exception ❑ - ❑ -2 O -3 Area: Exception O - ❑ - ❑ -3 Area: Exception ❑ - 0 O Form Not Required. This project does not contain work required to comply with code. 2. Simple or Complex Systems (Section 1317.9 or 1317.10) ❑ Simple System. Building contains only Simple HVAC System(s). Complete this form (4a) and equipment efficiency worksheets as required. Form 4b is not required. o Complex System. Project includes a Complex System. Complete this form (4a), form 4b and equipment efficiency worksheets as required. 3. Equipment Performance (Section 1317.5) ❑ No New HVAC Equipment. The building plans do not call for new electrical HVAC equipment, combustion heating equipment, or heat - operated cooling equipment. El Complies. All new HVAC equipment have efficiencies not Tess than those required by code. The following equipment efficiency worksheets are attached: ❑ -4a ❑ -4b ❑ -4c ❑ -4d ❑ -4e ❑ -4f ❑ -4g ❑ -4h ❑ -4i ❑ -4j 4. Duct Insulation and Sealing (Sections 1317.7 as 1317.8) ❑ No Ducts. The building plans and specifications do not call for new HVAC ducts or plenums. is Complies. The plans and specifications call for all air - handling ducts and plenums to be insulated and sealed as required by Sections 1317.7 &1317.8. 5. Distribution Transformers (Section 1316.1) El No Distribution Transformers. The plans /specs do not call for new distribution transformers. ❑ Complies. All new distribution transformers comply with efficiency, testing, and labeling requirements of Section 1316.1.1. ❑ Exception. The project qualifies for an exception per Section 1316.1.1, Exceptiion: ❑ - 0-2 0 0 0 ❑ e 0 0 0 ❑ 10 ❑ -1' 0 - 12 ❑ -13 ❑ -14 Attach relevant documentation for appropriate exception. The plans /specs show compliance in the "fir„ following locations: Vei 4 -1 April 2005 Compliance with OSSC, effective 01/01/05 Form 4a Project Name: Dartmouth Square Page: 3 SYSTEMS - GENERAL 6. HVAC Controls (Section 1317.4) 6.1 System Thermostat /Zone Controls (Section 1317.4.1) El Complies. All new HVAC systems include at least one temperature control device responding to temperatures within the zones. ❑ Exception. HVAC system qualifies for an exception from zone control requirements. The applicable code exception is Section 1317.4.2, Exception 0-1 0-2 Portions of the building that qualify: The plans /specs show compliance in the following locations: 6.2 Off - hour Controls Auto Setback or Shutdown (Section 1317.4.3) 2 Complies. Systems must have at least one of the following features: ❑ Control Setback Complies. Each system is equipped with automatic control capable of reducing energy through control setback during periods of non -use or alternate use of spaces served. ❑ Equipment Shutdown Complies. Each system is equipped with controls capable of reducing energy use through automatic shutdown during periods of non -use or alternate use of spaces. HVAC systems with equipment shutdown are equipped with at least one of the following: ❑ Programmable controls (1317.4.3.1 (1)) ❑ Occupant sensor (1317.4.3.1 (2)) ❑ Interlocked to a security system (1317.4.3.1 (3)) ❑ Manually activated timers with 2 -hour operation max (1317.4.3.1 (4)) ❑ Exception. The building qualifies for an exception to the requirement for automatic setback or shutdown controls. The applicable code exception is Section 1317.4.3 Exception 0-1 0-2 The plans /specs show compliance in the following locations: 6.3 Control Capabilities (Sec. 1317.4.2.1) O Complies. Zone thermostats are capable of being set to the temperatures described in Sec. 1317.4.2.1. Where used to control both heating and cooling, zone controls shall be capable of providing a temperature range or deadband of at least 5 degrees F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. ❑ Exception. The building qualifies for an exception to the deadband requirements. The applicable code exception is Section 1317.4.2.1 Exception 0-1 0-2 Portions of the building that qualify: The plans /specs show compliance in the following locations: 6.4 Optimum Start Controls (Section 1317.4.3.2) o Complies. Separate HVAC systems have controls capable of varying start-up time of system to just meet temperature set point at time of occupancy. ❑ Exception. HVAC systems have a design supply air capacity not exceeding 10,000 cfm. The plans /specs show compliance in the following locations: 6.5 Heat Pump Controls (Section 1317.4.4) O No Heat Pump. The plans /specs do not call for a new heat pump ❑ Complies. All new heat pumps equipped with supplementary heaters are controlled to minimize the use of supplemental heat as defined in Section 1317.4.4. e: ;- ' 11,, The plans /specs show compliance in the following locations: w4 • 4 -2 April 2005 Compliance with OSSC, effective 01/01/05 Form 4a Project Name: Dartmouth Square Page: 4 SYSTEMS - GENERAL 7. Economizer Cooling (Section 1317.3) ❑ No Cooling. The building plans do not call for a new fan system with mechanical cooling. El Complies. Each new fan system has an air economizer capable of modulating outside -air and return -air dampers to provide up to 100 percent of the design supply air as outside air. ❑ Exception At least one new fan system qualifies for an exception. The applicable code exception is Section 1317.3, Exception ❑ -1 ❑ -2 ❑ -3 ❑ - ❑ -5 ❑ -6 ❑ -7 If Exception 3 is selected complete the following: (a) Total cooling capacity of exempt units (Btu /hr) (b) Total installed building cooling capacity (Btu /hr) ❑ Complies. Sum of exempt units rated at Tess than 54,000 Btu /hr is <240,000 Btu /hr or a/b < 0.10 (10% of total building cooling capacity). Unit Identifier of exempt units: The plans /specs show compliance in the following locations: 8. Economizer Pressure Relief as Integration (Section 1317.3.1 and 1317.3.2) ❑ No Economizers Required. Project does not contain a new fan system requiring economizers. o Overpressurization Complies. The drawings specifically identify a pressure relief mechanism for each fan system that will relieve the extra air introduced by the economizer. ❑ Integration Complies. Economizer is capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. ❑ Exception. The applicable exception is Section 1317.3.2, Exception ❑ -1 ❑ -2 The plans /specs show compliance in the following locations: 9. Hot Gas Bypass (Section 1317.5) o No Hot Gas Bypass ❑ Complies. See allowable amount of hot gas bypass as a percentage of total cooling capacity in table below. Unit ID Rated Cooling Capacity Hot Gas Bypass Capacity Allowable Hot Gas Bypass Rated Cooling Capacity Max Hot Gas Bypass <240,000 Btu /hr 50% >240,000 Btu /hr 25% ❑ Exception. Unitary packaged system with cooling capacity no greater than 90,000 Btu /h 4 -3 April 2005 Compliance with OSSC, effective 01/01/05 Form 4a Project Name: Dartmouth Square Page: 5 SYSTEMS - GENERAL 10. Shutoff Dampers (1317.4.3.3) ❑ Not Required. Shutoff dampers are not required on this project. o Complies. Each outdoor air supply & exhaust system shall be equipped with motorized dampers. ❑ Exception. The building qualifies for an exception to the motorized damper requirement. The applicable code exception is Section 1317.4.3.3 Exception ❑ -1 ❑ -2 ❑ -3 ❑ - ❑ - ❑ -s The plans /specs show compliance in the following locations: 10.1. Shutoff Damper Controls (Section 1317.4.3.3.1) o Complies. Outdoor air supply and exhaust systems shall be provided dampers that automatically shut when systems or spaces served are not in use or during building warm -up, cooldown, or setback. ❑ Complies. Stair and shaft vents are capable of being automatically closed during normal building operation and interlocked to open as required by fire and smoke detection systems. The plans /specs show compliance in the following locations: 10.2. Motorized Damper Leakage (1317.4.3.3.2) El Complies. Motorized outdoor air supply and exhaust air dampers have a maximum leakage rate of 4 cfm /ft2 at 1.0 in w.g. when tested in accordance with AMCA Standard 500 -1998. ❑ Exception. Packaged HVAC equipment may have maximum leakage rate of 20 cfm /ft at 1.0 in w.g. when tested in accordance with AMCA Standard 500 -1998. The plans /specs show compliance in the following locations: 11. Piping Insulation (Section 1314) v No New Piping. The building plans and specifications do not call for new piping serving a heating or cooling system or part of a circulating service water heating system. ❑ Complies. All new piping serving a heating or cooling system or part of a circulating service water heating system complies with the requirements of the Code, Section 1314.1. ❑ Exception. New piping qualifies for exception: Section 1314.1, Exception 0-1 0 -2 12. Occupancy Ventilation o Complies. Mechanical ventilation systems provide the required amount of ventilation is indicated in plans /specifications as specified in Chapter 4 of the Oregon Mechanical Specialty Code. ❑ Complies. Natural ventilation systems provide required amount of ventilation as certified by a reg- istered architect or engineer as specified by Section1203.4.1, Exception. Attach worksheet 4m. The plans /specs show compliance in the following locations: The plans /specs show compliance ,, <. on the following pages: 4-4 April 2005 Compliance with OSSC, effective 01/01/05 Form 4a Project Name: Dartmouth Square Page: 6 SYSTEMS - GENERAL 13. High Occupancy Ventilation (Section 1317.2.2) ❑ Complies. HVAC systems with ventilation air capacities of 1,500 CFM or greater that serve areas having an average occupant Toad of 20 square feet per person or Tess from Table 1004.1.2 have a means to automatically reduce outside air intake. Identify applicable systems: Plans /specs indicate where equipment (i.e. carbon dioxide sensor) and sequence is specified: ❑ Exception. HVAC systems are equipped with an energy recovery device with at least 50% recovery effectiveness. O No High Occupancy Systems. Project does not contain an HVAC system as described above. 14. Exhaust Air Heat Recovery (Section 1318.3) ❑ Not Regulated. HVAC system does not have: 1) design supply air cap. of >10,000 cfm, and 2) min. outside air supply >70 %, and 3) at least 1 exhaust fan rated at 75% of min outside air supply. 2 Complies. Heat recovery system increases outside air temperature by 20 °F (Climte Zone 1) or 30 °F (Zone 2) and has provision to provide bypass during air economizer mode. ❑ Exception. An HVAC system qualifies for an exception to this requirement. Applicable exception from Section 1318.3 Exception0- 0-2 0-3 0-4 0-5 0-6 0-7 The plans /specs show compliance in the following locations: 15. Large Volume Fan Systems (Section 1318.4.2.4) ❑ Not Regulated. The building plans or specifications do not call for fan systems over 15,000 CFM that serve a single zone and function for the purpose of temperature control. O Complies. Fan systems are equipped with variable frequency drive or two speed motor to reduce airflow as required by Section 1318.4.2.3. The plans /specs show compliance in the following locations: 16. Variable Speed Drives (Section 1317.10.3.1) ❑ Not Regulated. The building plans or specifications do not call for fan and pump motors 10 horsepower and greater that serve variable -flow air or liquid systems. O Complies. All fan and pump motors 10 hp and greater which serve variable -flow air or liquid systems are controlled by a variable -speed drive. ❑ Exception. The building qualifies for an exception to the variable -speed drive requirement. Portions of the building that qualify: Applicable code exception is Section 1317.10.3.1, Exception The plans /specs show compliance in the following locations: 17. Service Water Heating (Sec. 1315) o No New Water Heating. The building plans and specifications do not call for new water heaters, hot water storage tanks or service hot water distribution systems. ❑ Complies. All new water heaters, hot water storage tanks or service hot water distribution systems comply with the requirements of the Section 1315. ❑ Exception. The applicable code exception is Section: Exception: Portions of the building that qualify: V" `' The plans /specs show compliance in the following locations: 4 -5 April 2005 Compliance with OSSC, effective 01/01/05 Form 4a Project Name: Dartmouth Square Page: 7 SYSTEMS - GENERAL 18. Swimming Pools, Spas and Hot Tubs (Section 1315.5) El No New Pools. The building plans and specifications do not call for new, swimming pools, spas or hot tubs. ❑ On /Off Controls Complies. Spa and hot tub heaters are equipped with a readily accessible ON /OFF switch as required by Section 1315.5.1. ❑ Ventilation Controls Complies. Pool ventilation system is controlled based on humidity. ❑ Cover Complies. All heated pools, hot tubs and spas are equipped with a cover. ❑ Heat Recovery Complies. Pools, Spas, and hot tubs, over 200 ft utilize recovered heat as required by Section 1315.5.3. ❑ Exception. Heat recovery is not necessary as pool is heated by renewable energy or waste heat recovery sources capable of providing at least 70 percent of the heating energy required over an operating season. 19. Fume Hoods (Section 1317.2.1.) a No Fume Hoods. The building plans do not call for fume hood systems that have a total exhaust rate greater than 15,000 cfm. ❑ Complies. Fume hood systems have at least one of the following features: ❑ Variable air volume hood exhaust and room supply systems capable of reducing exhaust and makeup air volume to 50% or less of design values. ❑ Direct makeup (auxiliary) air supply equal to at least 75% of the exhaust rate, heated no warmer than 2° F below room set point, cooled no cooler than 3° F above room set point, no humidification added, and no simultaneous heating and cooling used for dehumidification control. ❑ Heat recovery systems to precondition makeup air from fume hood exhaust in accordance with 1318.3 - Exhaust Air Energy Recovery, without using any exception. The plans /specs show compliance in the following locations: 20. Parking Garage Ventilation (Section 1317.2.3) El No Enclosed Garages. The building plans and specifications do not call for enclosed Group S -2 parking garages with a ventilation exhaust rate greater than 30,000 CFM. ❑ Complies. The plans and specifications call for carbon monoxide sensing devices as required by Section 1317.2.3. ❑ Exception. Open parking garages. 21. Kitchen Hoods (Section 1317.11) El Not Regulated. The plans /specs do not call for any new kitchen hoods with exhaust capacity greater than 5,000 cfm each. ❑ Complies. All new kitchen hoods with a total exhaust capacity greater than 5,000 cfm have at least 50 percent of the required makeup air; (a) unheated or heated to no more than 60 °F; and (b) uncooled or evaporatively cooled. Y*( The plans /specs show compliance in the following locations: 22. Outside Heating Systems (Section 1317.12) o No Outside Heating Systems. The plans /specs do not call for new permanently installed heating systems outside the building. ❑ Complies. All new permanently installed outside heating systems are radiant gas fired systems controlled by an occupancy sensor or timer switch as required by Section 1317.12. 4 -6 April 2005 Compliance with OSSC, effective 01/01/05 Form 4b Project Name: Dartmouth Square Page: 8 COMPLEX HVAC SYSTEMS Applic 1. Simple or Complex Systems (Section 1317.9, 1317.10 and 1318) ability Note: This form is required for complex systems only. If your plans qualify as a simple system Discussion of as defined by the code, this form is not required. qualifying excep- i instructions c in 2 . Air Transport Energy (Section 1318.4.2 instructions P gy ( 1318.4.2) section. ❑ Not Regulated. Each HVAC system does not have total fan nameplate horsepower of 7.5 HP an Motor or greater (include sum of all supply, return, & exhaust fans operating at design conditions). Energy 0 Brake Horsepower Complies. The energy demand of all HVAC fan systems meets code See Section 1318.4.2 for re q p requirements. Complete and attach Worksheet 41. maximum horse- ❑ Nameplate Horsepower Complies. Selected fan motors have nameplate ratings no larger power allowed. than is allowed by Section 1218.4.2.3. (Complete Worksheet 4L.) ❑ Exception. Section 1318.4.2, Exception 0 -1 0 -2 0 -3 0 -4 Portions of the building that qualify: The plans /specs show compliance in the following locations: Cooling 3. Cooling Tower Fans (Section 1317.5.4.1) Tower O No Cooling Tower There is no cooling tower in this project. Fans ❑ Complies. Cooling tower fans have control devices that vary flow by controlling leaving fluid temperature or condenser temperature /pressure of the heat rejection device. The plans /specs show compliance in the following locations: 4. Simultaneous Heating and Cooling (Section 1318.2.1) ❑ No Cooling. The building HVAC system has no cooling. 2 Complies. Controls prevent reheating, recooling or mixing of mechanically heated and mechanically cooled air. ❑ Exception. Code exception is Section 1318.2.1, Exception 0-1 0-2 0-3 0 -4 0-5 If exception 1 is used, complete and attach Worksheet 4k Portions of the building that qualify: The plans /specs show compliance in the following locations: 5. Electric Motor Efficiency (Section 1317.10.3 as Table 13 - T) ❑ Not Regulated. There are no NEMA Design A &B squirrel cage,T -frame induction, permanently wired polyphase motors of one horsepower or more which serve built up HVAC systems. El Complies. The efficiency of all regulated motors meets code requirements. Exceptions ❑ Exception. Section 1317.10.3, Exception 0-1 0 Discussion of qualifying Portions of the building that qualify: exceptions in instructions section. The plans /specs show compliance in the following locations: 6. VAV System Static Pressure Reset Controls (Section 1318.2.3) ❑ Not Regulated. The building plans or specifications do not call for a VAV system controlled by a static pressure sensor or direct digital control of individual zone boxes. ❑ Complies. The system static pressure set point automatically resets to the lowest point ait ,y'> possible while still providing the required air flow to the zones with the greatest demand. =�^; ❑ Exception. Section 1318.2.3, Exception `v The plans /specs show compliance in , I, the following locations: 4 -7 April 2005 Compliance with OSSC, effective 01/01/05 I Form 4b Project Name: Dartmouth Square Page: 9 COMPLEX HVAC SYSTEMS 7. VAV Terminal Units (Section 1317.4.2.1) ❑ Not Regulated. Project does not contain VAV terminal units. O Complies. VAV terminal units are programmed to operate at the minimum airflow setting without addition of reheat when the zone temperature is within the set deadband. Complete Worksheet 4k. ❑ Exception. Section 1317.4.2.1, Exception 0-1 0-2 The plans /specs show compliance in the following locations: 8. Supply - Air Temperature Reset Controls (Section 1318.2.5) ❑ Not Regulated. The building plans or specifications do not call for multiple zone HVAC systems. O Complies. Multiple zone HVAC systems include controls that automatically reset the supply -air temperatures in response to building loads or outside air temperature. ❑ Exception. The building qualifies for an exception to the supply -air reset controls requirement. Applicable code exception is Section 1318.2.5, Exception 0-1 0-2 0-3 Portions of the building that qualify: The plans /specs show compliance in the following locations: 9. Chilled and Hot Water Temperature Reset Controls (Section 1318.2.4) O Not Regulated. The building plans or specifications do not call for chilled or hot water systems with a design capacity exceeding 300,000 Btu /hr. ❑ Complies. Chilled and hot water systems include controls that automatically reset supply water temperatures by representative building loads or by outside air temperature. ❑ Exception. Section 1318.2.4, Exception 0-1 0-2 Portions of the building that qualify: The plans /specs show compliance in the following locations: , 10. Separate Air Distribution Systems (Section 1318.2.7) O Not Regulated. The building plans or specifications do not call for zones with special process temperature or humidity requirements. ❑ Complies. Separate air distribution systems serve zones with special process temperature or humidity requirements from those zones serving only comfort conditions, or supplementary control provisions are included so primary systems are specifically controlled for comfort purposes only. ❑ Exception. Section 1318.2.7, Exception 0-1 0-2 Identify zones with special process requirements: The plans /specs show compliance in the following locations: 11. Zone Isolation Controls (Section 1318.2.6) O Not Regulated. Building plans or specifications do not call for HVAC systems serving multiple occupancies or floors with >240,000 Btu /hr cooling capacity, or >300,000 Btu /hr heating capacity. ❑ Complies. HVAC systems serving multiple occupancies or floors with >240,000 Btu /hr cooling capacity, or >300,000 Btu /hr heating capacity are equipped with isolation devices capable of automatically shutting off supply air to and from each isolated area. Each isolated area is controlled independently and satisfies temperature setback (Section 1317.4.2) and optimum start control requirements. Central fan system air volume is reduced through fan speed reduction. The plans /specs show compliance in the + s�*x� following locations: wJ 4-8 April 2005 Compliance with OSSC, effective 01/01/05 • Form 4b Project Name: Dartmouth Square Page: 10 COMPLEX HVAC SYSTEMS 12. Humidity Controls (Section 1318.2.2) 2 No Moisture Added to Building. The building plans do not call for means to add moisture to maintain specific humidity levels. ❑ Complies. All new humidity control systems equipped with a humidistat when required. All humidifier preheating devices have an automatic value to shut off preheat when humidification is The plans /specs show compliance in the following locations: 13. Hydronic System Controls (Section 1318.2.8) 0 No Hydronic System. The building plans or specifications do not call for a new hydronic system. ❑ Complies. The hydronic system complies as follows: 13.1 Variable Flow Controls (Section 1318.2.8.4) ❑ System does not have a 10 hp or greater motor ❑ Complies. System has controls capable of varying pump flow The plans /specs show compliance in the following locations: 13.2 Three -Pipe System (Section 1318.2.8.1) ❑ System does not have a common return system (a three -pipe system) for both hot water and chilled water. 13.3 Two -Pipe Changeover System (Section 1318.2.8.2) ❑ System is not a Two -Pipe Changeover System ❑ Complies. System is: a. Designed to allow a deadband between changeover from one mode to the other of at least 15 °F outside air temperature. b. Designed to operate and provided with controls that will allow operation in one mode for at least four hours before changing over to the other mode. c. Provided with reset controls that allow heating and cooling supply temperatures at the changeover point to be no more than 30 °F apart. The plans /specs show compliance in the following locations: 13.4 Hydronic (Water Loop) Heat Pump System (Section 1318.2.8.3) ❑ System is not a Hydronic (Water Loop) Heat Pump System ❑ Complies. Hydronic heat pumps connected to a common heat pump water loop with central devices for heat rejection (e.g., cooling tower) and heat addition (e.g., boiler) have the following: a. Controls installed capable of providing a heat pump water supply temperature deadband of at least 20 °F between initiation of heat rejection and heat addition by the central devices (e.g., tower and boiler). b. Closed- circuit tower (fluid cooler) has either an automatic valve installed to bypass all but a minimal flow of water around the tower (for freeze protection), or low- leakage positive closure dampers. c. Open- circuit tower installed directly in the heat pump loop has an automatic valve installed to bypass all heat pump water flow around the tower. Open - circuit towers used in conjunction with a separate heat exchanger to isolate the tower from the heat pump loop are controlled by shutting down the circulation pump on the cooling tower loop. �,� d. A two- position valve at each hydronic heat pump for hydronic systems 5 "`' =`�'' having a total pump system power exceeding 10 hp. P : The plans /specs show compliance in the following locations: 4 -9 April 2005 Compliance with OSSC, effective 01/01/05 Worksheet 4a Project Name: Dartmouth Square Page: UNITARY AIR CONDITIONER - AIR COOLED Equipment (a) (b) (c) (d) (e) (f) Proposed Performance Discussion of equipment Cooling Seasonal or Compliance New or ratings and equipment Equip. ID Model Designation Capacity Steady State Part Load Schedule (A -E) Replacemnt? • definitions on page 4 -19. CU -1 PUY- A3ONHA 18000 14 E Required Indicate source of information Document ❑ ARI Unitary Directory, Section AC, page: ation ❑ ARI Applied Products directory, Section ULE, page: O Product data (Attach data furnished by the equipment supplier, I.e., "cut sheets ") Code Required Cooling Capacity (btu/hr) Minimum Rating Efficiencies Compliance Seasonal or Schedule Equipment Type Over But not over - Steady State Part Load New • 0 65,000 na 13 SEER Single Package Without a Replacement • 0 65,000 na 9.7 SEER A Heating Section or With Electric 65,000 135,000 10.3 EER n/a This schedule of equip Resistance Heat 135,000 240,000 9.7 EER n/a ment efficiencies was All 240,000 760,000 9.5 EER 9.7 IPLV reformatted from code, 760,000 - 9.2 EER 9.4 IPLV Table 13 -L. New • 0 65,000 na 13 SEER Split System Without a Heating Replacement " 0 65,000 na 10 SEER B Section or With Electric 65,000 135,000 10.3 EER Na Resistance Heat All 135,000 240,000 9.7 EER n/a 240,000 760,000 9.5 EER 9.5 IPLV 760,000 - 9.2 EER 9.2 IPLV New • 0 65,000 na 13 SEER Single Package With a Heating Replacement * 0 65,000 na 9.7 SEER C Section Other Than Electric 65,000 135,000 10.1 EER n!a Resistance All 135,000 240,000 9.5 EER n/a 240,000 760,000 9.3 EER 9.5 IPLV 760,000 - 9.0 EER 9.2 IPLV 00, "it.;. New • 0 - 65,000 na 13 SEER ' �. Replacement • 0 65,000 na 10 SEER `"'< Split System With a Heating J D Section Other Than Electri 65,000 135,000 10.1 EER Na .. Resistance All 135,000 240,000 9.5 EER Na ?'� 240,000 760,000 9.3 EER 9.7 IPLV 760,000 - 9.0 EER 9.4 IPLV E Condensing Unit Only All 135,000 - 10.1 EER 11.2 IPLV • Equipment is a new Installation or replaces existing equipment 4 -11 Compliance with OSSC, effective 01/01/05 Worksheet 4e Project Name: Dartmouth Square Page: 12 PACKAGED TERMINAL A.C. - AIR COOLED Equipment (a) (b) (c) (d) (e) Proposed Code Enter the cooling capacity Minimum in column (c ). If capacity Cooling is less than 7,000 Btu/hr, use 7,000. If above Capacity EER EER 15,000, use 15,000. Type of Equipment Equip. ID Model Designation (Btu/hr) (95 °F db) (95 °F db) RTU -1 SFHGC904 90,000 9.7 -6.7 Discussion of equipment ratings and equipment definitions on page 4 -19. Units Installed in New Construction Replacement of Existing Units (installed prior to 10/01/03) Required Indicate source of information Documentation ❑ ARI Unitary Directory, Section AC, page: ❑ ARI Applied Products directory, Section ULE, Page: p Product data (Attach data furnished by the equipment supplier, I.e., "cut sheets ") Code Calculate the code minimum EERs from the formulas below using the cooling capacity in column ( c ). Required Enter the results In column (e). New Construction: EER 95F Test Conditions = 12.5- (0.213x Cap/1000) Efficiencies Replacement Units : EER ® 95F Test Conditions = 10.9- (0.213x Cap/1000) 4-15 Compliance with OSSC, effective 01/01 /05 Worksheet 4k Project Name: Dartmouth Square Page: 13 Simultaneous Heating and Cooling * Additional pages may be necessary if building has more terminal units than there are lines in this form. If needed use Add New Worksheet button Complete this form for all terminal units with reheat to verify compliance with Section 1318.2.1 exception 1. Terminal Unit (Variable Air Volume (VAV) Box) CFM Design Conditions Required Information Comply Max. Ht CFM Ht. CFM Ht. CFM Maximum Cooling Occupancy < or = to < or = to < or = to Airflow is Terminal Unit ID or Sq. ft Area Airflow- Max. Heating Ventilation- 30% of 0.4 CFM Occupancy < or = to Description /Location Served CFM Airflow -CFM CFM Max per sq. ft Ventilation 300 CFM FP1 -1 First Floor 395 200 60 YES YES YES FP1 -2 First Floor 145 280 168 NO NO YES FP2 -1 Second Floor 459 700 210 YES NO NO FP3 -1 Third Floor 432 700 210 YES NO NO VAV 1 -1 1004 700 320 NO YES NO VAV 2 -1 800 800 320 NO YES NO VAV 3 -1 800 800 320 NO YES NO • 4 -21 Compliance with OSSC, effective 01/01/05 • Worksheet 41- Project Name: Dartmouth Square Page: 14 AIR TRANSPORT ENERGY Complete one worksheet for each fan system > 7.5 horsepower. Fan system horsepower is the sum of motor brake horsepower of all supply, retum, and exhaust fans (including series fan - powered terminal units) that operate during design conditions. Fan System ID:(RTU -1 j Areas Served:) ❑ System serves hospital or laboratory and Include flow control device for maintaining precise pressure control. Maximum Fan Type (Supply, Nameplate Fan Identifier Return, Exhaust, Series Constant Volume Motor Brake Nameplate Motor HP (Tag) VAV) CFM or VAV HP Motor HP Allowed RTU - 1 Supply 35,000 VAV 50.65 60 100.0 The Plans /Specs show brake hp, nameplate hp, and CFM in the following locations: Total System Total Total System Supply Fan Constant Volume, VAV, System Max Brake HP Brake HP Nameplate CFM or Hospital /Lab Brake HP Allowed Complies HP Complies 35,000 VAV 50.7 50.8 Yes Yes Additional Pressure Drop Credit (all systems). Complete the section below if system contains filtration with a pressure drop at design flow in excess of 1" w.c. ( when filters are clean), heat recovery, or direct evaporative humidifier /cooler. Additional Pressure Drop Credit for Hospitals and Laboratories. Complete the section below if system serves a hospital or laboratory and contains rully ducted retum /exhaust, retum /exhaust air flow control devices, or individual filter system efficiencies. Additional Pressure Drop Credits Pressure Drop, Inches, W.C. ❑ Filtration Pressure Drop >1" w.c. All Systems ❑ Heat Recovery ❑ Direct Evaporative Humidifier /Cooler Hospital and ❑ Fully Ducted Return /Exhaust (0.5" credit) Laboratory ❑ Return /Exhaust Flow Control Device (0.5" credit) Systems Oniy ❑ Individual Filter Efficiency > or = 85% (0.5" credit) Total Additional Pressure Drop Credit: ❑ Manufacturer's product data sheet(s) is attached and design values are shown in plans /specs in the following locations • Adjusted ' Total Brake Constant Volume or VAV (Use VAV Total Additional Max Allowed HP (from Adjusted Brake Supply CFM for Hospital or Lab Systems) Pressure Drop Brake HP above) HP Complies Add New Worksheet 41 3-22 .1 1 Compliance with OSSC, effective 01/01/05