Report Carlson Testing, • Construction Inspection & Related Tests
Inc. Geotechnica[ Consulting
P.O. Box 23814
JOB NO. 97
Tigard, Oregon 97281
Feb 17 , 1 997 Phone (503) 684-3460
REPORT OF IN -PLACE DENSITY TESTS FAX (503) 684 -0954
Client -IT ROTH CONSTRUCTION COMPANY
SIT 6:005F
Project R & W BUILDING
12570 SW 69TH TIGARD+ OR
Material Description 1 1 /2" -0 ROCK FROM NORTHFORK ROCK
Max. Dry Density 130.2 lbs. /cu. ft. Optimum Moisture 1 . 1 % Method of Test AASHTO T- 1 80
Serial # 1 739 NUC 344 0
DATE OF TEST ADJ. ELEV FIELD IN -PLACE DENSITY
TEST NO TEST LOCATION COLE DENS. FT M OIST RE WET BSJCU. DRY COMPACTION
SF NURTH PAD NW QUAD. +1
1
2 -11 3.9 122.6 112.6 86
SF 'NORTH PAD CENTER QUAD. +1
2
2-11 6.2 113.9 107.3 82
SF NORTH PAD SE QUAD. +1
2 -11 5.5 116.0 110.0 84
Remarks:
cc: CITY OF TIGARD
S t3: N EXCAVATION
OTAK INC
PDW DESIGN
P4,-, PE
TECHNICAL DIRECTOR
TED KORNOWSKI /CRW Review d By
1 weports perta i ri to the ma ter i a 1 tested/ i rispeccted o n l y . CARLSON TESTING INC.
Information contained herein is not to be reproduced, except in full, without prior authorization from this office.
C Construction Inspection & Related Tests
arlson Testing, Inc. Geotechnical Consulting
P.O. Box 23814
JOB NO. 97 Tigard, Oregon 97281
Apr. 07 1997 Phone (503) 684-3460
REPORT OF IN-PLACE DENSITY TESTS FAX (503) 684-0954
Client AT RnTH ffINP.TRUCTTAN CIIMPANY
SIT96-0055
Project R W DTNI(..; •
12570 SW 69TH TIGARD, OR
Material Description 4 " - RriCK FROM EATON
Max. Dry Density 1 7i; _ 7 lbs./cu. ft. Optimum Moisture % Method of Test AASHTO T-99
Serial # 2e;149 NUC: 2:440
DATE OF TEST % ADJ. ELEV. FIELD IN DENSITY
TEST LOCATION COARSE MAX. MOISTURE (LBSJCU.FT)
TEST NO PARTICLES DENS. FT % WET DRY COMPACTION
ST SOUTH END OF SANITARY FG
i SEWER TRENCH 25' NORTH
3-28 10.0 135.5 123.2
ST SOUTH END OF SANITARY - '
2 SEWER TRENCH 50 NORTH
10.9 130.1 117.3
Remarks: 93% COMPACTION REQUIRED
cc : CITY CIF TIGARD
S N EXCAVATION
OTAK
PDW DESIGN
Pik_ PE
TECHNICAL DIRECTOR
DILL YOUNGBLOOD /CRW Rev 1 ewed E:y