Loading...
Correspondence (634) November 22, 1996 CITY OF TIGARD P.D.W. Design OREGON 22 SE 134th Place Portland, OR 97233 Attn: Tim Roth RE: 2 -story Professional Office Bldg. (Shell Only) Building Plan Review 12570 SW 69th PC #: 10-71c BUP #: C 96 -0567 Submittal documents for the above referenced project have been reviewed for conformance with the applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The following comments are noted: Occupancy Classification: °B' Type of Construction: VN Location on Property: N - 120', S - 10', E - 15', W - 45' (c/I of street) Allowable Floor Area - 8000 s.f. Yards - Two (2) x 1.35 = 10,000 s.f. Stories - Two (2) x 2 = 20,000 s.f. Total Allowable Area Proposed - 8217 s.f. (3984 + 4233) Height - 32'6° Allowed - 40'0° Occupant Load: 1st Floor. 40 2nd Floor: 43 . ,.. ... i 7 . a -" C �P J s i YLK 'i�F • y 32 �. t A �, k , h(iA.aae . t - h i Y! Y 'C C, a L i i ry �►L,�� 1. Submit completed Energy Compliance Forms 2a, 3a, 3b, 4a through 4j, and 5a Ix b through 5c from the April 1, 1996 Revised Oregon Energy Code. I MESS191,ML •.� ,���,�+ ,5r ,. ;� �,,, � „ �4 77...,,; g ga rte, �V Nt aii 0 1. Provide an area of rescue assistance pursuant to Section 1107.2, OSSC. 04 2. Provide one (1) accessible drinking fountain. (O3. All required exits shall be constructed providing accessible means of egress in the same number as required for exits by Chapter 10, Table 10-A for persons with disabilities. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 2 -story Professional Office Bldg. (Shell Only) Building Plan Review PC #: 10-71c BUP #: 96 -0567 Page #2 4. All doors with controls and hardware shall be of the type providing accessibility to ® persons with disabilities [Section 1109.3]. Hardware on doors shall be lever or other shape not requiring tight grasping, pinching, or twisting to operate. Controls shall require a force no greater than 5 pounds—force to activate [Section .1109.3]. 5. Doors accessible for persons with disabilities shall have an 18° wide maneuvering space adjacent to the latch side of the door [Section 1109.9.3, Table 11 E]. 6. The environmental control (thermostat) and lighting controls shall not be located more than 54° above finish floor for accessible side reach approach or 44° for forward approach [Section 1109.2.3.6]. I FIREAVDUFESA,FET,Yfay_m �� °'€ '`11 .RI Exterior wall construction on the south and east walls shall have a one -hour, fire - resistive rating [OSSC, Table 5 -A]. / 2: The elevator shaft shall have a fire - resistive rating of one -hour [OSSC, Table / 6 -A]. / A trash dumpster with a capacity of 1.5 cubic yards or greater shall not be located /ply- under or within 5' of combustible construction [UFC 1103.2.2]. . Provide exit illumination having an intensity of not less than 1 foot candle at floor level, and provide a separate power source, such as an on -site generator or storage batteries to operate the lighting system in the exiting system [Section 1012.1 and 1012.2]. 5. Provide exit signs pursuant to OSSC, Section 1013. 6. If using locking hardware on main entrance, provide a sign on main entrance doors pursuant to 1004.3 (Exceptions). 7. Exterior stairways shall be constructed of wood not less than 2 inches in nominal thickness, or may be of noncombustible materials [OSSC, Section 606.4.3]. 8. Provide Type 2 -A fire extinguishers throughout so that the travel distance to a unit does not exceed 75 feet [NFPA 10 3.2.1]. 9. Glazing, in fixed or operable panels, adjacent to a door where the nearest exposed edge of the glazing is within a 24° arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is Tess than 60" above the walking surface, shall be tempered [2406.4(6)]. 10. A permit issued by the State of Oregon, Building Codes Division, is required for installation and operation of an elevator. Provide evidence of application for permits. 2 -story Professional Office Bldg. (Shell Only) Building Plan Review PC #: 10-71c BUP #: 96 -0567 Page #3 `Y�/,�,�7, �^+'s��/�� t t � g ,��xt -y� '�" v'C°�'.'93. �if1Y -�. w - k�Yt3�r't y cti� t^s�.'• %c',•.'[C+.� }� � «ter rt r J V r $TRV610: 1Wc*I iSiff n,i', sY^N.t ? •'1 eit 2rtel.�3n:. .`'_`rti° gAN ;"'6"�rif:'!': d .�- _ ;5.., e.:.�c - ? „+._ C� a�F.�lw�rr _aac�..Y_ .2)' a?; .�x.i.:3d r:;.Rw. .a. �.nb+Yv:.Y, a,.�. ..LS >.::_:c.w <vi'v1k ). Drawing #3: 1. Lateral calculations - V1- Shear wall PLF shown: 600 Your calcs require: 703 2. Mark Item "E ". A. 2" nailing requires 3x framing, staggered. Please indicate on drawings. 3. Provide sufficient weight on footings under H10DA holdowns to keep from overtuming. • Drawing #6 - Section 1 -6: Provide shear transfer with a row of flat blocks, use 4” nails, cup flat block to top plate below. t 4. Enclosed roof rafter spaces formed where ceilings are applied directly to the underside of roof rafters shall have cross ventilation of each separate space. Provide roof vents and cross ventilation of each rafter space [Section 1505.3]. 5. Toilet rooms shall be provided with openable exterior windows or a mechanically operated exhaust system capable of providing a complete change of air every 15 minutes [Section 1202.2.1]. 6. The suspended acoustical ceiling system shall be anchored to resist lateral seismic forces [Section 1630.2 and Table 16Q]. Provide suspension wires not smaller than No. 12 gauge spaced at 4' on center, perimeter wires on terminal ends of cross and main runners at a maximum of 8" from each wall, four No. 12 gauge wires splayed 90 degrees from each other at an angle not exceeding 45 degrees from the plane of the ceiling with a strut centered and extending to the structural members supporting the floor or roof above and spaced 12' on center in both directions starting 6' from each wall. All lighting fixtures weighing less than 56 lbs. shall be positively attached to the suspended ceiling system [ASTM C635 -94]. When using an intermediate grade system, No. 12 gauge wires shall be attached to the grid members within 3" of each comer of the fixtures, and lighting fixtures weighing less than 56 lbs. shall have two No. 12 slack wires connected from the fixture to the structure above. Ceiling mounted air terminals or services weighing less than 20 lbs. shall be positively attached to ceiling runners. Provide an illustration. 7. Toilet room floors shall have a smooth, hard, nonabsorbent surface which extends upward onto the walls at least 5 inches [OSSC, Section 807.1.2]. 8. Underfloor ventilation is required for all underfloor areas. Size of venting shall be computed on 1/150 of the underfloor area [Section 2317.7]. 2 -story Professional Office Bldg. (Shell Only) Building Plan Review PC #: 10-71c BUP #: 96-0567 Page #4 9. Provide weep holes 24° on center and at or slightly above grade in all brick veneer. 10. Roof overflow drains and scuppers shall be designed in accordance with OSSC, Section 1506.3. MECI A'NICAL 1. The heat/ventilation system shall provide outside air per occupant in all portions of the building [UBC Section 1202.2.1 and Table 12 -P]. A. Provide outside air specifications on the revised plans. 2. Each individual roof- mounted HVAC shall be permanently labeled as to the areas it serves [OMSC, Section 304.5]. In addition, each unit shall be equipped with a power disconnect and a 120 -volt receptacle shall be located within 25' of each unit [UMC, Section 309.1]. Please submit three copies of revised submittal documents and a letter indicating your response to the above comments for review. Please call me at (503) 639 -4171 if you have any questions. Sincerely, Ro ert Poskin, CBO PLANS EXAMINER U V RMSYSVOCUMENTIBUP96_05.6TPC 1 0.71 C.DOC