Loading...
Correspondence ..S41 gt. i C11.7 / C I 6 t March 28, 19971 l / r _,�,� i 1, JT Roth, Jr. CITY OF TIGARD 12600 SW 72nd #200 OREGON Tigard, OR 97223 RE: Tenant Improvement Building Plan Review 12570 SW 69th, #200 PC #: 3-76c BUP #: 97 -0140 Occupancy Classification: B Construction Type: 5N Occupant Load: 54 Submittal documents for the above referenced project have been reviewed for conformance with the applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The following comments are noted: ENERCt:COMPUANCE . . ` '- .. , ; - I 1. interior lighting loads shall be calculated on Forms 5a through 5c, Oregon Non - Residential Code, adopted April 1996. Your forms and calculations are from January 1993. I 'ACCESSIB1L17Y •_- - : { .,.. .. .. • _ .. I 1. An amount equal to 25% of the alteration cost shall be budgeted for removal of p, ar itectural barriers within the site and tenant space [ORS 447.241]. u' j 5 A. Barrier removal is determined in accordance with [OSSC, Section 111.3, c f c ORS 447.241 (4). n` B. The barrier removal plan shall include exterior improvements. i) Complete and retum the enclosed form with your response to the items in the plan review letter. The environmental control (thermostat) and lighting controls shall not be located (, forward approach [OSSC, Section floor 1f109.2.3 6] ible side reach approach or 44" for Doors accessible for persons with disabilities shall have an 18" wide maneuvering space adjacent to the latch side of the door [OSSC, Section ( ^ 1109.9.3, Table 11 E]. The following doors do not comply: Office #3, #4, #11, and #13. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 . Tenant Improvement Building Plan Review PC #: 3-76c BUP #: 97 -0140 Page #2 k. FIR ND UFE: SAFETY Provide a rated corridor in accordance with OSSC, Section 1005.7. Revised � drawings shall also include a door schedule. 2. The interior stairwell is considered as part of the corridor system and shall have the same construction standards set out in OSSC, Section 1005.7. If this stairwell exits into an exiting corridor, that corridor shall meet the requirements of OSSC, Section 1005.7, unless the stairwell exits directly to the outside. Please provide details. 3. Provide exit signs in accordance with OSSC, Section 1013.1 and illuminate same in accordance with OSSC, Section 1012.1. 4. Provide Type 2 -A fire extinguishers throughout so that the travel distance to an extinguisher does not exceed 75 feet [UFC Std. 10-1 3.2.1]. 5. All cabinets recessed into fire -rated wall assemblies, such as for portable fire - extinguishers, shall be fire - blocked at the top and bottom and have an additional layer of 5/8" GWB, Type X, between the back of the cabinet and the opposing GWB. Provide a detail in the revised plans. 1. Every page of each set of plans containing drawings and specifications required to be prepared by a State of Oregon licensed engineer must be stamped and signed with the expiration date of that engineer's license written below his or her signature [OAR 820 -10 -620 and ORS 672.020 (2)]. A. One set of revised plans, specifications and engineering shall have a fresh stamp and signature. i. Provide plans and specifications stamped appropriately. 2. Suspended acoustical ceiling systems shall comply with the following: A. Be anchored to resist lateral seismic forces [OSSC, Section 1630.2 and Table 16 -0] and provide suspension wires not smaller than No. 12 gauge spaced at 4" O /C, perimeter wires on terminal ends of cross and main runners at a maximum of 8" from each wall, four No. 12 gauge wires splayed 90 degrees from each other at an angle not exceeding 45 degrees from the plane of the ceiling with a strut centered and extending to the structural members supporting the floor or roof above and spaced 12" on center in both directions starting 6' from each wall; and - Tenant Improvement Building Plan Review PC#: 3-76c BUP #: 97 -0140 Page #3 B. All lighting fixtures weighing Tess than 56 Ibs, shall be positively attached to the suspended ceiling system [UBC Std., Section 25.213]; and C. #12 gauge wires shall be attached to the grid members within 3" of each comer of the fixtures; and D. Lighting fixtures shall have two No. 12 slack wires connected from the fixture to the structure above; and E. Ceiling- mounted air terminals or services weighing Tess than 20 Ibs. shall be positively attached to ceiling runners. i. Provide details in the revised plans. . Toilet rooms shall be provided with an openable exterior window of not less than 3 sq. ft. or a mechanically operated exhaust system capable of exhausting 50 CFM for each water closet or urinal installed [OSSC, Section 1202.2.5]. A. Provide the specifications on the revised plans. . Toilet room floors shall have a smooth, hard, nonabsorbent surface which extends upward onto the walls at least 5" [OSSC, Section 807.1.2]. A. Provide the specifications on the revised plans. ' M E C H A N I C A L . - - . - . ' . , . ', . _ - I 1. Provide an engineer's analysis of each structural member supporting the - additional HVAC units [OSSC, Section 106.3.2]. 2. The attachment of permanent equipment (HVAC) supported by the building's structural components shall be designed to resist the total design seismic forces prescribed in Section 1603.2 of the Structural Specialty Code. Provide an engineer's design specifying attachment requirements [OSSC, Section 106.3.2 and OMSC, Section 304.4]. 3. The heat/ventilation system shall provide outside air per occupant in all portions of the building [OSSC, Section 1202.2.1 and Table 12P]. A. Provide outside air specifications on the revised plans. 4. Each individual roof - mounted HVAC shall be permanently labeled as to the areas it serves [OMSC, Section 305.5]. In addition, each unit shall be equipped with a power disconnect. A 120 -volt receptacle shall be located within 25' of each unit [OMSC, Section 309.1]. Tenant Improvement Building Plan Review PC #: 3-76c BUP #: 97 -0140 Page #4 5. Air moving systems (combination of units), supplying air in access of 2000 CFM to enclosed spaces, shall be equipped with an automatic shut -off. The smoke detectors shall be supervised when a fire detection or alarm system is provided [OMSC, Section 608]. Please submit four copies of revised submittal documents and a letter indicating your response to the above comments for review. Please call me at (503) 639 -4171 if you have any questions. Sincerely, 7 R ert Poskin, CBO PLANS EXAMINER Enclosure T1PN6�7_OI. TC DOC • SUBJECT: ACCESSIBILITY • BARRIER IMPROVEMENT PLAN • REQUIREMENT: OREGON REVISED STATUTE (ORS) 447241. (1) Every project for renovation. alteration or modification to affected buildings and related facdr'hes shad be made to insure that the path of travel to the altered area and the restroom. telephones and drinking fountains are readily able to individuals with disabilities. unless such alterations are disproportionate to the overall alterations at terns of cost and scope (2) Alterations made to the path of travel to an altered area may be deemed disproportionate to the overall alteration when the cost exceeds twenty -1ve per -cent (25%). VALUATION of all renovation, alteration or modification being done excluding painting, wallpapering. ( $ multiply; 25% Barrier removal requirement — .25 BUDGET FOR BARRIER REMOVAL (21 $ • The dollar amount of the BUDGET established on line (2) in the computation above shall be spent providing the accessible elements in the following order. 1- An accessible route connecting the building to accessible pedestrian walkways, and the public way. $ (including but not United to club ramps, detectable warnings. marked crossing& ramps handrails and landings/. 2. Not less than one accessible parking space. $ (including but not famed to adjacent access aisle. signs and cub ramp connecting with the accessible route). 3. Accessible entry or entries. 3 (including but not limited to ramps. handrails. landings. door sill height. door width and door hardware]. 4. An accessible interior route to the altered area. 3 (including but not limited to door -ways. maneuvering clearances. door hardware and stairways]. 5. At least one accessible restroom for each sex. S 6. At least one accessible telephone where public phones are provided. $ 7. When drinking fountains are required, fifty per-cent but not less than one shall be accessible. 5 • 8. Additional accessible elements such as storage, reach ranges. alamu, etc.. $ • TOTAL; shall equal line 2 of Value Computation 5 ilotc4.doc(DST) •