Report Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing, Inc. FAX (503) 68954 Phone
FAX (503) 589 1309
November 4, 1999
99- 2536A.CTI
Permit No. BUP1999 -00234
SHOP INSPECTION REPORT @ Howser
DATES COVERED: October 28, 1999
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th — Tigard, OR
INSPECTOR: J. Svacek, COP#649, WABOSVA520867
10- 28 -99: CTI representative was at the shop of Howser for periodic inspection. Visual inspection of pieces
listed shows shop welds to be complete and acceptable by AWS and detail: beams 14A (4). Weld procedures
and welder qualifications were reviewed.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARL N TESTI , INC
CA!
PRESIDENT
Douglas W. Leach
President
JS /Ijm
cc: Specht Development Inc — Bob Burns
City of Tigard Building Dept
Baugh Construction Co
LRS Architects
VLMK
99- 2536A.fr
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
FAX (503) 684 -0954 FAX (503) 589 -1309
November 8, 1999
99- 2536A.CTI
Permit No. BUP1999 -00234
FIELD INSPECTION REPORT
DATES COVERED: November 4, 1999
PROJECT: TigardCor• • - - -n er - Buildinq B
ADDRESS: 12256
INSPECTOR: R. Baty, COP #728
11- 04 -99: CTI representative inspected the following field welds at second floor and roof level.
1. "Tee" plates per detail 3/S5.3 and RFI dated 10/20/99. Areas in the southeast corner were marked for
insufficient welds.
2. Angle iron per framing detail 4/5.3.
3. East entryway welding of the 1 /4" x 3" fillet per detail 2/S5.2 -were insufficient welding.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING, INC
r - ,
s a ex j,
PRESIDENT
Douglas W. Leach
President
RB:eah
cc: Specht Development Inc - Bob Burns
City of Tigard Building Dept
Baugh Construction Co
LRS Architects ,
VLMK 2 zt - 4 19 S
99- 2536A.fr
Carlson Testing, Inc. Construction In &Related Tests
Geotechnical Consulting
iEPORT O F6X 12 CONCRETE TEST SPECIMENS
P.O. Box 23814
ASTM C172/C1231/C39/C31/C1064/C143 Tigard, Oregon 97281
est Methods: Phone (503) 684 -3460
FAX # 684 -0954
)ate Molded:
11/10 19 99 BUP 1999- 00234
,lob No. 99 -2536A Permit No:
;Bent: SPECHT DEVELOPMENT INC - BOB BURNS
'roject: TIGARD CORPORATE CENTER - BLDG B
address: 12259 SW 69TH TIGARD OR
BAUGH CONSTRUCTION CO
;ontractor: Sub Contractor:
:oncrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 204 Ticket No. V--- 171279
.ast By: C • STASCH Cu. Yds. 11 1 Load No.
S HOWERS 57 49
Neather: Temp. High: Temp. Low:
ROOF MECHANICAL SLAB PADS
_ovation of Placement:
57
Test Time: Concrete Temp:
3500 28 4" 1
Strength Requirement: PSI ® days Slump Cement Type
35108 3/4"
Mix NoJNo. Sacks Air Content Max. Aggregate
Admix. Amount: Brand: Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
rea
No. Days Number Rec'd Test Load PSI No. By
7 1567 11/11 11/17 108,980 28.15 3870 WR
28 1567 11 /11 12/08 157,760 28.25 5580 DM
28 1567 11 /11 12/08 155,780 28.25 5510 DM
28 1567 11 /11 12/08 153,640 28.25 5440 DM
Remarks:
cc: CITY OF TIGARD BUILDING DEPT G I —
BAUGH CONSTRUCTION CO
LRS ARCHITECTS
VLMK •
LABORATORY MANAGER
Reviewed by:
Carlson Testing, Inc. Construction Inspection & Related Tests
Geotechnical Consulting
3EPORT OF 6X 1 2 CONCRETE TEST SPECIMENS P.O. Box 23814
festMethods: AS1 M C172/G1231./C39/G31./C10t,4 /(;143 Pone(03)684- -3460
FAX # 684 -0954
date Molded:
11/10 , 19 99 Job No. 99 -2536A Permit No: BUP 199! - 00234
:lient:
SPFCIII DEVELOPMENT INC - BOB BURNS
'ro]ect: TIGARD CORPORATE CENTER -- BLDG t1
4ddress: 12259 SW 69TH TIGARD OR
13AUGH CONSTRUCTION CO
.3ontractor: Sub Contractor:
Concrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 204 Ticket No. V.- 111.279
Cast By: t-
C. STASCH Cu. Yds. 1 ' 1 Load No)
SHOWERS 57 49
Weather: Temp. High: Temp. Low:
ROOF MECHANICAL SLAB PADS
Location of Placement:
57
Test Time: Concrete Temp:
Strength Requirement: 35010
28 41/
PSI @ days Slump Cement Type
35106 3/4"
Mix NoJNo. Sacks Air Content Max. Aggregate
Admix. Amount: Brand: _ Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
rea
No. Days Number Rec'd Test Load PSI No. By
7 1567 11 /11 11/17 108,980 28.15 3870 WR
28 1567 11/11 12/08
28 1567 11/11 12/08
HOLD 1567 11/11
Remarks:
cc: CITY OF TIGARD BUILDING DEPT /
BAUGH CONSTRUCTION CO /
LRS ARCHITECTS
".'----------.., ,...
VI_MK "
LABORATORY MANAGER
Reviewed by:
. . . . . .. . . . . . . - - --- .,..-- -- ---.._ ...n .. :.�_... _s... ....•1....:�n�an.. f m 1hIC nlfir.A.
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
FAX (503) 684 -0954 FAX (503) 589 -1309
November 12, 1999
99- 2536A. CTI
Permit No. BUP1999 -00234
FIELD INSPECTION REPORT
DATES COVERED: November 9, 1999
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th — Tigard, OR
INSPECTOR: R. Baty, COP #728
11- 09 -99: CTI representative was present onsite to provide special inspection on structural steel welding.
Inspected puddle welds and seam welds on the roof for the HVAC units at grids between A.9- B.5/7.8 -9 and
A.9- B.5/2 -3.3.
Work is in accordance with AWS D1.3 roof sketch dated 9/14/99 and drawings available.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTIN , INC
644 244 ki
PRESIDENT
Douglas W. Leach
President
RB:mbh
cc: Specht Development Inc — Bob Bums
City of Tigard Building Dept
Baugh Construction Co
LRS Architects
VLMK
99- 2536A.fr
G arison Ctrtion Inspection & Testing Inc. Geotechnical Consultin3
tEPORT OF 12 CONCRETE TEST SPECIMENS
P.O. Box 23814
ASTM C172/C1231/C39/C31/C1064/C143 Tigard, Oregon 97281
- est Methods: Phone (503) 684 -3460
FAX # 684 -0954
)ate Molded: 11/15 19 99 BUP1999-00234
Job No. 99 -2536A Permit No:
;Bent: SPECHT DEVELOPMENT INC - BOB BURNS
'roject:
TIGARD CORPORATE CENTER - BLDG B
address:
12259 SW 69TH TIGARD OR
BAUGH CONSTRUCTION CO
:ontractor: Sub Contractor:
:oncrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 208 Ticket No. 721728
:est By: R. A N D R EE Cu. Yds. 8 Load No t
RAIN 54 45
Neather: Temp. High: Temp. Low:
ROOF DECK
_ovation of Placement:
11 :00 65
Test Time: Concrete Temp:
3500 28 5"
Strength Requirement: PSI @ days Slump Cement Type
3510B 3/4"
Mix NoJNo. Sacks Air Content Max. Aggregate
Admix. Amount: Brand: Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
rea
No. Days Number Rec'd Test Load PSI No. By
1 7 1735 11/16 11/22 92,740 28.27 3280 WR
14 1735 11/16 11/29 119,070 28.23 4220 WR
28 1735 11/16 12/13 121,850 28.26 4310 WR
28 1735 11/16 12/13 130,730 28.26 4630 WR
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO /
LRS ARCHITECTS �'
VLMK ., --
LABORATORY MANeetcn
Reviewed by:
Carlson Testing, Inc. Construction Inspection spection & Related Tests
Geotechnical Consulting
REPORT OF 6X 12 CONCRETE TEST SPECIMENS - DEC 011999 P.O. Box 23814
Test Methods: AS TM C172/C1231/C39/C31/C1064/C 143 COMMUNITY DEVELOPMENT Tigard, Oregon 97281
Phone (503) 684 -3460
FAX # 684 -0954
Date Molded: 11/15 , 19 99 Job No. 99 -2536A PermitNo: BUP1999- 00234
Client: SPECHT DEVELOPMENT INC - BOB BURNS
Project: T.I GAR D CORPORATE CENTER - BLDG B
Address: 12259 SW 69TH TIGARD OR
Contractor: BAUGH CONSTRUCTION CO Cub Contractor:
Concrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 208 Ticket No. 721728
Cast By: R . A N D R EE Cu. Yds. 8 Load No. 1
Weather: RAIN g 54 45
Tem p High: Tem p Low:
Location of Placement: ROOF DECK
Test Time: 11 : 00 Concrete Temp: 65
Strength Requirement: 3 500 5 "
PSI @ 28 days Slump Cement Type
3510B 3 / 4 "
Mix NoiNo. Sacks Air Content Max. Aggregate
Admix. Amount: Brand: _ Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
rea
No. Days Number Rec'd Test Load PSI No. By
I 7 1735 11/16 11/22 92,740 28.27 3280 WR
14 1735 11/16 11/2
28 1735 11/16 12/13
28 1735 11/16 12/1.3
•
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
CONSTRUCTION CO
LRS ARCHITECTS
VLMK •
;
BAUGH
z i
LABORATORY MANAGER
Reviewed by:
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
C arlson Testing, Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
�� FAX (503) 684 -0954 FAX (503) 589 -1309
November 16, 1999
99- 2536A. CTI
Permit No. BUP1999 -00234
FIELD INSPECTION REPORT
DATES COVERED: November 15, 1999
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th — Tigard, OR
INSPECTOR: S. Herigstad COP#737
11- 15-99: CTI representative was onsite to inspect rebar for the two mechanical equipment room stem walls on
the roof. The rebar was placed per the approved plans. The concrete was late and this inspector could not stay
for the pour. Another CTI representative cast the cylinders.
Our reports pertain to the material tested/inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
ARLSON TESTING NC
PRESIDENT
Douglas W. Leach
President
SH /Ijm
cc: Specht Development Inc — Bob Burns
City of Tigard Building Dept
Baugh Construction Co
LRS Architects
VLMK
99- 2536A.fr
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
C arlson Testing, Inc. FAX (503) 68 0954 FAX (503) 5891 309
November 17, 1999
99- 2536A.CTI
Permit No. BUP1999 -00234
FIELD INSPECTION REPORT
DATES COVERED: November 10, 1999
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th — Tigard, OR
INSPECTOR: C. Stasch, COP #485
11- 10 -99: CTI representative was present at the jobsite and inspected 3500 psi concrete mix #3510B from
Ross Island placed in roof mechanical slab pad. All reinforcing was checked prior to placement of concrete
and it conformed to plans. All concrete was pumped and vibrated. One set of (4) concrete test cylinders was
made.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submi d,
ARLS TESTIN r, INC I
PRESIDENT
Douglas W. Leach
President
CS:eah
cc: Specht Development Inc — Bob Burns
City of Tigard Building Dept
Baugh Construction Co
LRS Architects
VLMK
99- 2536A.fr
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
FAX (503) 684 -0954 FAX (503) 589 -1309
ROOFING FIELD REPORT
JOB #: 99 -2536A INSPECTOR: D. Boone DATE: 11 - 17 - 99
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th, Tigard, OR
PERMIT #: BUP1999 -00234 GENERAL CONTRACTOR: Baugh Construction
INSPECTOR'S TIME IN: IOUT: CREW'S TIME IN: I OUT:
WEATHER: Overcast TEMPERATURE: °AM 58° PM
ASPHALT TYPE: Type III EVT: ° AM 490 PM
ROOFING SPECIFICATION # Malarky Glassply #500
BASE FLASHING TYPE AND /OR #
INSULATION TYPE: Manville .
BOTTOM: 2.5 Poly Iso "R" VALUE 18.2 SIZE: 4x8
TOP: %" Retro "R" VALUE 1.32 SIZE: 4x8
TOTAL 19.52
WORK AREA (USE GRID LINES AND /OR DIMENSIONS): 1- 10 /B.5 -C I SQUARES:
ITEM I CONFORMANCE 1 NON-CONFORMANCE I YES I NO
VAPOR B ARRIER CUT -OFFS INSTALLED
BASE SHEET DEBRIS CLEANED X
INSULATION X MATERIAL COVERED X
INTERPLYS X PENETRATIONS SEALED X
BALLASTS
BASE FLASHING
COUNTER FLASHING
WORK DESCRIPTION: Insulation installed per manufacturer's specifications with 5" hex screws with 3" round plastic
plates, (8) per 4x8 sheet. Retro board was installed per specifications with Type III asphalt. Interplys were installed per
specifications with Type III asphalt in a 3-ply manner. All work com "es with builders prints -` d specifications.
1
INSPECTOR D. Boone REVIEWED BY ki • •
Do glaresident
DB /Ijm
cc: Specht Development, Inc. — Bob Bums
City of Tigard Building Department
Baugh Construction Co.
LRS Architects
VLMK
Carlson Testing, Construction Inspection & Related Tests
ng, Inc. Geotechnical Consulting
3EPORT OF 12 CONCRETE TEST SPECIMENS P.O. Box 23814
Tigard, Oregon 97281
rest Methods: ASTM C172/C1231/C39/C31/C1064/C143 Phone (503) 684 -3460
FAX # 684 -0954
Date Molded: 11/18 , 19 99 Job No. 99 -2536 Permit No: BUP 1999 -00234
:liens: — SPECHT DEVELOPMENT INC - BOB BURNS
'roject: TIGARD CORPORATF CFNTER - RI DG B
Address: 12259 SW 69TH TIGARD OR
:.ontractor: BAUGH CONSTRUCTION CO Sub Contractor:
:oncrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 212 Ticket No. V- 172139
Oast By: 3. HALL Cu. Yds. 1 26 OF 148 Load No. 1 2
Weather: OVERCAST Temp. High: 46 36
Temp. Low:
Location of Placement: GARAGE RETAINING WALL FOOTING NORTH OF GARAGE
Test Time: 1 : 05 Concrete Temp: 62
Strength Requirement:
3000 PSI ® 28 4" days Slump Cement Type & I I
Mix NoJNo. Sacks 3010B Air Content Max. Aggregate
Admix. Amount: Brand: _ Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
No. Days Number Rec'd Test Load PSI No. By
II 7 1890 11/19 11/25 91,680 28.27 3240 WR
28 1890 11/19 12/16
28 1890 11/19 12/16 ,
HOLD 1890 11/19
Remarks:
RECEIVED ".,<....,....._
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION Co DEC 011999
LRS ARCHITECTS
VLMK ,-k
COMMUNITY DEVELOPMENT
Reviewed by: LABORATORY MANAGER
. . . .. . . .. . . ..... _ __ __�..__a .,.......•• I.. &ai ...Oh...4 win. at4hnrhafinn fmm this office.
Carlson Testing, Inc. Construction Inspection & Related Tests
Geotechnical Consulting
REPORT OF6X 12 CONCRETE TEST SPECIMENS P.O. Box 23814
Tigard, Oregon 97281
Test Methods: AS_IM C179/C1231/C39/C31/C1064/C143 Phone(503)684 - 3460
FAX # 684 -0954
Date Molded: 11/18 , 19 99 Job No. 99 - 2536A Permit No: BUP 1999 - 00234
client: C PECHT DEVELOPMENT TN(' - ROR RURNS
roject: TIGARD CORPORATE CFNTFR — RI DG B
Address: 12259 SW 69TH TIGARD OR
;,ontractor: BAUGH CONSTRUCTION CO Sub Contractor:
Concrete Supplier: ROSS I SI AND SAND & GRAVEL Truck No. 204 Ticket No. T- 172047
Cast By: T . HAI L Cu. Yds. 33 OF 148 Load No.
Weather: OVERCAST Temp. High: 46 Temp. Low: 36
Location of Placement: 30 ' NORTH OF SOUTH END . TEST AT V DECK SLAB A 1 TO 4 AND
C 1 TO 5.5
Test Time: 9 : 00 C oncrete Temp: 68
Strength Requirement: 3500 PSI @ 28 days Slump 4 1/2"
Cement Type' & I I
Mix NoJNo. Sacks 3510B Air Content Max. Aggregate
Admix. Amount: 1 X Brand: NC534 Admix. Amount: BranctiOT WATER
Set Test@ Register Date Date Total Area Unit Report Tested
No. Days Number Rec'd Test Load PSI No. By
I 7 1889 11/19 11/25 117,620 28.14 4180 WR
28 1889 11/19 12/16
28 1889 11/19 12 /1E
HOLD 1889 11/19 .
Remarks:
cc: CITY OF TIGARD BUILDING DEPT RECEIVED jY
BAUGH CONSTRUCTION CO
LRS ARCHITECTS DEC 011999
VLMK
COMMUNITY DEVELOPMENT LA BO R AT
•
Reviewed by
Carlson Testing, Inc. Construction Inspection & Related Tests
Geotechnical Consulting
lEPORT OF6X 12 CONCRETE TEST SPECIMENS
P.O. Box 23814
ASTM C172/C1231/C39/C31/C1064/C143 Tigard, Oregon 97281
est Methods: Phone (503) 684 -3460
FAX # 684 -0954
)ate Molded:
11/18 , 19 99 ,lob No. 99 -2536A permit No: BUP1999-00234
;liens: SPECHT DEVELOPMENT INC - BOB BURNS
'roject: TIGARD CORPORATE CENTER - BLDG 8
address: 12259 SW 69TH TIGARD OR
:ontractor: BAUGH CONSTRUCTION CO Sub Contractor:
oncrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 212 Ticket No. V- 172139
J.HALL 126 OF 148
:ast By: Cu. Yds. Load No 1
OVERCAST 46 36
Neather: Temp. High: Temp. Low:
GARAGE RETAINING WALL FOOTING NORTH OF GARAGE
_ovation of Placement:
1 :05 62
Test Time Concrete Temp:
3000 28 4" I & II
Strength Requirement: PSI @ days Slump Cement Type
3010B
Mix NoJNo. Sacks Air Content Max. Aggregate
Admix. Amount: Brand: — Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
rea
No. Days Number Rec'd Test Load PSI No. By
II 7 1890 11/19 11/25 91,680 28.27 3240 WR
28 1890 11/19 12/16 147,850 28.19 5240 WR
28 A 1890 11/19 12/16 141,870 28.19 5030 WR
28 1890 11/19 12/16 143,800 28.19 5100 WR
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO
LRS ARCHITECTS v
VLMK .
Reviewed by: LABORATORY MAMA(?
/,
Carlson Testi Construction Inspection & Related Tests
ng , Inc. Geotechnical consulting
lEPORT OF6X 12 CONCRETE TEST SPECIMENS
P.O. Box 23814
A STM C172/C1231/C39/C31/C10641'd143 h 03)68 97281
'est Methods: Phone (503) 684 --3460
FAX # 684 -0954
)ate Molded: 11/18 , 19 99 Job No. 99 -2536A Permit No: BUP1999-00234
;Bent: SPECHT DEVELOPMENT INC - BOB BURNS
'roject: TIGARD CORPORATE CENTER - BLDG B
address: 12259 SW 69TH TIGARD OR
;ontractor: BAUGH CONSTRUCTION CO Sub Contractor:
oncrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 204 Ticket No. T-172047
3ast By: J
J . HALL Cu. Yds. 33 OF 148 Load NO
OVERCAST 46 36
Neather: Temp. High: Temp. Low:
30' NORTH OF SOUTH END. TEST AT V DECK SLAB A 1 TO 4 AND
_ovation of Placement:
C 1 TO 5.5
9 :00 68
Test Time: Concrete Temp:
3 5 0 0 p S l @ 28 days Slump 1/2" Cement Type
& I I
Strength Requirement:
3510B
Mix NoJNo. Sacks Air Content Max. Aggregate
1/ N C5 34 n OT WATER
Admix. Amount: Brand: Amount: — A dmix. B ran
Set Test@ Register Date Date Total Area Unit Report Tested
No. Days Number Rec'd Test Load PSI No. By
I 7 1889 11/19 11/25 117,620 28.14 4180 WR
28 1889 11/19 12/16 141,800 28.26 5020 WR
28 1889 11/19 12/16 143,700 28.26 5080 WR
28 1889 11/19 12/16 151,260 28.26 5350 WR
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO
LRS ARCHITECTS 7 '
VLMK
Reviewed by: LABORATORY MANAGER • . . .. . .. . _- ___._.._.. -- -..:.. e........ I. .n... A r in fall wi$hn.d mint aldhnrlsatinn from this office.
• Construction Inspection & Related Tests
Carlson Testing, Inc. Geotechnical Consulting
3EPORT OF 6X12 CONCRETE TEST SPECIMENS P.O. Box 23814
Tigard, Oregon 97281
est Methods: ASTM C172/C1231/C39/C31/C1064/C143 Phone (503) 684 -3460
FAX # 684 -0954
)ate Molded: 11/19 , 19 99 Job No. 99 -2536A Permit No: BUP1999 -00234
;Iient: SPFCHT IlFVFI OPMFNT INC - ROB RIIRNS
'roject: TIGARD CORPORATF CFNTFR - RI DG 6
'ddress: - 12259 SW 69TH TIGARD OR
:ontractor: BAUGH CONSTRUCTION CO_ Sub Contractor:
:oncrete Supplier: ROSS ISLAND SAN[) & GRAVEL Truck No. 208 Ticket No. V- 172241
:ast By: J . HALL Cu. Yds. 44 OF 106 Load No. 4
Neather: OVERCAST Temp. High: 46 Temp. Low: 36
ovation of Placement: 25' SOUTH OF NORTH END . TEST AT V DECK SLAB A 7 TO 10 AND
C 5.5 TO 10.
Test Time: 8: 4 0 Concrete Temp: 68
3 500 PSI 28 4 1/4"
Strength Requirement: days Slump Cement Type I& 11
Mix NoJNo. Sacks 3510E Air Content - Max. Aggregate
Admix. Amount: 1 X Brand: NC534 Admix. Amount: BrandHOT WATER
Set Test@ Register Date Date Total Area Unit Report Tested
rea
No. Days Number Rec'd Test Load PSI No. By
1 7 1901 , 11/20 11/21. 127,540 28.18 4530 WR
28 1901 11/20 12/17
28 1901 11/20, 12/1 .
HOLD 1901 11/20
. _
Remits: RECEIVED
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO DEC 01 1999 i
LRS ARCHITECTS "'il
VLMK COMMUNITY DEVELOPMENT
LABORATORY MANAGER
Reviewed by: • . _ --- `--- ,„ ......„ .. n.n A.. n.l • in ti n wlrhnud minr aidhnrlsafinn from this o}flce.
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing, Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
FAX (503) 684 -0954 FAX (503) 589 -1309
November 19, 1999
99- 2536A. CTI
Permit No. BUP1999 -00234
FIELD INSPECTION REPORT
DATES COVERED: November 18, 1999
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th — Tigard, OR
INSPECTOR: D. Boone
11- 18 -99: CTI representative was onsite for a periodic roofing inspection. 2.5" Poly Iso insulation was installed per
specifications with 5" hex head screws and 3" round plastic plates. ' /Z" Retro board was installed per specifications
with Type III asphalt. Malarky #500 ply sheet was installed per specifications with Type III asphalt in a three ply
manner. All work complies with builders prints and specifications. 2.5" Poly Iso R value is 18.2. ' /s" retro value =
1.32. Total 19.52. Grid locations are: 1- 10 /A -A.5 and 1- 10 /B.5 -C.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
1 CAR ON TES G, IN j
ne mp =Nx
Douglas W. Leach
President
DB /Ijm
cc: Specht Development Inc — Bob Burns
City of Tigard Building Dept
Baugh Construction Co
LRS Architects
VLMK
99- 2536A.fr
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing, Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
�� FAX (503) 684 -0954 FAX (503) 589 -1309
November 19, 1999
99- 2536A. CTI
Permit No. BUP1999 -00234
FIELD INSPECTION REPORT
DATES COVERED: November 15, 1999
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th — Tigard, OR
INSPECTOR: R. Baty, COP #728
11- 15-99: CTI representative was onsite and visited the jobsite to inspect roof puddle welds, Hilti pins and seam
welding. Work is in accordance with AWS D1.3, roof sketch dated September 14, 1999 and drawings.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTI , INC
k.•
PRESIDENT
Douglas W. Leach
President
RB:eah
cc: Specht Development Inc — Bob Burns
City of Tigard Building Dept
Baugh Construction Co
LRS Architects
VLMK
99- 2536A.fr
Carlson Testing, onstruction Inspection & Related Tests
ng, Inc. Inc . Geotechnical Consultin3
3EPORT OF6X 12 CONCRETE TEST SPECIMENS
P.O. Box 23814
Tigard, Oregon 97281
'estMethods: ASTM C172/C1231/C39/C31/C1064/C143 Phone(503)684 - 3460
FAX # 684 -0954
)ate Molded: 11/19 ,19 99 Job No. 99-2536 permit No: BUP1999 - 00234
;tient: SPECHT DEVELOPMENT INC - BOB BURNS
'roject: TIGARD CORPORATE CENTER - BLDG B
lddress: 12259 SW 69TH TIGARD OR
;ontractor: BAUGH CONSTRUCTION CO Sub Contractor:
:oncrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 208 Ticket No. V - 172241
:ast By: J
J. HALL Cu. Yds. 44 OF 106 Load No4
OVERCAST 46 36
Neather: Temp. High: Temp. Low:
25' SOUTH OF NORTH END. TEST AT V DECK SLAB A 7 TO 10 AND
_ocation of Placement:
C 5.5 TO 10.
Test Time: 8: 40 Concrete Temp: 68
3 500 PSI @ 28 days Slump 1/4" Cement Type
& II
um
Strength Requirement: y p yp
351 0 B
Mix NoJNo. Sacks Air Content Max. Aggregate
7 . A dmix. Amount: Bran O WATER
Admix. Amount: 1 Brand: N C534 _
Set Test@ Register Date Date Total Area Unit Report Tested
No. Days Number Rec'd Test Load PSI No. By
1 7 1901 11/20 11/26 127,540 28.18 4530 WR
28 1901 11/20 12/17 159,220 28.26 5630 DM
28 1901 11/20 12/17 159,920 28.26 5660 DM
28 1901 11/20 12/17 151,280 28.26 5350 DM
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO
d/ o/ / / . / ;e 1-----
LRS ARCHITECTS s'
VLMK
Reviewed by : LABORATORY MANAGER
. . ... . .- `-• - __.... ...:.. :............ ..... e.i • in boll withn:d nrinr Al ohnrization from this office.
Construction Inspection & Related Tests
Jarlson Testi ng, Inc. Geotechnical Consulting
EPORT OF 6X 12 CONCRETE TEST SPECIMENS P.O. Box 23814
Tigard, Oregon 97281
estMethods: ASTM C172/C1231/C39/C31/C1064/C143 Phone(503)684 -3460
FAX # 684 -0954
ate Molded: 11/22 1 9 99 ,l ob No. 99 Permit No: BUP 1999 -00234
dent: SPECHT DEVELOPMENT INC - BOB BURNS
roject: TIGARD CORPORATE CENTER - BLDG B
ddress: 12259 SW 69TH TIGARD OR
:ontractor: BAUGH CONSTRUCTION CO Sub Contractor:
:oncrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 208 Ticket No. T
:ast By:
D. V I C K Cu. Yds. 22 OF 108 Load No. 2
SHOWER S 52 High: 52 4 8
Temp. Low:
Veather:
Q DECK BETWEEN 10 AND 7 A TO C, 7 TO 5.5 B TO C. TEST AT Q
.oration of Placement:
DECK 2 FLOOR BETWEEN 10 AND 9 A AND C.
Test Time: 8 Concrete Temp: 74
3500 PSI 28 days Slump 5 Cement Type' & I I
Strength Requirement:
35108 A
Air NoJNo. Sacks ir Content Max. Aggregate
ly. NC534 Admix Amount: BrandHOT WATER
>dmix. Amount: Brand: _
Set Test@ Register Date Date Total Area Unit Report Tested
No. Days Number Rec'd Test Load PSI No. By
7 1974 11/23 11/29 97,890 ,28.27 3460 WR
28 1974 11/23 12/20
28 1974 11/23 12/2C
HOLD 1974 11/23
Remarks:
cc: CITY OF TIGARD BUILDING DEPT G
BAUGH CONSTRUCTION CO ■�,
LRS ARCHITECTS *40A
VLMK
LABORATORY MANAGER
Reviewed by;
Carlson Testing Inc. Construction Inspection & Related Tests
Geotechnical Consulting
1EPORT OF6X 12 CONCRETE TEST SPECIMENS
P.O. Box 23814
A STM C172/C1231/C39/C31/C1064/C143 h 03) Oregon 8 - 346
"est Methods: Phone (503) 684 -3460 0
FAX # 684 -0954
)ate Molded: 11/22 , 19 99 ,lob No. 99 - 2536A Permit No: BUP 1999 - 00234
;tient: SI'ECHT DEVELOPMENT INC — BOB BURNS
'roject: TIGARD CORPORATE CENTER — BLDG B
lddress: 12259 SW 69TH TIGARD OR
:ontractor: BAUGH CONSTRUCTION CO Sub Contractor:
oncrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 208 Ticket No. T-172347
'.ast By: D. V I C K Cu. Yds. 22 OF 108 Load No?
S HOWERS Tem High: 52 Temp. Low: 48
Neather: Temp. g
ovation of Placement: Q DECK BETWEEN 10 AND 7 A TO C, 7 TO 5.5 B TO C. TEST AT Q
DECK 2 FLOOR BETWEEN 10 AND 9 A AND C.
Test Time: 8 : 20 Concrete Temp: 74
3 500 PSI @ 28 days Slump Cement Type
& I I
Strength Requirement: Y p
3510B Air Content Max. Aggregate
Mix NoJNo. Sacks gg ate g
N C534 HOT WATER
Admix. Amount: 1 Brand: Admix. Amount: Bran : _
Set Test@ Register Date Date Total A Unit Report Tested
rea
No. Days Number Rec'd Test Load PSI No. By
7 1974 11/23 11/29 97,890 28.27 3460 WR
28 1974 11/23 12/20 109,920 28.28 3790 DM
28 1974 11/23 12/20 103,980 28.28 3680 DM
28 1974 11/23 12/20 106,220 28.28 3760 DM
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO
LRS ARCHITECTS
iz
VLMK
LABORATORY MANAGER
Reviewed by:
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing, Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
b FAX (503) 684 -0954 FAX (503) 589 -1309
ROOFING FIELD REPORT
JOB #: 99 -2536A INSPECTOR: D. Boone DATE: 11 -23 -99
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th, Tigard, OR
PERMIT #: BUP1999 -00234 GENERAL CONTRACTOR: Baugh Construction
INSPECTOR'S TIME IN: OUT: CREWS TIME IN: OUT:
WEATHER: Overcast with sprinkles TEMPERATURE: °AM 52° PM
ASPHALT TYPE: Type 111 EVT: ° AM PM
ROOFING SPECIFICATION # Malarky Glassply IV #500
BASE FLASHING TYPE AND /OR #
INSULATION TYPE: Manville
BOTTOM: 2.5 Poly Iso "R" VALUE 18.2 SIZE: 4x8
TOP: ' /z' Retro "R" VALUE 1.32 SIZE: 4x8
TOTAL 19.52
WORK AREA (USE GRID LINES AND /OR DIMENSIONS): B.5- C/1 -10 I SQUARES: (40) approx.
ITEM 1 CONFORMANCE 1 NON - CONFORMANCE 1 ITEM I YES I NO
VAPOR BARRIER CUT -OFFS INSTALLED X
BASE SHEET DEBRIS CLEANED X
INSULATION X MATERIAL COVERED X
INTERPLYS X PENETRATIONS SEALED X
BALLASTS
BASE FLASHING
COUNTER FLASHING
WORK DESCRIPTION: Insulation installed per specifications with 5" Hex head screws with 3" round plastic plates. Retro
board installed per specifications with type III asphalt. Interplvs inst d per specifications w h type III asphalt in a 3 -ply
manner. All work complies with builders prints and specifications.
b
INSPECTOR D. Boone REVIEWED BY PRESIDENT
Douglas W. Leach - President
DB /Ijm
cc: Specht Development, Inc. — Bob Burns
City of Tigard Building Department
Baugh Construction Co. RECEIVED
LRS Architects
VLMK DEC 011999
COMMUNITY DEVELOPMENT
Construction Inspection & Related Tests
-1a rlson Testing Inc. Geotechnical Consultin3
EPORT OF
6X12 CONCRETE TEST SPECIMENS P.O. Box 23814
Tigard, Oregon 97281
est Methods: ASTM C172/C1231/C39/C31/C1064 Phone (503) 684 -3460
FAX # 684 -0954
ate Molded:
11/23 19 99 Job No. 99 -2536A Permit No: BUP1999-00234
Bent: SPECHT DEVELOPMENT INC - BOB BURNS
ro)ect: TIGARD CORPORATE CENTER - BLDG B
.ddress:
12259 SW 69TH TIGARD OR
BAUGH CONSTRUCTION CO
:ontractor: Sub Contractor:
oncrete supplier: ROSS ISLAND SAND & GRAVEL Truck No. 209 Ticket No. T-172507
B.PERRY PERRY 11 -108 -137
;ast By: Cu. Yds. Load No. 10
RAIN Temp. High: 54 45
Temp. Low:
\leather:
2ND LEVEL SLAB B -C/5 -6
.ocation of Placement:
Test Time: Concrete Temp: 67
3500 PSI ® 28
Strength Requirement: days Slump Cement Type I & I I
35108 Max.Aggregate
3/4"
Aix NoJNo. Sacks Air Content
Admix. Amount: Brand: _ Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
No. Days Number Rec'd Test Load PSI No. By
II 7 2017 11/24 11/3( 123,070 28.27 4350 WR
28 2017 11/24 12/21 ,
28 2017 11/24 12/21 ,
,
HOLD 2017 11/24 ,
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO � '
LRS ARCHITECTS
VLMK
LABORATORY MANAGER
Reviewed by:
Construction Inspection & Related Tests
Carlson Testing, Inc. Geotechnical Consulting
EPORT OF
6X12 CONCRETE TEST SPECIMENS
P.O. Box 23814
ASTM C172/C1231/C39/C31/C1064/C143 Tigard, Oregon 97281
est Methods: Phone (503) 684 -3460
FAX # 684 -0954
11/23 19 99 Job No. 99 -2536A Permit No: BUP1999-00234
)ate Molded:
aient:
SPECHT DEVELOPMENT INC — BOB BURNS
TIGARD CORPORATE CENTER — BLDG B
.roject:
12259 SW 69TH TIGARD OR
address:
BAUGH CONSTRUCTION CO
:ontractor: Sub Contractor:
:oncrete Supplier:
ROSS ISLAND SAND & GRAVEL Truck No. 208 Ticket No. T- 172405
B .PERRY Cu. Yds. 11 -•33 -140 Load No. 3
:ast By:
RAIN
Weather: Temp. High: 54 45
Temp. Low:
BUILDING 8 2ND LEVEL SLAB 8 -9 /B —C
.ovation of Placement:
8:45 71
Test Time: Concrete Temp:
3500 28 4 1/2" I & II
Strength Requirement:
PSI ® days Slump Cement Type
3510B 3/4
Aix NoJNo. Sacks Air Content Max. Aggregate
Admix. Amount: 17. Brand: NC534 Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
No. Days Number Rec'd Test Load PSI No. By
I 7 2016 11/24 11/3( 107,260 28.27 3790 WR
28 2016 11/24 12/21
28 2016 11/24 12/21
HOLD 2016 11/24
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO
LRS ARCHITECTS 7 VLMK t
Reviewed by: LABORATORY MANAr.FR
Carlson Testing, Construction Inspection & Related Tests
ng, Inc. Geotechnical Consulting
;EPORT OF6X 12 CONCRETE TEST SPECIMENS
P.O. Box 23814
estMethods: ASTM C172/C1231/C39/C31/C1064 Tigard, Oregon 97281 Phone(503)684 -3460
FAX # 684 -0954
)ate Molded: 11/23 19 99 Job No. 99 - 2536A Permit No: BUP1999
;Bent: SPECHT DEVELOPMENT INC - BOB BURNS
'roject: TIGARD CORPORATE CENTER - BLDG B
address: 12259 SW 69TH TIGARD OR
;ontractor: BAUGH CONSTRUCTION CO Sub Contractor:
oncrete supplier: ROSS ISLAND SAND & GRAVEL Truck No. 209 Ticket No. T- 172507
:ast By:
B .PERRY Cu. Yds. 11 -108 -137 Load No.
RAIN 54 4
Neather: Temp. High: Temp. Low:
2ND LEVEL SLAB B -C/5 -6
:_ovation of Placement:
Test Time: Concrete Temp:
67
3500 28 ® 2 8 days Slump Cement Typ & I I
Strength Requirement:
3510B 3/4
Mix NoJNo. Sacks Air Content Max. Aggregate
Admix. Amount: Brand: _ Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
rea
No. Days Number Rec'd Test Load PSI No. By
II 7 2017 11/24 11/30 123,070 28.27 4350 WR
28 2017 11/24 12/21 139,200 28.26 4930 DM
28 2017 11/24 12/21 140,220 28.26 4960 DM
_ I
28 2017 11/24 12/21 139,880 28.26 4950 DM
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO /
LRS ARCHITECTS v
VLMK
Reviewed by: LABORATORY MANAGEr*
.. . . .. ..... ...:.�_... _: . _..•• s. •i .. fmm $htc of na.
Carlson Testing, Construction Inspection & Related Tests
ng, Inc. Geotechnical Consulting
3EPORT OF6X 12 CONCRETE TEST SPECIMENS
P.O. Box 23814
rest Methods: ASTM C172/C1231/C39/C31/C1064/C143 Tigard, Oregon 97281 Phone(503)684 -3460
FAX # 684 -0954
)ate Molded: 11/23 ,19 99 ,lob No. 9 Permit No: BUP 1999 -00234
;liens: SPECHT DEVELOPMENT INC - BOB BURNS
project: TIGARD CORPORATE CENTER - BLDG B
>ddress: 12259 SW 69TH TIGARD OR
,ontractor: BAUGH CONSTRUCTION CO Sub Contractor:
3oncrete Supplier: ROSS ISLAND SAND & GRAVEL Truck No. 208 Ticket No. T- 172405
mast By: B .PERRY Cu. Yds. 11-.33-140 Load No:
RAIN
45
Weather: Temp. High: 54 Temp. Low:
Location otPlacement: BUILDING B 2ND LEVEL SLAB 8 -9 /B -C
Test Time: 8 : 45 Concrete Temp: 71
3500 Psl 28 days Slump Cement 1/2" CementTyp & II
Strength Requirement:
35106
3 / 4
Mix No/No. Sacks Air Content M ax. Aggregate
17.
Admix. Amount: Brand NC534 Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
rea
No. Days Number Rec'd Test Load PSI No. By
1 7 2016 11/24 11/30 107,260 28.27 3790 WR
28 2016 11/24 12/21 117,460 28.26 4160 DM
28 2016 11/24 12/21 119,720 28.26 4240 DM
28 2016 11/24 12/21 118,040 28.26 4180 DM
•
Remarks:
cc: CITY OF TIGARD BUILDING DEPT
BAUGH CONSTRUCTION CO
LRS ARCHITECTS '
VLMK .:;-- .• -4:.:. .
LABORATORY MANA•Frr
Reviewed by:
- - ' ---- ..__� _..__�• . t..:: ...:, .., ..i .....N.n.(��t n fmm thlc nff .A.
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing, Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
FAX (503) 684 -0954 FAX (503) 589 -1309
November 24, 1999
99- 2536A. CTI
Permit No. BUP1999 -00234 RECEIVED
FIELD INSPECTION REPORT DEC = 01 1999
DATES COVERED: November 19, 1999 COMMUNITY DEVELOPMENT
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th — Tigard, OR
INSPECTOR: R. Baty, COP #728
11- 19 -99: CTI representative visited the jobsite to inspect puddle welding and crimping, second floor between
grids 7 & 10 /A & C. All was acceptable except around landing without deck opening between 8.4 & 9.4/A.7 & B.
Returned at noon to inspect the landing without deck opening as requested. Found that it was still not ready.
Inspected welding of #5 A -706 rebar between girders on second floor between 1 & 10 /A -C. A total of (34) rebars
with a weld length of 6 %" to 7 1 /z' long were welded. Inspected puddle welding and crimping at second floor
between B -C/6 -7 and B.4- C/5.5 -6. Reinspected the above landing without decking opening between 8.4 & 9.4/A.7
& B and found the welding is acceptable. Work is in accordance with AWS and drawings available.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTIN , INC
PRESIDENT
Douglas W. Leach
President
RB:eah
cc: Specht Development Inc — Bob Burns
City of Tigard Building Dept
Baugh Construction Co
LRS Architects
VLMK
99- 2536A.fr
4►
Main Office Branch Office
; %• P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
FAX (503) 684 -0954 FAX (503) 589 -1309
November 29, 1999 RECEIVED
99- 2536A.CTI
Permit No. BUP1999 -00234
DEC 01 1999
FIELD INSPECTION REPORT COMMUNITY DEVELOPMENT
DATES COVERED: November 15, 18, 19, and 22, 1999
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th — Tigard, OR
INSPECTOR: R. Andree /J. Hall, COP#735 /D. Vick, COP #722 /P. L. Sanetra, COP #737
11- 15 -99: CTI representative, R. Andree, was onsite for an inspection of concrete. Cast one set of (4) cylinders off
of first truck. Slump was 5" and temperature was 65 °. 3500 mix with 3/4' aggregate.
11- 18 -99: CTI representative, J. Hall, was onsite and conducted a rebar placement inspection on second floor V
deck slab A/1-4, C/1 -5.5, and garage retaining wall footing north of garage. All of the rebar was in place and
conforms to the plan details as provided by the general contractor. Two sets of (4) concrete test cylinders were
cast. Slump and temperature tests were conducted with the test cylinders. Ross Island Sand and Gravel was the
ready mix concrete supplier. A 3 /4" aggregate 3500 psi concrete mix design #3510 with 1% NC534 accelerator
admixture and hot mixing water added was placed on the V -deck slab and a 3 /4" aggregate 3000 psi mix design
#3010B was the concrete mix design placed on the retaining wall footing. A concrete pump truck was used for
placement of the concrete and a mechanical vibrator was used for consolidation. A total of (148) cubic yards of
concrete were placed at this time. The general contractor Baugh Construction Co. was advised of the
concrete test results.
11- 19 -99: CTI representative, J. Hall, was onsite and conducted a rebar placement inspection on second floor V
deck slab at lines A/7 -10 and C/5.5 -10. All of the rebar was in place and conforms to the approved plans as
provided by the general contractor. One set of (4) concrete test cylinders was cast. Slump and temperature tests
were conducted with the test cylinders. Ross Island Sand and Gavel was the ready mix concrete supplier. A %"
aggregate 3500 psi mix design #3510B with 1% NC234 accelerator admixture added and hot mixing water was
the concrete mix placed. A concrete pump truck was used for placement and a mechanical vibrator was used for
consolidation of the concrete. A total of (106) cubic yards of concrete were placed at this time. The general
contractor Baugh Construction Co. was advised of the concrete test results.
11- 22 -99: CTI representative, D. Vick, was onsite and inspected rebar in Q-deck second floor building B between
A- C/10 -7 and B & C/7 & 5.5. A 3500 psi concrete mix #3510B was placed by pump and manually rodded.
Approximately (108) yards were placed. Performed slump, temperature test, and cast one set of (4) 6x12
samples. Rebar, placement, and concrete were in compliance with project plans and specifications.
99- 2536A.fr
•
November 29, 1999
99- 2536A. CTI
Page 2 of 2
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTI , INC
(
PRESIDENT
Douglas W. Leach
President
RA/JH /DV /Ijm
cc: Specht Development Inc — Bob Burns
City of Tigard Building Dept
Baugh Construction Co
LRS Architects
VLMK
99- 2536A.fr
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
Carlson Testing Inc. Phone (503) 684 -3460 Phone (503) 589 -1252
FAX (503) 684 -0954 FAX (503) 589 -1309
November 29, 1999
99- 2536A.CTI
Permit No. BUP1999 -00234
FIELD INSPECTION REPORT
DATES COVERED: November 22, 1999
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th — Tigard, OR
INSPECTOR: B. Baty COP#728
11- 22 -99: CTI representative was onsite and inspected puddle welding and crimping, second floor. There were
some areas missed and shown to the welder to fix. The areas were fixed and re- inspection was done. All of the
second floor was found to be in accordance with AWS and drawings available.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced,
except in full, without prior authorization from this office.
•
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
RLSON TESTING, i' C
Gu
PRESIDENT
Douglas W. Leach
President
BB /Ijm
cc: Specht Development Inc — Bob Burns
City of Tigard Building Dept
Baugh Construction Co
LRS Architects
VLMK
RECEIVED
DEC 011999
COMMUNITY DEVELOPMENT
99- 2536A.fr
Construction In & Related Tests
C arlson Testing, Inc. Geotechnical Consulting
P.O. Box 23814
Tigard, Oregon 97281
Phone (503) 684 -3460
FAX (503) 684 -0954
November 29, 1999
99- 2536A.CTI
PERMIT NO. BUP1999 -00234
FIELD INSPECTION REPORT
DATE COVERED: November 23, 1999
PROJECT: Tigard Corporate Center — Bldg. B
ADDRESS: 12259 SW 69' — Tigard, OR
INSPECTOR: B. Perry, COP #741, ICBO #72934
11- 23 -99: A CTI representative was present on site to perform continuous special inspection of
reinforced concrete. This inspector examined the reinforcing steel for the second level slab at grid
lines A- C/4 -10 and observed the placement of (137) cubic yards of Ross Bros. #351013 approved
mix concrete placed by boom pump into the above noted locations. Two sets of (4) cylinders were
cast and tested for slump and temperature.
Work observed this date conforms to project plans, details and specifications.
Our report pertains to the material tested /inspected only. Information contained herein is not to be
reproduced, except in full, without prior authorization from this office.
•
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING, INC.
__ t W. Leach
firieReh Manager
BP /tm
cc: Specht Development Inc. — Bob Burns
City of Tigard Building Dept.
Baugh Construction Co.
LRS Architects
VLMK
Main Office Branch Office
P.O. Box 23814 4060 Hudson Ave., NE
Tigard, Oregon 97281 Salem, OR 97301
C arlson Testing, Inc. FAX (503) 68954 FAX (503) 5891 309
ROOFING FIELD REPORT
JOB #: 99 -2536A INSPECTOR: T. Kastel DATE: 11 -29 -99
PROJECT: Tigard Corporate Center — Building B
ADDRESS: 12259 SW 69th, Tigard, OR
PERMIT #: BUP1999 -00234 GENERAL CONTRACTOR: Baugh Construction
INSPECTOR'S TIME IN: (OUT: CREWS TIME IN: OUT:
WEATHER: Overcast TEMPERATURE: 50 °AM ° PM
ASPHALT TYPE: 3 EVT: 485 ° AM PM
ROOFING SPECIFICATION # Malarky Cap Sheet IV #601
BASE FLASHING TYPE AND /OR # Malarky Cap Sheet IV #601
INSULATION TYPE: Manville
BOTTOM: 2.5 Poly 'so "R" VALUE 18.2 SIZE: 4x8
TOP: W Retro "R" VALUE 1.32 SIZE: 4x8
TOTAL 19.52
WORK AREA (USE GRID LINES AND /OR DIMENSIONS): Building B Perimeter I SQUARES:
ITEM I CONFORMANCE 1 NON - CONFORMANCE ITEM I YES I NO
VAPOR BARRIER CUT -OFFS INSTALLED X
BASE SHEET X DEBRIS CLEANED X
INSULATION X MATERIAL COVERED X
INTERPLYS X PENETRATIONS SEALED X
BALLASTS
BASE FLASHING X
COUNTER FLASHING
WORK DESCRIPTION: Base flashing installed at perimeter and all roof etrations. Work conf• ms with manufacturer's
specifications.
, °
INSPECTOR T. Kastel REVIEWED BY PRESIDENT
Douglas W. Leach - President
TK/Ijm
cc: Specht Development, Inc. — Bob Burns
City of Tigard Building Department
Baugh Construction Co.
LRS Architects
VLMK
Carlson Testing, Construction Inspection & Related Tests
ng, Inc. Geotechnical Consulting
DEPORT 0 F ' 3 2 CONCRE f E TEST SPECIMENS
P.O. Box 23814
AS TM C1.72/CI 231/C39/C31/C1064/C143 Tigard, Oregon 97281
test Methods: Phone (503) 684 -3460
FAX # 684 -0954
date Molded:
11/29 , 19 99 Job No. 99 2536A Permit No: BUP 1999 - -00234
:Bent: SP[ C11 f DEVELOPMENT INC - BOB BURNS
'roject: TIGARD CORPORATE CENTER •- BLDG 8
4ddress: 12259 SW 69TH TIGARD OR
,ontractor: HAUGH CONSTRUCTION CO Sub Contractor:
Concrete Supplier. ROSS I S SAND & GRAVEL Truck No. 201 Ticket No. A -1 /2622
Cast By:
G. ' WA f S ON C u. Y ds. I. 1 OF 1 1 Load No
S HOWL R S 52 45
Weather: Temp. High: Temp. Low:
BUILDING C SLAB I NF I I..L. S AT OPENINGS. TEST A 1• BUILDING 1 1 SLAB
Location of Placement:
MAILS AT OPENINGS.
8 : 15 62
Test Time: Concrete Temp:
3500 28 3 1/2" 1 & I I
Strength Requirement: PSI @ days Slump Cement Type
3510F1
Mix NoJNo. Sacks Air Content Max. Aggregate
Admix. Amount: Brand: Admix. Amount: Brand:
Set Test@ Register Date Date Total Area Unit Report Tested
No. Days Number Recd Test Load PSI No. By
1. / 208 11/30 12/06 84,770 28.2/ 3000 WR
28 2087 11/30 12/27 144,860 28.26 5130 DM
28 2087 11/30 12/27 147,700 28.26 5230 DM
Remarks:
cc: C1IY OF TIGARD BUILDING DEPT G //
BAUGH CONSTRUCTION CO
LRS ARCHITECTS a
VL.MK
LABORATORY MANAGER
Reviewed by:
,.. • . _.. •.... _ _ •• _ _ -.._ , .. - ........L.,.,. • • R u. Oh",d min, A tnrisatinn fmm this attics.
Construction inspection & Related Tests
Carlson Testing In Geotechnical consulting
6X12 CONCRETE
EPORT OF TEST SPECIMENS P.O. Box 23814
ASTM C172/C1231/C39/C31/C1064/C143 Tigard, Oregon 97281
Phone (503) 684 -3460
ast Methods: FAX # 684 -0954
11/29 19 99 Job No. 99 -2536A Permit No: BUP1999-00234
ate Molded:
SPECHT DEVELOPMENT INC - BOB BURNS
lient:
TIGARD CORPORATE CENTER - BLDG B
roject:
12259 SW 69TH TIGARD OR
ddress:
BAUGH CONSTRUCTION CO Sub Contractor:
ontractor:
ROSS ISLAND SAND & GRAVEL Truck No. 207 Ticket No. A- 172622
:oncrete Supplier:
G . WATSON Cu. Yds. 1 1 OF 11 Load No. 1
:ast By:
SHOWERS
Temp. High: 52 45
Temp. Low:
Veather:
BUILDING C SLAB INFILLS AT OPENINGS. TEST AT BUILDING B SLAB
ocation of Placement:
INF ILLS AT OPENINGS.
Test Time:
$ 1 62
Concrete Temp:
3500 28 3 1/2" Cement Typ & II
PSI @ days Slump
strength Requirement:
35108 Max. Aggregate
Aix NoJNo. Sacks Air Content
Admix. Amount: Brand:
>dmix. Amount: Brand: _ Adm Unit Report Tested
Set Testy Register Date Date Total Area Load PSI No. By
No. Days Number Rec'd Test
I 7 2087 11/30 12/06 84,770 28.27 3000 WR
•
28 2087 11/30 12/27 • •
28 2087 11/30 12/27
•
•
Remarks:
cc: CITY OF TIGARD BUILDING DEPT / ‘/--
BAUGH CONSTRUCTION CO `�,
LRS ARCHITECTS
VLMK
LABORATORYMANAGFp
Reviewed by:
..- - .. -__. ...o ...KM.4 nA,.r n,etuxl7Ation from this office.
■