Correspondence 5 OGG ZS 1
'
June 14, 1999
CITY OF TIG
OREGON
VLMK Consulting Engineers
3933 SW Kelly Avenue
Portland, OR 97201 -4393
Attn: Kim Schoefelder
RE: Tigard Corp. Ctr. "A" "B" "C" Site Plan Review
12123 SW 69th
PC #: 5 -78c SIT #: 99 -00023
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1998 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
Yv.r" fl `AM rte. YY. *E Ce I b F .A E'r+\ T S.- rt'`,'
1. We understand the engineer of record, Marcella Boyer, is no longer employed by
Geo- Engineers. Provide us with a letter from Geo - Engineers accepting full
responsibility for this report.
2. Page 4 " f rom Geo - Engineers report: the statements in paragraph 1
conflict. On one hand, settlement on 12 of fill state settlement of approximately 2
inches. The following sentence recommends fills thicker than 4 feet settle prior
to proceeding with construction. Explain!
6 REM -_ '' 7 ' "< # v 4 #� (j " r" 3' : Nt.:41 : a �a a G ; `' * u tfin.
, ±:�it w � f a�'•pyS�,. �+w'k.�S, '�..�� '���.�b6 � "4ir���:.
1. Provide one (1) additional hydrant and FDC at Building "B ". Locate 240 feet west
of the centerline of 69 in the landscaping area on the comer of SW 70 and SW
Elmhurst. UFC/TVFR 903.4.2.1.
2. Provide an FDC at the hydrant at Building "C" — UFC)TVFR 903.4.2.3.
IMESLE „ RTMEFI L � V E..Y NDI'
1. Complete all information required on the enclosed forms. Return forms and one
set of site and architectural plans to:
Tualatin Valley Fire and Rescue
PO Box 4755
- Beaverton, OR 97076
Attn: Eric T. McMullen
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Tigard Corp. Ctr. "A" "B" "C" Site Plan Review
9 p
PC #: 5 -78c BUP#: 99 -00023
Page #2
`� f-', ��," .x�' i p --:4-
� +.., "� -?>-
1. Your project is located in the Tualatin Valley Water District. Please contact Gary
Pippen or Stu Davis at 642 -1511.
ACC SS 1,0 '.' 4 04 M ATIVO ,.- r ;4 ^ 4 1
1. Building "B" requires six (6) accessible parking spaces. OSSC, Section 1104.
:SPEPO ` S`PECNt. _ #T <; p of a radii, �vm , " r
' �O.. - -,:r. �? r, ?�? ...u._.: `Et. � ,e ?' t...r7",. 3*. �s+,'c're..15x..,.�' -. tgi"R a...��.`g^�.,�'•,.. ,z...',� ?�+ ..,, ' ::
1. Special inspections will be required on the retaining walls.
Please submit three copies of revised submittal documents and a letter indicating your
response to the above comments for review. Please call me at (503) 639 -4171 if you
have any questions.
Sincerely,
•
R e rt Poskin, CBO
SENIOR PLANS EXAMINER
hbldglprmsys1sit99023.cloc