INSPECTION REPORT BY:
DATES COVERED: May 4; 2000
PROJECT: Tigard Corporate Center — Building A
ADDRESS: 12123 SW 69th, Tigard, OR
INSPECTOR: G. Seamster ICBO #5006921 -85
05- 04 -00: CTI representative was onsite and the following was noted.
1. Reviewed WPS and welder qualifications for Joe Taylor SSN# 537 -76 -7001 and William
Sasse SSN# 282 -54 -5553, with Glu Lam Structures (see attached for welder qualifications).
2. Verified torque value after installation of (6) 3 /4" diameter x 6" long Ramset wedge anchors
at 175 ft/Ibs per ICBO report #1372. Anchors were installed at grid line N3-4 roof line into
existing tilt up wall for angel iron joist ledger. Two wedge anchors, one at each ledger plate
were unable to meet required torque value. Re- inspection to follow once re- installed. All
anchors achieved 4" minimum embedment per detail 5 of fax received from Jim
Riemenschneider with VLMK Engineering (see attached).
Our reports pertain to the materials inspected /tested only. Information contained herein is not
to be reproduced, except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this
office.
i)
Respectfully submitted i.
CARLS !,. TESTING, 1 . _ j
CHIEF EXECUTIVE OFFICER
Douglas W. Leach
Chief Executive Officer
GS /Ijm
Attachments
cc: Specht Development, Inc. — Bob Burns
City of Tigard Building Department
Baugh Construction Co. .
LRS Architects
VLMK
Consulting Engineers
.. 3933 SW KELLY AVENUE, PORTLAND, OREGON 97201 -4393
7 (503) 222 -4453 / FAX (503) 248.9263
FAX TRANSMITTAL
(Please call 222 -4453 if all pages are not received)
TO: Baugh Construction - Ste DATE: May 3 2000
ATTN: Chris Hartson, John .Lawrence FROM: Jim Riemenschnelder
PROJECT: Tigard Corporate Center T.I NO. OF PAGES TO FOLLOW: 7
URGENT, PLEASE HAND DELIVER Yes COPY TO FOLLOW IN MAIL —
COMMENTS: 443 -2291, 221 -2077, 239 -8174
RE: TCC bldg. A roof reinforcement for Unit WITH concrete curb and concrete
pad. REVISED 5/03/2000
John, Chris, Mike and Mike:
Here's what needs to be done to reinforce the roof per the meeting on May 2nd,
for building A, under the new mechanical unit
PAY SPECIAL ATTENTION TO THE LOCATION OF THE UNIT AND THE
CURB OUTLINE. THE CURB MUST No EXTEND SOUTH OF THE
EXISTING JOIST THAT IS 10' NORTH OF GRID "3 ", NOR EXTEND
NORTH OF THE EXISTING JOIST THAT IS 10' NORTH OF GRID "4 ".
Questions or comments, give us a call ASAP.