Loading...
Correspondence T T R A N S M I T T A L To: Daryl Jones, City of Tigard Plans Examiner a Project. Luke-Dorf Project number: 201001 t+ Date: 1/24/02 Number of pages including this sheet: FAX number: Telephone number 503.639.4171 ext 392 We transmit: ❑ Fax ❑ US Mail 0 Messenger ❑ Overnight ❑ Other ti Item Date Description a a 3 Rev date 1.23.02 Revised drawings ° Daryl, Attached are the Plans with the revisions we discussed on the telephone on 1.23.02. The following is my response to your written comments: o a a. /1 The wall is now revised to show no door opening, and be infilled with wall construction per new Keynote 10. x The Office is used by a non staff person that uses the existing exterior door to the office. There is a existing Staff Office adjacent to the Dining Room revised, and corrrectly shown as +� a indicated. „X The noted requirements are now stated in revised Keynote 2. 4. The building square footage in now indicated under the revised Project Information notes. There is (16) residents, with an assumed 50% split of males and females. Per Table 29 -A, a O total of (2) toilets, (2) lays, and (2) showers are required with a total of (3) toilets, (3) lays, and (3) showers provided. Per Table 11 -B, (1) accessible Bathroom is provided. Note that no roll -in shower is required. 5. The sprinkler system in now indicated under the revised Project Information notes. 0 6. The noted requirements are now stated in revised Keynote 2. 7. The noted requirements are now stated in revised Keynote 8 8. The accessiblity compliance issues are also added to the revised drawing. Note that no elevator is required per section 1108.3.1.2. a Dan Purgiel Copies to: File e Transmitted by: n 0 eup 'Jo o 1- a) 0/ 7 January 23, 2002 Luke -Dorf Inc. CM OF 11G� 12900 SW Hwy 99th O REGO N Tigard, Or. 97223 RE: 10313 SW 69` The City of Tigard Building Division has reviewed the submitted building plans for the above referenced address in accordance with the Oregon Structural Specialty Code (OSSC), 1998 edition and the Uniform Fire Code, 1997 edition as amended by Tualatin Valley Fire & Rescue. The following items need to be addressed and are not in compliance with the above mentioned Codes: 1) 312A.3.2 Occupancy Separation. A one -hour occupancy separation is required between the office and the new bedrooms. The one -hour door and wall are required. 2) Door serving the office portion is required to be Accessible provide proper door clearances of 18 inches on the pull side and 12 inches on the push side. 3) Separation of sleeping rooms from other rooms and corridors by wall construction self closing and latching doors for smoke control. 4) The total square footage has not been submitted for review. Building shall be provided with the minimum plumbing fixtures as per table 29 -A. One shall be accessible to all customers. 5) Sprinkler system shall comply with UBC standard 9 -1. 6) All new doors shall be equipped with lever action hardware. • 7) Plans indicate egress control devices shall automatically deactivated upon activation of either the smoke detectors, electrical power outage or sprinkler system alarm. Please submit revised floor plans showing compliance with codes. If you have any questions regarding this review, please contact me at (503) 369 -4171 ext. 392. Sin ► D o ne P1 Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772