Loading...
Plans 20106 o - EQUIPMENT LIST Co TEC.HN 'G S Farme rs Insurance Regional Offices 302 -FN -5119 Fire Alarm 10/10/2005 System Item Part # Quantity Manufacturer Description 1 5815XL Silent Knight 5820XL SLC Expander, 127 Points 2 5815RMK * Silent Knight Remote Cabinet for 5815XL 3 SD500 -PS Silent Knight Addressable Pull Station 4 SD505 -APS Silent Knight Addressable Photo Smoke Detector 5 SD505 -AHS Silent Knight Addressable Heat Detector 6 SD505 -6AB * Silent Knight Detector Base 7 SD500 -MIM Silent Knight Addressable Input Mini - Module 8 SD500 -ARM Silent Knight Addressable Relay Module 9 BPS6A EST Booster Power Supply 10 GC -HDVM EST Temporal Ceiling Horn /Strobe, Multi -CD 11 GC -VM EST Ceiling Strobe, Multi -CD 12 757 -8A -T EST Horn /Strobe 110CD 13 757A -WB * EST Weatherproof Backbox 14 SLA1075 * Interstate 12V7Amp Hour Battery * - Catalog Cut Sheets not available • • PROPRIETARY DOCUMENT FOR APPROVAL ONLY 1 T D Printed: 3:38 PM 10/10/2005 , o " INTELLIKNIGHT ACCESSORY Model 5815XL , Signaling Line Circuit Expander ' , , Add flexibility to IntelliKnight® applications f y v ? with the 5815XL SLC Expander The Model 5815XL SLC Expander is a signaling line circuit controller for Silent Knight's IntelliKnight 5820XL addressable fire control panel. It allows you to add 127 addressable devices to the IntelliKnight system. Three 5815XLs can be added to the 5820XL for a maximum of 508 addressable devices per IntelliKnight system. 5815XL signaling circuits have the same functionality as the SLC that is built into the IntelliKnight panel and support the same addressable devices as the main panel. The 5815XL connects to the panel via the RS 485 bus and is housed in the IntelliKnight 5820XL or 5895XL cabinet. Model 5815X1 `"r "" w - Features ,c-, ' 1 •�..: t = . .... - Signaling Line Circuit Expander •Adds 127 addressable IntelliKnight system to an i - n ' l �' , - .� _ ' The 5815XL expands the �' � P . X13-. Three 5815XLs per system tt capabilities of the IntelliKnight I . I ► i • fire control panel by allowing ,. - `� • 't . k • 5815XL SLCs have same,, ,: _: ; :{ 127 additional addressable functionality as built -in, including " �; II se w -4 devices to be attached to the Style 6 (Class A) configuration , Vi r g .,, system. • Communicates with the . . , . a v<• . All functionality of the built -in IntelliKnight panel via RS 485 Model 5815XL SLC is provided with the system bus 5815XL. Three 5815XLs can be • LED indicates good S y ste m otions ht system commu S ystem C IntelliKnight system added to an IntelliKni g y supports three 5815XL for a total of 508 addressable • Housed inside IntelliKnight SLC Expanders. devices per system. 5820XL cabinet or remotely Each expander mounted inside the 5895XL supports 127 addressable devices; cabinet. IntelliKnight system Operation • UL 864 listed, complies with supports 508 devices NFPA 72 and 101 total. The 5815X1 communicates with • Communicates on most Operating Voltage 24 VDC the IntelliKnight FACP via an standard wiring systems (ideal RS 485 system bus. A green for retrofits) Current 55 mA minimum - LED on the 5815XL board • FM approved Consumption 125 mA max. (with 127 blinks to indicate good (standby and devices) communication. If an alarm) addressable device on a 5815XL fails, the loop SILENT Tem (0°C to 4s C) communicates the failure to the ` KNIGHT panel and continues to operate Mounting Inside IntelliKnight • normally. & FACP or 5895XL Y cabinet INTELLIKNIGHT ACCESSORY Model 5815XL Signaling Line Circuit Expander i • i Engineering Specifications The contractor shall provide a signaling circuit expander compatible with the IntelliKnight 5820XL fire control panel that allows 127 addressable devices to be added to the system. The IntelliKnight panel shall support three expanders for a total of 508 addressable devices per system. The expanders shall mount inside an IntelliKnight system cabinet, either the FACP or the 5895XL. The expanders shall provide signaling line circuits that have the same installation and functionality as built -in SLCs and shall communicate to the main panel via an RS 485 system bus. A green LED on the expander board shall blink to indicate communication with the main panel. FACP 5815XL 11 23 22 21 20 19 18 1 7 16 sc- s+ sc. s+ 11 . ..._ _ _ _ + A B IN_ _OUT , 1 , 11 l , , f 11 ...L.. . - , 11 1 . l , , , .._ ClassA 1 tow StINaSLic Cobgxaran 1 configurations . 3 w ..... Allit414«,v Mode 5815XL Modal 5813XL SLC Loop 1 SLC Loop 2 SLC Loop 3 FACP Cabinet 5815XL Block Diagram tt li SILENT KNIGHT MADE IN AMERICA FORM# 350098, Rev. 01/01 7550 Meridian Circle, Maple Grove, MN 55369 -4927 800 - 446 -6444 or in Minnesota 763 -493 -6435 Copyright © 2001 Silent Knight Security Systems FAX: 763 IntelliKnight is a Registered Trademark or Silent Knight World Wide Web: http: / /www.silentknight.com Flexput is a Trademark of Silent Knight - INTELLIKNIGHT ACCESSORY g SD500 -PS and SD500 -PSDA 1 - -�� Addressable Pull- Station u x b , g3 -- L IntelliKni ht's addressable pull stations . (4.7 .- A -; ., 4 combine fast response with pin -point ,. location ID. The SD500 -PS and SD500 -PSDA are a single action or dual action addressable manual fire alarm pull station for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SD500 -PS /PSDA provides a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. The SD500 -PS /PSDA mounts to a single gang box and features a rugged metal construction that lasts and lasts. Combine all this with the features you've come to expect from Silent Knight - easy installation and stable operation - and it adds up to a flexible solution for all your fire protection needs. Model SD500 -PS & • Extremely easy to operate SD500 -PSDA • Corrosion- resistant gold - plated Addressable Pull • contacts. 4 PULL • Reflective label makes it easier Station to locate in low light '" The SD500 -PS is a single action Operation t;'°;. • addressable fire pull station, and The SD500 -PS /PSDA single action ; the SD500 - -PSDA is a dual action pull stations are operated by a pull , F: r '` addressable fire pull station. The on the front pull cover of the SD500 -PS /PSDA feature rugged station. A plunger switch, wired to metal construction A terminal strip a self contained addressable, 1 on back of the pull station allows module, is released as the pull 1111 <--- interconnection of the pull station to station opens to initiate the alarm. , the SLC of an IntelliKnight control Once operated, the cover hangs panel. The SD500 -PS /PSDA is down and can be seen up to 100 /� ��/ designed for indoor use in non- feet away. The pull station is reset .I�1 LA Rill explosive environments. The by retuming the front cover to the normally open initiating point normal upright position and contacts are gold - plated to avoid relocking the station with a reset — ' a i i ` r risk of corrosion. The SD500- key. The reset keys are the same — , i, N. l • i PS /PSDA has been tested by UL keys used on Silent Knight for compliance to the requirements enclosures. of the Americans with Disabilities The SD500 -PS /PSDA includes a ACT (ADA). status LED which blinks, indicating SD500-PS Features that the addressable module is Ambient Temperature: 32 °F to 120 °F • UL Listed communicating with the loop. The (o °C to 49 °C) • CSFM listed status LED lights continuously Mounting: Single gang during an alarm. A dip switch on box - • ADA compliant the addressable module is used to Optional Red Surface Mount Box PS -SMBB • Key reset (Same key as Silent set the unique address. Knight enclosures) Specifications • Surface mount back box available Operating Voltage: 24VDC SILE Standby Current: .55mA KNIGHT • Terminals - accept up to 14 Alarm Current: .55mA gauge wire "'°""�i0`P°TM INTELLIKNIGHT ACCESSORY SD500 -PS and SD500 -PSDA f ,-: ,s 'z- Addressable Pull- Station ,:- A (Af 1 Engineering Specifications Manual pull station shall be addressable Module SD500- PS /SD500 -PSDA. Equipment shall be made of 14 gauge C.R.S.(Cold Rolled Steel), painted with a red enamel . The label shall contain the words Fire Alarm and be made of a reflective material embossed text 3/8 inches tall. Operating instruction shall be dearly visible on the same label. Manual station Shall contain a key operated test and reset lock using a lock plate actuator, the key shall match the control panel. Manual station shall contain four terminal blocks with two connected to the addressable module and two connect to the SLC loop. Manual station shall provide data to the control panel with an ID address programmed by dip switch settings . Manual stations shall be Underwriters Laboratories Inc. listed and installed within the limits defined in the American Disabilities Act. FACP .'°t \ \ -a. CBrSLMV Om A(31» r ?'. `C I. ' '�� ! ♦ \� l + Staab lbiuY Y 7t ' -:r1r:c.)6 ',. \ - :; -' r, x ; ♦ �` _ ` � 1 xj . Y so�oovsa�c- aoWPac. • `� • „L , f Wiring f k .x ' . f 1 Y Ltr 1 1 Mounting to Single Mounting to Optional Gang Electrical Box Surface Mount Box , -. , ., Aft p --. -;. [ -:- ;. 111111101111111111111 MN L: • SD500 -PSDA yc 4 elerciriced eoz smut be Installing SD500 -LK et ' Dimensions �" °t°° SILENT T KNIGHT . APtcp0 AACarrpiit 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800- 446 -6444 or in Minnesota 763- 493 -6435 FORM# 350342, Rev. 09/03 FAX: 763 - 493 -6475 World Wide Web: http: / /www.silentknight.com Copyright ® 2003 Silent Knight INTELLIKNIGHT ACCESSORY _. N Addressable 2 ; 1 Photoelectric Type r toN Smoke Detector t Detect smoldering fires quickly and get go . ) help fast with IntelliKnight® photoelectric wow i smoke detectors. IntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505 -APS photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds are wasted in determining location of an alarm. The SD505 -APS compensates automatically for contamination in the environment. And detector testing is simple —even from a remote site. Like other IntelliKnight detector models, the SD505 -APS offers a low profile for pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model SD505 -6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight smoke detectors—easy installation, stable operation, RF /transient protection, and vandal- resistant locking —and it adds up to a flexible solution for all your fire protection needs. Model SD505 -APS The light received is converted into Analog 1 Addressable an electronic signal. Under normal =Th Photoelectric Type conditions, the status LED blinks Smoke Detector approximately every 15 seconds, The SD505 -APS is particularly indicating that the head is - suited to detecting dense smoke communicating with the loop. The \ I typical of fires involving materials LED lights continuously during the such as soft fumishings, plastic, alarm period. "" foam or other similar materials Features which tend to smolder and produce • Low profile, 2 inches, including SD505 -APS Smoke Detector large visible particles. base Specifications The detector features automatic • Simple and reliable addressing Operating Voltage: 17 VDC compensation for contamination without mechanical switches Current Consumption: and a simple detector calibration • Automatic compensation for test procedure that can be run from sensor contamination Standby: .55 mA the panel or remotely (using the • Built -in fire test feature Alarm: .55 mA WindowsTM based downloading Simple detector calibration Ambient Temperature: 32 °F to 120 °F • software). testing through the control panel (0 °C to 49 °C) Operation or remotely through a Mounting: 4" Square, 4" The SD505 -APS units made up of WindowsTM based computer OCT, Single an LED light source and a silicon software. gang mud ring photo diode receiving element. In a • Vandal- resistance locking Relative Humidity: 85% normal standby condition, the features noncondensing receiving element receives rio light • Field cleanable pulsing light source. In the Air Velocity: 0 - 300 FPM from the p g g UL listed, meets NFPA 72 Ch 7 event or fire, smoke enters the requirements Compatible Bases: SD505 -6AB detector and light is reflected from CSFM approved (Sold Separately) (6" Base) • the smoke particles to the receiving SD505 - 4A6 element. • MEA approved (4" Base) • FM Approved SILENT Iv KNIGHT by Honeywell n INTELLIKNIGHT ACCESSORY L Model SD505 -APS . - Addressable Photoelectric Type Smoke Detector I Engineering Specifications . The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector Silent Knight SD505 -APS. The combination detector head, and twist -lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with Silent Knight SD505 -AIS Ionization Smoke Detector, or SD505- AHS Heat Detector. Base shall be the appropriate twist -lock base SD505 -6AB. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for extemal test apparatus. The vandal- resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SD505 -APS shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. 14 Diameter = 5- 15/16° /l Diameter = 3- 15116" N 11 N a ( ID •- C ! 0 J U 0 Height = 2 inches, '\ / inc base CI �' O \\ ANT o a�j Model SD505 -6AB Detector Base Model SD505 -APS Detector Head (front view) (front view) If N SILENT This document is not intended to be used for installation purposes. We try to MADE IN AMERICA til KNIGHT keep our product information up accurate. We cannot cover all specific applications or anticipate all -to -date requireme nts. All specifications are FORM# 350225 Rev C,. 05/05 subject to change without notice. For more information, contact Silent Knight by Honeywell 7550 Meridian Circle Suite 100, Maple Grove, Mn 55369 -4927. Copyright © 2005 Silent Knight Phone: (800) 328 -0103, Fax: (763) 493 -6475. . ' INTELLIKNIGHT ACCESSORY Addressable Heat Detector t I. IntelliKnight® addressable heat detectors gas `` ` �,, combine accurate heat detection with in- oint ,Y , ; , location ID. i' t An essential combination for any installation. IntelliKnight heat detectors are an essential component in virtually any IntelliKnight installation. The IntelliKnight panel recognizes each detector by its specific address, so precious seconds are not wasted in determining location of an alarm. Like other IntelliKnight detector models, the SD505 -AHS offers a low profile for pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model SD505 -6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight detectors —easy installation, stable operation, RF/transient protection, and vandal- resistant locking —and it adds up to a flexible solution for all your fire protection needs. Model SD505 -AHS If the temperature exceeds the trip Addressable Heat point (programmed at the panel) an alarm occurs. The status LED - Detector lights continuously during the alarm i } . The SD505 -AHS is a heat detector period. 1 suited to virtually any commercial Under normal conditions, the status \* '' • setting. The SD505 -AHS is an LED blinks approximately every 15 ` ._ absolute temperature device. This seconds, indicating that the head is means that it responds in alarm if communicating with the loop. 1 - the temperature goes above the trip point (programmed at the Features panel). • Low profile, 2 inches, including SD505 -AHS Heat Detector The SD505 -AHS provides accurate base Specifications temperature measurement data to • Absolute temperature device Operating Voltage: 17 to 41 VDC the fire alarm control panel. This • Simple and reliable addressing Current Consumption: heat detector is particularly suited • Standb y : 55 mA to environments where smoke Uses digital communication Alarm: .55 mA detectors cannot be used because Protocol presence of steam or • The SD505 -AHS is UL Listed Detection Temperature of the P Range: 135 °F to 150 °F cooking fumes, such as in a and meets the requirements (57 °C TO 65 °C) kitchen. outlined in NFPA 72 Inspection Ambient Temperature: 32 to 120 Testing and Maintenance, (04C to 49 Operation Chapter 7. Mounting: 4" SOR, 4' OCT The SD505 -AHS unit is made up of • CFSM listed Single gang mud an externally mounted thermistor ring with a specially designed cover that • MEA listed protects the thermistor while • FM approved Rated Spacin 70' between sensors on smooth allowing maximum air flow. The ceilings. thermistor reads the temperature SILENT Compatible Bases: SD505 -6AB from the air it takes in. It then KNIGHT (Sold Separately (6" Base) transmits a signal representing the SD505 -4AB temperature to the IntelliKnight (4" Base) panel. by Honeywell INTELLIKNIGHT ACCESSORY Model SD505 -AHS I Addressable Heat Detector 1 !I i Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable heat detector Silent Knight SD505 -AHS. The combination detector head, and twist -lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight fire alarm control panels. The base shall permit direct interchange with Silent SD505 -APS Photoelectric Smoke Detector, or SD505 -AIS Ionization Smoke Detector. Base shall be the appropriate twist -lock base SD505 -6AB. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel reset switch. The vandal- resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field removable when not required. Voltage and RF /transient suppression techniques shall be employed to minimize false alarm potential. N Diameter = 5- 15i16' iii . Diameter = 3-16/16" 11 •I . ; .. Ff f � \., / _ \ \ e Height = 2 inches, ._____ - r',;=V ' including base \ El J E..T i i0.x IT Model SD505 -6AB Detector Base Model SD505 -AHS Detector Head (Front View) (Front View) SILENT This document is not intended to be used for installation purposes. We try to MADE IN AMERICA N KNIGHT keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are FORM# 350229 Rev B,. 05/05 subject to change without notice. For more information, contact Silent Knight by Honeywell 7550 Meridian Circle Suite 100, Maple Grove, Mn 55369 -4927. Copyright © 2005 Silent Knight Phone: (800) 328 -0103, Fax: (763) 493 -6475. • l C INTELUKNIGHT ACCESSORY ' - • ` f 7 -. Model SD500 -AIM --- .� .---s. ° .r .4_ . :.. =are .M Addressable Input Module , z- And '' ..•� Model SD500 -MIM - - - -� ,'... Miniature Input Module ,. - . .- IntelliKnight's addressable contact monitor modules �' .. combine fast response with pin-point location ID. A combination that saves lives and property. The SD500 -AIM and SD500 -MIM are addressable input modules for use with Silent Knight's IntelliKnight fire control panel. The SD500 -AIM and SD500 -MIM are designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. The SD500 -AIM addressable input module mounts to a 4 "- square box. The SD500 -MIM mini input module fits inside a single gang box. The modules are supervised, single input contact monitors. Using an EOL resister, they monitor for alarm contact closures and for open circuit wiring fault conditions. The SD500 -AIM and SD500 -MIM offer a compact design for adaptability and pleasing aesthetics as well as easy installation and stable operation —a flexible solution for all your fire protection needs. Model SDSOO -AIM and SD500 -MIM Input Modules The addressable input modules i , - el __ _J . expand the flexibility of the I - 4 ,' M -'i Inte system by allowing the I , =a" �' . • use of contact type inputs. Typical 1 t . C , _ � a applications include manual pull _; ; stations and water flow switches. , j r a s •`" ' i- ? ,, ,., , • f Q° - a . o. Mures 1 �sw • Operates on Class A (Style 6 & Style t 7) or Class B (Style 4)SLC Loop. ::_ _:::.:::::_ ::::_::_._::__.:___::__4 J • Single contact monitor. 80500 -AIM SD500 - MIM • Up to 127 modules per SLC loop. • SD500 -MIM mounts in a single gang qo., Spedpadlons box. Each addressable input module is Operating Voltage: 24 VDC • SD500 -AIM mounts in a programmed with a unique SLC Standby Current: 0.55 mA 4 "- square or double gang electrical loop address. The module box, and has an attractive ivory supervises the wiring to the contact Alarm Current: 0.55 mA cover plate. with an End Of Line (EOL) resistor. Ambient Temperature: 32 °F to 120 °F • SD500 AIM/MIM are DIP switch If a fault occurs in the wiring, the (0°C to 49 °C) programmable. module alerts the FACP. Mounting: SD500 -AIM • Accepts up to 14 gauge wire. double gang box or • Both modules UL 864 listed; comply 4 " - square electrical with NFPA 72 box • 2500 ft max. wiring distance from SD500 -MIM input module to contact. single gang box • CSFM listed. • MEA 429 -92 -E, Vol. 9 SILENT • FM approved KN .I GH . ® T + KNIGHT 1 • • f 7 INTELLIKNIGHT ACCESSORY Model SD500 -AIM and SD500 -MIM Addressable Input and Mini Input Modules if' Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable input modules Silent Knight SD500 -AIM or SD500 -MIM. The modules shall be UL listed and compatible with Silent Knight's IntelliKnight FACPs. The SD500 -MIM shall fit inside a single gang electrical box. The SD500 -AIM shall be supplied with a plastic cover and shall be suitable for mounting to a 4 "- square or double gang electrical box. The SD500 -AIM addressable input module must provide a monitor LED that is visible from outside the cover plate. Model S0500-AIM FRONT VIEW BACK VIEW SIDE VIEW E:• ' ,.. 4anr 1 11,4 I i —al 1 • Model 5D500 -MIM it .. aide 9 2.112° It SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800 - 446 - 6444 or in Minnesota 763 -493 -6435 FORM# 350231, Rev. 11/01 FAX: 763 - 493 -6475 World Wide Web: http: / /www.silentknight.com Copyright ® 2001 Silent Knight 6,11 = INTELLIKNIGHT ACCESSORY` Model SD500 -ARM if Addressable Relay Module 'r .: i ,,• . £ Place relay applications anywhere on the. sap .. IntelliKnight loop with the SD500 -ARM Addressable Relay Module. The SD500 -ARM is an addressable device that adds great flexibility to the IntelliKnight system. Providing two Form C contacts rated at 2.0 amps @ 30 VDC or .6 amp @ 120 VAC. The SD500 -ARM allows you to control a wide variety of normally open and normally closed applications, including elevator recall, door closing, fan operation, and auxiliary notification. And, because the relay module is addressable, these applications can be located at any point in the signaling line circuit. Like other IntelliKnight SLC devices, the SD500 -ARM is compact for adaptability and pleasing aesthetics. Combine this with the features you've come to expect from Silent Knight fire protection devices —easy installation and stable operation —and it adds up to a flexible solution for all your fire protection needs. Model SD500 -ARM Features Addressable Relay Module • Two sets of Form C contacts. — _) The SD500 -ARM provides two 'Contacts are rated at 2A @ 30 ©m o .., Form C contacts rated at 2A @ VDC or .6A @ 120 VAC. 30 VDC or .6A @ 120 VAC. • Up to 127 relays can be used on ° each SLC loop. These contacts can be used for virtually any normally open or • Relay programming is I normally closed application. completely flexible —can be Model SD500 - ARM mapped to zone conditions. Spedfications • Polling LED visible through Operation cover plate. • UL listed, complies with NFPA Contact Rating: Form C Each relay module is 72. 2A@ 30 VDC programmed with a unique SLC • CSFM approved . 6A @ 120 VAC loop address. When an event • MEAApproved, 429 - 92 - E, Vol. 9 that controls the relay module • FM approved Standby Current: .55 mA occurs, the relay is triggered by the IntelliKnight panel. Alarm current: 55 mA Ambient 32 °F to 120 °F Temperature (0 °C to 49 °C) SILENT Mounting 4- square electrical box KNIGHT y n v > • INTELLIKNIGHT ACCESSORY • Model SD500 -ARM Addressable Relay Module Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable relay modules, Silent Knight SD500 -ARM. The modules shall be UL listed compatible with Silent Knight's Intelliknight FACPs. The relay module must provide two Form C dry contacts rated at 2.0 amps at 30 VDC or .6 amp at 120 VAC. The relay module must be suitable for mounting in a standard 4- square electrical box and must include a plastic cover plate. The relay module board must provide an LED that is visible from the outside of the cover plate. The relay must be fully programmable for such applications as are required by the installation. FRONT VIEW O (m it 0 3 !I o , �I [1,. ( it • H 4 -7/8" 1/4" 4, 1 Model SD500 -ARM Addressable Relay Module Dlmemioes It SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800 - 446 - 6444 or in Minnesota 763 -493 -6435 FORM# 350218, Rev. 11/01 FAX: 763- 493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2001 Silent Knight • • TM EDWARDS SYSTEMS TECHNOLOGY POWER SUPPLIES Compatibility 4 QuickStart FireShield EST2 EST3 LSS4 IRC-3 /FCC (a�xG."3 if1S it I Remote Booster Power Supplies Models: BPS6A and BPS1 OA Features • Extends power available to Notification Appliance Circuits (NACs). • Providesstrobesynchronization. • Use as auxiliary Power Supply. • Extensive UL Listings (Listed accessory under the following standards) Standard CCN Description 1�1 UL864 UOXX Fire Alarm Systems _ UL636 ANET, UEHX7 Holdup Alarm Units and Systems UL609 AOTX, AOTX7 Local Burglar Alarm Units and Systems supervise four Class B or two Class A NAC circuits and monitor two UL294 ALVY, UEHX7 Access Control Systems controlling inputs from external sources. UL365 APAW, APAW7 Police Station Connected Burglar Simple switch selection provides a wide variety of operational Alarm Units and Systems configurations. Each remote booster power supply is supplied ULC-S527 UOXXC Control Units, Fire Alarm (Canada) with its own enclosure providing ample space for additional ULC-S303 AOTX7 Local Burglar Alarm Units and Systems (Canada) interface modules and battery compartment. ULC - S304 AMCX7 Central and Monitoring Station The Remote Booster Power Supply is available in either a 6.5 or Burglar Alarm Units (Canada) 10 amp version @ 24 Vdc. C22.2 No. 205 Signaling Equipment (Canada) UL1076 APOU, APOU7 Proprietary Burglar Alarm System Units Application UL1610 AMCX Central Station Alarm Unit PP • Available in 10 amp and 6.5 amp versions. The Remote Booster Power Supply provides additional power for audible and visual devices helping remove system capacity or site • Includes four independent 3 amp NACs application constraints. The booster may also be used to power —each configurable as auxiliary outputs. auxiliary, access control and security devices, in addition to fire • Configurable signal rates. devices. • Field selectable input -to- output correlation. Fault conditions detected by the BPS will open the main panel's • Two inputs allow activation by Signature Series modules or NAC. This initiates a trouble condition and eliminates the need to existing NACs. wire a separate trouble contact back to the control panel. During alarm condition, detected faults are overridden and the main • NACs configure for either four Class B or two Class A circuits. panel's default configuration is continuous 24 Vdc on all NACs • 110 Vac and 230 Vac versions typically used to drive visual devices. On board trouble contact is • On -board status LEDs for easy recognition of wiring faults. supplied for applications requiring trouble contact monitoring. • Supports up to 24 Amp hour batteries for fire and security The booster power supply provides the capability to maximize applications, up to 65 Amp hour for access control applications. available power by being able to supply power for multiple services including Access Control, Security and Fire. For security applications, space is provided to mount a tamper switch in the Description On cabinet. When used for Fire Alarm notification with Genesis p Notification appliances, the booster provides the ability to syn- The Remote Booster Power Supply is a self- contained 24 Vdc chronize strobes as well as horn signals. The booster flexibility power supply designed to augment fire alarm audible and visual allows synchronization with upstream devices, or, the booster may power requirements as well as provide power for auxiliary, access be used to synchronize downstream devices, as well as other control and security applications. The booster contains all of the boosters and their connected devices. Up to 10 boosters deep necessary circuits to monitor and charge batteries, control and may be configured while maintaining strobe synchronization. EDWARDS SYSTEMS TECHNOLOGY U.S. SALES: BRADENTON, FL 888- 378 -2329; FAX 866-503 -3996 • CANADA SALES: OWEN SOUND, ON 519-376 -2430; FAX 519- 376 -7258 INTERNATIONAL SALES: 905-270-1711; FAX 905-270-9553 • CORPORATE HEADQUARTERS: CHESHIRE, CT • U.S. MANUFACTURING: PITTSFIELD & NEWPORT, ME Issue 1 Literature Sheet 41 -0125 Page 1 of 4 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. BPS notification appliance circuits easily configure for either of and, one for ac power. The trouble contact has a sixteen second two signaling rates: 3 -3 -3 temporal or continuous. California rate delay when an ac power failure or brownout condition is detected. is also available on certain models. This makes the BPS ideal for This reduces the reporting of troubles during short duration ac applications requiring signaling rates not available from the main brownouts. panel. It also allows independent setup of a notification appliance circuit without interfering with the main panel and its initiating NAC configuration options include: ac power fail delay (16 circuits. seconds or 6 hours); sensing input to NAC output correlations; and, auxiliary outputs. All NACs are configurable as auxiliary In addition to the generated signal rates, the BPS can also be outputs. Auxiliary outputs can be always on, or off after 30 configured to follow the signal rate of the main panel's notification seconds without ac power. As auxiliary output, the booster may appliance circuit. This allows seamless expansion of existing NACs. power access control and security devices. Should an overcurrent The BPS includes seven on -board LED indicators: one for each occur, the booster automatically opens the circuit. The booster automatically restores the circuit when the resident NAC; one for battery supervision; one for ground fault; Class Bwiring. overcurrent is removed. Jumpers configure the BPS for Class A or Class Engineering Specification Supply where needed EST BPS series Booster Power Supplies as NACs to follow the main panel's NAC or activate from intelligent an extension of Notification Appliance Circuits. The extension shall Signature Series modules. The booster NACs must be configurable be in the form of a stand alone booster power supply. The supply to operate independently at any one of the following rates: must incorporate its own standby batteries. Batteries must be sized continuous, California Rate, or 3 -3 -3 temporal. Fault conditions on for <24 >, <60> hours of standby followed by <5 >, <30> the booster shall not impede alarm activation of host NAC circuits. minutes of alarm. It must be possible to support up to 24 Amp hour batteries. The booster must be able to provide concurrent power for Notification devices, Security devices, Access Control equipment The booster supply must incorporate four independent supervised and Auxiliary devices such as door holders; The BPS must provide Notification Appliance Circuits. It shall be possible to configure the the ability to synchronize Genesis series strobes and horns. Installation and Mounting Power- limited - wiring area I S 0 0 0 r''' ''.,. yy $P r,` . • iv Top View i i % D2 • D3 ► 1: s ray® • m Front View g ❑ a +_ . _ • m • Route AC supply •• , *" . __ ,A, through these —, knockouts only n — —p Dt O D6 (Nonpower- limited •' ` ' • and supervised) Battery wiring' (nonpower- All knockouts limited and supervised) for 3/4 in conduit (1.9 cm) Battery Battery • • Notes 1. Maintain 1/4 -inch (6 mm) spacing between power- limited and nonpower- limited wiring or use type FPL, FPLR, or FPLP cable D1 02 D3 D4 05 06 per NEC. 17.0 in 3.5 in 13.0 in 6.5 in 3.375 in 12.0 in (21 Power - limited and supervised when not configured as (43.2 cm) (8.9 cm) (33.0 cm) (16.5 cm) (8.6 cm) (30.4 cm) auxiliary power. Non - supervised when configured as auxiliary power. (31 Source must be power - limited. Source determines supervision. 4. When using larger batteries, make sure to position the battery terminals towards the door. EDWARDS SYSTEMS TECHNOLOGY Page 2 of 4 Literature Sheet #85008-0125 Issue 1 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. ' - • Typical Wiring . Single booster anywhere on a notification appliance circuit Existing NAC end -of -line resistors are not required to be i installed at the booster's terminals. This allows multiple NAC Circuit > To next signaling boosters to be driven from a single NAC circuit without the NAC Circuit device, booster, or need for special configurations. EOLresistor g' g' > NAC output #1 Fire Alarm I N _ > MAC output #2 Control Panel > NAC output #3 5 a' )NAC output l 4 S S Booster Power Multiple boosters cascaded from a Supply single notification appliance circuit To next signaling NACU --v "device. b , or Multiple CC1(S) modules using the EOL resistor r > NAC output *1 BPS's sense inputs F. >, NAC output 10 Fire Alarm > NAC output tk1 Control Panel a NAC output 04 ° Notification appliance circuit (NAC) S TB1 Booster Power NAC1/ + El 4 UL listed Supply AUX1 - [� l EOL 15 Kr1 To nest signaling I/ 'device, booster, or NAC2/ + [� ] Notification appliance circuit NAC %1°°-0 l EOL resistor AUX2 - FAI p (NAC) I. NAC output 71 NAC3/ + U ,J UL listed S j HNAC 833 AUX3 - ELI EOL EOL 15 K0 J MAC output e4 NAC4/ + [� l AUX4 - [_l Booster Power 200 mAAUX lA [r•l Supply To next signaling Continuous p [� i - I , 'device, booster, or IN 1 + V EOL resistor r > NAC output in Sense 1 COM El - > NAC output #2 OUT Fill -' -EOL 47 K MAC Output a3 IN F..,1 + NncIi4 Sense 2 COM [A k - Booster Power OUT 1 —EOL 47 K [ 1 Supply NO t' 1 Trouble COM Fil 7 Inn 1 I i1 liEl i 1 NC F.1 10 9 10 9 TBi CC1(S) module CC1(S) module 8765 4 8765 4321 PP*.1 !+1 - ,lr; ITILATIPLa Security and access —. I BPS T131 NAC1/ 12V NAC1/ +trA Securit � Security EOL - F , �E�■ 24DC12 ■�■ _ monitoring NAC2/ [ 1 device devic device NAC2/ +F 1 AUX2 - 15,1 NAC3/ +t' 3 AUX3 -IA NAC4/ +F_•1 AUX4 - L" Control panel BPS [1) Card reader Card reader Card reader controller controller controller + - + - {. - + - + _ A-�- t- To next device or end [11 Disable the BPS's ground fault jumper (JP3) EDWARDS SYSTEMS TECHNOLOGY Issue 1 Literature Sheet #95006 -0125 Page 3 of 4 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. Specifications Model 6.5 amp Booster 10 amp Booster AC Line Voltage 120VAC or 220- 240VAC 50 /60Hz 120VAC or 220- 240VAC 50 /60Hz 250 watts 375. watts Notification Appliance Circuit Ratings 3.0A max. per circuit @ 24Vdc nominal 3.0A max. per circuit @ 24Vdc nominal 6.5A max total all NACs 10A max total all NACs Trouble Relay 2 Amps @ 30Vdc Auxiliary Outputs Four configurable outputs replace NACs 1, 2, 3 or, 4. as auxiliary outputs and 200 mA dedicated auxiliary. (See note 2.) Input Current (from an existing NAC) 3mA @ 12Vdc, 6mA @ 24Vdc Booster Internal Supervisory Current 70mA Signature Mounting Space Accomodates three two -gang modules. ' Maximum Battery Size 10 Amp Hours (2 of 12V10A) in cabinet up to 24 Amp hours with external battery cabinet for fire and security applications; up to 65 Amp hours for access control applications in external battery box. Terminal Wire Gauge 18-12 AWG Relative Humidity 0 to 93% non condensing @ 32 °C Temperature Rating 32° to 120°F (0° to 49°C) NAC Wiring Styles Class A or Class B Output Signal Rates Continuous, Califomia rate, 3 -3 -3 temporal, or follow installed panel's NAC. (See note 1.) Ground Fault Detection Enable or Disable via jumper Agency Listings UL, ULC, CSFM Notes 1. Model BPS *CAA provides selection for California rate, in place of temporal. 2. Maximum of 8 Amps can be used for auxiliary output. Ordering Information Catalog Number Description Shipping Wt. lb (kg) BPS6A 6.5 Amp Booster Power Supply 13 (5.9) II BPS6A/230 6.5 Amp Booster Power Supply (220V) 13 (5.9) BPS6CAA 6.5 Amp Booster Power Supply with California rate 13 (5.9) BPS10A 10 Amp Booster Power Supply 13 (5.9) BPS10A/230 10 Amp Booster Power Supply (220V) 13 (5.9) BPS1OCAA 10 Amp Booster Power Supply with California rate 13 ( 5.9) Related Equipment 12V6A5 7.2 Amp Hour Battery, two required 3.4 (1.6) 12V10A 10 Amp Hour Battery, two required 9.5 (4.3) 3 -TAMP Tamper switch BC -1 Battery Cabinet (up to 2 - 40 Amp Hour Batteries) 58 (26.4) BC -2 Battery Cabinet (up to 2 - 17 Amp Hour Batteries) 19 (8 12V17A 18 Amp Hour Battery, two required (see note 1) 13 (5.9) 12V24A 24 Amp Hour Battery, two required (see note 1) 20 (9.07) 12V40A 40 Amp Hour Battery, two required (see notes 1, 2) 32 (14.5) 12V50A 50 Amp Hour Battery, two required (see notes 1, 2) 40 (18.14) 12V65A 65 Amp Hour Battery, two required (see notes 1, 2) _ 49 (22.2) Notes 1. Requires installation of separate battery cabinet. 2. BPS supports batteries greater than 24 Amp hours for access control applications only. EDWARDS SYSTEMS TECHNOLOGY 1 It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST. C 2004 EST Pmrted in U.S.A. (origin) Page 4 of 4 Literature Sheet #85006-0125 Issue 1 Not to be used for installation purposes. For the most current literature and updates visit www.est.net. A product of EST Marketing, Bradenton, FL 1.j EDWARDS SYSTEMS TECHNOLOGY NOTIFICATION APPLIANCES Compatibility 9 QuickStart RreShield EST2 EST3 LSS4 IRC-3 /FCC Field Configurable Ceiling Horn - Strobes s GC Series • - �.. r Features : r • Field configurable - no need to remove the device) - 15/30/75/95 cd and 95/115/150/177 cd models available f - Switch settings remain visible even after the unit is installed _`rhs ° - � h as j f - Low/highdBsettings A _':. . •, ,,, 9 Y 7 + • Unique low- profile design - 30 per cent slimmer profile than comparable signals - Attractive appearance - No visible mounting screws One or more © ®( E © ' patents pending. • Easy to install pencling - Fits all standard 4" square electrical boxes with plenty of room behind the signal for extra wire -no extension ring or trim plate needed - Pre - assembled with captive hardware - no loose pieces FullLight strobe technology produces a smooth light distribution - #18 to #12 AWG terminals -ideal for long runs or existing wiring pattern without the spikes and voids characteristic of specular • Unparalleled performance reflectors. This ensures the entire coverage area receives consis- tent illumination from the strobe flash. As a result, Genesis strobes - Exclusive FullLight strobe technology produces the industry's with FullLight technology go well beyond the minimum UL- most even light distribution required °cross° pattern, significantly exceeding UL -1971 and ULC- - - Precision timing electronics meet tough synchronizing S526 light distribution requirements. standardsfor strobes - Single high - efficiency microprocessor controls Although all Genesis strobes are self-synchronizing, when installed both horn and strobe with an optional synchronization module, strobe flashes from - Low current draw minimizes system overhead devices on the same circuit synchronize to within 10 milliseconds - Independent horn control provided over a single of each otherindefinitely. This exceeds the two -hour minimum pair of wires specified in the UL standards. Only one synchronization module is - Highly regulated in -rush current allowsthe maximum required per circuit. number of strobes on a circuit Depending on the model, Genesis horn - strobes feature 15 to 95, or - 100 dB peak - multiple frequency tone improves 95 to 177 candela output (see ordering information), which is wall penetration selectable with a convenient) located switch on the front of the - Approved public and private mode applications device. The candela output setting is clearly visible even after final - UL/ULC listed for ceiling or wall use installation, yet it remains locked in place to prevent unauthorized movement after installation. Description Genesis horn output reaches as high as 99 dB (peak) and features a Genesis ceiling horn - strobes are small, compact, and attractive unique multiple frequency tonethat results in excellent wall audible - visible emergency signaling devices. Protruding no more penetration and an unmistakable warning of danger. All models than 1.6° (41 mm) from the ceiling, Genesis horn - strobes blend with may be configured for either coded or non -coded signal circuits. any decor. They can also be set for low dB output with a jumper cut that Thanks to patented breakthrough technology, EST Genesis strobes reduces horn output by about 5 dB. do not require bulky specular reflectors and lenses. Instead, an Genesis horn- strobesfeaturetextured housings in architecturally exclusive cavity design conditions Tight to produce a highly neutral white. An ingenious iconographic symbol indicates the controlled distribution pattern. Significant development efforts purpose of the device. This universal symbol is code - compliant and employing this new technology have given rise to a new bench- is easily recognized by all building occupants regardless of what mark in strobe performance - FullLighttechnology. language they speak. Models with "FIRE" markings are also available. EDWARDS SYSTEMS TECHNOLOGY U.S. SALES: BRADENTON, FL 888 -378 -2329; FAX 866- 503 -3996 • CANADA SALES: OWEN SOUND, ON 519 - 376 -2430; FAX 519-376-7258 INTERNATIONAL SALES: 905.270-1711; FAX 905-270-9553 • CORPORATE HEADQUARTERS: CHESHIRE, CT • US. MANUFACTURING: PITTSFIELD& NEWPORT, ME Issue 5 Literature Sheet 485001 -0559 Page 1 of 4 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. Application Horns The suggested sound pressure level for each signaling zone used with Genesis strobes are UL 1971 - listed for use indoors as ceiling- alert or alarm signals is at least 1'5 dB above the average ambient - mounted public -mode notification appliances for the hearing sound level, or 5 dB above the maximum sound level having a impaired. Prevailing codes require strobes to be used where duration of at least 60 seconds, whichever is greater, measured 5feet ambient noise conditions exceed 105 dBA (87dBA in Canada), (1.5 m) above the floor. The average ambient sound level is, A- where occupants use hearing protection, and in areas of public weighted sound pressure measured overa 24 -hour period. accommodation as defined in the Americans with Disabilities Act (see application notes - USA). Doubling the distance from the signal to the ear will theoretically result in a 6 dB reduction of the received sound pressure level. The Combination horn - strobe signals must be installed in accordance actual effect depends on the acoustic properties of materials in the with guidelines established for strobe devices. space. A 3 dBA difference represents a barely noticeable change in volume. Strobes The following guidelines are based on ANSI /NFPA 72 National Fire Alarm Code (2002). When applied and installed in accordance with Application Notes - USA that code, EST strobes meet or exceed the illumination produced by Audible signals in the public mode should never have a sound the ADA-specified 75 candela (cd) strobe at 50 feet. (ADA suggests level Tess than 75 dBA at 10' (3 m) per NFPA 72. Signals cannot using 75 cd strobes throughout an area, with spacing that never exceed 120 dBA per ADA and NFPA 72 at the minimum hearing exceeds 50 ft. from the strobe to any point in the protected space.) distance to audible appliance. Non - Sleeping Areas and Corridors: EST strobes rated at less than Strobes must be used to supplementaudible signals wherever the 110 cd per UL 1971 are intended for use in non - sleeping areas average ambient sound level exceeds 105 dBA. Combination only. Install with the bottom of the device at least 80 inches (2.0 m) and audible /visual signals must be installed in accordance with NFPA no more than 96 inches (2.4 m) above the finished floor. No point in guidelines established for strobes. any space (including corridors) required to have strobes should be ADA requires visible signals in the following areas: more than 50 feet (15.2 m) from the signal (in the horizontal plane). • rest rooms, meeting rooms, and other common use areas. Maximum Recommended • sleeping rooms by persons with hearing Maximum Area p' g ooms intended for use b Room Type (square room size) Ceiling Ceiling mount impairment (in accordance with Title 1 of ADA). Height Genesis Strobe 20 x 20 k. (6.1 x 6.1 m) 15 cd • work areas used by a person with a hearing impairment (per Title 1 of ADA). 30x30 ft. (9.1 x9.1 m) 10 feet 30cd 40 x 40 ft. (12.2 x 12.2 m) (3.05 m) 75 cd 50x50ft.(15.2x15.2m) 95cd Application Notes - Canada Non 20 x 20 ft. (6.1 x 6.1 m) 30 cd (Based in part on 1995 Canada National Building Code) Rooms 30 x 30 ft. (9.1 x 9.1 m) 20 feet 75 cd The fire alarm signal sound pressure level shall not exceed (ceiling 40 x 40 ft. (12.2 x 12.2 m) (6.10 m) 95 cd 110 dBA in normally occupied area. The sound pressure level mounted) any Y p 50 x 50 ft. (15.2 x 15.2 m) 115 cd from an audible signal in a floor area used for occupancies other 20 x 20 ft. (6.1 x 6.1 m) 75 cd than residential occupancies shall not be less than 10 dBA above 30 x 30 ft. (9.1 x 9.1 m) 30 feet 75 cd ambient levels, and never less than 65 dBA. In sleeping rooms the 40x40 ft. (12.2 x 12.2 m) (9.14 m) 115 15 c d sound pressure level from an audible signal shall not be less than 75 dBA when any intervening doors between the device and the 50 x 50 ft. (15.2 x 15.2 m) 150 cd sleeping room are closed. Audible signal devices shall be Note: Recommendations in the table above assume the strobe is placed in the installed not less than 1.8 m to the center of device above the m center of the room. If not, the maximum room size is determined by doubling the floor (per CAN /ULC S524). distance from the strobe to the farthest wall. The fire alarm audible signal shall be supplemented by fire alarm Sleeping areas: In sleeping areas, ceiling mounted strobes (and strobes in any floor area where the ambient noise level exceeds 87 wall mounted strobes installed Tess than 24 inches from the ceiling) dBA, or where the occupants of the floor area use ear protective must be rated at a minimum of 177 cd. Wall mounted strobes devices, are located within an audiometric booth, or are located installed more than 24 inches (610 mm) from the ceiling must be within sound insulating enclosures. This also applies to assembly rated at a minimum of 110 cd. In all cases, the distance from the occupancies in which music and other sounds associated with strobe to the pillow must not exceed 16' (4.8 m). performances could exceed 100 dBA Strobes shall be installed in a building so that the flash from one For detailed spacing requirements, consult The Handbook of device is visible throughout the floor area or portion thereof in Visib /e Notification Appliances for Fire Alarm Applications which they are installed. For maximum safety, EST recommends published by EST Press, or contact your local EST representative. that strobes be installed as per the guidelines shown here under Strobe Spacing. WARNING: These devices will not operate without electrical power. As fires frequently These visible signal appliances' flash intensity may not be adequate to alert or awaken causepowerinterruptions, wesuggestyoudiscuss furthersafeguardswdhyourlocal occupants in the protected area. Research indicates that the intensity of strobe fire protection specialist. needed to awaken 90% of slee persons is approximately 100cd. EST recommends that strobes in sleeping rooms be 110 cd minimum. EDWARDS SYSTEMS TECHNOLOGY Page 2 of 4 Literature Sheet 485001 -0559 Issue 5 Not to be used for installation purposes. For the most current literature and updates visit www.est.net. • 1 1 Specifications Housing White textured UV stabilized, color impregnated engineered plastic. Exceeds 94V -0 UL flammability rating. Lens Optical grade polycarbonate (clear) 1 Mounting North- American 4" square box, 2 1/8° (54 mm) deep (indoor wall or ceiling applications only). Wire connections Screw terminals: single input for both horn and strobe. #18 to #12 AWG (0.75 mm to 2.5 mm wire size Operating environment Indoor: 32 -120 °F (0 -49°C) ambient temperature. 93% relative humidity Agency Meets or exceeds ULC -S541, year 2004 UL requirements for standards UL1638 and UL1971, and complies with listings/approvals UL1480. All horn - strobes comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule. CSFM, FM and MEA pending. I Operating voltage GC -HDVM series temporal -tone horn - strobes: non - coded, filtered 16-33 Vdc or unfiltered 16 -33 Vdc FWR (or coded (audible NAC only) when used with optional G1M Genesis Signal Master) Strobe output rating UL 1971, UL 1638, ULC S526: selectable 15/30/75/95 cd (GC -HDVM) and 95/115/150/177 cd (GC- HDVMH) GC -HDVM series temporal -tone horn - strobes: one flash per second synchronized with optional G1M Genesis Strobe flash rate Signal Master indefinitely within 10 milliseconds (or self- synchronized within 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) I Temporal setting (private mode only): synchronized to temporal output of horns on same circuit Synchronization modules G1M -RM, SIGA -CC1S, SIGA -MCC1S I GC -HDVM series temporal -tone horn - strobes: temporal rate synchronized with optional G1M Genesis � Horn pulse rate Signal Master indefinitely within 10 milliseconds (or self- synchronized within 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) Temporal audible pattern Yz sec ON, 1 /2 sec OFF, 1 /2 sec ON, Y2 sec OFF, 1/2 sec ON, 1 sec OFF, then repeat cycle I Current Draw GC -HDV Temporal tom- strobe: High dB Setting GC -HDVMH High al Temporal Hom- strobe: High d8 Setting Notesand Catunents M • UL Nameplate Rating (UL1971, Effective May 2004) UL Nameplate Rating (UL1971, Effective May 2004) 1. Current values are shown 15 cd 30 cd 75 cd 95 al 95 cd 115 cd 150 cd 177 cd in mirk. RMS RMS RMS RMS RMS WAS RMS RMS 2. UL Nameplate Rating 18 Vdc 147 190 316 372 341 399 506 570 can vary from Typical Current due to 16 Vfwr - 189 253 417 451 467 578 670 711 measurement methods EST) Typical and instrumentsused. Typical Current (Measured by ypical Current (Measured by EST) 15 cd 30 cd 75 ed 95 cd 95 cd 115 cd 150 cd 177 cd 3 ESTrecommends using RMS Mean RMS Mean RMS ,Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean the Typical Current for 16 Vdc 111 95 152 143 281 276 333 328 324 , 322 377 374 477 474 554 551 system design including 20 Vdc 91 80 124 117 219 214 257 251 258 256 299 296 369 366 417 414 NAC and Power Supply 24 Vdc 80 71 108 101 185 180 212 207 220 217 252 249 304 301 341 338 loadingandvoltagedrop 33 Vde 69 62 89 84 144 140 160 158 172 169 188 185 223 220 244 241 calculations. 16 Vfwr 153 81 218 123 388 240 420 268 463 265 535 312 665 400 718 442 4. Use the Vdc RMS 20 V1wr 141 70 190 100 325 188 378 219 392 211 439 240 517 _ 287 587 334 current ratings for filtered 24 Vfwr 135 64 176 90 280 154 310 180 346 _ 179 382 212 458 246 498 271 power supply and battery 33 Viwr 139 61 167 _ 80 241 _ 122 254 133 296 142 323 152 358 178 387 194 AH calculations. Use the Vfwr RMS current ratings for unfiltered power GC -HDVM Temporal Harry-strobe: Low dB Setts GC -HDVMH High cd T SupptyCelCUlatiorlS. Po n9 9h Temporal Hom- strobe: Low dB Setting Typical Current (Measured by EST) Typical Current (Measured by EST) 5. Fuses,circuitbreakers 15 cd 30 cd 75 cd 95 cd 95 cd 115 cd 150 al 177 cd and other overcurrent RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean protection devices are 16 Vdc 108 91 149 139 275 269 327 322 317 315 378 376 480 477 544 542 typically rated for current 20 Vdc 87 75 120 113 214 209 250 245 252 250 292 290 364 382 414 411 in RMS values. Most of 24 Vdc 76 66 103 97 180 175 205 201 212 211 245 243 297 295 334 332 these devices operate based upon the heating 33 Vdc 64 57 85 80 138 135 153 150 159 157 181 179 _` 215 213 234 232 affect of the current 16 Vfwr 141 76 204 118 384 239 418 265 461 265 521 305 656 396 705 432 flowing through the 20 Vfwr 127 65 176 95 312 181 371 214 381 208 437 242 508 285 576 326 device. The RMS current 24 Vfwr 118 60 162 82 262 149 301 171 335 172 _ 370 195 440 235 485 264 (not the mean current) 33 Vfwr 127 56 155 73 229 118 249 129 285 134 308 149 349 169 373 186 determines the heating affect and therefore, the trip and hold threshold for those devices. Ex Our industry has used 'mean' currents over the ' years. However,ULwill directthe industry to use the 2004 R MS values in the future. EDWARDS SYSTEMS TECHNOLOGY Issue 5 Literature Sheet *85001 -0559 Page 3 of 4 • Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. . • , Light output - (effective cd) dBAoutput Ceiling Temporal Homs, Horn- strobes - High dB Setting Percent of UL rating versus angle UL464 Average Peak +ru fte« Ram, 9 ,ra „o to0Sp ro a w tl >o m m 0 m a x o SO n m 0 p ,CO 110 120 Temporal Steady Temporal/Steady Temporal/Steady ti. a ; .:I 16 Vdc 79.8 83.2 90.6 93.6 £ . , t, 1 24 Vdc 83.3 85.4 93.6 96.6 .rs- , , � ' . : - > ` .. . ''' "• 33 Vdc 85 87.8 95.7 98.7 'iii: t a" ; r so Ceiling Temporal Homs, Horn-strobes - Low dB Setting , „ e' ' . ' UL464 Average Peak . ,',',1-;.,,,..' 4 . .,r a• Temporal Steady Y py T empora l /Stead Temporal/Steady \ ^�. , •, 16 Vde 75 79.3 86.3 88.7 -.. i .K z 24 Vde 78 83 88.8 92.4 ns• _ o• s 33 Vdc 80.9 85.9 91.8 95.1 Notes 1. All values shown are dBA measured at 10feet (3.01m). Dimensions 2. UL464 values measured in reverberation room. 1 Average and Peak values are measured in anechoic chamber. 6.8' &a. (173 mm) • 1 Wiring + Y 1 � ' ' h J ,, (25 mm) Field wiring terminals accommodate #18 to #12 AWG (0.75 mm y ' ° " to 2.5 mm wiring. Horn /strobes are interconnected with a single 0.60115 mm) pair of wires as shown below. • 0 Installation and Mounting Polarity shown in T ° next device alarm condition i; i __ ________ _ °f devi e 0 0 All models are intended for , . •. indoor wall or ceiling ` O 0 c / ., applications only. Horn- 0 p: O p I ^ ' , strobes mountto anyflush Note: strobes must have continuous voltage. : � , i' ; North- American4 square t ,�/ i� electrical box. I D Ordering Catalog Num In ber formation � Genesis horn - strobes � o simply unlatch and twist to • Ship Wt. White With FIRE Description open. This gains access to Finish Marking Ibs (kg) mounting screws and the Genesis Ceiling/Wall selectable candela switch. GC- GCF- Horn - Strobe (selectable 15, 0.82 The shallow depth of Genesis devices leaves ample room behind HDVM HDVM (1.8) 75, or 95 cd output) the signal for extra wiring. Once installed with the cover in place, no mounting screws are visible. GC- GCF- Genesis Ceiling/Wall 0.82 HDVMH HDVMH Horn - Strobe (selectable 95, (1.8) EST recommends that these fire alarm horn - strobes always be 115, 150, or 177 cd output) installed in accordance with the latest recognized edition of national and local fire alarm codes. Accessories Genesis Signal Master 0.2 Field Configuration G1M -RM - Remote Mount (1 -gang) (0.1) Depending on the model, Genesis horn - strobes may be set for 15 SIGA Intelligent Synchronization Output Module 0.5 to 95, or 95 to 177 candela output (see ordering information). The CC1S (2 -gang) (0.23) output setting is changed by simply opening the device and sliding the switch to the desired setting. The horn - strobe does not SIGA- Intelligent Synchronization Output Module 0.18 have to be removed to change the output setting. The setting MCC1S (Plug-in UI0) (0.08) remains visible through a small window on the front of the device after the cover is closed. • • :q c. 'fi t Field Configurable Ceiling Horn - Strobes may be ordered . with or without optional 'FIRE' marking. The horn - strobe comes factory set for high dB output. Low dB ` 1 '" output may be selected by cutting a jumper on the circuit board. This reduces the output by about 5 dB. Genesisand FullLight Strobe TechnologyaretrademarksofEST. EDWARDS SYSTEMS TECHNOLOGY It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST. 4 2005 EST Printed in U.S.A. lorigini Page 4 of 4 Literature Sheet #85001 -0559 Issue 5 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. A product of EST Marketing, Bradenton, FI. GENESIS. EDWARDS SYSTEMSTECHNOLOGY NOTIFICATION APPLIANCES Compatibility 4 QuickStart FireShield EST2 EST3 LSS4 IRC -3 /FCC Field Configurable Ceiling Strobes l askland , Genesis Series .1 771 • s'Rer Features • field configurable - no need to remove the device! - 15/30/75/95 cd and 95/115/150/177 cd models available • F x " - Switch settings remain visible even after the unit is installed - Low /high dB settings V M d � ;tit • Unique low-profile design 4 3 a w - 30 per cent slimmer profile than comparable signals — T - Attractive appearance - No visible mounting screws One or more © C C t� E N64 patentspending. • Easy to install O - Fits all standard 4' square electrical boxes with plenty of room behind the signal for extra wire -no extension ring or trim plate needed - #18 to #12AWG terminals - ideal for long runs or existing wiring • Unparalleled performance FullLight strobe technology produces a smooth light distribution - Exclusive FullLight strobe technology produces the industry's pattern without thespikesandvoidscharacteristicofspecular most even light distribution reflectors. This ensures the entire coverage area receives consis- - Precision timing electronics meet tough synchronizing tent illumination from the strobe flash. As a result, Genesis strobes standards for strobes with FullLight technology go well beyond the minimum UL- - Low current draw minimizes system overhead required "cross" pattern, significantly exceeding UL -1971 and - Highly regulated in -rush current allows the maximum ULC- S526 light distribution requirements. number of strobes on a circuit Although all Genesis strobes are self - synchronizing, when installed • Approved for public and private mode applications with an optional synchronization module, strobeflashesfrom - UL 1971 - listed as signaling devices for the hearing impaired devices on the same circuit synchronize to within 10 milliseconds - UL 1638 - listed as protective visual signaling appliances of each other indefinitely. This exceeds the two -hour minimum - ULJULC listed for ceiling or wall use specified in the UL standards. Only one synchronization module is required per circuit. Depending on the model, Genesis ceiling strobes feature 15 to 95, Description or 95 to 177 candela output (see ordering information), which is Genesis ceiling strobes are small, compact, and attractive visible selectable with a conveniently-located switch. The candela output emergency signaling devices. Protruding no more than 1.6' setting remains clearly visible even after final installation, yet it is (41 mm) from the ceiling, Genesis strobes blend with any decor. locked in place to prevent unauthorized movement after installa- tion. Thanks to patented breakthrough technology, EST Genesis strobes Genesis trobesfeaturetexturedhousin housings neutral do not require bulky specular reflectors and lenses. Instead, an 9 architecturally exclusive cavity design conditions light to produce a highly white. An ingenious iconographic symbol indicates the purpose of controlled distribution pattern. Significant development efforts the device. This universal symbol is code-compliant and is easily employing this new technology have given rise to a new bench- recognized by all building occupants regardless of what language mark in strobe performance - FullLighttechnology. they speak. Models with "FIRE" markings are also available. All Genesis strobes are fully compatible with Enhanced Integrity signals. The two product lines may be mixed on the same circuit. EDWARDS SYSTEMS TECHNOLOGY U.S. SALES: SARASOTA, FL 941 - 739 -4200; FAX 941- 727 -0740 • CANADA SALES: OWEN SOUND, ON 519-376-2430; FAX 519- 3767258 INTERNATIONAL SALES: 905-270-1711; FAX 905-270-9553 • CORPORATE HEADQUARTERS: CHESHIRE, CT • U.S. MANUFACTURING: PITTSFIELD& NEWPORT, ME Issue 3 Literature Sheet #85001 -0557 Page 1 of 4 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. Application Genesis strobes are UL 1971- listed for use indoors as wall or Sleeping areas: In sleeping areas, ceiling mounted strobes (and - ceiling mounted public -mode notification appliances for the wall mounted strobes installed less than 24 inches from the ceiling) hearing impaired. Prevailing codes require strobes to be used must be rated at a minimum of 177 cd. Wall mounted strobes where ambient noise conditions exceed 105 dBA (87dBA in installed more than 24 inches (610 mm) from the ceiling must be Canada), where occupants use hearing protection, and in areas of rated at a minimum of 110 cd. In all cases, the distance from the public accommodation as defined in the Americans with Disabi/i- strobe to the pillow must not exceed 16' (4.8 m). ties Act. Recommended Strobes: The following guidelines are based on ' For detailed spacing requirements, consult The Handbook of ANSVNFPA 72 National Fire Alarm Code (2002). When applied and Visib /e Notification Appliances for Fire Alarm Applications installed in accordance with that code, EST strobes meet or exceed published by EST Press, or contact your local EST representative. the illumination produced by the ADA- specified 75 candela (cd) strobe at 50 feet. (ADA suggests using 75 cd strobes throughout an area, with spacing that never exceeds 50 ft. from the strobe to any Application Notes - USA point in the protected space.) Strobes must be used to supplement audible signals wherever the Non - Sleeping Areas and Corridors: EST strobes rated at less than average ambient sound level exceeds 105 dBA. Combination 110 cd per UL 1971 are intended for use in non - sleeping areas audible /visual signals must be installed in accordance with NFPA only. Install with the bottom of the device at least 80 inches (2.0 m) and guidelines established for strobes. no more than 96 inches (2.4 m) above the finished floor. No point in ADA requires visible signals in the following areas: any space (including corridors) required to have strobes should be more than 50 feet (15.2 m) from the signal (in the horizontal plane). • rest rooms, meeting rooms, and other common use areas. • sleeping rooms intended for use by persons with hearing Maximum Area Maximum Recommended impairment (in accordance with Title 1 of ADA). Room Type (square room size) Ceiling ceiling mount • work areas used by a person with a hearing Height Genesis Strobe Y P g impairment (per 20 x 20 ft. (6.1 x 6.1 m) 15 cd Title 1 of ADA). 30x30f.(9.1x9.1m) 10 feet 30cd Application Notes - Canada 40 x 40 ft. (12.2 x 12.2 m) ( 3.0 5 m) 75cd pp 50 x 50 ft. (15.2 x 15.2 m) 95 cd (Based in part on 1995 Canada National Building Code) 20 x 20 ft (s.1 x 6.1 m) 30 cd The fire alarm audible signal shall be supplemented by fire alarm . Non - sleeping strobes in any floor area where the ambient noise level exceeds 87 Rooms 30 x 30 ft. (9.1 x 9.1 m) 20 feet 75 cd dBA, or where the occupants of the floor area use ear protective (ceiling 40 x 40 h. (12.2 x 12.2 m) (6.10 m) 95 cd devices, are located within an audiometric booth, or are located mounted) 50 x 50 ft. (15.2 x 15.2 m) 115 cd within sound insulating enclosures.This also applies to assembly 20 x 20 ft. (6.1 x 6.1 m) 75 cd occupancies in which music and other sounds associated with 30 x 30 ft (s.l x 9.1 m) 30 feet 75 cd performances could exceed 100 dBA 40 x 40 ft. (12.2 x 12.2 m) (9.14 m) 115 cd Strobes shall be installed in a building so that the flash from one 50 x 50 ft. (15.2 x 15.2 m) 150 cd device is visible throughout the floor area or portion thereof in which they are installed. For maximum safety, EST recommends Note: Recommendations in the table above assume the strobe is placed in the that strobes be installed as per the guidelines shown here under center of the room. If not, the maximum room size is determined by doubling the Strobe Spacing. distance from the strobe to the farthest wall. Light output (effective cd) Dimensions Percent of UL rating versus angle 6.6• dia. Peraendpe armed wow - (173 mm) .-- -•••• 120 110 100 b e0 70 e0 50 40 30 70 10 0 10 20 30 40 50 00 70 e0 SO 100 110 120 • l s- a `��• _-L - > ` (2 mm) t S ti .' Z 1`l \\ 60' 15 mm) r 1 . r 1 f 5. ♦5 0' Angle Horizontal and vertical *daub reflect the same pattern EDWARDS SYSTEMS TECHNOLOGY Page 2 of 4 Literature Sheet #85001 -0657 issue 3 Not to be used for installation purposes. For the most current literature and updates visit www.est.net. • • Specifications Housing White textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating. Lens Optical grade polycarbonate (clear). Flush mount to North American 4 -inch square electrical box, 2 -1/8 (54 mm) inches deep. Mounting No extension ring required. Suitable for indoor wall or ceiling applications. Wire Connections Screw terminals: #18 to #12 AWG (0.75 mm to 2.5 mm wire size. Operating Voltage Regulated 16 to 33 Vdc, 16 to 33 Vfwr. Operating environment • Indoor: 32 -120° F (0-49° C) ambient temperature; 0 -93% relative humidity. Meets or exceeds year 2004 UL requirements for standards UL1638 and UL1971 and Canadian requirements Agency listings/approvals for standards CAN/ULC S526 -02 and CAN /ULC S524 -01. All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule. CSFM, FM and MEA pending. Strobe output rating UL 1971, UL 1638, ULC S526: selectable 15/30/75/95 cd (GC -VM) and 95/115/150/177 cd (GC -VMH) Strobe operating voltage GC -VM series strobes: non - coded, filtered 16 -33 Vdc or unfiltered 16-33 Vdc FWR. GC -VM series strobes: one flash per second synchronized with optional G1M Genesis Signal Master indefinitely within 10 milliseconds (or self- synchronized within 200 milliseconds over thirty minutes Strobe flash rate on a common circuit without G1M Genesis Signal Master). Temporal setting (private mode only): synchronized to temporal output of Genesis audible signals on same circuit. Meets or exceeds UL 1971 requirements. Maximum allowed resistance between any two devices is 20 Ohms. Synchronization Refer to specifications for the synchronization control module, this strobe, and the control panel to determine allowed wire resistance. Compatible synchronization G1M -RM, SIGA -CC1S, SIGA- MCC1S. J J modules Current Draw UL Nameplate Rating (UL1971, Effective May 2004) UL Nameplate Rating (UL1971, Effective May 2004) 15 cd 30 cd 75 cd 95 cd 95 cd 115 cd 150 cd 177 cd RMS RMS RMS RMS RMS RMS RMS RMS 16 Vdc 109 151 281 318 330 392 502 565 16 Vfwr 131 194 379 437 432 518 643 693 Typical Current (Measured by EST) Typical Current (Measured by EST) 15cd 30cd 75 cd 95cd 95cd 115cd 150cd 177cd RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean RMS Mean 16 Vdc 94 87 140 135 273 268 325 323 333 330 392 390 499 496 551 545 20 Vde 74 68 108 105 205 203 244 242 259 257 303 301 378 375 429 426 24 Vdc 63 59 90 88 168 166 194 192 212 210 245 243 306 304 342 340 33 Vdc 48 46 70 68 124 123 139 138 155 153 180 174 211 209 236 234 16 Vfwr 126 67 187 108 368 231 403 260 484 283 570 339 673 411 724 446 20 Vfwr 108 54 156 84 281 168 333 199 380 212 438 248 537 312 604 352 24 Vfwr 97 47 139 71 240 135 270 156 318 172 361 198 434 243 484 273 33 Vfwr 89 39 119 56 197 100 214 111 245 123 269 137 _ 308 160 338 176 Notes and Comments 1. Currentvaluesareshown in mA. 2. UL nameplate rating is higher than typical current due to measurement methods and instruments used. 3. EST recommends using the typical currentfor system design including NAC and Power Supply loading and voltage drop calculations. 4. Use the Vdc RMS current ratings forfiltered power supply and battery AH calculations. Use the Vfwr RMS current ratings for unfiltered power supply calculations. 5. Fuses, circuit breakers and other overcurrent protection devices are typically rated for current in RMS values. Most of these devices operate based upon the heating affect of the current flowing through the device. The RMS current(notthe mean current) determines the heating affect and therefore, the trip and hold threshold for those devices. & Our industry has used 'mean' currents over the years. However, UL will direct the industry to use the 2004 RMS values in the future. EDWARDS SYSTEMS TECHNOLOGY Issue 3 Literature Sheet 085001 -0657 Page 3 of 4 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. a 4 • • '1 : • t . 4.6 . • Installation Ordering Information All models are intended for indoor applications only. Strobes Catalog Number • mount to any flush North - American 4' square electrical box, 2' / Ship Wt. White With FIRE Description (54 mm) deep. Finish Marking Ibs (kg) Genesis ceiling strobes simply unlatch and twist to open. This gains Genesis Ceiling/Wall Strobe 0.82 access to mounting screws and the selectable candela switch. The GC -VM GCF -VM (selectable 15, 30, 75, (1.8) shallow depth of Genesis devices leaves ample room behind the or 95 cd output) • signal for extra wiring. Once installed with the cover in place, no Genesis Ceiling/Wall Strobe 0.82 mounting screws are visible. GC -VMH GCF -VMH (selectable 95, 115, 150, (1.8) or 177 cd output) 0 O O , o • - _ Accessories 0 • O 0 • ` G1 - RM Genesis Signal Master 0.2 / d 1 , _ Remote Mount (1 -gang) (0.1) : �• > • �i� l '� ti SIGA- Intelligent Synchronization Output Module 0.5 rt �� CC1S (2 -gang) (0.23) j!� l f -; Ti SIGA- Intelligent Synchronization Output Module 0.18 ,2=:0 MCC1S (Plug -in UIO) (0.08) 0 / r c x -, : . g Feld Configurable Ceiling Strobes maybeordered ;,s` `' "rr '�.'' with or withoutoptional 'FIRE' marldng. Field Configuration Depending on the model, Genesis ceiling / Candela switch strobes may be set for 15 to 95, or 95 to 177 candela output (see ordering informa- �® tion). The output setting is changed by simply opening the device and sliding the switch to the desired setting. The strobe \ r does not have to be removed to change the output setting. The setting remains Indicator Cr visible through a small window on the front of the device after the cover is closed. Wiring Field wiring terminals accommodate #18 to #12 AWG (0.75 mm to 2.5 mm wiring. Strobes are interconnected with a single pair of wires as shown below. 11 To listed To next fire alarm To or • control I 0f� (f� ri end of Panel �� device ti ti • WARNING: These devices will not operate without electrical power. As fires frequently cause power interruptions, we suggest you discuss further safe- guards with your local fire protection specialist. These visible signal appliances' flash intensity may not be adequate to alert or awaken occupants in the protected area. Research indicates that the intensity of strobe needed to awaken 90% of sleeping persons is approximately 100 cd. EST Genesis and FullLight Strobe Technology are trademarks of recommends that strobes in sleeping rooms be 110 cd minimum. Edwards Systems Technology, Inc. EDWARDS SYSTEMS TECHNOLOGY It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST. m 2004 EST Printed in U.S.A. (origin) Page 4 of 4 Literature Sheet #85001 -0557 • Issue 3 Not to be used for installation purposes. For the most current literature and updates visit www.est.net. A product of EST Marketing, Sarasota, FL • • r ' „tea . at low „rail . T ce d: 1 hs e s t' r ows = 1" 00ixay °n' , S _ • EDWARDS SYSTEMS TECHNOLOGY , �.. NOTIFICATION APPLIANCES Compatibility 4 QuickStart FireShield EST2 EST3 LSS4 IRC-3 /FCC Temporal Horn and Horn - strobe 757 Series Patented Features • UL 1971 - listed synchronizing strobe ' ai Integrity strobes synchronize to the latest UL 1971 requirements when used with an extemal control module (G1M or SIGA-CC1S). h ..;r k_ _• • Adjustable Audible Output Select temporal or continuous tones, and High setting for 98 dBA output or Low setting for 94 dBA sound output. _ (E) MEA (E • Genesis - compatible • Can be mixed with Genesis signals. All Genesis and Integrity - strobes on the same circuit meet UL 1971 synchronization requirements when used with an external control module. • Approved for public and private mode applications UL 1971- listed as signaling devices for the hearing impaired and UL 1638 - listed as protective visual signaling appliances. Integrity's rugged plastic housing is made from durable and fire ■ Satisfies ADA code requirements retardant, high impact plastic with a slightly textured surface. Its • Integrity strobes provide the "Equivalent Facilitation" allowed ingenious mounting plate firmly holds the device in place with a under ADA Accessibility Guidelines. A single strobe in rooms up single screw. A separate trim plate is not required. Terminals to 50 ft x 50 ft satisfy both ADA and NFPA codes. accept up to #12 AWG (2.5mm wire for polarized connections. ■ Low pitched "growl" tone HORN: During installation, the horn is configured for steady or Demands attention and provides superior wall penetration. temporal tone signal and either low (94 dBA) or high (98 dBA) • Durable red or white Noryl front plate output. When temporal output is selected all horns on a common Ideal for outdoor, industrial or harsh environments. two -wire circuit are self- synchronized (see specifications). External control modules are not required for audible synchronization. • Field changeable field markings Lens language or standard 'FIRE" marking is easily changed with STROBE: As part of the Enhanced Integrity line of products, 757 optional LKW and LKC series lens kits. Series strobes exceed UL synchronization requirements (within 10 • Screw terminal wire connection milliseconds other over a two -hour period) when used with a Large terminals speed installation and accept up to #12 AWG separately - installed G 1 M Signal Master or SIGA -CC1 S Synchroni- (2.5mm wire. zation Module. They are fully compatible with Genesis signals. • Easy Installation Synchronization is important because a small portion of the Flush mount to standard North American 4' square or two -gang population have a condition which may cause them to become box. Integrity's universal mounting plate allows it to be wired disoriented from multiple random flashes of light. Integrity strobes and then left hanging free for easy inspection and testing before it minimize this risk. is fastened to the electrical box. Strobes are shipped with standard wall mount style "FIRE" lens markings. Where ceiling orientation, other languages, or different Description lens markings are required, EST offers optional LKW and LKC Integrity temporal horns and temporal horn - strobes are specially series Lens Marking Kits. These optional lens markings simply snap designed for use with compatible life safety communication and on to the strobe. Consult EST for availability of special lens control equipment to alert occupants of a life safety event. The markings. horn emits a piercing low frequency sound that is easily heard Integrity horns and horn - strobes are designed for 20 to 31 Vdc above moderate ambient noise levels. The flash from its strobe can operation and must be connected to signal circuits that output a be noticed from almost any position in the room, corridor, or constant (not pulsed) voltage. A diode is used to allow full signal large open space. circuit supervision. EDWARDS SYSTEMS TECHNOLOGY U.S. SALES: SARASOTA, FL 941 - 739 FAX 941 • CANADA SALES: OWEN SOUND, ON 519 - 376-2430; FAX 519 INTERNATIONAL SALES: 905. 270 - 1711, FAX 905. 270.9553 • CORPORATE HEADOUARTERS: CHESHIRE, CT • US. MANUFACTURING: PITTSFIELD & NEWPORT, ME Issue 5 Literature Sheet #85001 -0341 Page 1 of 4 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. 1. . , , ••., • Horn Application Suggested sound pressure level for each signaling zone used with published by EST Press, or contact your local EST representative. • alert or alarm signals is at least 15dB above the average ambient sound level, or 5dB above the maximum sound level having a Sleeping rooms: EST 110 cd strobes are intended for use in duration of at least 60 seconds, whichever is greater, measured 5' sleeping rooms and should be installed along with a smoke (1.5m) above the floor. The average ambient sound level is the RMS, detector. It must be wall mounted at least 80" (2.03 m) above floor A- weighted sound pressure measured over a 24 -hour period. level, but no closer than 24° (610 mm) to the ceiling. The distance from the strobe to the pillow must not exceed 16' (4.8 m). Doubling the distance from the signal to the ear will theoretically result in a 6 dB reduction of the received sound pressure level. The actual Sleeping Rooms EST wall mounted strobe effect depends on the acoustic properties of materials in the space. A 3 Any size _ 110 cd within 16 feet of pillow dBA difference represents a barely noticeable change in volume. Application Notes - USA Typical Sound Output OxitPut Angle - Degre Audible signals should never have a sound level Tess than 75 dBA at dBA measDistribution ed at 10 ft -1 ♦'s s�+o 15 10' (3m) per NFPA 72. Signals cannot exceed 120 dBA per ADA ♦ + s+ ••ion 30 (130 dBA per NFPA 72) at the minimum hearing distance to audible 757 Series anechoic chamber - 45 oral ♦ ♦ • ��aI ���ilfi • � #0 ♦ ♦ • • ♦ appliance. Audible signals shall be installed with the top ofthe device ♦ ®: �, 4 ti i�Ai In °® ♦ • l above the floor not less than 90• (2.3m) and below the finished ceiling Horn ('HIGH'output) ♦� 4' 4; �1 �'+OA at least 6°(150 mm) (per NFPA 72). 75 � e \,1 ..'sat Strobes must be used tosupplementaudiblesignalswhereverthe .90 a�t,� "' // _!ari • . average ambient sound level exceeds 105 dBA. Combination 105 95 85 75 dBA 75 85 95 105 AudibleNisible signals must be installed per NFPA guidelines — Temporal Horn (dBA) established for strobes. Strobe Application ADA suggests that the following areas may require Visual Alarm Signals: EST strobes are UL 1971 - listed for use indoors as wall- mounted • rest rooms, meeting rooms, and other general usage areas. public -mode notification appliances for the hearing impaired. • lobbies, hallways, and other common use areas. Prevailing codes require strobes to be used where ambient noise • sleeping rooms intended for use by persons with hearing conditions exceed 105 dBA (87dBA in Canada), where occupants use impairment (per Title 1 of ADA). hearing protection, and in areas of public accommodation as defined • work areas used by a person with a hearing impairment (per in the Americans with Disabilities Act (see application notes- USA). Title 1 of ADA). Combination horn - strobe signals must be installed in accordance Application Notes - CANADA with guidelines established for strobe devices. pp Based in part on 1995 Canada National Building Code - The fire Strobes alarm signal sound pressure level shall not exceed 110 dBA in any The following guidelines are based on ANSI /NFPA 72 National normally occupied area. The sound pressure level from an audible Fire Alarm Code (1999). When applied and installed in accordance signal in a floor area used for occupancies other than residential with that code, EST strobes meet or exceed the illumination occupancies shall be not less than 10 dBA above the ambient produced by the ADA- specified 75 candela (cd) strobe at 50 feet.* noise, and never less than 65 dBA. The sound pressure level in sleeping rooms from an audible signal shall not be less than Non - Sleeping Rooms EST wall mounted strobes* 75 dBA when any intervening doors between the device and the Up to 20' x 20' (6.1 m x 6.1 m) One 15 cd strobe sleeping room are closed. Audible signal devices shall be Up to 30 x 30 (9.1 m x 9.1 m) One 30 cd or two 15 cd strobes installed not less than 1.8 m to the center of the device above the Up to 40' x 40' (12.2 m x 12.2 m) One 75 cd or two 30 cd strobes floor (per CAN/ULC S524). Up to 50' x 50' (15.2 m x 15.2 m) One 110 cd or two 75 cd strobes The fire alarm audible signal shall be supplemented by fire alarm Corridors Strobes in any floor area where the ambient noise level exceeds 15 cd strobes spaced at 100' 87 dBA, or where the occupants of the floor area use ear protective Any length. (30.5 m) max. Strobes must be devices, are located within an audiometric booth, or are located Maximum width: 20' (6.1 m). placed within 15' (4.5m) of each within sound insulating enclosures. This also applies to assembly end of the corridor. occupancies in which music and other sounds associated with • ADA suggests using 75 cd strobes throughout an area, with spacing that never performances could exceed 100 dBA. exceeds 50 ft from the strobe to any point in the protected space. Strobes shall be installed in a building so that the flash from not Non - Sleeping Rooms and Corridors: EST strobes rated at less than less than one device is visible throughout the floor area or portion 110 cd per UL 1971 are intended for use in non - sleeping areas only. thereof in which they are installed. For maximum safety, EST Install with the bottom of the device at least 80 inches (2.0 m) and no recommends that strobes be installed as per the guidelines shown more than 96 inches (2.4 m) abovethe finished floor. No point in any here under Strobe Application. space (including corridors) required to have strobes should be more than 50 feet (15.2 m) from the signal (in the horizontal plane). For detailed spacing requirements, consult The Handbook of Fordetailedspacingrequirements ,consult TheHandbookof Visible Notification Appliances for Fire Alarm Applications Visible Notification Appliances for Fire Alarm Applications published by EST Press, or contact your local EST representative. EDWARDS SYSTEMS TECHNOLOGY Page 2 of 4 Literature Sheet 185001 -0341 Issue 8 Not to be used for installation purposes. For the most current literature and updates visit www.est.net. Specifications • Standalone Synchronization Strobe flash at 1 per second within 200 milliseconds on common circuit l • Characteristics (note 2) Hom pulses at temporal rate within 200 milliseconds on common circuit Operating Volts Strobe: 20 -24 Vdc Continuous; Horn: 20 -31 Vdc Continuous Rated Strobe Output - candela (cd) 757 -1A -T 757 -7A -T 757 -8A -T illE UL 1971 15 cd wall 110 cd wall N/A 15 cd ceiling 60 cd ceiling (horn only) UL 1638 8 ULC 5526 75 cd 110 cd Anechoic: High Setting - 104 dBA (peak) /98 dBA (avg); Low Setting - 99 dBA (peak1/94 dBA (avg) Horn Output (note 1) Reverberant: High Setting - 85 dBA (continuous)/82 dBA (temporal); Low Setting - 82 dBA (continuous)/75 dBA (temporal) Hom Current High Output: 40 mA @ 24 Vdc; 55mA @ 24 Vrms FWR; Low Output: 20 mA @ 24 Vdc; 28 mA @ 24 Vrms FWR Strobe Flash Synchronization Synchronized at one flash per second. Extemal control module necessary to meet UL 1971 synchronization requirements of 10 milliseconds over a two -hour period. Compatible Synchronization Modules G1M, G1M -RM, SIGA -CC1S, SIGA-MCC1S Strobe Marking Supplied with LKW -1 'FIRE' red letters, vertical both sides (Wall Mount) - see LKW and LKC series for ceiling style and optional markings. Rash Tube Enclosure Clear LEXAN with white marking sleeve Housing Textured, color impregnated engineered plastics - exceeds 94V-0 UL flammability rating Wire Connections Terminals - separate, polarized inputs for Hom & Strobe, *12 AWG (2.5mm maximum INDOOR Operating Environment 32 -120° F (0-49° C) ambient temperature. 93% relative humidity @ 40° C OUTDOOR Operating Environment 98% relative humidity @ 40° C; -35 -150° F (- 31 -66° C) ambient temperature (must use weatherproof box) (757 -7A: rated at 17.7 cd @ -35° C per UL/@ -40° C per ULC) (757 -8A: rated at 70.7 cd @ -35° C per UL/@ -40° C per ULC) . Flush: North- American 2 -gang box, 3' high x 4' wide x 21/4' (69 mm) minimum Mounting - INDOOR Surface: 757A -S8 Back box Bi- directional: 757A -BDF Mounting Frame Mounting - OUTDOOR Surface: 757A -WB Weatherproof Box • Agency Listings UL 1971, UL 1638, UL 464, ULC S526, ULC S525, MEA, CSFM, FM. CE • (AU models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule) Note 1 - Measured at l0 ft (3m) @ 24 Vdc. Subtract 3 dBA for models with strobes. Note 2 - Temporal audible pattern is defined as:'%sec ON, 1/2 sec OFF, 'A sec ON,'%see OFF, 1/2 sec ON, 1 % sec OFF, then repeat cycle. Light Output Patterns Current Draw 7A' Series Strobe 8 Notes and Comments Typical Current (measured by EST) vuw 4e Vertical Output 1. Current 15/75 cd 110 cd -w •9475 **p, '""'° ° sh 100 40 750 RMS Mean Peak RMS Mean Peak lii '-45 ° "m ° " 2. ULName IateRatin 9 20 Vde 121 115 277 248 241 402 � '�P ar 11 IP /I.30 1 001 1l �� / ; 30 can vary from Typical "O"°"a y_ I 50 ��1��/���_ 15 !r7 - �� 15 Current due to 24 Vde 101 96 204 203 197 338 p ' ASV Ire g 50 7l �, 1 measurement methods 31 Vde 81 76 173 155 151 280 cd cd d 0 m �f y; 0 and instrumentsused ; g Vfwr 168 97 452 342 202 868 � � \ \ 15 a 50 II�� *.�a15 3. EST recommendsus 24 Vfwr 146 79 446 286 159 788 { 50 11 1`�` ���3° Ilt\\\ � %30 the Typical Cu rrent for UL Ratin9 ,f 111` ` 45 system design including 15/75 ed 110 cd " 100 90 5 150 45 1 90,`5 NACandPowerSuPPIY RMS Mean Peak RMS Mean Peak loading and voltage 20Vde 113 107 248 228 222 420 drop calculations. 7A' Series Strobe '8A' Series Strobe 4 Use the Vdc RMS 24 Vde 90 85 214 180 175 360 Horizontal Output Horizontal Output currentretin for 31 Vdc 65 62 174 125 122 280 degrees degrees 15 0 5 15 0 5 filtered power supply 20 Vfwr 153 81 540 327 177 952 X530 11111/ 30 a5 30 `•s seae� a, 30 45 and battery AH 24 Vfwr 128 64 412 260 _ 134 808 `f\� ��� ` . •• " • e• ° � 4 5 calculations.Use Q�� / j �� ;. Vfwr RMS current ratings for unfiltered power supply calculations. �` j �� 5 -7 ,4 �`(� •a SS 75 5. Fuses, circuit breakers and other overcurrent protection devices are typically .90�== f( =��90 -'s .. . x::90 rated for current in RMS values. Most of these devices operate based upon the 100 50 cd 50 100 200 100 cd 100 200 heating affect of the currentflowing . TheRMScurrent(not 0""""° 1°aW.I.Mil 111= -•°,al 10°01~! I=J the mean current) determines the heating affect and therefore, th e trip and hold threshold for th ose devices. 6. Our industry has used 'mean' currents over the years. However, UL will direct the industry to use the 2004 RMS values in the future. EDWARDS SYSTEMS TECHNOLOGY Issue 5 Literature Sheet •88001 -0341 Page 3 of 4 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. • Installation and Mounting -- o North American 2-gang electric box, 2W (69mm) minimum All models fit to a standard flush mounted, North- ► ^ O (Alternative: 4' square box • American two -gang electrical box, 2'/4 inch (69 mm) 2 -Ire' (54mm) deep) minimum. Optional flush trims are not required. For Mounting Plate (provded) . surface mount, use EST's custom indoor and I outdoor surface boxes painted in color-matched red o r white epoxy. EST recommends that fire '�® alarm horn /strobes always be installed in accord- ance with the latest recognized edition of national ` �, 1114141071‘% and local fire alarm codes. � I� . I , �M6 32 screws (by others) Su rfa ce Box - 5.5/6' (143mm) sq. x • Housing 3.9/16' (91 mm) deep Typical Wiring , 5-1n (140mm) x 5-12' (140mm) x 5/6' (16mm) The strobe must be connected to signal circuits Single Mounting Screw (provided) which output a constant (not pulsed) voltage. The horn can be connected to continuous voltage circuits. HORN and STROBE RUT OEYICE ON SAME CIRCUIT MoneRaabs Ilawillebe T Ordering Information Rre Alarm Control Snl we= Pend Signet Chant c ,� �^! Catalog Ship Wt. 'te ro Next Device Number Description Ib. (kg) - or Eat Resistor Temporal Horns >+ 7 57 -1A -T+ 'Temporal Horn, Red 1 1.7 (0.8) HORN and STROBE - Temporal Horn- Strobes ON SEPARATE CIRCUIT + 757 -7A -T` Temporal Horn - Strobe, 15/75cd, Red To utnnc Listed . T o nod Dolce 2.0 (0.9) Fire Alarm Control a E0L Resistor 757$A -T• Temporal Horn - Strobe, 110cd, Red Panel Signal Circuit Synchronization Modules utn roncListed + E G G1M -RM Genesis Signal Master 0.2 (0.1) Rre - -a a To neat Strobe Device Remote Mount (1 -gang) Panel Signal Cease erEOtismr Synchronization Output Module SIGA -CC1S 0.5 (0.23) . (Standard Mount) SIGA -MCC1S Synchronization Output Module 0.18 (0.08) d BA output (UIO Mount) p Mounting Accessories Hom strobes 757A -SB• Surface Box, Red, Indoor 1.5(.7) High dB UL464 Average Peak 757A -WB+ Weatherproof Box, Red, Surface 1.5(.7) Output Temporal Steady Temporal 1 Steady Temporal 1 Steady 757A - BDF+ Bi - directional Frame, Red 4(1.8) 20 Vdc 79.0 82.0 93.5 100.0 Lens Marking Kits (see note 1) 24 Vdc 79.0 _ 85.0 _ 97.0 102.0 LKW -1 "FIRE ", Wall Orientation (supplied) LKW -1R "FIRE ", Wall Orientation, RED Low dB UL464 Average Peak LKW -2 "FEU ", Wall Orientation Output Temporal Steady Temporal 1 Steady Temporal 1 Steady LKW - 3 "FIRE/FEU ", Wall Orientation 20 Vdc 75.0 79.0 89.2 95.4 LKW - 4 "SMOKE ", Wall Orientation 0.1 24 Vdc _ 75.0 _ 79.0 93.0 98.0 LKW - 5 "HALON ", Wall Orientation (.05) LKW -6 "CO2", Wall Orientation Horns LKW -7 "EMERGENCY ", Wall Orientation High dB UL464 Average Peak LKW -8 "ALARM ", Wall Orientation Output Temporal Steady Temporal 1 Steady Temporal 1 Steady LKW -9 "FUEGO ", Wall Orientation 20 Vde 79.0 82.0 97.0 102.5 • Add Suffix "W" to catalog no. for WHITE. (e.g. 757- 7A -TW) 24 Vde 82.0 85.0 98.0 104.0 Note 1 - Change "W" to 'C" for CEILING mount. (e.g. LKC -1) Low dB UL464 Average Peak Output Temporal Steady Temporal /Steady Temporal /Steady WARNING: These devices will not operate without electrical power. As fires 20 Vde 75.0 79.0 92.3 98.4 frequently cause power interruptions, we suggest you discussfurther safeguards 24 Vde • 75.0 82.0 94.0 99.0 with your local fire protection specialist. These visual signal appliances' flash intensity may not be adequate to alert or waken occupants in the protected area. • • All values shown are d BA measured at 10 feet (3.01m). Research indicates that the intensity of strobe needed to awaken 90% of sleeping • UL1 450 values measured in reverberation room. persons is approximately 100 cd. EST recommends that strobes in sleeping rooms • Average values are measured in anechoic chamber. be 110 cd minimum. EDWARDS SYSTEMS TECHNOLOGY it is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST. O 2003 EST Rimed in U.S.A. (origin) Page 4 of 4 Literature Sheet *85001 -0341 Issue 5 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. AproductofESTMarketing ,Sarasota,FL