Correspondence - R goo,s-z, A August 31, 2005 CITY OF TIGARD OREGON American Heating Inc Dale Hammett 1339 SE Gideon St Portland, OR 97202 RE: TI MECHANICAL SYSTEM — CADENCE Project Information Building Permit: MEC2005-00522 Occupancy Type: B Tenant Name: Cadence Construction Type: II- B Address: 13221 68 Parkway4 /0() Occupant Load: 47 Area: unk Sq Ft Stories: The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; The submitted plans are approved subject to the following. 1. The building or structure shall not be weakened by the installation of mechanical systems. Where floors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with the Building Code. The cutting, notching and boring of framing members shall comply with OMSC 302 Sections 302.3.1 through 302.5.3. 2. Ducts shall be supported with approved hangers at intervals not exceeding 10 feet or by other approved duct support systems designed in accordance with the Building Code. Flexible and other factory-made ducts shall be supported in accordance with the manufacturer's installation instructions. 603.10 OMSC 3. Metallic Ducts shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) — Metal and Flexible. OMSC 603.4 4. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 5. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Mercury Thermostats. The State of Oregon prohibits the installation of thermostats that contain mercury in commercial and residential buildings. "In accordance with ORS 455.355, the disposal of thermostats that contain mercury shall be in accordance with programs established by thermostat manufacturers, their representative or distributor, or by delivery to sites that will ensure that the mercury does not become part of the solid waste stream or wastewater." Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. 4. ly, Val Henzel, Senior Plans Examiner �f 1 FIRE ALARM SYSTEM INSPECTION CERTIFICATION Facility Name: PLAZA WEST Monthly Quarterly Address: 9600 SW OAR Sent-Annual Annual X (My/State/Zip: TIGARD, OR 97223 Teat Date 6 -4 -96 Operator: 94 I Panel In test 9:00a 1 Panel out of test NOON Control Panel: Type: HARDWIRE It of zones: 6 ModetF FC 72 # of zones used: 6 Non -Reset voltage: 26 # of panel audible circuits: 2 Reset voltage: 26 Battery voltage: 13/13 Communication Circuit(s) voltage: N / A Verify fuses: # 1 , 2. 3, 4 , 5, AC Auxiliary Panels: . Audible circuit expander. Type and size: N / A Batteries voltage: Power supplies: Type and size: N / A Function: Battery voltage: Auto Olaier: Type SR 5107 Battery voltage: 13 Devices Tested: (Attach printout if available) Smoke detector 10 Meet detector 0 Pull Statton7 0 Sprinkler FIT: 0 Duct detector: 0 Audible signals tested: Yes. No- Panel Outputs Tested: Auto dialer: # of zones sent off Site 6 Alarm 5 Trouble 1 # of zones received: 6 Alarm 5 Trouble 1 Zones Rested 6 Yes: X Na Door holder Number 8 Results: OR Elevator recall: NO Number of cabs: Results: MVAC Shia: Number of NO • units: Results: Test Results: Panel returned to normal: Yes: X No: ezneamaimmageommi -asap System deficiencies: PHONE LINE TWO HAS TALK VOLTAGE, BUT DIAL TONE DOES NOT APPEAR ON DEMAND. 4 EAST SMOKE DETECTORS ARE STILL DIS- CONNECTED DUE TO MULTIPLE FALSE ALARMS. Recommendations: HAVE PHONE COMPANY REPAIR PHONE LINE TWO. 4 SMOKE DETECOTRS ARE DISCONNECTED DUE TO MALFUNCTION CAUSING MULTIPLE FALSE ALARMS— ' REPLACEMENT OF DETECTORS IS PENDING — MANAGEMENT APPROVAL FOR UPGRADE. (PLEASE SEE ATTACHED PROPOSAL) Technician: ' 1 Date: T.wsw Advanced ServicesScooiration P.O. Box 55608 $ PORT LAY 1R 97238 -5608 + (503)287 -3889 + tax 287. FAX Date: August 12, 1996 To: Deborah• ASA Properties . Fax: 224 -5153 From: Tania Albert Regarding: Plaza West- Fire Alarm System Pages Including This Cover: 1 Message: Deborah: In response to your questions regarding the communication between your Fire Alarm Control Panel and your Monitoring Company, both of your phone lines appear to be communicating efficiently. In speaking with Operator 90 at Alarm Central Station, it was determined that there have been no reports of Phone Line Trouble or Failure in recent months, and I was also advised that your panel is sending a test signal consistently. All test signals are sent via the phone lines, therefore should your phone lines he in a trouble status, the monitoring company would be receiving no timer test, or a failure to communicate signal code. If you have any questions, or if I can be of further assistance, please do not hesitate to contact me. Thank you. Sinceroly, Tania L. Albert Office Manager