Loading...
Specifications lc Fire Alarm Submittal . _C)'°;) -41`- 6 4 ro.ROO6— od Z .2 - 2 -- 19" \I 2,- r' c * \C) O r \ � 0 Universit y of Phoenix T•I• Triangle Corporate Park Building III ii Prepared By: or Perjototaftee svaeffa Integration Corporation 7759 SW Cirrus Drive Beaverton, Oregon 97008 info @psintegrated.com (503) 641 -2222 (503) 641 -1464 Fax 5/24/2005 • • jil 4 EDWARDS SYSTEMS TECHNOLOGY INTELLIGENTINITIATING DEVICES • Compatibility - • QS4 /QS1 EST2 EST3 IRC-3 /FCC Intelligent Photoelectric . Smoke Detec Model SIGA -PS '/ • Note: Some features described here may not be supported by all control systems. Check your control panel's Installation and 1 • ": Operation Guide for details. ' Features ( ) f .'' . 0"" -'' ,d, - • Integral microprocessor '` — (E 8 e • Non - volatile memory MEA , Awilartion Available Notes • Automatic mapping device • Electronic addressing • Environmental compensation The information stored in the detector's memory includes: • Intelligent detector - detector type, serial number, and address • Wide 0.67% to 3.77 % /ft. sensitivity range - date of manufacture, hours of operation, and last maintenance date • Twentypre- alarmsensitivityvalues,setin5% increments' - current detector sensitivity and environmental compensation values • Identification of dirty or defective detectors - original detector sensitivity values upon manufacturing • Automatic day /night sensitivity adjustment - number of recorded alarms and troubles • Twin RED /GREEN status LEDs - time and date of last alarm' • Standard, relay, fault isolator, and audible mounting bases - analog signal patterns just before the last alarm' • Designed and manufactured to ISO 9001 standards - most recent trouble code logged by the detector —32 possible trouble codes may be used to diagnose faults. Description In the unlikely event that an unwanted alarm does take place, the P control panel's history file can be called up to help isolate the EST's Signature Series Model SIGA -PS Intelligent Photoelectric problem and prevent it from happening again. Smoke Detector gathers analog information from its smoke sensing element and converts it into digital signals. The detector's on- Automatic Device Mapping - The loop controller learns where board microprocessor measures and analyzes these signals. It each device's serial number address is installed relative to other compares the information to historical readings and time patterns devices on the circuit. The mapping feature provides supervision to make an alarm decision. Digital filters remove signal patterns of each device's installed location to prevent a detector from that are not typical of fires. Unwanted alarms are virtually elimi- being reinstalled (after cleaning etc.) in a different location from • Hated. where it was originally. The history log for the detector remains The microprocessor in each detector provides four additional benefits relevantand intact regardless of its new location. - Self-diagnostics and History Log, Automatic Device Mapping, The Signature Series Data Entry Program also uses the mapping Stand -alone Operation and Fast, Stable Communication. feature. With interactive menus and graphic support, the wired Self- diagnostics and History Log - Each Signature Series detector circuits between each device can be examined. Layout or "as- built" drawing information showing wire branches (T-taps), device types Constantly runs self - checks to provide important maintenance and their address are stored on disk printing hard copy. This information. The results of the self -check are automatically updated takes the mystery out of installation. The preparation of "as- built" and permanently stored in the detector's non - volatile memory. drawings isfast and efficient. This information is accessible for review any time at the control panel, PC, or by using the SIGA -PRO Signature Program /Service Device mapping allows the Signature loop controller to discover: Tool. - unexpected additional device addresses - missing device addresses ' EST3 V.2 only. 'Retrievable with SlGA -PRO programming tool. - changes to the wiring in the circuit. EDWARDS SYSTEMS TECHNOLOGY U.S. SALES: SARASOTA. FL941- 7394638; FAX 941-727-1214 • CANADA SALES: OWEN SOUND, ON 519-376-2430; FAX 519-376-7258 INTERNATIONAL SALES: 905. 270- 1711; FAX 905- 2709553 • CORPORATE HEADQUARTERS: CHESHIRE, CT • US. MANUFACTURING: PITTSFIELD6 NEWPORT, ME Issue 8 Literature Sheet #86001 -0289 Page 1 of 4 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. Stand -alone Operation: A decentralized alarm decision by the Status LEDs: Twin LEDs are visible from any direction. Aflashing detector is guaranteed. On -board intelligence permits the detector GREEN LED shows normal system polling from the loop to operate in stand -alone mode. If loop controller CPU communi- controller. Aflashing RED LED means the detector is in alarm cations fail for more than four seconds, all devices on that circuit state. Both LEDs on steady shows alarm state - stand -alone mode. go into stand -alone mode. The circuit acts like a conventional alarm Normal GREEN LED activity is not distracting to building occupants, receiving circuit. Each detector on the circuit continues to collect but can be quickly spotted by a maintenance technician. and analyze information from its surroundings. The detector alarms Quality and Reliability: EST detectors are manufactured in North if the preset smoke obscuration level is reached. If the detector is America to strict international ISO 9001 standards. All electronics mounted to a relay base, the relay operates. Similarly, if it is utilize surface mount technology (SMT) for smaller size and greater mounted to an audible base, the on -board horn sounds. immunity to RF noise. A conformal coating is used for humidity Fast Stable Communication: On -board intelligence means less and corrosion resistance. All critical contacts are gold plated. information needs to be sent between the detector and the loop controller. Other than regular supervisory polling response, the detector only needs to communicate with the loop controller when Installation it has something new to report. This provides veryfast response time and allows a lower baud rate (speed) to be used for Signature Series detectors mountto North American 1 -gang communication on the loop. The lower baud rate offers several boxes, 3 -1/2 inch or 4 inch octagon boxes, and to 4 inch square advantages including: electrical boxes 1 -1/2 inches (38 mm) deep. They mount to - less sensitivity to circuit wire characteristics European BESA and 1 -gang boxes with 60.3 mm fixing centers. - less sensitivity to noise glitches on the cable - less emitted noise from the data wiring (20 mm) - twisted or shielded wiring is not required. Electronic Addressing: The loop controller electronically ad- 2.0' (51 mm) dresses each detector, saving valuable time during system �� commissioning. Setting complicated switches or dials is not �o ` required. Each detector has its own unique serial number stored in q.q (112 mm) its "on -board memory". The loop controller identifies each device _ on the circuit and assigns a "soft" address to that device's serial 11- - �I ►;- number. If desired, detectors can be addressed using the SIGA- PRO Signature Program/Service Tool. Tamper - Resist Lever Arm - Break off to disable - Compensation: Detection sensitivity is virtually (Located on Base) s independent of its installed environmentand its physical condition. Environmental compensation meansthe sensing elementadapts to long -term changes caused by dirt, humidity, aging etc. It even com- Access slat for pensatesfor small amounts of normal ambient smoke. Approximately Tamper - Resist Mechanism , i +}. sox times every hour the detector adjusts and updates the sensitivity (/o obscuration) baselinefor its sensing element. Approximately ? " ® a; once every hour this information is written to its permanent memory. °' The detector's "learned" baseline is not lost, even when the detector is removed for cleaning. Signature Series environmental Testing �t Maintenance compenstion is so reliable that it meets NFPA72 field sensitivity testing requirements — without the need for external meters. Each detector automatically identifies when it is dirty or defective The detector's sensitivity setting selected bythe installerfloats up and causes a "dirty detector" message. The detector's sensitivity or down to remain constant relative to the changing baseline. This measurement can also be transmitted to the loop controller. A is called differential sensing. sensitivity report can be printed to satisfy NFPA sensitivity meas- Sensitivity Range: The SIGA -PS Photoelectric Detector has a urements which must be conducted at the end of the first year and everytwo years thereafter. sensitivity range or window of 0.67% to 3.77 %. The installer .� selects the detector's ALARM sensitivity level from five available The user - friendly maintenance program shows the current state of settings within the range. each detector and other pertinent messages. Single detectors may be turned off temporarily from the control panel. Availability of Pre- Alarm: The detector stores one of 20 pre -alarm sensitivityvalues maintenancefeatures is dependent on thefire alarm system used. to alert local personnel prior to the sensor reaching a full evacuation Scheduled maintenance (Re ularorSelected)for proper detector sensitivity. Sensitivity values can be set in 5% increments.' operation should be planned to meet the requirements of the Automatic Day /Night Sensitivity Selection: Signature Series Authority Having Jurisdiction (AHJ). Refer to current NFPA72 and detectors may be programmed for different sensitivities during day ULCCAN/ULC 536 standards. and night periods. This allows the detector to be more sensitive during unoccupied periods when lower ambient background conditions are expected. Compatibility Stability: The SIGA -PS detector's sensitivity remains stable in wind The SIGA -PS detectors are compatible only with EST's Signature velocities upto 5,000ft/min (25.3 m /sec). Ambient temperature has Loop Controller. very little affect on the detector. The detector may be installed in rooms with ambienttemperatures up to 120 °F (49 °C). ' EST3 V.2 only. EDWARDS SYSTEMS TECHNOLOGY Page 2 of 4 Literature Sheet #85001 -0289 Issue 8 Not to be used for installation purposes. Application Although photoelectric detectors have a wide range of fire sensing capabilities they are best suited for detecting slow, smoldering fires. - The table below shows six standard testfires used to rate the sensitivity of smoke and heat detectors. The table indicates that no single sensing element is suitedfor all testfires. - EST recommends that this detector be installed according to I test recognized edition of national and local fire alarm codes. Type of Detector SIGA -HRS and SIGA -HFS Rate -of SIGA -PHS Photo /Heat SIGA -IPHS Test Fire SIGA -IS Ion SIGA -PS Photo -Rise /Fixed Temp. 3D Ion /Photo /Heat 4D Open Wood optimum unsuitable optimum very suitable optimum Wood Pyrolysis suitable optimum unsuitable optimum optimum Smouldering Cotton very suitable optimum unsuitable optimum optimum Poly Urethane Foam very suitable very suitable suitable very suitable optimum n- Heptane optimum very suitable very suitable optimum optimum Liquid Fire without unsuitable unsuitable optimum very suitable very suitable Smoke Typical Wiring The detector mounting bases accept #18AWG (0.75mm #16 (1.Omm #14AWG (1.5mm and #12 AWG (2.5mm wire sizes. Note: Sizes #16 AWG (1.0mm and #18 AWG (0.75mm are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Standard Detector Base, SIGA -SB, SIGA -SB4 Relay Detector Base, SIGA -RB, SIGA -RB4 Normally Normally- Term Description Remote LED Term Descrlptlon Common Closed Open 1 Normally Open (SIGA - LED) 1 Not Used Max. Resistance 2 DATA IN/OUT ( +) 2 DATA IN /OUT ( +) • It ■ per Wire 3 Not Used 3 Common _ + Must NOT Exceed 100 4 DATA IN ( -) 4 Not Used Fri 4 DATA IN ( -) 4 Remote LED ( -) 5 Remote LED ( +) . • :: �, \ 5 Normally - Closed \ 6 Not Used 6 DATA OUT ( -) 14 7 DATA OUT (-) 1 / l .2.:� A CONTACT RATING — 1.0 Amp 30 VDC IP _ 4�� DATA IN ( -) i DATA OUT ( -) (Pilot Duty) I DATA IN ( -) O �" z / DATA OUT ( -) DATA IN ( +) DATA OUT ( +) DATA IN ( +) DATA OUT ( +) From Signature Controller To Next Device From Signature Controller To Next Device or Previous Device or Previous Device Isolator Detector Base, SIGA -IB, SIGA -1B4 Audible Detector Base, SIGA -AB4G e o o c Term Description 1 Not Used Volume setting Tone setting b 6 ` , 2 DATA IN /OUT (+) High Default = Temporal pattern ( ) Default = r l h volume O "0!� o.` 0 3 DATA IN ( - Cut for low volume ® Cut for steady tone • ,r". o' 4 N o t U CD v IV" _ ate.. PAW WA* „C o 5 Not Used K 6 DATA OUT (-) � o ' ; 0 • cs, 7 Not Used i:�.r�i r�.r. +1 To configure output volume tcQ 101010.10.101 or tone, cut the circuit board DATA IN ( -) ' \ z � O DATA OUT ( -) ' ' ' ' ' 8s shown. 1111111 24 Vdy or . ■-■' 24 Vdc out From power supply or . 111 - To next base or EOL relay • DATA OUT (+) previous base DATA IN ( +) To Next Device D ata In From Signature Controller - Data out or Previous Device From Signature controller or • To next Signature device previous device EDWARDS SYSTEMS TECHNOLOGY Issue 6 Literature Sheet #85001 -0289 Page 3 of 4 Not to be used for Installation purposes. Accessories Warnings Er Cautions All detector mounting bases have wiring terminals that are This detector will not operate without electrical power. As fires accessible from the " room - side" after mounting the base to the frequently cause power interruption, we suggest you discussfurther . electrical box. The bases mount to North American 1 -gang boxes safeguards with your fire protection specialist. and to 31/2 inch or 4 inch octagon boxes, 1 inches (38 mm) deep. This detector will NOT sense fires that start in areas where smoke They also mount to European BESA and 1 -gang boxes with 60.3 cannot reach the detector. Smokefrom fires in walls, roofs, or on the . mm fixing centers. The SIGA-SB4, SIGA-RB4, and SIGA -IB4 mount opposite side of closed doors may not reach the detector to arm it. to North American 4 inch sq. electrical boxes in addition to the above boxes. They include the SIGA -TS4 Trim Skirt which is used to cover the "mounting ears" on the base. The SIGA -AB4G mounts to a 4" spare box only. Specifications � =�. Catalog Number SIGA -PS r • °. ?, Sensing Element Photoelectric - Light Scattering Principle it ; v 1 • ,� -`� Storage & Air Velocity Range: 0 to 5,000 ft/min (0 to 25.39 m/s); �� Operating Humidity: 0 to 93% RH, Non-C SIGA -AB SIGA•SB SIGA -IB SIGA -its SIOA -LED Environment Operating Temp: 32 F to 120 F (0 C to 49 C); Audible Base Standard Base Isolator Base Relay Base Remote LED Storage Temp: - 4°F to 140 °F ( - 20 °Ct0 60 °C) Sensitivity Range ULI/ULC - 0.67% to 3.77% obscuration/foot Standard Base SIGA -SB, SIGA -SB4 - This is the basic mounting User Selected Most Sensitive: 1.0 %/ft.; More Sensitive: 2.0 %/ft.; base for EST Signature Series detectors. The SIGA -LED Remote Alarm Sensitivity Normal: 2.5 %/ft.; LED is supported by the Standard Base. Settings Less Sensitive: 3.0%/ft.; Least Sensitive: 3.5 %/ft. - Relay Base SIGA -RB, SIGA -RB4 - This base includes a relay. Pre -alarm Sensitivity 5% increments, allowing up to 20 pre -alarm settings Normally open or closed operation is selected during installation. Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal) The dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relay's Quiescent: 45NA @ 19 V; Alarm: 45pA @ 19 V - position is supervised to avoid accidentally jarring it out of position. Operating Current Emergency Stand -alone Alarm Mode: 16mA The SIGA -RB can be operated as a control relay if programmed to Pulse Current: o0 NA (100 msec); P Y P 9 During Communication: 9 mA max. do so at the control panel (EST3 V.2 only). The relay base does not Construction 8 Finish High Impact Engineering Polymer - White supportthe SIGA -LED Remote LED. SIGA -SB Standard Base, Audible Base SIGA -AB4G - This base is designed for use where Compatible SIGA -RB Relay Base, SIGA -IB Isolator Base, g Mounting Bases SIGA -AB4, SIGA -AB4G Audible Bases localized or group alarm signaling is required. When the detector senses an alarm condition, the audible base emits a local alarm On -board Green LED - Flashes when polled; signal. The optional SIGA -CRR Polarity Reversal Relay can be used On -board Red LED - Flashes when in alarm for sounding to other audible bases on the same 24 Vdc circuit. LED Operation Both LEDs - Glow steady when in alarm (stand - alone) g Compatible Remote Red LED (model SIGA -LED) Relay and Audible Bases operate as follows: Flashes when in alarm - at system power -up or reset, the relay is de- energized Compatibility Use With: SIGNATURE Loop Controller - when a detector is installed in the base with the power Address Requirements Uses one Device Address on, the relay energizesfor four seconds,then de-energizes Agency Listings UL, ULC, MEA, CSFM - when a detector is removed from a base with the power on, UL Listed Spacing 30 ft the relay is de- energized - when the detector enters the alarm state,the relay is energized. Isolator Base SIGA -1B, SIGA - IB4 -This base includes a built -in line Ordering Information fault isolator for use on Class A circuits. A detector must be Catalog Ship Wt. installed for it to operate. The isolator base does not support the Number Description Ibs (kg) SIGA -LED Remote LED. Intelligent Photoelectric Detector The isolator operates as follows: SIGA -PS - UL/ULC Listed 51.23) - a short on the line causes all isolators to open within 23 msec Accessories - at 10 msec intervals, beginning on one side of the Class A SIGA -SB Detector Mounting Base - Standard - circuit nearest the loop controller, the isolators close to SIGA -SB4 4-inch Detector Mounting Base provide the next isolator down the line with power c/w SIGA -TS4 Trim Skirt - when the isolator nextto the short closes, reopenswithin 10 msec. SIGA -RB Detector Mounting Base w/Relay SIGA -R84 4 -inch Detector Mounting Base w/Relay, The process repeats beginning on the other side of the loop c/w SIGA -TS4 Trim Skirt .2 (.09) controller. Detector Mounting Base SIGA -IB w/Fault Isolator Remote LED SIGA -LED - The remote LED connects to the SIGA -SB or SIGA -SB4 Standard Base only. Itfeatures a North American size SIGA -IB4 4-1nch Detector Mounting Base 1 -gang plastic faceplate with a white finish and red alarm LED. w/ Fault Isolator, c/w SIGA -TS4 Trim Skirt SIGA -LED Remote Alarm LED SIGA -TS4 Trim Skirt - Supplied with 4 inch bases, it can also be SIGA -AB4G Audible (Sounder) Base .3 (0.15) ordered separately to use with the other bases to help hide surface SIGA -TS4 Trim Skirt (supplied with 4-inch bases) .1 (.04) imperfections not covered by the smaller bases. EDWARDS SYSTEMS TECHNOLOGY It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST. O 2004 EST Printed in U.SA Page 4 of 4 Literature Sheet #85001 -0289 Issue 8 Not to be used for installation purposes. C in tegr ity ,� >> ce d! Rnha noed is Ll� 19 _� JZI strobe _ "'ee a t ion s tr syn ch ron i entsi % kk k Pr X" requ ire "' ' EDWARDS SYSTEMS TECHNOLOGY T4 NOTIFICATION APPLIANCES Compatibility 4 QuickStart FireShield EST2 EST3 LSS4 IRC-3 /FCC Temporal Horn and Horn - strobe Patented I = ' ti 757 Series 4. Features II • UL 1971-listed synchronizing strobe 1 - ! • Integrity strobes synchronize to the latest UL 1971 requirements when used with an external control module (G1 M or SIGA-CC1 S). • Adjustable Audible Output — Select temporal or continuous tones, and High setting for 98 dBA output or Low setting for94dBAsoundoutput. (0) MEA ((© LC <> • Genesis - compatible Can be mixed with Genesis signals. All Genesis and Integrity strobes on the same circuit meet UL 1971 synchronization requirementswhen used with an external control module. • Approved for public and private mode applications UL 1971 - listed as signaling devices for the hearing impaired and UL 1638 - listed as protective visual signaling appliances. Integrity's rugged plastic housing is made from durable and fire retardant, high impact plastic with a slightly textured surface. Its • Satisfies ADA code requirements Integrity strobes provide the "Equivalent Facilitation" allowed ingenious mounting platefirmlyholdsthedeviceinplacewitha under ADA Accessibility Guidelines. A single strobe in rooms up single screw. A separate trim plate is not required. Terminals to 50 ft x 50 ft satisfy both ADA and NFPA codes. accept up to #12 AWG (2.5mm wire for polarized connections. • Low pitched "growl" tone HORN: During installation, the horn is configured for steady or Demands attention and provides superior wall penetration. temporal tone signal and either low (94 dBA) or high (98 dBA) • Durable red or white Noryl front plate output. When temporal output is selected all horns on a common two -wire circuit are self-synchronized (see specifications). External Ideal for outdoor, industrial or harsh environments. control modules are not required for audible synchronization. • Field changeable field markings Lens language or standard °FIRE° marking is easily changed with STROBE: As part of the Enhanced Integrity line of products, 757 optional LKW and LKC series lens kits. Series strobes exceed UL synchronization requirements (within 10 • Screw terminal wire connection milliseconds other over a two -hour period) when used with a Large terminals speed installation and accept up to #12 AWG separately - installed G1 M Signal Master or SIGA -CC1S Synchroni- (2.5mm2)wire. zation Module. They are fully compatible with Genesis signals. • • Easy Installation Synchronization is important because a small portion of the Flush mountto standard North American 4° square or two-gang population have a condition which may cause them to become - box. Integrity's universal mounting plate allows it to be wired disoriented from multiple random flashes of light. Integrity strobes and then left hanging freefor easy inspection and testing before it minimize this risk. is fastened to the electrical box. Strobes are shipped with standard wall mount style "FIRE" lens markings. Where ceiling orientation, other languages, or different Description lens markings are required, EST offers optional LKW and LKC Integrity temporal horns and temporal horn - strobes are specially series Lens Marking Kits. These optional lens markings simply snap designed for use with compatible life safety communication and on to the strobe. Consult EST for availability of special lens control equipment to alert occupants of a life safety event. The markings. horn emits a piercing low frequency sound that is easily heard Integrity horns and horn - strobes are designed for 20 to 31 Vdc above moderate ambient noise levels. The flash from its strobe can operation and must be connected to signal circuits that output a be noticed from almost any position in the room, corridor, or constant (not pulsed) voltage. A diode is used to allow full signal large open space. circuit supervision. EDWARDS SYSTEMS TECHNOLOGY U.S SALES: SARASOTA, FL 941-739-4638; FAX 941-727-1214 • CANADA SALES: OWEN SOUND, ON 519 - 376-2430; FAX519- 376 -7258 INTERNATIONAL SALES: 905- 270. 1711 ; FAX 905 - 2709553 • CORPORATE HEADQUARTERS: CHESHIRE, CT • U.S. MANUFACTURING: PF SFIELD &NEWPORT,ME Issue 5 Literature Sheet #85001 -0341 Page 1 of 4 Not to be used for Installation purposes. For the most current literature and uodates visit www.est.net. Horn Application Suggested sound pressure level for each signaling zone used with published by EST Press, or contact your local EST representative. alert or alarm signals is at least 15dB above the average ambient Sleeping rooms: EST 110 cd strobes are intended for use in sound level, or 5dB above the maximum sound level having a duration of at least 60 seconds, whichever is greater, measured 5' sleeping rooms and should be installed along with a smoke (1.5m) above the floor. The average ambient sound level is the RMS, detector. It must be wall mounted at least 80° (2.03 m) above floor A- weighted sound pressure measured over a 24 -hour period. level, but no closer than 24° (610 mm) to the ceiling. The distance • from the strobe to the pillow must not exceed 16' (4.8 m). Doubling the distance from the signal to the earwill theoretically result in a 6 dB reduction of the received sound pressure level. The actual Sleeping Rooms EST wall mounted strobe effect depends on the acoustic properties of materials in the space. A3 , Any size 110 cd within 16 feet of pillow dBA difference represents a barely noticeable change in volume. Application Notes - USA Typical Sound Output Dwtput Angle - Deg Audible signals should never have a sound level less than 75 dBA at Distribution -1 0 15 10' (3m) per NFPA 72. Signals cannot exceed 120 dBA per ADA dBA measured at 10 ft - 30 � o •WaMMI* * *, 30 (130 dBA per NFPA 72) at the minimum hearing distanceto audible in anechoic chamber -45 �•��� 0 ... .. e s* * •∎, 5 appliance. Audible signals shall be installed with the top of the device 757 Series Temporal 60� � � , � , ` , �� above the floor not less than 90° (2.3m) and below the finished ceiling Horn ('HIGH' output) 75 ♦;� ���� ��� • 5� a 41 at least 6" (150 mm) (per NFPA 72). �,� � � I � 1 �� �75 i I � i:• � � Strobes must be used to supplement audible signals whereverthe -90 "Ill/ ' ' - �� - 90 average ambient sound level exceeds 105 dBA. Combination 105 95 85 75 dBA 75 85 95 105 AudibleNisible signals must be installed per NFPA guidelines — Temporal Horn (dBA) establishedforstrobes. Strobe A Application ADA suggests that the following areas may require Visual Alarm p p Signals: EST strobes are UL 1971 - listed for use indoors as wall- mounted • rest rooms, meeting rooms, and other general usage areas. public -mode notification appliances for the hearing impaired. • lobbies, hallways, and other common use areas. Prevailing codes require strobes to be used where ambient noise • sleeping rooms intended for use by persons with hearing conditions exceed 105 dBA(87dBA in Canada), where occupants use impairment (per Title 1 of ADA). hearing protection, and in areas of public accommodation as defined • work areas used by a person with a hearing impairment (per in the Americans with Disabilities Act (see app lication notes– USA). Title 1 of ADA). Combination horn - strobe signals must be installed in accordance Application Notes - CANADA with guidelines established for strobe devices. Based in part on 1995 Canada National Building Code - The fire Strobes alarm signal sound pressure level shall not exceed 110 dBA in any The following guidelines are based on ANSI /NFPA 72 National normally occupied area. The sound pressure level from an audible Fire Alarm Code (1999). When applied and installed in accordance signal in a floor area used for occupancies other than residential with that code, EST strobes meet or exceed the illumination occupancies shall be not less than 10 dBA above the ambient produced by the ADA- specified 75 candela (cd) strobe at 50 feet.* noise, and never less than 65 dBA. The sound pressure level in sleeping rooms from an audible signal shall not be less than Non - Sleeping Rooms EST wall mounted strobes* 75 dBA when any intervening doors between the device and the Up to 20' x 20' (6.1 m x 6.1 m) One 15 cd strobe sleeping room are closed. Audible signal devices shall be Up to 30' x 30' (9.1 m x 9.1 m) One 30 cd or two 15 cd strobes installed not less than 1.8 m to the center of the device above the Up to 40' x 40' (12.2 m x 12.2 m) One 75 cd or two 30 cd strobes floor (per CANNLC S524). Up to 50' x 50' (15.2 m x 15.2 m) One 110 cd or two 75 cd strobes The fire alarm audible signal shall be supplemented by fire alarm Corridors strobes in any floor area where the ambient noise level exceeds 15 cd strobes spaced at 100' 87 dBA, or where the occupants of the floor area use ear protective . Any length. (30.5 m) max. Strobes must be devices, are located within an audiometric booth, or are located Maximum width: 20' (6.1m). placed within 15' (4.5m) of each within sound insulating enclosures. This also applies to assembly end of the corridor. occupancies in which music and other sounds associated with • ADA suggests using 75 cd strobes throughout an area, with spacing that never performances could exceed 100 dBA. exceeds 50 ft from the strobe to any point In the protected space. Strobes shall be installed in a building so that the flash from not Non - Sleeping Rooms and Corridors: EST strobes rated at less than less than one device is visible throughout the floor area or portion 110 cd per UL 1971 are intended for use in non - sleeping areas only. thereof in which they are installed. For maximum safety, EST Install with the bottom of the device at least 80 inches (2.0 m) and no recommends that strobes be installed as per the guidelines shown more than 96 inches (2.4 m) above the finished floor. No point in any here under Strobe Application. space (including corridors) required to have strobes should be more than 50feet (15.2 m) from the signal (in the horizontal plane). For detailed spacing requirements, consult The Handbook of Fordetailedspacingrequirements ,consult TheHandbookof Visible Notification Appliances for Fire Alarm Applications Visible Notification Appliances for Fire Alarm Applications published by EST Press, or contact your local EST representative. EDWARDS SYSTEMS TECHNOLOGY Page 2 of 4 Literature Sheet #85001-0341 Issue 5 Not to be used for Installation purposes. Specifications Standalone Synchronization Strobe flash at 1 per second within 200 milliseco on common circuit / - Characteristics (note 2) Horn pulses at temporal rate within 200 milli ds on common circuit Operating Volts Strobe: 20 -24 Vdc Continuous; Horn: Vdc Continuous Rated Strobe Output - candela (cd) 757 -1A -T 757 -7A -T 757 -8A -T 15 cd wall 110 cd wall UL 1971 15 cd ceiling 60 cd ceiling N/A (horn only) UL 1638 & ULC S526 75 cd 110 cd Anechoic: High Setting - 104 dBA (peak) /98 dBA (avg); Low Setting - 99 dBA (peak) /94 dBA (avg) Horn Output (note 1) Reverberent: High Setting - 85 dBA (continuous)/82 dBA (temporal); Low Setting - 82 dBA (continuous)/75 dBA (temporal) Horn Current High Output: 40 mA @ 24 Vdc; 55mA @ 24 Vrms FWR; Low Output: 20 mA @ 24 Vdc; 28 mA @ 24 Vrms FWR Strobe Flash Synchronization Synchronized at one flash per second. Extemal control module necessary to meet UL 1971 synchronization requirements of 10 milliseconds over a two -hour period. Compatible Synchronization G1M, G1M -RM, SIGA -CC1S, SIGA -MCC1S . Modules Strobe Marking Supplied with LKW -1 °FIRE° red letters, vertical both sides (Wall Mount) see LKW and LKC series for ceiling style and optional markings. Flash Tube Enclosure Clear LEXAN with white marking sleeve Housing Textured, color impregnated engineered plastics - exceeds 94V -0 UL flammability rating Wire Connections Terminals - separate, polarized inputs for Horn & Strobe, #12 AWG (2.5mm maximum INDOOR Operating Environment 32 -120° F (0-49° C) ambient temperature. 93% relative humidity @ 40° C OUTDOOR Operating Environment 98% relative humidity @ 40° C; -35 -150° F (- 31 -66° C) ambient temperature (must use weatherproof perOperating box) (757 -7A: rated at 17.7 cd @ -35° C per UL/@ 40° C per ULC) (757 -8A: rated at 70.7 cd @ -35° C per UU@ -40° C per ULC) Flush: North - American 2 -gang box, 3° high x 4° wide x 2 (69 mm) minimum Mounting - INDOOR Surface: 757A -SB Back box Bi- directional: 757A -BDF Mounting Frame Mounting - OUTDOOR Surface: 757A -WB Weatherproof Box Agency Listings UL 1971, UL 1638, UL 464, ULC S526, ULC S525, MEA, CSFM, FM. CE (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule) Note1- Measured at10ft(3m)@24 Vdc. Subtract 3 dBAfor models with strobes. Note 2 - Temporal audible pattem is defined as: %secON,'h sec OFF,' secON, %secOFF,y sec ON, 1½ sec OFF, then repeat cycle. Light Output Patterns Current Draw 7A' Series Strobe '8A' Series Strobe Notes and Comments Typical Current (measured by EST) V°'""l Vertical Output Vertical Output 1. Current values are 15/75 cd 110 cd ao -eo- -90.75 A� c37A - - 90.75 0 °"'"°° -a showninmA. RMS Mean Peak RMS Mean Peak 11/'6 -45 r-7, 150 11 / kg 100 4- 45 0 „ae uL.m 2 UL Nameplate Rating 20 Vdc 121 115 277 248 241 402 ar 50 I'I �� 100 I / /�I / can vary from Typical 24 Vdc 101 96 204 203 197 338 I/l ��� ll(ii ♦ • 15 Current due to • r - V�p . 15 ° 50 � i % �° measurement methods 31 Vdc 81 76 173 155 151 280 Br cd t Sk��'�. 0 0 20 Vfwr 168 97 452 342 202 868 and instruments used. r� NB', as i i I m 3. ESTrecommendsusin 24Vfwr 146 79 446 286 159 788 i !: 15 50 1\\0 15 g 50 11 5 30 BO � •30 1oo'��f) the Typical Cu rrent for UL Rating � system design including 15/75 cd _ 110 cd 100 1 0 5 60 150 90 60 90 NAC a nd Power Supply RMS Mean Peak RMS Mean Peak loading and voltage 20 Vdc 113 107 248 228 222 420 '7A' Series Strobe '8A' Series Strobe drop calculations. 24 Vdc 90 85 214 180 175 360 Horizontal Output Horizontal Output 4. UsetheVdcRMS 31 Vdc 65 62 174 125 122 280 degrees degrees current ratings for fitteredpowersupply 20Vfwr 153 81 540 327 177 952 - 30 15 10 1 5 30 -30 ;� 0 30 -30 5 30 and battery A 24 Vfwr 128 64 412 260 134 808 45 ``� � � � �� 45 45 / 4 p,5 calculations. Use the -60 VW 0 - 60 �� - ICC �60 Vfwr RMS current ratings for unfiltered power supply calculations. 7 \ � yj75 • IN N 4 . ( ���e r,o4. 75 5. Fuses, circuit breakers and other overcurrent protection devices are typically -90 .« .. - 90 1. 6 _. 4 ':: 90 rated for current in RMS values. Most of these devices operate based upon the 100 50 cd 50 100 200 100 cd 100 200 heating affect of the current flowing through the device. The RMS current (not Q ➢A AWN. 01 ,SCIIu rein MOO ID°A Menge ad 'wed wn+n I= the mean current) determines the heating affect and therefore, the trip and hold thresholdforthose devices. 6. Our industry has used 'mean' currents over the years. However, UL will direct the industry to use the 2004 RMS values in the future. EDWARDS SYSTEMS TECHNOLOGY Issue 5 Literature Sheet #85001 -0341 Page 3 of 4 Not to be used for Installation purposes. Installation and Mounting ,''O North American 2-gang electric box, 2 (69mm) minimum All models fit to a standard flush mounted, North- ° : Q (Alternative: 4' square box American two -gang electrical box, 2 inch (69 mm) I ` 2 1 /8 (54mm) deep) minimum. Optional flush trims are not required. For Mounting Plate (provided) surface mount, use EST's custom indoor and ' , outdoor surface boxes painted in color- matched E • red or white epoxy. EST recommends that fire ` / � ® 1 il 1 alarm horn /strobes always be installed in accord- ance with the latest recognized edition of national � I and local fire alarm codes. 0 ' . <1 I� #6 -32 screws (by others) Surface Box - 5-5/8" (143mm) sq. x ■ Housing 3.9/16 (91mm) deep Typical Wiring / 5-1/2' (140mm) x 5-1/2' (140mm) x 5/8 (16mm) The strobe must be connected to signal circuits V . Single Mounting Screw (provided) which outputa constant (not pulsed) voltage. The horn can be connected to continuous voltage circuits. HORN and STROBE FIRST DEVICE ON SAME CIRCUIT Horn/Strobe Rom/Strobe TeuLnlLDUsted Ordering Information FlreAlarmControl S113 ■ice v Panel Signal Circuit ■m Catalog Ship Wt. -e � as To Next Device Number _Description Ib. (kg) or EOL Resistor Temporal Horns ' >+ 757 -1A -T* (Temporal Horn, Red 1 1.7 (0.8) HORN and STROBE - Temporal Horn - Strobes ON SEPARATE CIRCUIT FIRST DEVICE + 757 -7A -T* Temporal Horn - Strobe, 15/75cd, Red To UWLC Listed + To Next Device 2.0 (0.9) Fre Alarm Control Horn/Strobe Horn/Strobe or EOL Resistor 757 -8A -T* Temporal Horn - Strobe, 110cd, Red Panel Signal Circuit h011 ..palnl Synchronization Modules : OM ■ Genesis Signal Master To UL/ULC Listed + ii r7,ST! G 1 M -RM g 0.2 (0.1) Are Alarm Control - r_- -all To Next Strobe Device Remote Mount (1 -gang) Panel Signal Circuit or EOL Resistor SIGA -CC1S Synchronization Output Module 0.5 (0.23) + (Standard Mount) SIGA -MCC1S Synchronization Output Module 0.18 (0.08) (UIO Mount) d BA output Mounting Accessories Horn - strobes 757A -SB* Surface Box, Red, Indoor 1.5(.7) High dB UL464 Average Peak 757A -WB* Weatherproof Box, Red, Surface 1.5(.7) Output Temporal Steady Temporal I Steady Temporal I Steady 757A - BDF* Bi - directional Frame, Red 4(1.8) 20 Vdc 79.0 82.0 93.5 100.0 Lens Marking Kits (see note 1) 24 Vde 79.0 _ 85.0 _ 97.0 102.0 LKW -1 "FIRE ", Wall Orientation (supplied) LKW -1R "FIRE ", Wall Orientation, RED Low dB UL464 Average Peak LKW -2 "FEU ", Wall Orientation Output Temporal Steady Temporal 1 Steady Temporal 1 Steady LKW - "FIRE/FEU ", Wall Orientation 20 Vdc 75.0 79.0 89.2 95.4 LKW -4 "SMOKE ", Wall Orientation 0.1 • 24 Vdc 75.0 79.0 93.0 98.0 LKW -5 "HALON ", Wall Orientation (.05) LKW -6 "CO2 ", Wall Orientation Horns LKW -7 "EMERGENCY ", Wall Orientation • High dB UL464 Average Peak LKW -8 "ALARM ", Wall Orientation Output Temporal Steady Temporal I Steady Temporal 1 Steady LKW - "FUEGO ", Wall Orientation 20 Vdc 79.0 82.0 97.0 102.5 ' Add Suffix "W" to catalog no. for WHITE. (e.g. 757- 7A -TVA 24 Vdc 82.0 85.0 98.0 104.0 Note 1 - Change "W" to "C" for CEILING mount. (e.g. LKC -1) Low dB UL464 Average Peak Output Temporal Steady Temporal /Steady Temporal /Steady WARNING: These devices will not operate without electrical power. As fires 20 Vdc 75.0 79.0 92.3 98.4 frequently cause power interruptions, we suggestyou discuss further safeguards 24 Vdc 75.0 82.0 94.0 99.0 with your local fire protection specialist. These visual signal appliances' flash intensity may not be adequate to alert or waken occupants in the protected area. • All values shown are dBA measured at 10feet (3.01m). Research indicates that the intensity of strobe needed to awaken 90 %ofsleeping • UL1480 values measured in reverberation room. persons is approximately 100 cd. EST recommends thatstrobes in sleeping rooms • Average values are measured in anechoic chamber. be110cdminimum. EDWARDS SYSTEMS TECHNOLOGY It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST Cl 2003 EST Printed in U.S.A. (origin) Page 4 of 4 Literature Sheet #85001 -0341 Issue 5 Not to be used for Installation purposes. „ ced Inte9r I • strobe n n' ®ets at i n � En _e d 1 str Synch rements� i GG_1 reel J q kA 1 g 4 • EDWARDS SYSTEMS TECHNOLOGY NOTIFICATION APPLIANCES Compatibility 4 QuickStart FireShleld EST2 EST3 LSS4 1RC-3 /FCC Synchronized Strobe Models: 202 -7A, 202 -8A, 203 -8A f I s i Features • UL 1971-listed syn ronizingstrobe .� /- 1 202 Series strobes synchronize to the latest UL 1971 requirements �'� when usedwithan external control module (G1MorSIGA- CC1S). - • • Genesis- compatible Can be mixed with Genesis signals. All Genesis and Integrity strobes on the same circuit meet UL 1971 synchronization ,i 1- requirementswhen used with an external control module. - • Approved for public and private mode applications - - Z• UL 1971 - listed as signaling devices for the hearing impaired and `o UL 1638 - listed as protective visual signaling appliances. Patented • Satisfies ADA code requirements All 202 strobes provide the "Equivalent Facilitation" allowed C4 MEA ( ( CODI.. 5 -M under ADA Accessibility Guidelines. A single strobe in rooms up to 50 ft x 50 ft satisfy both ADA and NFPA codes. Durable red or white Noryl front plate Synchronization is important because a small portion of the • Durable industrial white or harsh l environments. ont pl population have a condition which may cause them to become disoriented from multiple random flashes of light. 202 Series • Rated for wall or ceiling installation strobes minimizethis risk. • Field changeable field markings The flash from 202 Series strobes can be noticed from almost any Lens language or standard °FIRE° marking is easily changed with position in the room, corridor, or large open space. Light disper- optional LKW and LKC series lens kits. sion is controlled with a specially shaped reflector that directs a minimum of 12 per cent of rated Tight output above and below the • Screw terminal wire connection strobe, and a minimum of 25 % of rated Tight straight out both Large terminals speed installation and accept up to #12 AWG sides. 202 Series strobes are UL 1971 listed with both wall and (2.5mm wire. ceiling cd intensity ratings (see Specifications). This is useful in • Fits one -gang flush box areas where the Authority Having Jurisdiction (AHJ) permits • Ideal for retrofit and renovation projects. Optional color- matched ceiling - mountstrobes. surface boxes available. Strobes are shipped with standard wall mount style "FIRE" lens markings. Where ceiling mount, other languages, or different Tens • markings are required, EST offers optional LKW and LKC series Description Lens Marking Kits. These optional lens markings simply snap on to 202 Series strobes are specially designed for use with compatible the strobe. Consult ESTfor availability of special lens markings. life safety communication and control equipment to alertthe 202 Series strobes are designed for 20 to 31 Vdc operation and hearing impaired of a life safety event. Strobes are available with must be connected to signal circuits that outputa constant (not 15/75 cd, and 110 cd effective flash intensity. They are fully pulsed) voltage. A diode is used to allow full signal circuit supervi- compatible with Genesis signals. sion and polarized connections are made to terminals that accept up to #12 AWG (2.5mm wire. The 203 Series strobe operates As part of the Enhanced Integrity line of products, 202 Series from a 120 Vac /60 hz signal circuit and is not synchronized. strobes exceed UL synchronization requirements (within 10 milliseconds other over a two -hour period) when used with a The strobe housing/front plate is finished in red or white and is separately-installed G1M Signal Master or SIGA-CC1SSynchroni- made from durable and fire retardant, high impact plastic with a zation Module. slightlytexturedsurface. EDWARDS SYSTEMS TECHNOLOGY U.S. SALES: SARASOTA, FL 941 - 7394638; FAX941- 727 -1214 • CANADA SALES: OWEN SOUND, ON 519- 376-2430; FAX519- 376 -7258 INTERNATIONAL SALES: 90 - 1711 ; FAX 905 - 270-9553 • CORPORATE HEADOUARTERS: CHESHIRE, CT • U.S. MANUFACTURING: PITTSFIELD &NEWPORT, ME issue 9 Literature Sheet #85001 -0389 Page 1 of 4 Not to be used for Installation purposes. For the most current literature and updates visit www.est.net. • Application Application Notes — USA EST strobes are UL 1971 - listed for use indoors as wall- mounted Strobes must be used to supplement audible signalswherever the public -mode notification appliances for the hearing impaired. average ambient sound level exceeds 105 dBA. Combination Prevailing codes require strobes to be used where ambient noise audible /visual signals must be installed in accordance with NFPA conditions exceed 105 dBA (87dBA in Canada), where occupants guidelines established for strobes. use hearing protection, and in areas of public accommodation as • defined in the Americans with Disabilities Act (see application ADA suggests that the following areas may require visual alarm notes —USA). signals: • rest rooms, meeting rooms, and other general use areas. Combination horn - strobe signals must be installed in accordance • lobbies, hallways, and other common use areas. with guidelines established for strobe devices. • sleeping rooms intended for use by persons with hearing impairment (in accordance with Title 1 of ADA). Strobes • work areas used by a person with a hearing impairment (per The following guidelines are based on ANSI/NFPA 72 National Fire Title 1 of ADA). Alarm Code (1999). When applied and installed in accordance with that code, EST strobes meet or exceed the illumination produced by the ADA - specified 75 candela (cd) strobe at 50 feet.* Application Notes — CANADA Non - Sleeping Rooms EST wall mounted strobes* (Based in part on 1995 Canada National Building Code) Up to 20' x 20' (6.1 m x 6.1 m) One 15 cd strobe The fire alarm audible signal shall be supplemented by fire alarm Up to 30' x 30' (9.1 m x 9.1 m) One 30 cd or two 15 cd strobes strobes in any floor area where the ambient noise level exceeds • Up to 40 x 40' (12.2 m x 12.2 m) One 75 cd or two 30 cd strobes 87 dBA, or where the occupants of the floor area use ear protective devices, are located within an audiometric booth, or are located Up to 50' x 50' (15.2 m x 15.2 m) One 110 cd or two 75 cd strobes within sound insulating enclosures. This also applies to assembly Corridors occupancies in which music and other sounds associated with 15 cd strobes spaced at 100' performances could exceed 100 dBA. Any length. (30.5 m) max. Strobes must be Strobes shall be installed in a building so that the flash from not Maximum width: 20' (6.1 m). placed within 15' (4.5m) of each less than one device is visible throughout the floor area or portion end of the corridor. thereof in which they are installed. For maximum safety, EST ADA suggests using 75 cd strobes throughout an area, with spacing that never recommends that strobes be installed as per the guidelines shown exceeds 50 ft from the strobe to any point In the protected space. here under Strobe Application. Non - Sleeping Rooms and Corridors: EST strobes rated at less than 110 cd per UL 1971 are intended for use in non - sleeping areas only. Install with the bottom of the device at least 80 inches (2.0 m) Typical Wiring — 24 Vdc and no more than 96 inches (2.4 m) above the finished floor. No point in any space (including corridors) required to have strobes should be more than 50 feet (15.2 m) from the signal (in the horizontal plane). ULNL L lsted Place an end-of- 24V de line resistor on the For detailed spacing requirements, consult The Handbook of Fire Alarm last device (resistor Visib /e Notification Appliances for Fire Alarm Applications central Panel supplied with (signal circuit) control panel) published by EST Press, or contact your local EST representative. Sleeping rooms: EST 110 cd strobes are intended for use in () sleeping rooms and should be installed along with a smoke detector. It must be wall mounted at least 80° (2.03 m) above floor WARNING: These devices will not operate without electrical power. • level, but no closer than 24° (610 mm) to the ceiling. The distance As fires frequently cause power interruptions, we suggest you discuss from the strobe to the pillow must not exceed 16' (4.8 m). further safeguards with your local fire protection specialist. These visual signal appliances' flash intensity may not be adequate to Sleeping Rooms EST wall mounted strobe alert or waken occupants in the protected area. Research indicates that the intensity of strobe needed to awaken 90% of sleeping persons is Any size 110 cd within 16 feet of pillow approximately 100cd. EST recommends that strobes in sleeping rooms be 110cd minimum. CAUTION: This unit is designed to be used on signal circuits that output a constant voltage. Do not connect this unit to a coded or pulsating voltage. Electrical supervision requires wire run to be broken at each device. Do not loop signal circuit field wires around the strobe terminals. EDWARDS SYSTEMS TECHNOLOGY Page 2 of 4 Literature Sheet 485001 -0389 issue 9 Not to be used for Installation purposes. , Specifications Catalog Number 202 -7A 202 -8A I 203 -8A UL 1971 Rated Strobe Output - candela (cd) 15cd (wall or ce ng) 110cd (wall); 60cd (ceiling) UL 163 S526 75cd 110cd Rated Strobe Output Synchronized at one flash per second. External control module Non - synchronized Strobe Flash Rate necessary to meet UL 1971 synchronization requirements at one fps. of 10 milliseconds over a two -hour period. Compatible Synchronization Modules G1M, G1M -RM, SIGA -CC1S, SIGA -MCC1S Strobe Operating Volts Continuous 20 to 31 Vdc or 20 to 27 Vfw 1 120 Vac /60Hz Operating Environment INDOOR: 85% relative humidity @ 30° C; 32 -120° F (0-49° C) ambient temperature Lens Markings Supplied with LKW -1 "FIRE" red letters, vertical both sides (Wall Mount). See LKW and LKC series for ceiling style and optional markings. Wire Connections Terminals - polarized input, #12 AWG (2.5mm max wire size Flash Tube Enclosure Clear LEXAN Strobe Plate, Finish Textured color - impregnated plastic - Exceeds 94V -0 UL Flammability Rating Mounting Flush - One -gang, 2 -inch deep North American electrical box; Surface - EST 27193 series box or one -gang wiremold box. • Agency Listings UL 1971, UL 1638, ULC S526, CE, FM, CSFM, MEA (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule) Current Draw Distribution Patterns UL Rating 110 cd 15/75 cd UL 1971 WALL MOUNTED STROBE LIGHT OUTPUT RMS Mean Peak RMS Mean Peak 20 Vdc 248 241 402 121 115 277 EST HORIZONTAL TYPICAL EST -7A MODELS TYPICAL EST -BA MODELS 24 Vdc 203 197 338 101 96 204 1 1 Av er age _ 90 _ , s — 1 70 - - 1 _ 31 Vdc 155 151 280 81 76 173 EN UL1971 _ 20 Vfwr 342 202 868 168 97 452 Minimum u == 50 =---� 24 Vfwr 288 159 788 146 79 446 la 1s - _ _ _ o -- R (D) 0 (0) 10 — = w .1s - - -- - - - - -- Typical Current 110 cd 15/75 cd ° .30 -- .s =- •� _ - (measured RMS Mean Peak RMS Mean Peak d0 = ,o =ill by EST) 20 Vdc 228 222 420 113 107 248 90, V 's -GO - eo erdial 24 Vdc 180 175 360 90 85 214 0 10 20 30 40 50 80 70 93 0 25 50 75 100 125 150 175 31 Vdc 125 122 280 65 62 174 r 1211 1 90 (cd) (cd) 20 Vfwr 327 177 952 153 81 540 1 , • i VERTICAL 24 Vicar 260 134 808 128 64 412 0° TYPICAL EST -7A MODELS TYPICAL EST -BA MODELS Horizontal •n1 so i m _� 70 ° so � All so NotesandComments I� 90^ __ 1. Current values are showninm = I _ __ A 45 = _ 30 ===== 30 2. UL Nameplate Rating can vary from Typical Current due to measurement co 10 10 s methods and instruments used. (0) - — - (0) o - 3 EST recommends using the Typical Currentfor system design including NAC w — __ •15 —= and Power Supply loading and voltage drop calculations. ° -30 = _ = _= 30 - - -- 00 ;__ e5 =_ -- 4. Use the Vdc RMS current ratings for filtered power supply and battery AH �� ill calculations. Use the Vfwr RMS current ratings forunfilteredpowersupply _ 75 =� calculations. 5. Fuses, circuit breakers and other overcurrent protection devices are typically 0 10 20 30 40 50 60 70 60 0 25 50 75 100 125 150 rated for current in RMS values. Most of these devices operate based upon the (`d) (d) heating affect of the currentflowing through the device. The RMS current (not the mean current) determines the heating affect and therefore, the trip and hold threshold forthose devices. 6. Our industry has used 'mean' currents over the years. However, UL will direct the industry to use the 2004 RMS values in the future. EDWARDS SYSTEMS TECHNOLOGY Issue 9 Literature Sheet #86001 -0389 Page 3 of 4 Not to be used for Installation purposes. Installation and Mounting All models fit to a standard flush mounted, North American one -gang electrical box, two inch (51 mm) deep minimum. Optional EST color- matched indoor surface -mount boxes are available. Strobes must be connected to signal circuits which output a constant (not pulsed) , voltage. EST recommends that these strobes always be installed in accordance with the latest recognized edition of national and local fire alarm codes. . MOUNTING PLATE FRONT VIEW SIDE VIEW .09 0.25' (28 mm (6 mm) � 1110 3018 81111 / F 1 Q IL: == 1 O 0 0 5' a S' (127 mm) 89 (127 m) flu.= THIS SIDE OUT A / \ �1.9' Two pan head slotted screws are provided to 1E 3.4' 'FlRE' lens (wall orientation) supplied.Other (48 mm) secure mounttng plate to 1-gang electrical bar. (88 mm) lens marldngs are available (see below). Ordering Information Ordering Information ` — Strobes — Lens Marking Kits Catalog Ship Wt. Catalog Ship Wt. Number Description Ib. (kg) Number Description Ib. (kg) 202 -7A -T Strobe - 15/75 cd, Red LKW -1 "FIRE" - Wall Orientation (supplied) 202 -7A -TW Strobe - 15/75 cd, White LKW -1R "FIRE" - Wall Orientation (Red) 202 -8A -T Strobe - 110 cd, Red LKW -2 "FEU" - Wall Orientation 202 -8A -TW Strobe - 110 cd, White 1 (0.45) LKW -3 "FIRE/FEU" - Wall Orientation 203 -8A -T Strobe - 110 cd, 120 Vac, Red LKW-4 "SMOKE" - Wall Orientation 203 -8A -TW Strobe - 110 cd, 120 Vac, White LKW -5 "HALON" - Wall Orientation Synchronization Modules LKW -6 "CO2" - Wall Orientation G1M -RM Genesis Signal Master 0.1 (0.05) LKW -7 "EMERGENCY" - Wall Orientation Remote Mount (1 -gang) LKW -8 "ALARM" - Wall Orientation SIGA -CC1S Synchronization Output Module 0.5 (0.23) LKW -9 "FUEGO" - Wall Orientation 0.2 (Standard Mount, 2 -gang) (0.1) LKC -1 "FIRE" - Ceiling Orientation SIGA -MCC1S Synchronization Output Module 0.18 (0.08) LKC -2 "FEU" - Ceiling Orientation (U10 Mount) Mounting Accessories LKC -3 "FIRE/FEU" - Ceiling Orientation 27193 -11 Surface Mount Box- Indoor, 1 -gang Red LKC-4 "SMOKE" - Ceiling Orientation 27193 -16 Surface Mount Box - Indoor, 1 -gang White 1 (0.45) LKC -5 "HALON" - Ceiling Orientation LKC-6 "CO2" - Ceiling Orientation LKC -7 "EMERGENCY" - Ceiling Orientation . LKC -8 "ALARM" - Ceiling Orientation LKC -9 "FUEGO" - Ceiling Orientation EDWARDS SYSTEMS TECHNOLOGY It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST. © 2003 EST Printed In U.S.A. (origin) Page 4 of 4 Literature Sheet #85001 -0389 Issue 9 Not to be used for Installation purposes.