Specifications City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
November 28, 2007 ✓p 2c0? _
C�t75 ,
RE: FIRE SPRINKLER SYSTEM
Proiect Information T I GARD
Building Permit: BUP2007 -00588 Construction Type: VB
Tenant Name: Pacific Source Occupancy Type: B
Address: 13010 SW 68 St. Occupant Load: 71
Area: NA Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; National Fire Protection Association, Standard 13 (NFPA 13)
2002 edition and the State of Oregon Fire Code (OFC) 2007edition.
GENERAL
1. A supply of spare sprinklers (never Tess than 6) shall be maintained on the
premises so that any sprinklers that have operated or been damaged in any
way can be promptly replaced. These sprinklers shall correspond to the types
and temperature ratings of the sprinklers on the property. Sections 6.2.9.1 &
6.2.9.2 NFPA 13.
2. The spare sprinklers shall be kept in a cabinet located where temperatures
will not exceed 100 degrees "F" at any time. A special sprinkler wrench shall
be provided and kept in the sprinkler cabinet to be used in the removal and
installation of sprinklers. Sections 6.2.9.3 & 6.2.9.6 NFPA 13.
3. The clearance between the deflector and the top of storage shall be 18 inches
or greater. Section 8.6.6.1 NFPA 13. The distance shall be increased to 36
inches for Large Drop sprinkler heads. Section 8.11.6 NFPA 13
4. Sprinklers shall be located a minimum of 4 inches from walls and spaced not
less than 6 feet on center. Sections 8.6.3.3 & 8.6.3.4.1 NFPA 13.
5. Clearances shall be provided around all piping extending through platforms,
foundations, walls and floors. The diameter of the hole shall be 2 inches
larger than the penetrating pipe for pipe sizes 1 inch through 3' /z inches. The
diameter of the hole shall be 4 inches larger than the penetrating pipe for pipe
sizes 4 inches and larger. Sections 9.3.4.1 & 9.3.4.2 NFPA 13.
6. The system piping shall be braced to resist both lateral and longitudinal
horizontal seismic Toads to prevent vertical motion resulting from seismic
loads. The structural components to which bracing is attached shall be
determined to be capable of carrying the added applied seismic Toads. Sway
braces shall be designed to withstand forces in tension and compression.
Bracing shall be attached directly to feed and cross mains.
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
7. The end sprinkler on a line shall be restrained against excessive vertical and
lateral movement.
8. All concealed spaces enclosed wholly or partly by exposed combustible
construction shall be protected by sprinklers.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval
stamp, shall be maintained on the jobsite. The plans shall be available to the
Building Division inspectors throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of
the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists
the City of Tigard in tracking and processing the documents.
Itespectfu
Dan Nelson,
Senior Plans Examiner
(503) 718 -2436
dann @tigard- or.gov
•
i '
tqcc I Fire & Building ;
Products * vE0
MW 14 2007 ��--��,
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 1 y u1� 1 �uA®®iL�it.d
Series TY -B — 2.8 5.6 and 8.0 K -f c or��� DIVISION
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it °:
Description is recommended that the end user be 'z
consulted with respect to the suitability
The Series TY -B, 2.8, 5.6, and 8.0 of these coatings for any given corro-
K- factor, Upright and Pendent Sprin- sive environment. The effects of ambi- [ft j
klers described in this data sheet are ent temperature, concentration of
response - standard cover- f
s
ag
tandard res
P chemicals, and gas /chemical velocity,
age, decorative 5 mm glass bulb type should be considered, as a minimum,
spray sprinklers designed for use in along with the corrosive nature of the
light, ordinary, or extra hazard, com- chemical to which the sprinklers will be — k
mercial occupancies such as banks, exposed.
hotels, shopping malls, factories, refin-
eries, chemical plants, etc. An intermediate level version of the •
Series TY -B Pendent Sprinkler can be
The recessed version of the Series obtained by utilizing the Series TY -B . .,,,0■11 \
TY -B Pendent Sprinkler, where appli Pendent Sprinkler in combination with ----
cable, is intended for use in areas with the Model S2 Shield.
a finished ceiling. It uses a two -piece
Style 10 (1/2 inch NPT) or Style 40 (3/4 WARNINGS . ( '
inch NPT) Recessed Escutcheon. The The Series TY -B Sprinklers described I 1114N ,
Recessed Escutcheon provides 1/2 herein must be installed and main -
inch (12,7 mm) of recessed adjust- tained in compliance with this docu- �•
ment or up to 3/4 inch (19,1 mm) of ment, as well as with the applicable I
total adjustment from the flush pen- standards of the National Fire Protec-
dent position. The adjustment pro- tion Association, in addition to the , 1, 4 `>•
vided by the Recessed Escutcheon re- standards of any other authorities hav- '' --- - .
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may a *'
pipe drops to the sprinklers must be impair the performance of these de- '
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain -
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition.
that which would otherwise be ob- The installing contractor or sprinkler
tained when exposed to corrosive at- manufacturer should be contacted
mospheres. Although corrosion resis- with any questions.
tant coated sprinklers have passed the
standard corrosion tests of the appli-
Model/Sprinkler
IMPORTANT Identification
Always refer to Technical Data Numbers
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal- TY1151 - Upright 2.8K, 1/2 "NPT
lation of sprinkler systems and com- TY1251 - Pendent 2.8K, 1/2 "NPT
• ponents. Improper handling and in- TY3151 - Upright 5.6K, 1/2 "NPT
stallation can permanently damage TY3251 - Pendent 5.6K, 1/2 "NPT
a sprinkler system or its compo- TY4151 - Upright 8.0K, 3/4 "NPT
nents and cause the sprinkler to fail TY4251 - Pendent 8.0K, 3/4 "NPT
to operate in a fire situation or cause TY4851 - Upright 8.0K, 1/2 "NPT
it to operate prematurely. TY4951 - Pendent 8.0K, 1/2 "NPT
Page 1 of 8 MARCH, 2007 TFP151
Page 2 of 8 TFP151
ESCUTCHEON 7/16" (11,1 mm)
a PLATE SEATING 1/2 ** NOMINAL SSU
SURFACE NPT MAKE -IN DEFLECTOR
1 \---
Y 1 % 5
!��
2 -1/4" 2 -3/16" 4
(57,2 mm) = ' (55,6 mm)
1
2
1- 9/16"
kill
WRENCH I 6'�' I�
(39,7 mm) FLATS kV
3
:�
� 6
' i II
SSP 7
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
STANDARD RESPONSE SERIES TY -B UPRIGHT (TY1151) AND PENDENT (TY1251) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10
PLATE SEATING 1/2 ** NOMINAL RECESSED
SURFACE NPT MAKE -IN ESCUTCHEON SSU*
DEFLECTOR
t �_ / /1r Rte. i, iiT 1 1'm 1/1f'IsA 6*
rr 7/16" ° 5
2 -3/16" —� MI ` , ' ( 11,1 mm)
(55,6 mm) A = �
r I- NOMINAL i I _ � MAKE -IN
1 -1/2" ' r� 2 -3/16" b v 2
(38,1 mm) > �
WRENCH (55,6 mm) 0 3
= L�
■ 1 ._ _ ,- -. -��1 FLATS = 1 1
1
SSP DEFLECTOR - F — 2 -7/8° (73,0 mm) DIA. 1/2" NPT ** f
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY3151) AND PENDENT (TY3251) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
TFP151 Page 3 of 8
ESCUTCHEON 1/2" (12,7 mm) STYLE 40
PLATE SEATING ** NOMINAL RECESSED
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
t 6 *
_ . 5
1/2" 1
2 -5/16" Ii ,� ( 12,7 mm)
(58,7 mm) Imo N OMINAL MAKE -IN
1 9/16" ' � � II
te _ 2 -1/4" 1 2
lit / IM
(39,7 mm) �`, I �MII. (57,2 mm)
WRENCH l � f�
-- -- • _ -., -- -- • - --- FLATS 1 fif
1
SSP DEFLECTOR * 2 -7/8" (73,0 mm) DIA. - 3/4" NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4151) AND PENDENT (TY4251) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING 1/2 ** NOMINAL SSU
SURFACE NPT MAKE -IN DEFLECTOR
I /J 1 -1 - - 1'Q;1 'm/"TTY.
Y
' 5
2 -1/4" 2- 3/16"
i
(57,2 mm) NW 04 4
1 -9/16 " (55,6 mm) ii WRENCH — I
(39,7 mm) FLATS � 2
1 — V
3
1
SSP
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw ** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS
8.0 K- FACTOR, 1/2 INCH NPT
Page 4 of 8 TFP151
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE*" LEAD WAX WAX OVER
LIQUID BRASS PLATED POLYESTER COATED COATED LEAD COATED
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
2.8 (TY1251) 1, 2, 3 N/A
1/2" and 175 °F /79 °C Yellow
NPT UPRIGHT 200 °F /93 °C Green
(TY1151)
286 °F /141 °C Blue
360 °F /182 °C Mauve 1, 2
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY3251) 1,2,3,4,5,6,7 1,2,3,5 1,2,3,5 1,2,3,5
and 175 °F /79 °C Yellow
UPRIGHT 2O0F/93°C Green
5.6 (TY3151)
286 °F /141 °C Blue 1" 2" 3" 5" 11" 2", 3" 5"
1/2"
NPT 360 °F /182 °C Mauve N/A
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3251)' 175 °F /79 °C Yellow
Figure 4 200F/93°C Green
286 °F /141 °C Blue 1, 2
135F/57°C Orange
PENDENT 155 °F /68 °C Red
(TY4251) 1,2,5 1,2,3,5 1,2,5
and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7
8.0 UPRIGHT 200F/93°C Green
3/4" (TY4151)
28&F/141°C Blue 1",2", 3" 5" I 1" 2" 5"
NPT
360F/182°C Mauve N/A
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4251)* 175 °F /79 °C Yellow
Figure 5 200F/93°C Green
286 °F /141 °C Blue 1, 2
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
8.0 (TY4951)
1/2" and 175F/79°C Yellow 1, 2, 3, 4, 5, 6 N/A
NPT UPRIGHT 200 °F /93 °C Green
(TY4851)
286 °F /141 °C Blue
360F/182°C Mauve
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL).
3. Approved by Factory Mutual Research Corporation (FM).
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/03).
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05).
8. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C -UL Listed, the
sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated
Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
150 °F /66 °C Maximum Ceiling Temperature.
TABLE A, LABORATORY LISTINGS AND APPROVALS
TFP151 Page 5 of 8
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD WAX WAX OVER
BRASS PLATED POLYESTER COATED COATED LEAD COATED
2.8 PENDENT (TY1251)
1/2" and 175 PSI (12,1 BAR) N/A
NPT UPRIGHT (TY1151)
PENDENT (TY3251)
5.6 and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
1/2" UPRIGHT (TY3151) OR
NPT RECESSED PENDENT 175 PSI (12,1 BAR)
(TY3251) (SEE NOTE 1) N/A
8.0 PENDENT (TY4251)
3/4" and 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4151)
RECESSED PENDENT
(TY4251) 175 PSI (12,1 BAR) N/A
8.0 PENDENT (TY4951)
1/2" and 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4851)
NOTE:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C -UL); and, the Approval by the City of New York.
TABLE B, MAXIMUM WORKING PRESSURE
Technical Operation
Data The glass Bulb contains a fluid which
expands when exposed to heat. When
Approvals the rated temperature is reached, the
UL and C -UL Listed. fluid expands sufficiently to shatter the
FM, LPCB, VdS, and NYC Approved. glass Bulb, allowing the sprinkler to
(Refer to Table A for complete ap- activate and water to flow.
proval information including corrosion
resistant status.) Design
Maximum Working Pressure
Refer to Table B. Criteria
Discharge Coefficient
K = 2.8 GPM /psi / (40,3 LPM /bar1/2) The Series TY -B Pendent and Upright
K = 5.6 GPM /psi / (80,6 LPM /bar1 /2) Sprinklers are intended for fire protec-
K = 8.0 GPM /psi / (115,2 LPM /bar1 /2) tion systems designed in accordance
with the standard installation rules rec-
Temperature Ratings ognized by the applicable Listing or
Refer to Table A. Approval agency (e.g., UL Listing is
Finishes based on the requirements of NFPA
Sprinkler: Refer to Table A. 13, and FM Approval is based on the
Recessed Escutcheon: White Coated, requirements of FM's Loss Prevention
Chrome Plated, or Brass Plated. Data Sheets). Only the Style 10 or 40
Recessed Escutcheon, as applicable, E
Physical Characteristics is to be used for recessed pendent m 0
Frame Bronze installations. 1-
Button Brass /Copper m
Sealing Assembly m
Beryllium Nickel w /Teflont y
Bulb Glass 0 cc
Compression Screw Bronze
Deflector Copper a
Bushing (K =2.8) Bronze o
}
Page 6of8 TFP151
2 -7/8" DIA. L�
5/8±1/4" (73,0 mm) 3/4" (19,1 mm)
(15,9±6,4 mm) 2.1 /4^ DIA. 1/4" (6,4 mm) WRENCH RECESS
"A" USED FOR
FACE OF (57,2 mm) 1 MOUNTING ^ (END
2" NPT MODELS)
SPRINKLER I PLATE
FITTING
1/8" WRENCH RECESS
(3,2 mm) (END "B" USED FOR
3/4" NPT MODELS)
/✓ �� P FIGURE 7
�� �� W -TYPE 6 SPRINKLER
} WRENCH
MOUNTING
SURFACE PR _ -,
WRENCH
CLOSURE SERIES 1 -1/4" (31,8 mm) RECESS
TY-B 3/4" (19,1 mm)
FIGURE 5
SERIES TY -B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 2
PUSH WRENCH
IN TO ENSURE
2 -7/8" DIA. ENGAGEMENT
(73,0 mm) 3/4" (19,1 mm) WITH SPRINKLER
5/8±1/4" WRENCHING AREA
(15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm)
(57,2 mm) FIGURE 8
FACE OF MOUNTING W -TYPE 7 RECESSED
SPRINKLER PLATE SPRINKLER WRENCH
FITTING
1/8"
J •I (3,2 mm) Installation
� ' The Series TY -B Sprinklers must be
follow-
1111111 1 — installed in accordance with the follow -
� ing instructions:
MOUNTING NOTES
SURFACE _ • Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
CLOSURE SERIES 1 -5/16" (33,3 mm) liquid from the bulb. With the sprinkler
TY-B 13/16" (20,6 mm) held horizontally, a small air bubble
should be present. The diameterofthe
air bubble is approximately 1/16 inch
FIGURE (1,6 mm) for the 135 °F /57 °C to 3/32
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY tech mm) for the 360 °F /182 °C
temperature ratings.
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON A leak tight 1/2 inch NPT sprinkler joint
8.0 K- FACTOR, 3/4 INCH NPT should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
' mum of21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
TFP151 Page 7 of 8
leakage or impairment of the sprinkler. heated rod, in order to prevent the by brushing it with a soft bristle brush.
• Do not attempt to make -up for insuffi- installer from being burned. Care must be exercised to avoid dam -
cient adjustment in the escutcheon age to the sprinklers - before, during,
plate by under- or over - tightening the The Series TY -B Recessed Pendent and after installation. Sprinklers dam -
sprinkler. Readjust the position of the Sprinklers must be installed in ac- aged by dropping, striking, wrench
sprinkler fitting to suit. cordance with the following instruc- twist/slippage, or the like, must be re-
The Series TY -B Pendent and Up- lions placed. Also, replace any sprinkler
right Sprinklers must be installed in Step A. After installing the Style 10 or that has a cracked bulb or that has lost
accordance with the following instruc- 40 Mounting Plate, as applicable, over liquid from its bulb. (Ref. Installation
tions. the sprinkler threads and with pipe Section).
Step 1. Pendent sprinklers are to be thread sealant applied to the pipe Frequent visual inspections are rec-
installed in the pendent position, and threads, hand tighten the sprinkler into ommended to be initially performed for
upright sprinklers are to be installed in the sprinkler fitting. corrosion resistant coated sprinklers,
the upright position. Step B. Tighten the sprinkler into the after the installation has been com-
sprinkler fitting using o the W -Type pleted, to verify the integrity of the cor-
Step 2. With pipe thread sealant ap- 7 Recessed Sprinkler Wrench (Ref. rosion resistant coating. Thereafter,
plied to the pipe threads, hand tighten annual inspections per NFPA 25
the sprinkler into the sprinkler fitting. Figure 8). With reference to Figure 3 or 4, the W -Type 7 Recessed Sprinkler should suffice; however, instead of in-
specting from sampling of the floor visual random
the floor level, a rando
Step 3. Tighten the sprinkler into the Wrench is to be applied to the sprinkler
sprinkler fitting using only the W -Type wrench flats. tions should close-up
made, so as t i better
c -
except that
6 Sprinkler an n 8 (Ref. adjustable Figure 7 Step C. After the ceiling has been in- determine the exact sprinkler condi-
8 or or 10 inch adj stalled or the finish coat has been ap- tion and the long term integrity of the
coated Crescent wrench is to be used for wax plied, slide on the Style 10 or 40 Clo- corrosion resistant coating, as it may
Figures 1, 2, sprinklers. With reference to sure over the Series TY -B Sprinkler be affected by the corrosive conditions
inkl n h or 4 the W-Type to a and push the Closure over the Mount- present.
Crescent wrench, , as the adjustable ing Plate until its flange comes in con -
Cresce applicable is s to tact with the ceiling. The owner is responsible for the in-
be applied to the wrench flats.
spection, testing, and maintenance of
When installing wax coated sprinklers their fire protection system and de-
with the adjustable Crescent wrench, Ca and vices in compliance with this docu-
additional care needs to be exercised ment, as well as with the applicable
to prevent damage to the wax coating Ma standards of the National Fire Protec-
on the sprinkler wrench flats or frame The Series TY -B Sprinklers must be tion Association (e.g., NFPA 25), in
arms and, consequently, exposure of p addition to the standards of any other
bare metal to the corrosive environ- maintained and serviced in accord- authorities having jurisdiction. The in-
ment. The jaws of the wrench should ance with the following instructions: stalling contractor or sprinkler manu-
be opened sufficiently wide to pass facturer should be contacted relative
NOTES over the wrench flats without damag- N to any questions.
ing the wax coating. Before wrench Before closing a fire protection system
tightening the sprinkler, the jaws of the main control valve for maintenance It is recommended that automatic
wrench are to be adjusted to just con - work on the fire protection system that sprinkler systems be inspected,
tact the sprinkler wrench flats. After it controls, permission to shut down the tested, and maintained by a qualified
wrench tightening the sprinkler, loosen affected fire protection system must be Inspection Service in accordance with
the wrench jaws before removing the obtained from the proper authorities local requirements and /or national
wrench. and all personnel who may be affected codes.
by this action must be notified.
After installation, the sprinkler wrench
flats and frame arms must be in- The owner must assure that the sprin-
spected and the wax coating re- klers are not used for hanging of any
touched (repaired) whenever the coat- objects; otherwise, non - operation in
ing has been damaged and bare metal the event ofa fire or inadvertent opera -
is exposed. The wax coating on the tion may result.
wrench flats can be retouched by gen- Absence of an escutcheon, which is
tly applying a heated 1/8 inch diameter used to cover a clearance hole, may
steel rod to the areas of wax that have delay the time to sprinkler operation in
been damaged, to smooth it back over a fire situation.
areas where bare metal is exposed.
Sprinklers that are found to be leaking
. NOTES or exhibiting visible signs of corrosion
Only retouching of the wax coating ap- must be replaced.
plied to the wrench flats and frame Automatic sprinklers must never be
arms is permitted, and the retouching painted, plated, coated or otherwise
is to be performed only at the time of altered after leaving the factory. Modi-
the initial sprinkler installation. fied sprinklers must be replaced.
The steel rod should be heated only to Sprinklers that have been exposed to
the point at which it can begin to melt corrosive products of combustion, but
the wax, and appropriate precautions have not operated, should be replaced
need to be taken, when handling the if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
Page 8 of 8 TFP151
P/N 57- XXX -X -XXX
I I
SPRINKLER TEMPERATURE
MODEUSIN RATING
530 2.8K UPRIGHT (1/2 "NPT) TY1151 1 NATURAL BRASS 135 135F/57°C
531 2.8K PENDENT (1/2 "NPT) TY1251 4 WHITE POLYESTER 155 155 °F /68 °C
570 5.6K UPRIGHT (1/2 "NPT) TY3151 3 WHITE (RAL9010) * 175 175 °F /79 °C
571 5.6K PENDENT (1/2 "NPT) TY3251 9 CHROME PLATED 200 200 °F /93 °C
590 8.0K UPRIGHT (3/4 "NPT) TY4151 7 LEAD COATED 286 286 °F /141 °C
591 8.0K PENDENT (3/4 "NPT) TY4251 6 WAX COATED 360 360 °F /182 °C
286 °F /141 °C MAX. -
560 8.0K UPRIGHT (1/2 "NPT) TY4851
8 WAX OVER LEAD
561 8.OK PENDENT (1/2 "NPT) TY4951 286 °F /141 °C MAX.
TABLE C
PART NUMBER SELECTION
SERIES TY -B PENDENT AND UPRIGHT SPRINKLERS
any other legal theory, for incidental,
Limited indirect, special or consequential dam Ordering
Warranty ages, including but not limited to labor
charges, regardless of whether TFBP ' P rocedure
was informed about the possibility of
Products manufactured by Tyco Fire & such damages, and in no event shall When placing an order, indicate the
Building Products (TFBP) are war- TFBP's liability exceed an amount full product name. Refer to the Price
ranted solely to the original Buyer for equal to the sales price. List for complete listing of Part Num-
ten (10) years against defects in mate- The fore of warranty is made in lied bers.
rial and workmanship when paid for 9 y
and properly installed and maintained of any and all other warranties. ex- Contact your local distributor for avail -
under normal use and service. This press or implied. including warranties ability.
warranty will expire ten (10) years of merchantability and fitness fora par -
from date of shipment by TFBP. No ticular purpose, Sprinkler Assemblies with NPT
Thread Connections:
warranty is given for products or com- This limited warranty sets forth the ex- Specify: (Specify Model /SIN), Stand -
ponents manufactured by companies clusive remedy for claims based on and Response, (specify K- factor),
not affiliated by ownership with TFBP failure of or defect in products, materi-
or for products and components which als or components, whether the claim (specify temperature rating), Series
have been subject to misuse, improper is made in contract, tort, strict liability TY-B or
or
or any other legal theor
installation, corrosion, or which have Sprinkler inkll er rwith (specify Pendent o g) (specify type of r Upright)
C.
y. coating), P/N (specify from Tab le e C).
not been installed, maintained, modi-
fied or repaired in accordance with ap- This warranty will apply to the full ex-
plicable Standards of the National Fire tent permitted by law. The invalidity, in Recessed Escutcheon:
Protection Association, and /or the whole or part, of any portion of this Specify: Style (specify 10 or 40 ) Re-
standards of any other Authorities warranty will not affect the remainder. cessed Escutcheon with (specify *) fin-
Having Jurisdiction. Materials found
ish, P/N (specify*).
by TFBP to be defective shall be either • Refer to Technical Data Sheet TFP770.
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor Sprinkler Wrench:
• authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56- 000 -6 -387.
the sale of products or parts of prod-
• ucts. TFBP shall not be responsible for Specify: W-Type 7 Sprinkler Wrench,
sprinkler system design errors or inac-
P/N 56- 850 -4 -001.
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446