Plans ., = Product 5ORHR,5ORVR
Data 5ORHS,5ORVS
Horizontal and Vertical
C arr i e r : AquazoneTM Water Source
Heat Pumps
1 /2 to 6 Nominal Tons
a
,,,,, 5.4,:, °µo,' A Q U A Z O N E" os,E0 -
Carrier's AquazoneTm single - packaged
horizontal and vertical water source
heat pumps are available in standard
and high efficiency configurations.
Carrier provides the optimum balance
between maintaining occupant comfort
conditions, high product quality, low
energy utilization, and a flexible water
source heat pump design that is user
friendly to both system designers and
service personnel. Aquazone units are
characterized by:
�, ' - . .�. 3 • Efficient water- cooled equipment
O ..,;.r O provided as an integral part of sys-
o
0 a tems designed for energy efficiency
and year -round cooling and heating
flexibility
• Ideal application for office buildings,
° hotels /motels, apartments, condo -
O • p 1 p
( � miniums, schools, universities, and
• hospitals
• Utilizes decentralized system con -
f
a l�a a ! cept, which provides for individual
.-- 4 . k • . zone conditioning for maintaining
� ` 1 ��� � _� ! • ® and controlling comfort conditions
.
. '� l ��� a ��� l = Available for use with standard and
I �
.aa2- 2���2 -2� o extended entering water tempera - • .. „ �� 0 0
a2�,�::l�! a
+1.��a C tures to accommodate closed -loop
m ∎ a l a ,� +�
o , and open-loop boiler/tower and
_ _.,. �f���= geothermal applications
•, • Extensive offerings assist with
design specifics through the provi-
sion of various airflow configura-
tions, high efficiency capability,
sound attenuation package, choice
of water heat exchanger, and
selection of complete or deluxe
controllers
Copyright 2001 Carrier Corporation Form 50R -1 PD
Features /Benefits
c p- �,e?
Operating efficiency Blower and motor assembly — Vertical units are available in three air -
Carrier horizontal and vertical water Permanent split capacitor (PSC) three- flow patterns including top discharge
source heat pumps are designed for speed blowers are provided with all with right or left return. Extended wa-
quality and high performance over a units to satisfy many air distribution ter temperature range between 20 F
lifetime of operation. Standard efficien- applications including an upgrade in and 110 F offers maximum design flex -
cy models offer cooling EER's to 13.3 certain sizes for high static conditions . ibility for all applications. Water flow
and heating COP's to 4.6. High effi- and fan speed control to accommodate rates as low as 1.5 gpm per ton assist
ciency models offer cooling EER's reduced sound operation and dehumid- with selection from a various range of
to 16.0 and heating COP's to 5.3. All ification control with the correct con- circulating pumps. Factory - installed
efficiencies stated are in accordance troller option. Blower motors are de- options are offered to meet specific
with standard conditions under ISO (In- signed to operate at lower tempera- design requirements.
ternational Organization for Standard - tures to help improve the reliability of Safe, reliable operation
ization) Standard 13256 -1 and provide the water source heat pump.
among the highest ratings in the indus- Refrigeration /water circuit — Standard safety features for the refrig-
try, exceeding ASHRAE (American Units have a sealed refrigerant circuit erant circuit include high - pressure
Society of Heating, Refrigerant and Air including a rotary, reciprocating, or switch, low - pressure sensor to detect
Conditioning Engineers) 90.1 Energy scroll compressor. Refrigerant circuits loss of refrigerant and low air tempera -
Standards. are provided with a standard thermo- ture sensor to safeguard against freez-
static expansion valve (TXV) for higher ing. Equipment safety features include
High quality construction and accuracy and performance. Also water loop temperature monitoring,
testing standard are a reversing valve (4 -way voltage protection, water coil freeze
All units are manufactured to meet ex- valve), water -to- refrigerant coaxial protection, and standard electronic
tensive quality control protocol from (tube in tube) coil, and enhanced condensate overflow shutdown. All
start to finish through an automated aluminum fin /rifled copper tube air to safety features are tested and run at the
control system, which provides contin- refrigerant heat exchanger coil. High factory to assure proper operation of
uous monitoring of each unit and efficiency units are provided with all components and safety switches.
performs quality control checks as larger air to refrigerant coils for com- All components are carefully de-
equipment progresses through the pro- bined ultra high efficiency. signed and selected for endurance,
duction process. Standard construction — Aquazone units have ARI durability, and carefree day -to -day
features of the Carrier AquazoneTm (Air Conditioning & Refrigeration Insti- operation.
units include: tute)/ISO, NRTL (Nationally Recog- The unit is shipped to provide inter -
Cabinet — Standard unit fabrication nized Testing Lab), or CSA (Canadian nal and external equipment protection.
consists of heavy gage galvanized sheet Standards Association) labels and are Shipping supports are placed under
metal cabinet construction designed for factory tested under normal operating the blower housing and compressor
part. standardization (i.e., minimal conditions at nominal water flow rates. feet. In addition, horizontal and vertical
number of parts) and modular design. Quality assurance is provided via test- units are both mounted on oversized
Cabinet interior surfaces are lined with ing report cards shipped with each unit pallets with lag bolts for sturdiness and
1 /2 in. thick, 1 lb. acoustic type in- to indicate specific unit performance maximum protection during transit.
sulation. Sheet metal surfaces are under cooling and heating modes of Ease of installation
treated for maximum corrosion protec- operation. Water source heat pumps
Lion to ensure resilience for long term are New York City IvAEA (Materials The unit is packaged for simple low
vitality. Compact cabinet dimensions Equipment and Acceptance) 60 -00 -E cost handling, with minimal time re-
are designed to fit tight space limita- rated. quired for installation. All units are pre -
tions in both horizontal and vertical wired and factory charged with refrig-
configurations. Quiet operation erant. Horizontal units are provided
Compressor — Standard efficiency Fan motor insulation and compressor with factory- installed hangar isolation
units include a rotary compressor de- springs are provided for sound isola- brackets. Vertical units are provided
sign in size 006 through 024, recipro- tion, cabinets are fully insulated to re- with an internally trapped condensate
eating compressor in sizes 019 duce noise transmission, low speed drain to reduce labor associated with
through 048, and scroll compressor in blowers are utilized for quiet operation installing an external trap for each
size 060. High efficiency models offer through reduced outlet air velocities, unit. Water connections (FPT) and Ion-
a rotary compressor design in 015 and air -to- refrigerant coils are designed densate drains (FPT) are anchored
through 036 sizes and scroll compres- for lower airflow coil face velocities. securely to the unit cabinet.
sor design for sizes 042 through 070. Design flexibility
Compressor isolating springs are spe Airflow configurations for horizontal
cially selected for each compressor snits are available in for patterns in
size. The external springs are mounted eluding left or right return, and left,
on an isolated railing system (i.e., from right, or back discharge. Horizontal
the cabinet) that maximizes vibration units are field convertible from left or
isolation and minimizes transmission to right discharge to back discharge.
the unit structure.
2