Plans City of Tigard, Oregon 0 13125 SW Hall Blvd. o Tigard, OR 97223 g'�" p ; s " t -d& 2 v r. Y .+ July 23, 2008 -.... r. RE: FIRE SPRINKLER SYSTEM Project Information I GARD, Building Permit: BUP2008 -00242 Construction Type: 2 -B Tenant Name: Tigard Triangle Occupancy Type: B Address: 12909 SW 68 Pkwy. Occupant Load: NA Area: NA Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; National Fire Protection Association, Standard 13 (NFPA 13) 2002 edition and the State of Oregon Fire Code (OFC) 2007edition. GENERAL 1. The clearance between the deflector and the top of storage shall be 18 inches or greater. Section 8.6.6.1 NFPA 13. The distance shall be increased to 36 inches for Large Drop sprinkler heads. Section 8.11.6 NFPA 13 2. Sprinklers shall be located a minimum of 4 inches from walls and spaced not Tess than 6 feet on center. Sections 8.6.3.3 & 8.6.3.4.1 NFPA 13. 3. Clearances shall be provided around all piping extending through platforms, foundations, walls and floors. The diameter of the hole shall be 2 inches larger than the penetrating pipe for pipe sizes 1 inch through 3 inches. The diameter of the hole shall be 4 inches larger than the penetrating pipe for pipe sizes 4 inches and larger 2 inches is required. Sections 9.3.4.1 & 9.3.4.2 NFPA 13. 4. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads to prevent vertical motion resulting from seismic loads. The structural components to which bracing is attached shall be determined to be capable of carrying the added applied seismic loads. Sway braces shall be designed to withstand forces in tension and compression. Bracing shall be attached directly to feed and cross mains. 5. The end sprinkler on a line shall be restrained against excessive vertical and lateral movement. 6. All concealed spaces enclosed wholly or partly by exposed combustible construction shall be protected by sprinklers. 7. Sprinkler heads must have 1 inch free movement in any direction at head penetration in ceiling tile or a flexible head design. Phone: 503.639.4171 o Fax: 503.684.7297 o www.tigard - or.gov o TTY Relay: 503.684.2772 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respecff Ily, 2 Dan Nelson, Senior Plans Examiner (503) 718 -2436 dann @tigard- or.gov • e (j d a cog - DOa� Bulletin 136 Rev.M Model F1FR Reliabld (r . Model F1FR Recessed Quick Response ci Sprinklers CD Model F1FR Sprinlder Types Standard Upright o Standard Pendent N ' _ Conventional l r�'' ° Vertical Sidewall Horizontal Sidewall , f _ . ■ - HSW 1 Deflector,` t ' Model F1FR Recessed Sprinlder Types Recessed Pendent Recessed Horizontal Sidewall Upright Pendent - HSW 1 Deflector 0 Listings & Approvals , , 1. Listed by Underwriters Laboratories, Inc. (UL) ` , 2. Listed by Underwriters' Laboratories of Canada (ULC) 3. Certified by FM Approvals 4. Loss Prevention Council (LPC, UK) ' rAz ;:_ , 5. NYC BS &A No. 587 -75 -SA 6. Meets MIL- S-901C and MIL STD 167 -1 7. Verband der Schadenversicherer (VdS, Germany) 8. NYC MEA 258 -93 -E UL Listing Category Vertical Sidewall Conventional Sprinklers, Automatic & Open Quick Response Sprinkler UL Guide Number VNIV n, . # 41441 • - ..., ,,, , „„2, „.....- . ,, ,,,,' ,.., 1 " .1 k ''''' ''; ' ' ? ' Ilif. 1 Patents: US Patent No. 6,374,920 Applies to - z Model F1 FR Vertical Sidewall Sprinklers. Product Description Horizontal Sidewall Recessed Pendent Reliable Models F1FR and F1FR Recessed Sprinklers are HSW 1 Deflector (Model FP Shown) I quick response sprinklers which combine the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler. pands, forcing the bubble smaller and smaller as the liquid The Models F1FR and F1FR Recessed automatic sprinklers pressure increases. Continued heating forces the liquid to utilize a 3.0 mm frangible glass bulb. These sprinklers have push out against the bulb, causing the glass to shatter, demonstrated response times in laboratory tests which are opening the waterway and allowing the deflector to distrib- five to ten times faster than standard response sprinklers. This ute the discharging water. quick response enables the Model F1FR and F1FR Recessed sprinklers to apply water to a fire much faster than standard Application sprinklers of the same temperature rating. Quick response sprinklers are used in fixed fire protec- The glass bulb consists of an accurately controlled amount tion systems: Wet, Dry, Deluge or Preaction. Care must be of special fluid hermetically sealed inside a precisely manu- exercised that the orifice size, temperature rating, deflector factured glass capsule. This glass bulb is specially con- style and sprinkler type are in accordance with the latest structed to provide fast thermal response. The balance of published standards of the National Fire Protection Asso- parts are made of brass copper and beryllium nickel. ciation or the approving Authority Having Jurisdiction. At normal temperatures, the glass bulb contains the fluid Quick response sprinklers are intended for installation as in both the liquid and vapor phases. The vapor phase can specified in NFPA 13. Quick response sprinklers and stan- be seen as a small bubble. As heat is applied, the liquid ex- dard response sprinklers should not be intermixed. The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552 J Model F1 FR Quick Response Upright, Pendent & Conventional Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: Sprinkler T K Factor Sprinkler Identification Standard- Upright (SSU) a nd Pendent (SSP) i Metric „ � g M r O A �ti� SSU Number (SIN) Y," (15mm) Standard orifice with," NPT (Ry) Thread 5.6 80 2.2' (56mm) 1,2,3,4,5,6,7 R3625 R3615 %," (20mm) Large Ordce with X" NPT (R3/4)Thread 8.0 I 115 2.3" (58mm) , 1,2,3,4,7,8 R3622 R3612 , 5/ (17mm) Small Orifice with }2" NPT (R)) Thread 4.2 I 60 22' (56mm) 1 1.2,8 R3623 R3613 y" (10mm) Small Orifice with f,," NPT (R) Thread 2.8 40 2.2" (56mm) 1 1,2,8 1 R3621 R3611 1 10mm Orifice XLH with R" Thread 4.2 60 56mm 4,6,7 R3624 R3614 Conventional- Install in Upright or Pendent Position 10mm Orifice XLH with R% Thread 4.2 60 56mm — R3674 15mm Standard Orifice with, " NPT (R,1) Thread 5.6 80 56mm 4,6,7 R3675 20mm Large Orifice with 34" NPT (R3/4)Thread 8.0 115 58mm 4,7 1 R3672 :. I6 115 ' ., -- rs:- "iiP ti: it, ::,„„„ I i t ;]„ , .ter Upright Pendent Conventional Model F1 FR Quick Response Recessed Pendent Sprinkler 1 Installation Wrench: Model GFR1 Sprinkler Wrench - Installation Data: • Nominal Thread K Factor Sprinkler Approval Sprinkler Identification Orifice Size US Metric Height Organizations Number (SIN) ,Y," (15mm) J;" NPT (RY) 5.6 80 2.2' (56mm) 1,2,3,4,5,7,8 i R3615 '%_' (20mm) ;" NPT (R34) 8.0 115 2.3" (58mm) 1,2,3,8 R3612 j' " (11mm) 2 " NPT (R'/z) 4.2 60 2.2'(56mm) 1,2.8 R3613 1 e" (10mm) y" NPT (R'h) 2.8 40 22' (56mm) 1,2,8 R3611 10mm R% 4.2 60 56mm 4.7 1 R3614 (1) Refer to escutcheon data table for approvals and dimensions. . f .. ,. . :F "'r -E PM r r'Ftc. - :.. 2 5/7.3" G1.4. (55.7 -' J .�! i ~ �.sm�; p:a —" cup ! i ii 1 C'1;AR ',- -' l ArRN +inlet P "■•7 1 L. 1 .. Ai-.AS? ...PR, I t N I i — � -- - - z , 1 — _ t - _ f � - _ ;, , or �r .£,L ..G 7= 1 ` _ 1._.........._......_......... %I .....__!_ . `\ . ...[ � ._._......._._ l ors « ..: e l p ; l r 1 .L e ... .. F ... . ..... .. 4!A , ,I Fie r .,J uPVT'? PVT'? •'.. c f ... :..0 rE:)N r� , ra. =f`R .:FrFiV.t•.5 .1:1!' .r.UF.N,S :.....i. - r!";, V FP 175 .,. .r .. ^ •.i '4 ,.,� F ^, • .rrr r:V .:T:. .. v .�.N: 2. Model F1 FR Quick Response Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench . Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy Installation Data: ' Nominal Thread K Factor Sprinkler Approval Sprinkler Orifice Size US 1 Metric Height Organizations Identification ) Number (SINSIN I Vi' %z" NPT (R' /) 5.6 80 2.2" (56mm) 1, 2, 3, 6, 8 R3685 15mm '/" NPT (R' /z) 5.6 80 2.2" (56mm) � 4 (1) (I) LPC Approval is for Pendent position only. Orientation Deflector to Ceiling Dimension (Min. - Max.) CIIS:4' Upright 4" - 12" (102mm - 305mm) ( Pendent 6" - 12" (152mm - 305mm) 1 Il ' Vertical Sidewall 1 US Patent No. 6,374,920 Model F1 FR Quick Response Horizontal Sidewall Sprinkler Deflector: HSW 1 Installation Wrench: Model D Sprinkler Wrench Installation Data: K Factor Approval Organizatlons ypeofApproval Sprinkler Nominal Thread Identification Sprinkler Light Ordinary Number (SIN) Orifice Size I US Metric Length Hazard I Hazard I X" (15mm) y" NPT(R' /) 5.6 80 2.63" (67mm) 1,2,3,5,8 I 1,2.5,8 I R3635 NOTE: UL, ULC and MEA Listing permits use with F1 or F2 recessed escutcheon. 3c' 0r V I / / / ///' / /1 ' • ;ACE Or rf rI.j,: TO _ . {--.- .4 7 E. - o 1 . �. r A N _ - 1 3 '- :.17.1i 1 1-5.2,mj ` .t fir,.: -� .. OCT; 'r? S -- - - lr -- 1 - I Horizontal Sidewall '" :;:; � ; 1 " . �;;� -�• :f4 .. ........T :n , IL, 't'Ci-', ::+y .':.A 14 1 ? ,!; \ , ,C:. 3. 1 • • Installation Quick response sprinklers are intended for installation as cleaning fluids. Remove dust by using a soft brush or gen- specified in NFPA 13. Quick response sprinklers and stan- tle vacuuming. Remove any sprinkler which has been • dard response sprinklers should not be intermixed. painted (other than factory applied) or damaged in any The Model F1 FR Recessed Quick Response Sprinklers are to way. A stock of spare sprinklers should be maintained to - be installed as shown. The Model F1 or F2 Escutcheons iilus- allow quick replacement of damaged or operated sprin- • trated are the only recessed escutcheons to be used with the kiers. Prior to installation, sprinklers should be maintained Model F1FR Sprinklers. The use of any other recessed escutch- in the original cartons and packaging until used to mini - eon will void all approvals and negate all warranties. mize the potential for damage to sprinklers that would When installing Model F1FR Sprinklers, use the Model D Sprin- cause improper operation or non - operation. Icier Wrench. When installing Model F1FR Recessed Pendent or Sidewall Sprinklers, use the Model GFR1 Sprinkler Wrench. Any Sprinkler Types other type of wrench may damage these sprinklers. Standard Upright Glass bulb sprinklers have orange bulb protectors to minimize Standard Pendent bulb damage during shipping, handling and installation. RE- MOVE THIS PROTECTION AT THE TIME THE SPRINKLER Conventional SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Re- Sidewall (Vertical, Horizontal HSW1) moval of the protectors before this time may leave the bulb vul- Recessed Pendent nerable to damage. RASCO wrenches are designed to install Recessed Horizontal Sidewall HSW1 sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS Finishes ") of TO REMOVE THE PROTECTORS. Standard Finishes Sprinker Escutcheon Temperature Ratings _ Bronze Brass Sprinkler Chrome Plated Chrome Plated (3) Max. Ambient Bulb Classlflcatlon Temperature Temp. Color White Polyester Coated White Painted 131 1 °C °F Ordinary 58 135 100`F (38'C) Orange Special Application Finishes Ordinary � 6 155 100'F (38"C) Red Sprinkler Escutcheon Intermediate 79 175 150`F (66°C) Yellow Bright Brass Bright Brass Intermediate 93 200 150°F (66 Green Black Plated Black Plated High (1) 141 286 225°F(107"C) Blue ■ Black Paint Black Paint t' Not available for recessed sprinklers. Off White Off White • Escutcheon Data Satin Chrome Satin Chrome ' FaDe 1t) Other finishes and colors are available on special order. Escutcheon Ads Adjustment `A" to a Consult the factory for details. Dimension • Mock! Wan Dimension :21 FM Approvals is limited to bronze and brass, chrome or black 1)'," plated finishes only. Max Recess (38.1 mm) y4' - 'y6 (3) FP Push- on/Thread -off escutcheon F1 1,2,4,8 Min Recess (5mm - 24mm) (19.1mm) Ordering Information 1y „ Max Recess (38.1mm) Ys" -'Y,e' Specify: F2 1,2,3,4,5,7,8 1 Min Recess 3 6 ^ (5mm -17mm) 1. Sprinkler Model (24mm) 2. Sprinkler Type FP 1,2 Max Recessed ' / ,8 ' 1y" (38.1mm) 3. Orifice Size Push-on/ { 11 mm) 4. Deflector Type Thread -off 1,2 Min Recessed c2 Y." 1" 1' (25.4mm) 5. Temperature Rating No Dimensional Figure for FP 6. Sprinkler Finish 7. Escutcheon Type Maintenance 8. Escutcheon Finish (where applicable) The Models F1FR and F1FR Recessed Sprinklers should be inspected quarterly and the sprinkler system Note: When Model F1FR Recessed sprinklers are maintained in accordance with NFPA 25. Do not clean ordered, the sprinklers and escutcheons are packaged sprinklers with soap and water, ammonia or any other separately. The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are instated and serviced by the most highly qualified and reputa- ble sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by ® The Reliable Automatic Sprinkler Co., Inc. e R � c!ed ReIiabIe (800)441 -105 Sales Offices (800)848-6051 Sales Fax Revision lines indicate updated or new data (914)668 -3470 Corporate Offices www.reiiaOlesprinkIer.corn Internet Address -G Printea ir a S A 7/05 P;Ns9?997002