The revised drawingsand documents have been reviewed by the City of Tigard
Building Division and are approved subject to the following conditions. This
review was performed under the provisions of the State of Oregon Structural
Specialty Code, 1998 edition (OSSC), Oregon Mechanical Specialty Code, 1999
edition (OMSC) and the Uniform Fire Code (UFC).
1. The medical gas room shall be separated from the rest of the building by
not less than one -hour fire - resistive construction. Doors to the medical gas
enclosure shall be self - closing smoke - and - draft - control assemblies having
a fire protection rating of not less then one -hour. OSSC Section 410
2. Penetration through the gas room walls shall be firestopped in accordance
with OSSC Section 710.2 though 710.3
3. Exits and the path of egress travel shall be identified and illuminated in
accordance with OSSC Section 1003.2.8
4. Doors shall be openable from the inside with the use of a key or any
special knowledge or effort. OSSC Section 1003.3.1.8
5. Door opening force shall not exceed 81 pounds for exterior doors and 5
pounds for interior doors. OSSC Section 1109.9.9
6. A portion of the payment counter shall provide for a 36 inch long area not
more than 36 inches above the finished floor. OSSC Section 1109.23.2
7. Restroom floors shall have a smooth, hard nonabsorbent surface such as
portland cement, concrete, ceramic tile or other approved material that
extends upward onto the walls at least 5 inches. OSSC 807.1.1
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
8. Walls within 2 feet of the front and sides of urinals and water closets shall
have a smooth, hard nonabsorbent surface such as portland cement,
concrete, ceramic tile or other smooth, hard nonabsorbent surface to a
height of 4 feet. OSSC Section 807.1.2
9. A copy of the approved plans shall be on the job site and made available
to the city inspectors for inspection purposes.
10. Prior to utilizing the structure for its intended use, a final inspection and
certificate of occupancy is required. OSSC Section 109.1
If you have any questions or concerns regarding this review, please contact me
at (503) 718 -2448.