Loading...
Specifications City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 GU S6v • December 11, 2006 - ; TIGARD Delta Fire Inc. Matthew Staley 14795 SW 72" Ave. Portland, OR 97224 RE: FIRE SPRINKLER SYSTEM MODIFICATION Project Information Building Permit BUP2006 -00561 Construction Type: III -B Tenant Name: OHCA Occupancy Type: B Address: 11740 SW 68 Pkwy #250 Occupant Load: 68 Area: 6,800 sq ft Stories: 2 Hazard: Light Hazard The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition, Oregon Fire Code 2004 edition, and NFPA 13. The submitted plans are approved subject to the following. TESTING - Section 16.2.1 1. Hydrostatic testing of the system shall occur at sprinkler final. The contractor's material and test certificate required by NFPA 13, 16.1 shall be completed and signed by both the installer and building owner. 2. Unless permitted by 16.2.1.2 through 16.2.1.6, all piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested at 200 psi (13.8 bar) and shall maintain that pressure without loss for 2 hours. Loss shall be determined by a drop in gauge pressure or visual leakage. The test pressure shall be read from a gauge located at the low elevation point of the system or portion being tested. WATER FLOW ALARMS: - Section 6.9.1 3. Water flow alarm apparatus shall be listed for the service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler of the smallest orifice size installed on the system will result in an audible alarm on the premises within 5 minutes after such flow begins and until such flow stops. SPRINKLER SYSTEM MONITORING :: OSSC 901.6. - NFPA 13 sec 8.16 4. All valves controlling the water supply for automatic sprinkler systems and water -flow switches on all sprinkler systems shall be electrically monitored where the number of sprinklers are more than 20. HANGERS: NFPA 13 sec 9.2 5. The maximum distance between hangers shall not exceed that specified in Table 9 -2.2. Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard or.gov • TTY Relay: 503.684.2772 6. The maximum distance between hangers for listed nonmetallic pipe shall be modified as specified in the individual product listings. SWAY BRACING: - Section 9.3.5 - 9.3.5.8 7. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads and to prevent vertical motion resulting from seismic loads. The structural components to which bracing is attached shall be determined to be capable of carrying the added applied seismic loads. Sway braces shall be designed to withstand forces in tension and compression. Bracing shall be attached directly to feed and cross mains. RESTRAINT OF BRANCH LINES. - Section 9.3.6 . 8. Restraint is considered a lesser degree of resisting loads than bracing and shall be provided by use of one of the following. (1) A listed sway brace assembly • (2) A wraparound U -hook satisfying the requirements of 6- 4.5.3, Exception Number 3 (3) No. 12, 440 -1b (200 -kg) wire installed at. least 45 degrees from the vertical plane and anchored on both sides of the pipe (4)Other approved means 9. Wire used for restraint shall be located within 2 ft (610 mm) of a hanger. The hanger closest to a wire restraint shall be of a type that resists upward movement of a branch line. The end sprinlder on a line shall be restrained against excessive vertical and lateral movement. Where upward or lateral movement would result in an impact against the building structure, equipment, or finish materials, branch lines shall be restrained at intervals not exceeding 30 ft (9 m) SPARE SPRINKLERS: - Section 6.2.9 10. The stock of spare sprinklers shall include all types and ratings installed and shall be as follows: a. For systems having less than 300 sprinklers, not fewer than six sprinklers Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Val Henzel, Senior Plans Examiner OCT /25/2003/SAT 03:27 PM FAX No, P. 003 6ut Paao6 -oos i Dyna-FIow® High Strength Steel Pipe The original high - strength lightwall sprinkler pipe with hydraulics superior to Schedule -10. Dyna -Flow pipe is the "original" high Specifications strength lightwall sprinkler pipe. Dyna- NPS Nominal 1.0, Wt. Wt. (1120 Filled) PCs( WtJUtt (21') Milt (24') Wt/Llf (25') Flow has outstanding hydraulic capabilities and is recognized as the In; mm In; mm Lbs/Ft; Kg/m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg most popular alternative to Schedule -10 1" 1.191 0.830 1.31 91 1,586 1,812 1,888 pipe. Lightweight, easy to cut and easy 25 30.3 1.2 1.95 91 719 822 856 to handle for installation. Dyna -Flow is a 11/4 1.536 1.059 1.87 61 1,356 1,550 1,615 valuable addition to any fire protection 32 39.0 1.6 2.78 61 615 703 733 system. VA' 1.728 1.667 2.71 61 2,135 2,440 2,542 Superior Hydraulics 40 43,9 2,5 4.03 61 968 1107 1153 2° 2.203 2104 3.79 37 1,634 1,868 1,946 With an inside diameter of up to 11% 50 56.0 3.1 5.64 37 741 847 883 larger than Schedule -40 and up to 7% 214' 2.703 2.564 5.10 30 1,615 1,846 1,923 Larger than Schedule -10, Dyna -Flow 65 68.7 3.8 7.59 30 733 837 872 pipe hydraulics are exceptional. Larger 3' 3.314 3.387 7.18 19 1,351 1,544 1,608 1.D.s enable Dyna -Flow, and related 80 84.2 5.0 10.69 19 613 700 729 components, to be down -sized within the 4° 4.310 4.473 10.86 19 1,784 2,039 2,124 system, thus increasing the potential for 90 109.5 6.7 16.16 19 809 925 963 job cost savings. For complete Hazen - Williams charts, refer to "Dyna -blow Hydraulic Data. Tables" Coatings & Fabrication Specifications & Approvals Additional Benefits Dyna -Flow products are coated with Dyna -Flow /Super Flo pipe is manufac- • Lightweight and easy to install, an environmentally approved and tured to meet ASTM A -795 Type E, resulting in more efficient use of your specially formulated modified - acrylic or Grade A and is in compliance with freight and labor dollars. water -based coating. This durable coating NFPA -13 and NFPA •14. All sizes of , provides stability needed to comply is paintable. The black coating acts as Dyna Flow /Super Flo are UL Listed, FM Approved and ULC Listed. with standard hanger spacing an excellent primer and is resistant to (15 ft O.C.) per NFPA. Weathering and U.V. degradation from 0 outdoor storage. 41> • Available in Standard lengths for your Metallurgical properties provide excellent Listed Approved Listed convenience, or can be ordered in fabrication characteristics for end prep custom lengths upon approval. Dyna -Flow /Super Flo is UL/ULC Listed finishes, welding and roll grooving. • Fast cutting use with roll grooved, plain -end g and welding, as well as There is no special process or equipment couplings, and welded joints for wet, dry, easy roll grooving and end preparation. needed for fabrication and installation. prcaction and deluge systems. It is FM • Available in Factory roll grooved form The internal surface of all black Allied Approved for roll grooved, plain -end, and for quicker shop turnaround. Tube & Conduit Fire Sprinkler pipe welded joints for wet systems. Refer to products up to 4.5000" in diameter is appropriate documentation for up -to -date • Clean, durable mill coating provides coated with our new Antibacterial listing and approval information. Dyna- longer "shelf life" and acts as an Formula, "ABF ". In scientific laboratory Flow /Super Flo is now available "hot- excellent primer for custom paint test, ABS proved to have superior dip" galvanized and has been specifically applications, resistance to microbial colonization of approved by FM for dry systems uses. pipe walls, thereby delaying or possibly preventing the onset of Microbiologically Influenced corrosion (MIC) when the First Sprinkler System is first installed. 16100 S. Lathrop • Harvey, IL 60426 Customer Service: */ICp / Flow Control allied 11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882 -5543 TUBE d CONDUIT 2525 N. 27 th Ave. • Phoenix, Az 85009 Fax 708 - 339 -1806 S2 -3 FAX No. P. 004 OCT/25/2003/SAT 03:17 PM ..,': .-.; .--.4.,::::,:,,..;•':!::'..:...:.L'.,::'.."::::::'::'/'N'::-1...1.::::::'..::-....:.::.i.'''.,'...)•::".;i"';'‘.::‘''''.::..:::::'.....„:.',;.::,:',.'....'li.'s'Z'.:i.7:1''..-::',':?'":::./;,..il,,:t...,'..../;'-':''..',..“.:-.:*"-: :::', '.,;;,;:',',.,'.,,..;, ,...., • ,.....,.... :',....-.'..... --...,:,;',.! %:';',,,:?;;:''I'....r.f.'''.'..'':',..',';',1-',' .'1.`,:':.',..s,,.;- -','.'.,•;...:,;',....-2::$,.'.,;1,;:;,,',:. '',.'.'..;":,,,:';:'..1::;::';f...',1'::''',;:.'i:,-.',.:::' 6 ,....,;;;...T:'7,:';',21.•:...ii."::,.'fV,,c:.;.;.'::;:...1.-:',.;ilf..:','-''''''''''.. ... - .'t . :?,: . ' " .:'..'. ' ' ' ..; '..'.... .2 '''.i.-1.1-''''.:J;.:..""i'..-r-6,-.:'..!'"'''''''':.!'.4:...:::::'.11`.,"..:: '.:..' .-;'-',•;.:, ..,:-.:::'":"...::;,) ,. ii,;,',.:.?;;;:,.'.....';',:',.'';'.'....''''',:..'.'" .,,,!.:;:::::.:-.'..:: , "::-..,. ' ', : ..:',. ;:::: ..,..,..,..1,,,,,,. il:,:::::',.',';',:::...,::.n: -;,+5'.....:',.;,..,::'.:-3;.,,,a,,;i:..,,,,,y_,•ft■,.. ,......,,,. ,,, .' ..: " :''. ".: ':....'"-,' 7, .... . :.;."'"•,:.', ':'...::V.'1...;:::.,,....';',,,.',',.■:••• i:,:".:4;.:1',... 4 ;;,,.:,!.',......,,.;;;,:i.. -......■ ;.... '',:"....,,...:..',...,, ' : '.,.. .,..: ‘,..: , ,,,. ;.,.' )...... - - . - ,...... . ;,...' • 4 - -. ,. ,.... , ., ,. ''" . . :,- ..; . .,.1 , . ... . . ,.. :., • ...:. . ... .. ,....'..■ '''' ' r ... '' ....' ...r. .-2i.,, tl •■••:`'3.....,-:',::= ';'..,.....i...Z..:j:■:.,..-):,:..1 ,:,.,■,,!:,....:.'..,,...;° .. ::::':::.. .':-:::'-:.tijEiE8,: Coi4bbi:•17::. ' :...•:,.:..;:.::::.':':.:,-:::.....?.,:.:....';',.'..-.::::.:-:-:.-..r.,'.:',•.::..,,,..Y....,..............L.-- .it..:.., ,i.,-.,-.-.A,f,•::: ;.,.i.'5 i ...: „..:....,,,,..,....,..........,....„. : ....:.:„....... . ... - — . - . - ..' -- - — • ' - --. - . , i g. . ; ..._.,. .. „,.. .... • , ...., . . ,. . • .. , ....,......, -..........;;;,,•: •,...---....;..;;-:: ,..,..,.-.-...--.::,,,. ..,.-:-: ir::•.... , .: • s. . ... ,,,,....,...,,...,,,..;.., 7 ..: "' ' :+-;.:' ' 6 1: -::1 Ii,'.,'7::',..:;....,..:1-;,-;'.;.'.-; ;;'?:%.:.•:' ,''' '';''...-.'.;,..'-:' ..- ' ' ' .: • . ..:. ..::::...-,41 , .„,... ,:,..0,,,...:,,,Ist.,;,1 or...'..; '7'........i."..:.'.',........:::r.,)!....:.,i.,:,:,..', ''...........,..,.,... ...I 4 . ... •I• • .• 4.44 ". ,..• ,•••••••,•• • • I' ; 1 L. . , .... . . . . •• , .,.., .. ,, ....„..,...,„ r ,, . , ':. ., ,,,,,, ■■,:. ,'...:::...',.'". " ...' ...-:- : .... - ''''...."::.''':'''''' , ''.::...r.','.....1.'''''''.::,■'■':‘!:;.:;:''''-'''4..... ,.. , :.... ,.,■41/...,V. , : ' :.-,....... • ! i 1 :',71;''','..:.4.:7.!3‘;';.::',*4•":,j.':.!-,..2.''.‘2::.1....,..,,.:`,., ..,....,..Z ...:.::: ,,-,......, .21 • ...4.1,.,..4,,. ... 1)i::,-,:t4■7!"j.::, : ■ .. .' : ,':, ki.J 4 :!, It'e.,...3',..',17.7.,;■■•3,?,!1'.'....(....1'.:':.........'.:',....:.[,. '::.,'.', :' ,..1 ,.,1'..":::,...;?...'...r..-::-;.': - '''',',.....;‘',1,..,.:',....,.,,,..7',..e.A.,",4= li;f41,1403 ', :, 1. ...t. u .. - .:, s• E ,r,■'' . i •• i ' .r • . 2; : .,:‘.... .... '...• -,,,:',•I''.:j.i.:;.',,,•,,,',;-:;','••.•••,,•••••.;::::?,,V.:',..' ,:', ' ,• ." .. ; , ' , . • ,' , '; I 'r • i ' !'•,..liic,,f;; ...... 1'. . P :: , (OUiy•t 1 ..,.,.: •••,,x ' . '' . I, V ..,d; , • '; • ..%4 -: i - ..... ..,;r?', .' •••; ,,.... - ...;-.. , ....1. , ',',';...',, 1:- :,..4-..; : ; , : ? . 1 : , : - .. , ' , ;' , ..i.;. 1 .-:.• , ....:,- - ...;:i,,t•.; . ., . ....:. ,;,',f7:--; j ir ,. 6 ,,7', Z ., 1 i...,-.1v.iA,...,,,iwr ' .:' : • -s ' 1 p ,,,,■,-,...• .,,,.;,,),:-:...5.:•,:',:•,.;:.•-• .'.• ", :• ' -'•;••• • • ' :, ' • '''•:'% 1• '''''':'`•`•• • • - s' :;:l'-'%'''','•'%.'..-%:•.'''M•.• 4:C* •k " )..5 1 ." 6,i'vi: ,'. - . 21'..-,-. .- .'"• *I':!:..r*;'7-1'1.'•::-.4'.);::.:;.:..,-:1 '..,'-','.,",---.; '''' : .: ..:.'`.'F' !?:-- .c.- - 4. , , •r ' - 1!: et •,.:..: ! :::,: li:.'ii . ":•'•;• . ' ' . : ''-'.- ,,•,,' t r . .; t'7 'i . :'',',5 P':: :; ' -j!.. 1 .!'.. : ':.I . 5.:. ‘ i 7 7 . .....,. ,.5.: Ztt ,; ,1 '.5 ''..,:-.! ; LVIX7.iik.1)4' .31 ;. '.' ....,' A;:"A,75•:•I't.',,•.';"5-:•,,,:7,-,7:, I.. ,,,!...41±.-!.,,t.-,4,:,;:, ;lu ,,, :t,: $.1.•0_,.% 1,..4‘.■ '; . .! •,'-'' ,: ;'. i( :' 141.7 • • . .': - ;%!•,,=•:::,..4:,:::,;',;:i.',.,i".•••,'",•,` - `;': .;■.:`,•,;:•:",;*:.••':'.."'.," ' -.7'..:...,1'...7...-1.41.?4;4,',4:,.,,. 01.,-.; ,:i''.; :.:.•::...:1,:;.3:, •i';'-...-''' ' ..trr-,3.F.itri, ..'. .''.$.;•!ir r,:Cii:;:4 14,. ri;;;;.-,:',',..,.tV .i ,'' CE;'..;''.1:4‘.,i4-;!..;'.4:ii•I'...ji;... ;•.:' ;:.'ILYL!.'"'i'.■:,.F:',. •••;.*. l'I.•: {: ...". ;.` •:. •' 4 * .. r..• , - ; , i:o. , .:.g.,•1-s•-'9. i c• • •••• r 1 :,... ...v.5:;•:: • •; Is-. !*,...,!.••••.*:*;:••,.,: ca .,.,,. „.: . - • ,,,, *•4 k ,.,- y,;• 4 .. -.0(.i.lt..;.=",•.-'3a,":i.V...;,',' ; 1 : , ,f'..:•-)..?; .... .•,• .. r...:.•,. ,.;.;:: .••• • ..,•• 1 .. ... .. • •• • t'4 . , ... ,..,.„ ; !N . ■ •ftw . . /I . r.-r?... A., . ..... ■,,r, Tr,".q.... , ■ :•I ,■••,.;•',4;:t.. ...,. •...', .,•."•,.■ ,..,;',..! f'•;'•• 1 .. ••:. •!: • 4, :1•1:;'::•1"."i'A:!..!! '.:•.'; • i " -:: 'e'; c* . t . ,V2.1 . 1,..?:,,,..3•,.4 . ,•-;' ' ..,.., ii "... 1 ' ..; 0; •.•'''• • j .(,,' i • . s . ' •':', : '..,:i,1 • 1 ' •!,' 1 : '. • ri.::; •:'••1 .....'.:..Cli,2,,•. . '' i••4"" t'Pit "C ' '. . ''l ' • ". - . 1 ;e.,•; , :i.1.1•.•!•,,_; i . • ..:•:.,:... .....••.,: . ::- 4 .' •• . . ..,i.10,0q.. • )N. . 1,„,,,..,,,=,,,,.A. . 0 ." ' - l...: .: '..',.• 1';',.:!:, ••••'-'.• • ,' :1 .. ,..1 ..;': . 1. ). 13 '" •:• •I W Ifi ..;.P .vd 'r,,I rdi, ,•,.. ii :"iii-4_,,,i4.teii, .I •••!•,' • . • 1. • s h - .::; '...... . . i ; :' !•.:■::.:.!. .-,'-'..!..•': ; ' • i ••• ' 1.. :f , .• oAPI Vr.' , , , tg.ei;.'i l ,"4:S. i '!. :i; ... •,,, -.-; • •••"•::•., •:;'.,:*::-:.•::,•*-!:,. • /l ;;';'• : '..':;;.:::.:,..•:,...1.:*.:.' .; , . r•::: *,• • .1; !..,, I •••••:.,.:.,!;;LIP.0.. • .., r•q b.:I ,:., f,-„.; •.,.••• ,•:•,.. •.: • ...::...,:•, 5o u ) 4 • • •.:. .: .,: • •.,',.:. ".i•14.*:4 : : 7 : - A !'• ..:.•:1'! -'4, . ' . Ci C''' .1 ' : * f' '..... ;. •■ 2 ' . . i. ! 7 •: ' ;.' ... '•';''..•:•,....... •'.:•:, ,•*., 1.; ' . . ;1''': t; ; ,. : =I PA r t..,„ : ',.•$1, .1• iii%V ..4,?•-• 7: 'i • es';.:..::' , ...0, , si p i x,3 1 , • . ;: ,.... : .:,,,,.;:;;;;•.,::.....:•;.!;;;,,I. a,,i,p.,..,...;.:::;;;...;:,;;;;:,..i:.,,,,,t,...,;;; •1.::' 'il,',,i'ri',..?,.;.:.'..,:i:;. '.:..:1.1!i".:ArftieP...;?!1:.;:dik,i.:: 4 i.**.. : : • 1,.. :Zp-P.iiglei, . •;.:-*;*•..,;,.,,;.',;,,ilii„,,i; -.. .1 .• .:Iti. . ,. •:;• ,;1;9;•.....,E1.,,';:titi?:Ai•Q.i.; 9F-0 -. ,••ti ; ,:_--','....;:•••• '.;„1.,,I§,..,..e.,:,-.14',1, cl' !*i.:i 0 * • "•• :,•....r..,. ,...,1..., ..... .,.:,..,:a..1::;:,:..... ,, ;., .• •• : :.... .1.. , z :I,' i.,.:,::.,,..,4:1;:!., • i. ,..i;f . „7, •.,... ,...,..,,,,:•. „ .4.,-,.. .: :•..: ...•::: i„.... .. •,:,: . ... ::.,...4.1,,,,!,:[.,..:...,..,...,..:,..,.. , T ;17'.-; . — .f: ,'AFt.....;; :. . • .,. ; . cr .1! !, "1:4;:-J'e7-4., • 11. 12 : • : ! .' i'''''.:!.': '41'.''.1.i1,;'.Tile':::: "0.'4011.:, ; ' .::';'' ;474,;1.1,11),;1;.; il 1., ' l ' .' ..... '. ..■::: 4a.''.::. . • ; . • : . :.: CQ . 1.;; , , '.:.1";:i1; ..ri- ;;;' 1,;i'io..i.:•;,'.Y.',:;;';,''t..c1'.1'1'. • - . -- . l '; 71 . i LIIIII:ft 4. _..• •.:::......::•:„. . .. ••.:•• :w „•:::•.i,..,•:.::: v:••.,...:1_,...73., 2 4 '.' ii..';1'..".,::...'.:''.1;!1:1!;',.':....1•4'.1J,1 ,:•.,..,....;. W... '...1F■,::..,.,...,.1::;1:'.1;1 .■••::.*' ' 1 g ; . ...,,;'• ' !Mr; filr4iliTill ' rIrp ;/..,•1;',1:1. ", r ' i : • ... •. 'I.: ••,, :;;17',..0, •••,;•• • ...!....: 5,,l'■'':,• 4,1X.g.q,P,..tr,::::1-ii.r.i. ., .•,. ... ''', ". .. ...'.....•• ;,•'; . ••"•■•!.- ... . :• ' • • , •:.'•-■:: i• i;•••;•••• .: '.: '• ''',".•:•,'.'..: !''.;:.f.,:er,:14,..?.. ' : ;•• , i ., , .. ; t i . i .V: ' ,f4 . ,:;•!•■ •r X•r• •.; f••• ,......,...:•:::. .• .. . . ----. . . • • ,.. ... . •• .. . . ....: , 1,, .. -• p •••: . .., .: ,„.. )1.":1,..--•3:' ''. ,, . . • . . , „ . . • .• '.....f:..1:•.1!;:,..14-••••:,:!;:•'•?' • ,•, • • • •• ; • :. Zli .''',-.• : :. .... l' ., ... . .• • . ........ . — , . iji. .:: •;;'•-■:',11:: •-. !::1 '.''.''/,'''•':i.,::•j-...'• ,gCQ . •'•'%'.•' • ..- • "/..'.:'.; . :. : ' '...." . . •,;;.!..,.. _:;;.',.........:%•••• '',',.., 11 • •::..,.., ''''''.",':::.::' • . I. : ' "" • .. ' . ., ' itC ',•• '.:::..'. .:s. Zo. I. ... ; : • 1:1.;:: • ' . , ,_.... , , ., • . . • 14 , ,, . . . . . .. .• 4:.. , .: • . • • O. ,, ' . i • ,., , ::!. ..,,. . • . . • Zg• ' ' , : •• ,,, ,Y.: 1 , , : - ... • — ,-.',,• . 7,.'--El• . i . . . " ' & - • . • :9's;i'.....1.',4)::i'l.''''.;....*:'... - . • tl ' • .. ... , . . . ... ' • - . .,- .. . ' ' • ' - . ... . . ...,.. S , , 4 • , ., , „.• , a u .'t ' '' '' , ?•4t •• ; J •' ; ''' ' '' ,. .... :e*L % , - • • L• •.• • . 4!•_,,,,ip.: --:•••.'-.,,-:,.:.",',::. . : . ZLc .. • ., ... • : ..- ,• - - '••-...;r:::•:::•';-.1-•'•,: - ' . 1 ... ' ' 4 • . , • al- • ; 47 i '••!:;•:.,...,......,•:, • :.....,: . . . ,... .'•••:' . _ . .. -.,....= _ ..: 4:C,.... . . ,... .___ ... ... _ _.._. , - : --• .).< ....: . -._— ,• :----- : • ' - •:••;•.: . • -...•.... •:::=---,--- -•,' • . 4 ,:••.-1.,•:....„, ;IP • • . .._-_ . • • . • , i' .‘:•-• • , . . ,. ...., .... ..••,.''''''.,'.**14 • -"A : ''''. • . ... • ,, . • . • • (9 DYNA THREAD • OCT /25/2003/SAT 03:27 PM FAX No. P.005 Dyna-Thread ® Full Line Sch -40 Replacement Dyna - Thread' offers the life expectancy of Sch-40 with superior hydraulics and greater value. . Dyna - Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages- Comparison to Schedule 40 Comparison to L.W.T. Pipes - • Dyna- Thread's inside diameter is up • With its increased strength and lighter • More wall thickness at the thread to 3.6% larger than Sch -40 giving it weight, Dyna- Thread reduces (CRR =1.00) gives Dyna- Thread superior hydraulics. And, when used installation fatigue and is ideal for better life expectancy than lightwall in combination with Dyna -Flow pipe, retro -fit applications. threadable pipe joints. down sizing often occurs. Corrosion Resistance Ratio (CRR) is a • Unlike lightwall threadable pipe, • Dyna -Thread is fully listed and UL (Underwriters Laboratory) term for Dyna Thread has no thread gauge approved by UL, ULC, and FM for the estimated life expectancy of a pipe warning. fire sprinkler applications. joint. This is based on the calculated wall thickness at the base the first 'Dyna - Thread is approved for se o • The life expectancy of Dyna -Thread standard hanger spacing (15 ft. and Sch-40 are cqual based on the exposed thread, assumed to be the weakest point of the pipe length. Dyne- O.C.), can be used as earthquake calculated wall thicknesses per UL. sway bracing, and is safe to use as Thread and Sch -40 have the same drops. • The consistent quality of steel used to calculated wall thicknesses at this paint make Dyna- Thread facilitates smooth and are both assigned the same CRR of • Dyna - Thread is safer to weld on. threading and lower maintenance 1,00. costs • • Dyna- Thread is more widely The internal surface of all black Allied accepted than lightwall threadable • The exterior of Dyna- Thread is where Sch-40 is specified. protected by a clean, durable mill Tube & Conduit Fire Sprinkler pipe coating for extended shelf life and products up to 4.5000" in diameter is easy paint application. coated with our new Antibacterial Formula, "ABF". In scientific laboratory test, ABS proved to have superior Specifications & Approvals resistance to microbial colonization of Super 40/Dyna- Thread pipe is 0 GO pipe walls, thereby delaying or possibly preventing the onset of manufactured to meet: ASTM A -135, Microbiologically Influenced corrosion Grade A and is in compliance with Listed Approved Listed NFPA -13. All sizes of Super 40/Dyna- (MIC) when the First Sprinkler System Thread are rated at 300 psi working is first installed. pressure. Super 40/Dyna- Thread is UL Specifications and ULC Listed for wet, dry deluge and • pre - action sprinkler systems and FM NPS Nominal I.D. Wi. Wt. (H20 Filled) Pas/ Wt/Lltt (21') WVLIft (24') WVLIft (25') Approved for use in wet systems. Super In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft KgIm Lilt Lbs; Kg Lbs; Kg Lbs; Kg 40/Dyna Thread can be "hot -dip" 1" 1.080 1.330 1.75 70 1955 2234 2327 galvanized to meet FM requirement for 25 27.4 2.0 2.60 70 887 1013 105E dry systems. Super 40/Dyna- Thread is 1' /., 1.408 1.870 2.54 51 2002 2288 2384 approved for all threaded couplings and 32 35.8 2,8 3.78 51 908 1038 1081 welded outlets and is suitable for all 1'/z 1.639 2,290 3.22 44 2115 2418 2519 roll grooved, and plain end fittings. 40 41.6 3.4 4.79 44 959 1097 1143 (Sec listing information). 2" 2.104 3.050 4.57 30 1921 2196 2287 50 53.4 4.5 6.80 30 871 996 1032 t` CO Flow Control 16100 S. Lathrop • Harvey, IL 60426 Customer Service: / n IIiecJ 11350 Noncom Rd. • Philadelphia, PA 19154 (800) 882 -5543 TUBE a coniourr 2525 N. 27 th Ave. • Phoenix, AZ 85009 Fax 708 - 339 - 1806 - S3 - OCT/25/2003 /SAT 03:27 PM FAX No. P. 006 Bulletin 117Rev.Q co miniiiiiimmommilivem Rehabid M odel F1 Model F1 Recessed 5 5. Standard Response Se rinklers b The Designer Model F1 Sprinkler ..L Standard Upright Standard Pendent S is Extended Coverage Pendent Conventional Vertical Sidewall Horizontal Sidewall Upright Pendent - HSW 1 Deflector Horizontal Sidewall Extended Coverage . - EC-6 Deflector ll II The Designer Model F1 Recessed Sprinkler r 1 Recessed Pendent Recessed Extended Coverage Pendent I Recessed Extended Coverage Horizontal Sidewal Vertical Sidewall Conventional Approval Organizations 1. Underwriters Laboratories Inc. , .- 2. Underwriters' Laboratories of Canada ' w; ' ` 3. Factory Mutual Research Corp. '437,, 4. Loss Prevention Council 5. NYC BS&A No. 587 -75-SA Horizontal Sidewall Recessed Pendent 6. Pleniere Assemblee 7. Verband der Schadenversicherer J 8. NYC MEA 258 -93 -E l: .,' = '»1. UL Listing Category '\‘ '�° r %-` Sprinklers, Automatic & Open (VNIV) , `? -.!' •,, Product Description Extended Coverage Recessed Extended The F1 Glass Bulb Sprinkler combines the durability of a Horizontal Sidewall Coverage Horizontal standard sprinkler with the attractive low profile of a decora- Sidewall _ tive sprinkler. Whether installed on exposed piping or in an office ceiling, it is functional and attractive. The Horizontal and Vertical SIdewall Sprinklers provide an equally attractive kt appearance when ceiling piping cannot be used. . ', Beautifully versatile is the description for the Reliable " Tv�'J . �> Model F1 Recessed Designer glass bulb sprinkler. Re , ., cessing The Designer' enhances its already low profile dec- orative appearance, and facilitates a rapid and perfect Extended Coverage Recessed Ectended installation. Pendent Coverage Pendent Model F1 Recessed Designer's escutcheon is highly ad- At normal temperatures, the glass bulb contains the fluid in justable. The two piece construction makes field installation a both the liquid phase and in the vapor phase. The vapor very easy and rapid task. This also allows ceiling panels to phase can be seen as a small bubble. As heat is applied, the later be removed without shutting down the fire protection liquid expands forcing the bubble smaller and smaller as the system, thus facilitating maintenance of above ceiling ser- liquid pressure increases. Continued heating forces the liq- vices. uid to push out against the bulb, causing the glass to shatter, The Designer Automatic Sprinkler utilizes a frangible opening the waterway and allowing the deflector to distribute glass bulb. The glass bulb consists of an accurately con - the discharging water. trolled amount of special fluid hermetically sealed inside of a The F1 Sprinkler temperature rating is identified by the precisely manufactured glass capsule. This glass bulb is color of the glass bulb capsule as well as frame color where specially constructed to provide fast thermal response. applicable. The ReliableAutomaticSprinldorCo., Inc, 525 North MacQuesten Parkway, Mount Vernon, New York 10552 - OCT /25/2003/SAT 03:28 PM FAX No, P.007 Model F1 Upright, Pendent & Conventional Sprinklers Installation Wrench: Model D Sprinkler Wrench . '�4�^ f " � ,--1- Upright Pendent Conventional Upright (2) Installation Data: Nominal Sprinkler Nominal Thread Sprinkler Approval Identification Orifice Size K Factor Height Organization Numbers (SIN) US 1 Metric Upright I Pendent Standard- Uoricht (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position W (15mm) 'h" NPT (R1/21 5.6 80 2.2" (56mm) 1.2,3 4,5,6,7 R1725 R1715 'i'.i' (20mm) 94" NPT (R14) of 8.0 115 2.3" (58mm) 1.2,3.4.7.8 R1722 R1712 I 'h° (15mm) 'h" NPT (RVs) 5.6 80 2.2" (56mm) 7 R1795 R1705 /as" (20mm) 44" NPT (RVA) . 8.0 115 2,3" (58mm) 7 R1792 R1702 Ya (11mrn) . 'h" NPT (RVs) (2) 4,2 60 2.54" (65mm) L2,8 - R1723 R1713 3:" (10mm) W NPT (R1/21 (3) 2.8 40 2.54" (65mm) 1.2.8 R1721 (91711 1Omm XLH 1 R' /° 4.2 60 58.1mm 4.8,7 R1724 R1714 Cpnventional Install in Upright or Pendent Position 10mm XLH R'/5 4.2 60 56.1 mm - 81774 15mm 'h" NPT (R' /) 5.6 80 56.1mm 4,6.7 R1775 20mm W NPT (RsA) 8.0 115 58.1mm 4,7 P1772 ('1 LPC Approval up 286 °F (141°C) (a) Smell Orifice identified by a pintie extending beyond the deflector. (3 FM Approval for SSU only, up to 200 °F (83 °C). (4) VdS Approval for Intermediate Response 155 °F (68 °C) only. - 2. OCT /25/2003/SAT 03:28 PM FAX No, P,008 Model F1 Recessed Pendent Sprinkler Installation Wrench: Model RC1 Sprinkler Wrench r-I a, _ - / 14/1• ax r — 1" - -- -- :1 r 1 _ e • x r/r FIERCER nay mOrt 4 ...... - ,,,,.. w" " ..,4 cir)wir i. _Li that. WO F1 Recessed I - IIrJLOIA !n= al When Installed directly into a tee. the escutcheon dimension's adjustment will be reduced, Installation Data: Nominal Sprinkler Nominal Thread K Factor Sprinkler Approval Identification Orifice Size us Metric Height Or Numbers (SIN) Y," (15mm) Y" NPT (RA) 5.6 BO 2.2" (56mm) 1,2,3 R1715 '/ " (20mm) Y:" NPT (RN) _ 8,0 115 2.3" (58mm) 1,2,3 R1712 1 Y," (15mm. Y" NPT (RY) 5.6 80 2.2° (5¢rny�) 7 R1705 , X," (20mm) 3." NPT (R3.) 8.0 115 2.3" (58mm) 7 R1702 (11mm) (21 y" NPT (R`.') 4.2 60 2.54" (65mm) 1,2.8 R1713 3e" (10mm) (21 , Y" NPT (RY /) 2.8 40 2.54" (65mm) 1,2,8 R1711 10mm R3 _ 4.2 60 _ 56.1mm _4 R1714 (1) FM Approval - • Light Hazard – No Limitations. • Ordinary Hazard – Groups 1 & 2. Wet Systems only (2) identified by a pinta extending beyond the deflector. (3) LPG Approval is XLH, OHt and 01-111 Occupancies only, • 57°C through 93 °C ratings. (4) VdS Approval for Intermediate Response 155 ° F (68 °C) only. 3. OCT/25/2003 /SAT 03:28 PM FAX No, P, 009 Model F1 Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench Installation Position: Upright or Pendent '; , Approval Type: Light Hazard Occupancy : Vertical Sidewall U.S. Patent No. 6,374,9201 Installation Data: - Nominal Sprinkler Nominal Thread K Factor Sprinkler Approval Orifice Size Height Organizations identification (SIN) Metric Numbers (SIN) . y (15mm) y NPT (Ry) 5.6 80 2,2" (56,1mm) 1,2,3,4�' 6 ,8 81785 (1i LPC Approval is pendent only, 57 °C through 83 °C ratings. Sprinkler Deflector to Type Ceiling Distance (Min. - Max.) , Upright 4 °(102mm) • 12 °(305mm) Pendent 4•(102mm) - 12'(305mm) Model F1 Horizontal Sidewall Sprinkler Deflector: HSW 1 Installation Wrench: Model D Sprinkler Wrench ;iii ..: a.r ,ii0,.i it Horizontal Sidewall Installation Data: , Nominal Approval Organizations Nominal Thread K Factor Sprinkler pp g Sprinkler Orifice Size Length Light Ordinary Numbers (SIN) Numbers ( US Metric Hazard _ - Hazard YE" (15mm) _ W' NPT (RW) 5.6 80 2.63" (67mm) 1,2,3,5 1,2,5 R1735 Note: UL and ULC Listing permits use with F1 escutcheons, light hazard only, 4. OCT /25/2003/SAT 03:28 PM FAX No. P. O1 Model F1 Extended Coverage Pendent Sprinkler Deflector: EC Pendent Installation Wrench: Model D Sprinkler Wrench Approval Type: Extended Coverage -- Light Hazard Occupancy /., c ..:=s Installation Data: \ ` J c. Sprinkler Nominal Thread I Factor Sprinkler Approval T Rating Identification Identification Orifice Size US Metric Height Organizations 'F °c Numbers (SIN) V.," (20mm) 3:" NPT (H%) 8.0 115 2.2" (56mm) 1.2.8 135: 155 57: 88 R1742 Extended Coverage y," (15mm) y," NPT (RA) 5.6 80 2.2" (56mm) 1,2.8 135: 155 57: 68 R1745 Pendent COVERAGE AREA Pressure Flow Rate Nominal Max Area • K-8.0 (115) K =5.6 (80) Width x Length qpm Umin psi bar psi bar R. x tt. m x nt 26 98.4 10.6 0,7 21.6 1,5 16x16 4.9x4.9 33 125.0 17.0 1.2 34.7 2,4 18 x 18 5.5 x 5.5 40 151.4. 25.0 1,7 51.0 _ 3,5 20x20 6.0 x 6.0 Model F1 Recessed Extended Coverage Pendent Sprinkler Deflector: EC Pendent Installation Wrench: Model RC1 Sprinkler Wrench f.v.� Approval Type: Extended Coverage - Light Hazard Occupancy is ai r l I • x .v. • =mar /.....,, x la Inn, NWv COU,t9 - - - - - - IJ r' x r � INDuC[W 1004 Ap/! nl / '� 1909 r IZ I I , I r r r.7T/7� L _ .,. ' 'I 3/1' AlW91Y[NT rU {:.:t`•-• 1 r he 27 ,.__LI „....,„:„.,:.:, mi ____ Extended Coverage A __ 4 '., Recessed 117F604 I ! 27/)}' pd. (29.9,.9.1 '" When Installed directly into a tee, the escutcheon - dimension's adjustment will be reduced. Installation Data: Nominal Temperature Sprinkler Nominal Thread K Factor Sprinkler Approval Ratlna Identification Orifice Size US Metric Height _ Organlzat(ons °F °C Numbers (SIN) ' /,, (20mm 3:" NPT (1934) 8.0 115 2.2" (56mm) 1,2,8 135: 155 57: 68 191742 Y" (15mm) y," NPT (Rib) 5.6 80 2.2" (56mm) _ 1,2,8 _ 135: 155 57: 68 , R1745 COVERAGE AREA Pressure Max. Area Flow Rate Nominal Width x Length K=8. r 115 = • BO upm Umin psi bar psi , bar ft. x ft. m x m 26 98.4 10 -6 0,7 21.6 1,5 16x16 4.9x4.9 33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5 40 151,4 25.0 1 7 51.0 3 5 20 x 20 8.0 x 8.0 5. . OCT /25/2003/SAT 03:28 PM FAX No, P. 011 Model F1 Extended Coverage Horizontal Sidewall Sprinkler Deflector: EC - Glass Bulb: 3mm 155°F (68 °C) Standard, Unless 5mm 135 °F (57 °C) is Specified Installation Wrench: Model D Sprinkler Wrench Approval Type: Extended Coverage — Light Hazard Occupancy Extended Coverage Horizontal Sidewall Installation Data: Temperature Sprinkler Nominal Thread K Factor Sprinkler Approval Rating__ Identification Orifice Size US Metric Height Organizations , =C Numbers (SIN) % " (20mm) x, " NPT (RN) 8.0 115.3 2.75" (70mm) 1,2,8 135 (5mm bulb) 57 8 155 (3mm bulb) 68 COVERAGE AREA Max. Area Deflector to Flow Rate Pressure Width x Length Ceiling Dimensions (Min. - Max.) ppm Umin psi bar ft. x ft. m x m 36 138.3 20.3 1,4 16 x 22 4.9 x 6.7 4'(102mm) - 8 "(152mm) 39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4 "(102mm) - 6 "(152mm) 6. OCT /25/2003/SAT 03:28 PM FAX No, P. 012 Model F1 Recessed Extended Coverage Horizontal Sidewall Sprinkler Deflector: EC -6 Glass Bulb: 3mm 155 °F (68 °C) Only Installation Wrench: Model a FR1 Sprinkler Wrench Approval Type: Extended Coverage — Light Hazard Occupancy I5/16' tit' rl \ Mimed a• to e `` (IW4mm r0 fSd+mwJ .�: r\ tiJ•I rume ! ' r _ {, � 4099. i;. r 4/14. a _ � �Ill,i i l �' s i� w 11 (492 -4 i -. ("ma -4 ) Recessed Extended Coverage : l Horizontal Sidewal l■ (9>2/ l 01 W' /ner$IYf79r (19. ImV 4 ' ) When installed directly into a tee, the escutcheon dimension's adjustment will be reduced. Installation Data: Nominal Thread K Factor Sprinkler Approval Temperature Sprinkler Orifice Size Height Organizations a patina Identification US Metric F °C Numbers (SIN 1 %" (20mm) " NP7 (8 8.0 115.3 2.75" (70mm) 1,2,8 155 68 R1762 COVERAGE AREA Max. Area Deflector to Ceiling Flow Rate Pressure Width x length Dimensions (Min. - Mex.) qpm IJmin psi bar ft. x ft. m x m 36 136.3 20.3 1,4 16 x 22 4.9 x 6.7 4 "(102mm) • 6 °(152mm) 39 147.8 23.8 1,6 18 x 24 4.9 x 7.3 4 °(102mm) - 6'(152mm) 7. OCT/25/2003 /SAT 03:28 PM FAX No, P. 013 Model F1 & F1 Recessed Sprinklers Maintenance Application The Models F1 and Fi Recessed Sprinklers should Model F1 and Fi Recessed sprinklers are used in fixed be inspected quarterly and the sprinkler system main - fire protection systems: Wet, Dry, Deluge or Preactlon, tained in accordance with NFPA 25. Do not clean sprin- Care must exercised that the orifice size, temperature rat- klers with soap and water, ammonia or any other cleaning fluid. Remove any sprinkler which has been ing, deflector style and sprinkler type are in accordance painted the latest published standards of the National Fire Pro- ainted (other than factory applied) or damaged in any tection Association or the approving Authority Having way. A stock of spare sprinklers should be maintained Jurisdiction. to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be installation maintained in the original cartons and packaging until Model F1 sprinklers are standard response sprinklers in- used to minimize the potential for damage to sprinklers tended for installation as specified in NFPA 13. They must that would cause improper operation or non - operation. also be installed with the Model D Sprinkler Wrench specifi- cally designed by Reliable for use with these sprinklers. The Model F1 Recessed �Sprinklers are to be installed Temperature Ratings with a maximum recess of 3 4 inch (19mm). The Model F1 Sprinkler Maximum Ambient Escutcheon illustrated is the only recessed escutcheon to Classification Temperature Temperature Bulb be used with the Model F1 Pendent and EC Sprinklers. The °F °c °F °c Color use of any other recessed escutcheon will void all approv- Ordinary 135 57 100 38 Orange als and negate all warranties. When installing Model F1 Re- Ordinary 155 68 100 38 Red cessed Pendent, EC Pendent, and EC HSW Sprinklers, use Intermediate 175 79 150 66 Yellow the Model GFR1 Sprinkler Wrench. Any other type of Intermediate 200 93 150 66 Green wrench may damage these sprinklers. High (tt 286 141 225 107 Blue Y g p Extra High 380 182 300 149 Mauve Glass bulb sprinklers have orange covers to protect the bulb during the installation process. REMOVE THIS PRO- "' Not Available For Fi Recessed TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO- Patents: U.S. Patent No. 6,374,920 STATICALLY TESTED AND, WHEN APPLICABLE, THE Applies to Model Fi Vertical Sidewall Sprinklers. ESCUTCHEONS HAVE BEEN INSTALLED. RASCO wrenches are designed to install sprinklers when covers Finishes (1) are in place. Standard Finishes Sprinkler Escutcheon Bronze Brass Chrome Chrome Ordering Information White Polyester Coated White Painted . i Specify: Special Application Finishes 1. Sprinkler Model Sprinkler Escutcheon 2. Sprinkler Type Bright Brasse ''' Bright Brass Black Plated ' Black Plated 3. Orifice Size Black Paint " Black Paint 4. Deflector Type Off White a' a) Off White 5. Temperature Rating: Satin Chrome Satin Chrome P g: Load Plated Specify Bulb Size when ordering Wax Coated "'"' " Wax Over Lead "'u "° Model F1 EC HSW Sprinkler. r " Other colors and finishes are available on special order. 6. Sprinkler Finish Consult factory for details. 7. Escutcheon Finish (where applicable) m 200 °F (93 °C) maximum. "' UL and ULC Listed, and NYC Approved Only. "' 155 °F to 200°F (68°C to 93 °C) ratings only. 1° ' 286 °F (141 °C) Sprinklers may be coated for ambient conditions not exceeding 150 °F (66 °C). "' LPC approved for l0mm and 15mm sprinklers only. The equipment presented In this bulletin Is to be Installed in accordance with the latest pertinent Standards of the National Flre Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are Installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries Manufactured by rsw i The Reliable Automatic Sprinkler Co., Inc. IeIiaIII 44 -105 Sales Offices 0 (800) 6488051 Sales Fax Revision lines indicate updated or new data. (914) 668-3470 Corporate Offices waw.retsblesprkaler.com Internet Address EG printed In USA. 12/03 P/N 999E1970011 •