Dyna-Thread ®
Full Line Sch -40 Replacement
Dyna - Thread' offers the life expectancy of Sch-40 with superior hydraulics and greater value. .
Dyna - Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages.
Comparison to Schedule 40 Comparison to L.W.T. Pipes
• Dyna- Thread's inside diameter is up • With its increased strength and lighter • More wall thickness at the thread
to 3.6% larger than Sch -40 giving it weight, Dyna- Thread reduces (CRR=1.00) gives Dyna - Thread
superior hydraulics. And, when used installation fatigue and is ideal for better life expectancy than lightwall
in combination with Dyna -Flow pipe, retro -fit applications. threadable pipe joints.
down sizing often occurs.
Corrosion Resistance Ratio (CRR) is a • Unlike lightwall threadable pipe,
• Dyna -Thread is fully listed and UL (Underwriters Laboratory) term for Dyna - Thread has no thread gauge
approved by UL, ULC, and FM for the estimated life expectancy of a pipe warning.
fire sprinkler applications. joint. This is based on the calculated
wall thickness at the base of the first • Dyna- Thread is approved for
• The life expectancy of Ilyna- Thread standard hanger spacing (15 ft.
equal based on the exposed thread, assumed to be the
and Sch-40 are c
q weakest point of the pipe length. Dyna- O.C.), can be used as earthquake
calculated wall thicknesses per UL. Thread and Sch-40 have the same sway bracing, and is safe to use as
• The consistent quality of steel used to calculated wall thicknesses at this point drops.
make Dyna- Thread facilitates smooth and are both assigned the same CRR of • Dyna - Thread is safer to weld on.
threading and lower maintenance 1.00.
costs • Dyna- Thread is more widely
The internal surface of all black Allied accepted than lightwall threadable
• The exterior of Dyna- Thread is where Sch-40 is specified.
protected by a clean, durable mill Tube & Conduit Fire Sprinkler pipe
coating for extended shelf life and products up to 4.5000" in diameter is
easy paint application. coated with our new Antibacterial
Formula, "ABF'. In scientific laboratory
test, ABS proved to have superior Specifications & Approvals
resistance to microbial colonization of Super 40/Dyna- Thread pipe is
® ® pipe walls, thereby delaying or possibly
preventing the onset of manufactured to meet: ASTM A -135,
Listed Approved Listed Microbiologically Influenced corrosion Grade A and is in compliance with
Ifl d i
1V
(MIC) when the First Sprinkler System FPA -23. All sizes of Super 40/byna-
is first installed. Thread are rated at 300 psi working
pressure. Super 40/Dyna- Thread is UL
Specifications and ULC Listed for wet, dry deluge and
pre- action sprinkler systems and FM
HPS Homioal I.O. Wt. Wt. (H20 Filled) Pcs/ WI/LIIt (21') WULIfl (24') W1/1.111 (25' , Approved for use in wet systems. Super
In; mm In; mm Lbs/Fr, Kg/m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg 40/Dyna- Thrcad can be "hot -dip"
1' 1.080 1.330 1.75 70 1955 2234 232 galvanized to meet PM requirement for
25 27.4 2.0 2.60 70 887 1013 105: dry systems. Super 40/Dyna -Thread is
1'/i 1.408 1.870 2.54 51 2002 2288 23; ' approved for all threaded couplings and
32 35.8 2.8 3.78 51 908 1038 108 welded outlets and is suitable for all
1W 1.639 2.290 3.22 44 2115 2418 251 roll- grooved, and plain -end fittings.
40 41.6 3.4 4.79 44 959 1097 114 (Sec listing information).
2' 2.104 3.050 4.57 30 1921 2196 228
50 53.4 4.5 6.80 30 871 996 103
* CO now Control 16100 S. Lathrop • Harvey, IL 60426 Customer Service:
T 11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882 -5543
y / TUBE a cav 2525 N. 27 th Ave. • Phoenix, AZ 85009 Fax 708.339 -1806
53 -3
OCT/25/2003/SAT 03:27 PM FAX No. F. 006
Bulletin 117Rev.Q co
IIIIMIIMIIIIIIIIINIIIIIIIMIMIIIIIIIIIIIIIIII MN
Reilabit gg:Ii M Recessed 1 ai
Standard Response 7
S • rinklers a
The Designee Model F1 Sprinkler Standard Upright
Standard Pendent • J
Extended Coverage Pendent - i
Conventional �
Vertical Sidewall ,.
Horizontal Sidewall Upright Pendent
- HSW 1 Deflector
i
Horizontal Sidewall Extended Coverage
- EC-6 Deflector , "
The Designer Model F1 Recessed Sprinkler ! .
Recessed Pendent
Recessed Extended Coverage Pendent i
Recessed Extended Coverage Horizontal Sidewal Vertical Sidewall Conventional
Approval Organizations
1. Underwriters Laboratories Inc. .. __ — . �' " .
2. Underwriters' Laboratories of Canada = ,,_ • `
3. Factory Mutual Research Corp. " ter :';_, :
4. Loss Prevention Council -
5. NYC BS&A No. 587 -75 -SA Horizontal Sidewall Recessed Pendent
6. Pleniere Assemblee
7. Verband der Schadenversicherer
8. NYC MEA 258 -93 -E - °' .
_
UL Listing Category _
Sprinklers, Automatic & Open (VNIV)
Product Description Extended Coverage Recessed Extended
The F1 Glass Bulb Sprinkler combines the durability of a Horizontal Sidewall Coverage Horizontal
standard sprinkler with the attractive low profile of a decors- Sidewall
five sprinkler. Whether installed on exposed piping or in an
office ceiling, it is functional and attractive. The Horizontal
and Vertical Sidewalk Sprinklers provide an equally attractive ii
appearance when ceiling piping cannot be used.
Beautifully versatile is the description for the Reliable IA)
Model F1 Recessed Designer glass bulb sprinkler. Re-` =
cessing The Designee enhances its already low profile dec
orative appearance, and facilitates a rapid and perfect Extended Coverage Recessed Extended
installation Pendent Coverage Pendent
Model F'1 Recessed Designers escutcheon is highly ad- At normal temperatures, the glass bulb contains the fluid in
justable. The two piece constructior, makes field installation a both the liquid phase and in the vapor phase. The vapor
very easy and rapid task This also allows ceiling panels to phase can be seen as a small bubble. As heat is applied, the
later be removed without shutting down the fire protection liquid expands forcing the bubble smaller and smaller as the
system, thus facilitating maintenance of above ceiling ser- liquid pressure increases. Continued heating forces the liq-
vices. uid to push out against the bulb, causing the glass to shatter,
The Designer Automatic Sprinkler utilizes a frangible opening the waterway and allowing the deflector to distribute
glass bulb. The glass bulb consists of an accurately con - the discharging water.
trolled amount of special fluid hermetically sealed inside of a The F1 Sprinkler temperature rating is identified by the
precisely manufactured glass capsule. This glass bulb is color of the glass bulb capsule as well as frame color where
specially constructed to provide fast thermal response. applicable.
The Reliable Automatic Sprinkler Co., Inc, 525 North MacQuesten Parkway, Mount Vemon, New York 10552
OCT /25/2003/SAT 03:28 PM FAX No, P. 007
Model F1 Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
...'' .- ' t - -. - . , ,
. al
1(
-:_ . r . ill $ _ , J • . ,
R
Upright Pendent Conventional Upright (2)
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval Identification
Orifice Size Height Organization Numbers (SIN)
US ( Metric Upriuht 1 Pendent
Standard- Uprloht (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position
14" (15mm) Ye NPT (R'ri21 5.6 80 2.2" (56mm) 1.2,3.4,5,6,7 R1725 R1715
V.." (20mm) 34" NPT (R44) (1) 8.0 115 2.3" (58mm) 1 2 3 4 7 8 R1722 fl1712 ,
I +h° (15mm)C Ve NPT (R') 5,8 80 2.2" (56mm) 7 R1795 R1705
`Ye' (20mrr.) 44" NPT (RN) 8.0 115 2,3" (58mm) 7 R1792 R1702
' (11mm) W' NPT (Rye) (2) 4,2 60 2.54" (65mm) . 1,2,8 R1723 R1713
Y:" (10mm) h NPT (R41 (2)(3( 2.8 40 2.54" (65mm) 1.2.8 R1721 R1711
10mm XLH R' /e I 4.2 60 58 1m 4.6.7 R1724 R1714
Conventional- Install in U right or Pendent Position
10mm XLH R Ye 4.2 CO 56.1 mm — R1774
15mm 'fa" NPT (R1/2) 5.6 80 56.1mm 4,6,7 R1775
20mm 1 34" NPT (R9k) 8.0 115 1 58.1mm 4,7 R1772
( ' I LPC Approval up 286 °F (141 °C)
(a) Small Orifice identified by a pinta extending beyond the deflector.
(3l FM Approval for SSU only, up to 200 °F (93 °C).
I (4) VdS Approval tor Intermediate Response 155 ° F (68 ° C) only.
2.
OCT/25/2003 /SAT 03:28 PM FAX No, P. 008
Model F1 Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
4 g : . - 4 0 . , 6..,
— 1 IS/I.
r« -r-°i
_ _ r r 4z amcctn
F t *WIC" '°' I
�k� lac t �rJ �jfa`� 1,,,t,,,
( 11 .-L-1
F1 Recessed
� 1�' .—I 1
-- r
1.7 .
rn When Installed directly into a tee, the escutcheon dimension's
adjustment will be reduced.
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval
Orifice Size - Height Organizations Identification
US Metric Numbers (SIN)
Y," (15mm) y" NPT (97,) 5.6 80 2.2" (56mm) 1,2,3 R1715
%" (20mm) 3:" NPT (R3'J 8.0 115 2.3" (58mm) 1,2,3 R1712
y," (15mm) Y" NPT (Ry) 5.6 80 2.2" (5��nrr) 7 91705
'X, (20mm) 3:" NPT (R3;) 8.0 115 2.3" (58mm) 7 81702
y„; 01mm) ( 'I X" NPT (FM) 4,2 60 2.54" (65mm) 1.2.8 R1713
_3f Ornm1 Y," NPT (R %n) 2.8 40 2.54" (65mm) 1,2,8 R1711
10mm 1 Rr„ 4.2 60 58.1mm 4 R1714
(1) FM Approval
• Light Hazard - No Limitations.
• Ordinary Hazard - (3roups 1 & 2, Wet Systems only.
(2) Identified by a pintle extending beyond the deflector.
(3) LPC Approval is )(LH, OHI and OHII Occupancies only,
57°C through 83 °C ratings.
I (A( VdS Approval for Intermediate Response 155 °F (68 °C) only.
3.
OCT /25/2003/SAT 03:28 PM FAX No. P.009
Model F1 Vertical Sidewall Sprinkler
installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
i
Vertical Sidewall
U.S. Patent No. 6,374,9201
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval
Orifice Size Height Organizations Identification
US Metric Numbers (SIN)
I'" (15mm) Y" NPT (R)) 5.6 80 2.2" (56.1mm) 1.2.3.4 8.8 R1785
(') LPC Approval is pendent only. 57 °C through 93 °C ratings.
Sprinkler Deflector to •
Type Ceiling Distance
(Min. • Max.)
Upright 4 "(102mm1- 1P°L'i05mm1
Pendent 41102mm) - 12'(305mm) I
Model F1 Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench '£= �``
?iii r / �
'.4kss 4 a.
Horizontal Sidewall
Installation Data:
Nominal
Approval Organizations
Nominal Thread K Factor Sprinkler pp g Sprinkler
Orifice Size Length Light Ordinary Identification
US Metric Hazard Hazard Numbers (SIN)
'/P" (15mm) '/a" NPT (RYz) 5.6 80 2.63" (67mm) 1,2,3,5 1,2.5 81735
Note: UL and ULC Listing permits use with F1 escutcheons, light hazard only.
4.
OCT/25/2003/SAT 03:28 PM FAX No. 3.010
Model F1 Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model D Sprinkler Wrench :•
Approval Type: Extended Coverage -- Light Hazard Occupancy 4 . • .
''
Installation Data: ill.
. . l
Temperature
Nominal Thread T re Sprinkler
Factor Sprinkler Approval RatirRating _
Orifice Size Height Organizations Identification
US Metric °F °C Numbers (SIN)
'X," (20mm) };" NPT (Ri4) 8.0 115 2.2" (56mm) 1,2.8 135: 155 57: 68 R1742 Extended Coverage
Y" (15mm) _ Y" NPT (R'r) 5.6 80 2.2" (56mm) 1,2.8 _ 135: 155 57: 66 _ R1745 Pendent
COVERAGE AREA
Pressure Max. Area
Flow Rate Nominal Width x Length
K=8.O (115) K =5.6 (80)
qpm UmIn psi bar psi , bar ft. x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16x16 4.9x4,9
33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 1,7 51.0 3,5 20x20 6.0 x 6.0
Model F1 Recessed Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model RC1 Sprinkler Wrench -ij ,r.
Approval Type: Extended Coverage - Light Hazard Occupancy
t f ; °"
AIM COuA9 'r _ __ /%
CA
Mk WV
Y°fJ�L7�!1021 F f' .. Roues, - ! \ fl , 1
rr
{� ,,,, ,,,
y - (It 6.4 ... ,, _ Extended Coverage , I�f
Recessed
IINIXIS4 f s. /a' dr.
()
'' When Installed directly into a tee, the escutcheon
dimension's adjustment will be reduced.
Installation Data:
Nominal Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating identification
Orifice Size US Metric Height Organizations , ° Numbers (SIN)
1 %, (20mm) 3" NPT (R44) I 8.0 115 2.2" (56mm) 1,2,8 135; 155 57; 68 R1742
Y," (15mm) 7," NPT (R'h) 5.6 80 2.2" (56mm) 1,2,8 135: 155 57: 68 R1745
COVERAGE AREA
Pressure
Flow Rate Nominal Max. Area
Width x Length
K = 8.0 (115) K=5,6_(80)
stem Umin psi bar pal bar ft. x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9
33 125.0 17.0 1.2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 _ 1,7 _ 51.0 , 3,5 20x20 _ 6.0x6.0
5.
OCT /25/2003/SAT 03:28 PM FAX No. P.011
Model F1 Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC -6
Glass Bulb: 3mm 155°F (68 °C) Standard, Unless 5mm 135 °F (57 °C) is Specified
Installation Wrench: Model D Sprinkler Wrench
Approval Type: Extended Coverage — Light Hazard Occupancy
Extended Coverage Horizontal Sidewall
Installation Data:
Nominal Thread K Factor Sprinkler Approval Temperature Sprinkler
Rating__ Identification
Orifice Size Height Organizations
US Metric °F °C Numbers (SIN)
V%,;' (20mm) f;" NPT (R',4) 8.0 115.3 2.75" (70mm) 1,2,8 135 (5mm bulb) 57 ,8
155 (3mm bulb) 68
COVERAGE AREA
Max. Area Deflector to
Flow Rate Pressure Width x Length Ceiling Dimensions
(Min. - Max ")
gpm ' I../min pal bar ft. x ft. m x m
36 136.3 20.3 1.4 16 x 22 4.9 x 6.7 4 "(102mm) - 6 "(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4"(102mm) - 6 "( 152mm )
6.
OC1/20/2003/SAT 03:28 PM FAX No, P. 012
Model F1 Recessed Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC -6
Glass Bulb: 3mm 155 °F (68 °C) Only
Installation Wrench: Model GFR1 Sprinkler Wrench
Approval Type: Extended Coverage — Light Hazard Occupancy
lolfce.1 _i
S.
(ro+aw" ro isa "...)
\I RAW Meld C0141.9
r r __ _, wiz= I o va
.1.. :?4_2 . 1 , 7 '''.:... r " 2 . Il 111 fiV
Recessed Extended Coverage E: J
Horizontal Sidewall
„,....,7 i, lsss�eY CO
W Awrsrwrr
1'9i
'" When installed directly into a tee, the escutcheon dimension's
adjustment will be reduced.
Installation Data:
Nominal Thread K Factor Sprinkler Approval Temperature Sprinkler
Retina Identification
Orifice Size US Metric Height Organizations , eC Numbers (SIN)
1 7 / 32 " (20mm) 3;" NPT (R�<) 6.0 115.3 2.75" (70mm) 1,2,8 155 68 R1762
COVERAGE AREA _
Max. Area Deflector to Ceiling
Flow Rate Pressure Width x length Dimensions
(Min. - Max.)
nom tlmin psi bar ft. x ft. 1 m x m
36 136.3 20.3 1,4 16 x 22 14.9 x 6.7 4 "(102mm) • 6 *(152mm)
39 147.6 23.B 1,6 16 x 24 4.9 x 7.3 4'(102mm) 6 (152mrn)
7.
OCT /25/2003/SAT 03:28 PM FAX No. P. 013
Model F1 & F1 Recessed Sprinklers Maintenance
Application The Models F1 and F1 Recessed Sprinklers should
Model F1 and F1 Recessed sprinklers are used in fixed be inspected quarterly and the sprinkler system main -
fire protection systems: Wet, Dry, Deluge or Preaction, tained in accordance with NFPA 25. Do not clean sprin-
Care must exercised that the orifice size, temperature rat- klers with soap and water, ammonia or any other
ing, deflector style and Sprinkler Cleaning fluid. Remove any sprinkler which has been
in
g ty type are in accordance painted (other than factory applied) or damaged in any
with the latest published standards of the National Fire Pro- way. A stock of spare sprinklers should be maintained
faction Association or the approving Authority Having to allow quick replacement of damaged or operated
Jurisdiction. sprinklers. Prior to installation, sprinklers should be
Installation maintained in the original cartons and packaging until
Model F1 sprinklers are standard response sprinklers in- used to minimize the potential for damage to sprinklers
tended for installation as specified in NFPA 13. They must that would cause improper operation or non - operation.
also be installed with the Model D Sprinkler Wrench specifi-
cally designed by Reliable for use with these sprinklers.
The Model F1 Recessed Sprinklers are to be installed Temperature Rating
with a maximum recess of 3 /4 inch (19mm). The Model F1 - Sprinkler Maximum Ambient
Escutcheon illustrated is the only recessed escutcheon to Classification Temperature Temperature Bulb
be used with the Model F1 Pendent and EC Sprinklers. The _ °F °c °F °c Color
use of any other recessed escutcheon will void all approv- Ordinary 135 57 100 38 Orange
als and negate all warranties. When installing Model F1 Re- Ordinary 155 68 100 38 Red
cessed Pendent, EC Pendent, and EC HSW Sprinklers, use Intermediate 175 79 150 66 Yellow
the Model GF1:11 Sprinkler Wrench. Any other type of Intermediate 200 93 150 66 Green
High 286 141 225 107 Blue
wrench may damage these sprinklers. Extra High t 360 182 300 149 Mauve
Glass bulb sprinklers have orange covers to protect the -
bulb during the installation process. REMOVE THIS PRO- "' Not Available For F1 Recessed
TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO- Patents: U.S. Patent No. 6,374,920
STATICALLY TESTED AND, WHEN APPLICABLE, THE Applies to Model Fl Vertical Sidewall Sprinklers.
ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
wrenches are designed to install sprinklers when covers Finishes (1)
are In place. Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Chrome
Ordering Information White Polyester Coated White Painted
Specify: Special Application Finishes
1. Sprinkler Model Sprinkler Escutcheon
2. Sprinkler Type Bright Bras &" Bright Brass
Black Plated °' Black Plated
3. Orifice Size Black Paint Black Paint
4. Deflector Type Off White'" Off White
5. Temperature Rating: Lead Chrome , " Satin Chrome
Specify Bulb Size when ordering Wax Coated O1M0I
•
Model F 9 1 EC HSW Sprinkler. Wax Over Lead O1 "'"
"'Other colors and finishes are available on special order.
6. Sprinkler Finish Consult factory for details.
7. Escutcheon Finish (where applicable) °' 200 °F (93 °C) maximum.
rz UL and ULC Listed, and NYC Approved Only.
"' 155 °F to 200°F (68 °C to 93 °C) ratings only.
11 ' 286 °F (141 °C) Sprinklers may be coated for ambient conditions
not exceeding 150 °F (66 °C).
"' LPC approved for lOmm and 15mm sprinklers only.
The equipment presented In this bulletin is to be Installed i accordance with the latest pertinent Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are Installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States. Canada end foreign countriea
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. °1 Reawm
fleliabld (800) 431-1585 Sales Offices �� NW
(800) 648 -6051 Sales Fax Revision lines Indicate updated or new data.
(914) 668 -3470 Corporate Offices
www. reaeflasprIt Ode r.c n Internet Address Ea printed In USA 12/03 P/N 9999970011