Specifications City of Tigard, Oregon ® 13125 SW Hall Blvd. O Tigard, OR 97223 _., ' e •
•
November 20, 2006
6 - � y/v` ; •
yT I•G ARID,
Na
Delta Fire Inc.
4^; Matt Staley
14795 SW 72 Ave.
Portland, OR 97224
RE: FIRE SPRINKLER SYSTEM MODIFICATION
Project Information
Building Permit BUP2006 -00528 Construction Type: III -B
Tenant Name: Oregon medical Association Occupancy Type: B
Address: 11744) SW 68 Ave. #100 Occupant Load: 449
Area 17,130 sq ft Stories: 2
Hazard: Light Hazard
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition,
Oregon Fire Code 2004 edition, and NFPA 13. The submitted plans are approved subject to the following.
TESTING - Section 16.2.1
1. Hydrostatic testing of the system shall occur at sprinkler final. The contractor's material and test
certificate required by NFPA 13, 16.1 shall be completed and signed by both the installer and building
owner.
2. Unless permitted by 16.2.1.2 through 16.2.1.6, all piping and attached appurtenances subjected to
system working pressure shall be hydrostatically tested at 200 psi (13.8 bar) and shall maintain that
pressure without loss for 2 hours. Loss shall be determined by a drop in gauge pressure or visual
leakage. The test pressure shall be read from a gauge located at the low elevation point of the system
or portion being tested.
WATER FLOW ALARMS: - Section 6.9.1
3. Water flow alarm apparatus shall be listed for the service and so constructed and installed that any flow
of water from a sprinkler system equal to or greater than that from a single automatic sprinkler of the
smallest orifice size installed on the system will result in an audible alarm on the premises within 5
minutes after such flow begins and until such flow stops.
SPRINKLER SYSTEM MONITORING: OSSC 901.6. - NFPA 13 sec 8.16
4. All valves controlling the water supply for automatic sprinkler systems and water -flow switches on all
sprinkler systems shall be electrically monitored where the number of sprinklers are more than 20.
HANGERS: NFPA 13 sec 9.2
5. The maximum distance between hangers shall not exceed that specified in Table 9 -2.2.
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard - or.gov • TTY Relay: 503.684.2772
6. The maximum distance between hangers for listed nonmetallic pipe shall be modified as specified in the
individual product listings.
SWAY BRACING: - Section 9.3.5 - 9.3.5.8
7. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads and to
prevent vertical motion resulting from seismic loads. The structural components to which bracing is
attached shall be determined to be capable of carrying the added applied seismic loads. Sway braces
shall be designed to withstand forces in tension and compression. Bracing shall be attached directly to
feed and cross mains.
RESTRAINT OF BRANCH LINES. - Section 9.3.6
8. Restraint is considered a lesser degree of resisting loads than bracing and shall be provided by use of one
of the following.
(1) A listed sway brace assembly
(2) A wraparound U -hook satisfying the requirements of 6- 4.5.3, Exception Number 3
(3) No. 12, 440 -1b (200 -kg) wire installed at least 45 degrees from the vertical plane and anchored on
both sides of the pipe
(4)Other approved means
9. Wire used for restraint shall be located within 2 ft (610 mm) of a hanger. The hanger closest to a wire
restraint shall be of a type that resists upward movement of a branch line. The end sprinkler on a line
shall be restrained against excessive vertical and lateral movement. Where upward or lateral
movement would result in an impact against the building structure, equipment, or finish materials,
branch lines shall be restrained at intervals not exceeding 30 ft (9 m)
PIPING CLEARANCE: - Section 9.3.4
10. Where pipe passes through holes in platforms, foundations, walls, or floors, the holes shall be sized
such that the diameter of the holes is 2 in. (50 mm) larger than the pipe for 1 in. (25 mm) nominal to
3 ' /2" (89 mm) nominal and 4 in. (100 mm) larger than the pipe for pipe 4 in. (100 mm) nominal and
larger. Clearance from structural members not penetrated or used, collectively or independently, to
support the piping shall be at least 2 in.
SPARE SPRINKLERS: - Section 6.2.9
11. The stock of spare sprinklers shall include all types and ratings installed and shall be as follows:
a. For systems having less than 300 sprinklers, not fewer than six sprinklers
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained
on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of
construction. 106.3.1 OSSC
When submitting revised drawings or additional information, please attach a copy of the enclosed City of
Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and
processing the documents.
Respectfully
Val Henzel, Senior Plans Examiner
r MA1/4
14795 S.W. 72ND AVENUE
FIRE _
M PORTLAND, OR 97224
® 9 503 620 40 6417503-620-1058
.,
UL i 2006
CITY OF rICiARD
BUILDING DIVISION
Tigard Triangle Commo
Oregon Medical
Association
DATA SUBMITTAL
FOR
FIRE PROTECTION SYSTEM
DELTA FIRE, INC.
October 27, 2006
Matt Staley
06 -3367
Tigard Triangle Commons — Oregon Medical association
October 27, 2006
Page 2 of 2
TABLE OF CONTENTS
Pipe & Fittings
Black DynaFlow
Black DynaThread
CIS Fittings
Victaulic Mechanical Tee Fig. # 920/921
Hangers
Tolco Pipe Rings Fig. #2
Tolco C -type Beam Clamp Fig. # 65
Sammy Xpress
Sprinkler Heads
Reliable Model F1 /FR' /2" 155 Degrees Pendent
Reliable Model F3 Dry %2" 165 Degrees Pendent
FIRE PROTECTION CONTRACTORS
•
a O
■1 •p
•
im,-U . 0
,Q�,
d Al o%j -Vubfp : M Ohi- euifp
0
- & u p• - iiteld -tiu 07-- " Ari old - euifp a
,____ . _
io,.......„............. .... .
...
., ,.. .........,........_ ,.........„_____... -,
. ....... _ . .,
_. .. . . ... ...._, „ 1
,, ,hr-riaa majd.,:ieu ' At old-I:puff&
f N.
ett
1.4 -.g ,�fp MOad -eurfa Mo/r -esaa •
2
.,..
_____... __......
, _,
iii
; . .
i
4
'
s � ,
'AI o/d -outfp • M oI I -eu a . a4 o%.4-ellA .
, @ rNN
•
e, a ' - ��.
Dyna-FIow®
High Strength Steel Pipe
The original high- strength lightwall sprinkler pipe with hydraulics superior to Schedule -10.
Dyna -Flow pipe is the "original" high- Specifications
strength lightwall sprinkler pipe. Dyna-
Flow has outstanding hydraulic NPS Nominal I.D. Wt. Wt. (H20 Filled) Pcs/ Wain (2V) WVlift (24') Wt/Lift (25')
capabilities and is recognized as the In; mm In; mm Lbs/Ft; Kg /m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg
most popular alternative to Schedule -10 1° 1.191 0.830 1.31 91 1,586 1,812 1,888
pipe. Lightweight, easy to cut and easy 25 30.3 1.2 1.95 91 719 822 856
to handle for installation. Dyna -Flow is a 1W 1.536 1.059 1.87 61 1,356 1,550 1,615
valuable addition to any fire protection 32 39.0 1.6 2.78 61 615 703 733
system. 1W 1.728 1.667 2.71 61 2,135 2,440 2,542
Superior Hydraulics . 40 43.9 2.5 4.03 61 968 1107 1153
2° 2.203 2.104 3.79 37 1,634 1,868 1,946
With an inside diameter of up to 11% 50 56.0 3.1 5.64 37 741 847 883
larger than Schedule -40 and up to 7% 2Y2' 2.703 2.564 5.10 30 1,615 1,846 1,923
larger than Schedule -10, Dyna -Flow 65 68.7 3.8 7.59 30 733 837 872
pipe hydraulics are exceptional. Larger 3° 3.314 3.387 7.18 19 1,351 1,544 1,608
I.D.s enable Dyna -Flow, and related 80 84.2 5.0 10.69 19 613 700 729
components, to be down -sized within the 4° 4.310 4.473 10.86 19 1,784 2,039 2,124
system, thus increasing the potential for 90 109.5 6.7 16.16 19 809 925 963
job cost savings. For complete Hazen -
Williams charts, refer to "Dyna - Flow
Hydraulic Data Tables"
Coatings & Fabrication Specifications & Approvals Additional Benefits
Dyna -Flow products are coated with Dyna -Flow /Super Flo pipe is manufac- • Lightweight and easy to install,
an environmentally approved and tured to meet ASTM A -795 Type E, resulting in more efficient use of your
specially formulated modified - acrylic or Grade A and is in compliance with freight and labor dollars.
water -based coating. This durable coating NFPA -13 and NFPA -14. All sizes of
is paintable. The black coating acts as Dyna Flow /Super Flo are UL Listed, FM • Provides stability needed to comply
an excellent primer and is resistant to Approved and ULC Listed. with standard hanger spacing
(15 ft O.C.) per NFPA.
weathering and U.V. degradation from
outdoor storage. ® i li e 415 • Available in Standard lengths for your
Metallurgical properties provide excellent Listed Approved Listed convenience, or can be ordered in
fabrication characteristics for end prep custom lengths upon approval.
Dyna- Flow /Super Flo is UL/ULC Listed
finishes, welding and roll grooving. for use with roll grooved, plain -end • Fast cutting and welding, as well as
There is no special process or equipment couplings, and welded joints for wet, dry, easy roll grooving and end preparation.
needed for fabrication and installation. preaction and deluge systems. It is FM
• Available in Factory roll grooved form
The internal surface of all black Allied Approved for roll grooved, plain -end, and for quicker shop tumaround.
Tube & Conduit Fire Sprinkler pipe welded joints for wet systems. Refer to
products up to 4.5000" in diameter is appropriate documentation for up -to -date • Clean, durable mill coating provides
coated with our new Antibacterial listing and approval information. Dyna- longer "shelf life" and acts as an
Formula, "ABF ". In scientific laboratory Flow /Super Flo is now available "hot- excellent primer for custom paint
test, ABS proved to have superior dip" galvanized and has been specifically applications.
resistance to microbial colonization of approved by FM for dry systems uses.
pipe walls, thereby delaying or possibly
preventing the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
NCO /Flow Control ^III��.I 16100 S. Lathrop • Harvey, IL 60426 Customer Service:
7 t ,, t `J 11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882 -5543
TUBE & CONDUrT 2525 N. 27 th Ave. • Phoenix, AZ 85009 Fax 708 - 339 -1806
S2 - 3
•
.. •
• • .
. - .
. ... .
•
. .
•
. . _ . ..
... ..
• ' • • . .
.. . .,. .. •.. ii..._lig,
. .
. .. . . .
.-. . • t
§14....,.
1:1
. . , ..,..... , .,....,....:,.... • . .
. ,. , .f.. ',....:-.: ,• ....,,',.., ..-- 1,.-,,.•.,-...... . „-, -.....,_ •., .... ..,-.. - .. -. .7 ...,.... ...,.... _ -. .... • ......-.. . ,;......, .....:_„.....„..:„...,..,...._:....- ..- ,,,,.„....,,..„7.-, ..,—.-..-.-....
.. . ..
,.. ,. ... .....:•, .. _ ..-.. , .,.. : - • . ,.„.,....,,;,,,rd _ 7- • , „.• ...............7 .: _ 7..7 i r -. t.i.: -., --, " -..., • .., ',.':.•,-^•-••- it-s ._ ' . . _ , . -,, ., a I. ,
. . . ,.
.VNAO _YNA a ..VAIACI - ..VP•91., "i 1 11 . . .
. • -.. 1911,
...
..;I• i . Y
ict
. .....,., 0.
. °---- - - - -
. .
- . .. ..
. .
•
. . .
. •
. .
. ,
" ' . ,,- • .. , .. . . .
. . . .,.. , .... - -
• . ., . • ..,,,-.''. " .., .." • ..- . , • • „.. •• ,„.. . ' . . •
• . „ . .
' ' • ' • , .. . . •
. ,
' • . . .
• - .
. . . .
ILI
. .
- •. .
''• ''. .. iiiIiit . - - :V 1' 14 k*Cl .--- .V ''' 6 • '''....' ' ''. - '' -. '-7. ' ',.. ' ill - A . :G - - .: • .-- 7.- 11 ' 1 .. ' ' . " 7.111[1 ' :Q '. • " 1
• - - .- ..-..: - .I.
. , • IZ
.. . . .
- - - .
. .
. . .._-: .. . ..- .• • - • - , , .. .
5 - - . . : . . ,. . .., . . . . . . . . . . . . •
, . . .
... . .,.. .. . , .. , ,. ., . .. . • . .
, . .
, . . - •
. .. . ...
• „ , . .
— • • -r ,, -,.: :.•••. -.,-,--. -...-- -..--:,,...'..', .-::•• ,-...!,.."!;, °.ii:. -...-:•;...
• . • .. . .
,,.,. : . .. - -- "... • •,-.. - . -- .. - - - 7- • -fairut - ---- .:-... - - - -", ,, -.'. , .-Avtr.
- tO ,VNAO . le,IIVA0 • ...VNA.CI - ..VPIA0 " . ..,...
II
... . .
. . . .
- .. ... • •
. , .. •,. - .
. : . .
. .
.. .
• - . . , . .
• . , ..
, .
. .
. .
. . „ .
. - • - ..- - .
. _ .
. . . . .,
- .
. . .
•... . . , _,
. • . ' ' • • • '''',,,, ..
. i , . . .
' • ■
. ,
. .
- -
- - •
,. , • -.• .
. . • . ,..,..,,.. ,... ,.„ .
,-.- - • .:',... :.. 31' cl:
/. p .:_ . ' 4 2 r .'+:•.:'-.' •
' Ni. -,', —"' '7; :::-.- ••"-... 6 v ..'4,1i - -.: ' --- :: """ CIV32.11 . 4
,, ,:, ,--- -• 1'
2
. .. ... ,_,....
....
......,,,.. VNACI
, .. . . .. .V.NA0 " .vNAa lftvAa ..vNAr ; ., • 40.,$ .--•--,. .-
. , ..
• • , - - ".,-.
....,:. .....- ...,-...-; _._ , ..-
. . .
. .
. . . . . . , ..
. .,
. .. . . . - . :. • f ... _
..-••. . "..
, . •_ . .. •
>
. .
. . . • . . .. .
. , . .
. .
. . • . . • .. .
. ' ' . fr ..• ' /
•
: .. - . • -.) . . .
• - - . ' '''- ' '''.i.i•ri .. . ---" - .W.ir -'.'a"v •,. .. .''.: ,-:...„-,"4v-.,til,
1:1
.. .. . , .
• 1111 a MNA a : svNAa ......' .•:, :. - .1frii
- - - - - - •
..... ... __. . „ . ,. .
. .
. „.
. .
. , • '
- . . • ,, ..- . _ . .
. . .„.
. .
• • , • . : . • : .
.. . .•
. -
. . . - •
•
. . - .
. .
. .
. . .
... ,. . • . . .. . _
.• • . . .
.
.. , ,• . „ ,,, _ .. " • . .
"" ,, - -- • --- .. ,,e4 '...-- -.,-„:-- . ""; .
.•
= Dyna.Thread®
Full Line Sch -40 Replacement
Dyna - Thread offers the life expectancy of Sch-40 with superior hydraulics and greater value.
Dyna - Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
and longevity of traditional Sch -40 pipe with quality and superior hydraulic advantages.
Comparison to Schedule 40 - Comparison to L.W.T. Pipes
• Dyna- Thread's inside diameter is up • With its increased strength and lighter • More wall thickness at the thread
to 3.6% larger than Sch-40 giving it weight, Dyna - Thread reduces (CRR =1.00) gives Dyna - Thread
superior hydraulics. And, when used installation fatigue and is ideal for better life expectancy than lightwall
in combination with Dyna -Flow pipe, retro -fit applications. threadable pipe joints.
down sizing often occurs.
Corrosion Resistance Ratio (CRR) is a • Unlike lightwall threadable pipe,
• Dyna- Thread is fully listed and UL (Underwriters Laboratory) term for Dyna - Thread has no thread gauge
approved by UL, ULC, and FM for the estimated life expectancy of a pipe warning.
fire sprinkler applications. joint. This is based on the calculated
•
wall thickness at the base of the first wall is approved for
• The life expectancy of Dyna - Thread exposed thread, assumed to be the standard hanger spacing (15 ft.
and Sch-40 are equal based on the O.C.), can be used as earthquake
calculated wall thicknesses per UL. weakest point of the pipe length. Dyna- sway bracing, and is safe to use as
Thread and Sch-40 have the same drops.
• The consistent quality of steel used to calculated wall thicknesses at this point
make Dyna - Thread facilitates smooth and are both assigned the same CRR of • Dyna- Thread is safer to weld on.
threading and lower maintenance 1.00.
costs. • Dyna- Thread is more widely
accepted than lightwall threadable
• The exterior of Dyna - Thread is The internal surface of all black Allied where Sch-40 is specified.
protected by a clean, durable mill Tube & Conduit Fire Sprinkler pipe
coating for extended shelf life and products up to 4.5000" in diameter is
easy paint application. coated with our new Antibacterial
Formula, "ABF ". In scientific laboratory
test, ABS proved to have superior Specifications & Approvals
resistance to microbial colonization of
41) ® ® pipe walls, thereby delaying or possibly Super 40/Dyna- Thread pipe is
preventing the onset of manufactured to meet: ASTM A -135,
Microbiologically Influenced corrosion Grade A and is in compliance with
Listed Approved Listed NFPA -13. All sizes of Super 40/Dyna-
(MIC) when the First Sprinkler System
is first installed. Thread are rated at 300 psi working
pressure. Super 40/Dyna- Thread is UL
Specifications and ULC Listed for wet, dry deluge and
pre- action sprinkler systems and FM
NPS Nominal I.D. Wt. Wt. (H20 Filled) Pcs/ WI/Lift (21') Wt/Lift (24') Wt/Lift (25') Approved for use in wet systems. Super
In; mm In; mm Lbs/Ft; Kg/m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg 40/Dyna Thread can be "hot - dip"
1' 1.080 1.330 1.75 70 1955 2234 2327 galvanized to meet FM requirement for
25 27.4 2.0 2.60 70 887 1013 1056 dry systems. Super 40/Dyna- Thread is
11/4' 1.408 1.870 2.54 51 2002 2288 2384 approved for all threaded couplings and
32 35.8 2.8 3.78 51 908 1038 1081 welded outlets and is suitable for all
1' /z° 1.639 2.290 3.22 44 2115 2418 2519
roll - grooved, and plain -end fittings.
40 41.6 3.4 4.79 44 959 1097 114 (See listing information).
2° 2.104 3.050 4.57 30 1921 2196 2287
50 53.4 4.5 6.80 30 871 996 1037
tgCO /Flow Control died 16100 S. Lathrop • Harvey, IL 60426 Customer Service:
11350 Norcom Rd. •Philadelphia, PA 19154 (800) 882 -5543
TUBE & CONDUIT 2525 N. 27 th Ave. • Phoenix, AZ 85009 Fax 708 -339 -1806
S3 -3
`i
i
Standards and Specifications (0)/ INT[ANAiIONAI. i
:
Dimensions Material Galvanizing Thread Pressure FederaUOther
Rating
M.I. Fittings
Class 150 /PN 20 ASME 816.3• ASTM A -197 ASTM A -153 ASME 8120.1+ ASME 316.3• ASME 316.3"
Class 300 /PN 50 ASME B16.3• ASTM A -197 I ASTM A -153 ASME 8120.1+ ASME 816.3•
M.I. Unions
Class 1 50/PN 20 ASME 816.39. ASTM A•197 ASTM A -153 ASME 3120.1+ ASME B16.39• ASME 316.39"'
Class 250 ASME 816.39• ASTM A -197 ASTM A -153 ASME 8120.1+ ASME 816.39•
Class 300 /PN 50 ASME 816.39• ASTM A -197 ASTM A -153 ASME 8120.1+ 1 ASME 816.39•
Cast Iron Threaded Fittings .
Class 125 ASME B16.4• ASTM A -126 (A) ASTM A -153 ASME 31.20.1+ ASME 816.4• ASME 816.411
Class 250 ASME B16.4• ASTM A•126 (A) ASTM A -153 ASME 81.20.1+ ASME 1316.4• ASME 816.40
C. 1. Plugs and Bushings
ASME 816.14• ASTM A- 126 (A) ASTM A•153 [ ASME 81.20.1+ J ASME 816.14• I WW
C. 1. Drainage Threaded Fittings
ASME 816.12• ASTM A - 126 (A) ASTM A•153 ASME 81.20.1+ ASME 816.12• I
4� C. 1. Flanges and Flanged Fittings
Class 125 ( r 12'1 ASME 816.1. ASTM A -126 (A) or (B) ASTM A -153 ASME 81.20.1+ ASME 816.1 ASME 816.1•
Class 125 (14' -up) ASME 816.1• ASTM A -126 (8) ASTM A -153 ASME 81.20.1+ ASME B16.1 ASME 816.1•
Class 250 (11%1 21 ASME B16.1• ASTM A -126 (A) or (8) ASTM A•153 ASME 81.20.1+ I ASME B16.1 ASME 816.1•
Class 250 (14• -up) ASME B16.1• ASTM A -126 (8) ASTM A -153 ASME 81.20.1. I ASME 816.1 ASME 816.1•
Forged Steel Threaded Fittings
Class 2000. 3000. ASTM AI05.
6000 ASME 816.11• ASTM A182. ASMEBI.20.1+ ASME 816.11•
ASTM A350
Pipe Nipples
Steel Pipe ASTM A733 ASTM A53 ASME 81.20.1+ WWN 351
- Welded Type F or Type E
Steel Pipe
• Seamless ASTM A733 ASTM A106 Gr. 8 ASME 81.20.1+ WWN 351 _
(High Temp.) .
Brass ASTM 843 " ASME 81.20.1+ WWN 351
• The standard
•an American National standard (ANSI)
+ASME 81.20.1 was ANSI 82.1
(Formerly WW-P -501
• ••Formerly WW -P -521
• • • Formerly WW -U-531
PF- 149 I
IPS CARBON STEEL PIPE — HOLE CUT PRODUCTS 11.02
VIC IAUI IC IS AN ISO 900' CERFIF IED COMPANY
Styles 920 and 920N Mechanical -T® Bolted Branch Outlets
PRODUCT DESCRIPTION
Victaulic Mechanical -T" Outlet provides a direct branch connection at any location a hole can be cut in
pipe. The hole is cut oversize to receive a "holefinder" locating collar which secures the outlet in position
permanently. A pressure responsive gasket seals on the pipe O.D.
•
\ Cross -type connections can be achieved by utilizing two upper housings of the same style and size, with
the same or differing branch size connections. NOTE Style 920 and Style 920N housings cannot be
• mated to achieve a cross connection
e Style 920 and Style 920N Mechanical -T outlets are available with grooved or female threaded outlet.
Specify choice on order. Units are supplied painted with plated bolts. Galvanized housings are available,
- supplied with plated bolts.
Styles 920 and 920N All sizes of Style 920 and 920N are rated at 500 psi (3450 kPa) working pressure on Schedule 10 and 40
carbon steel pipe. They may also be used on high density polyethylene or polybutylene (HDPE) pipe.
Pressure ratings on HDPE are dependent on the pipe rating. Contact Victaulic for ratings on other pipe.
L Style 920 and 920N are not recommended for use on PVC plastic pipe.
Standard piping practices dictate that the Mechanical -T Styles 920 and 920N must be installed so that
the main and branch connections are a true 90° angle when permanently attached to the pipeline surface.
Style 920 Cross
VdS u0 ®u c
ee ictaulic
ublication 1 . 1
for details.
See chart on page 5
for pressure ratings.
MATERIAL SPECIFICATIONS
Housing/Coating: Ductile iron conforming to ASTM A -536, grade 65- 45 -12, with orange enamel coating.
Ductile iron conforming to ASTM A -395, grade 65- 45 -15, is available upon special request.
• Optional: Hot dipped galvanized
Gasket: (Specify choice')
• Grade "E" EPDM
EPDM (Green color code) Temperature range -30 °F to +230'F ( -34 to +110'C). Recommended for
cold and hot water service within the specified temperature range plus a variety of dilute acids. oil -free
air and many chemical services. UL Classified in accordance with ANSI /NSF 61 for cold --86'F
( +30'C) and hot +180 °F ( +82'C) NOT RECOMMENDED FOR PETROLEUM SERVICES.
• Grade "T' nitrile
Nitrile (Orange color code). Temperature range -20'F to +180 °F ( -29'C to +82 °C) Recommended for
petroleum products. air with oil vapors, vegetable and mineral oils within the specified temperature
range. Not recommended for hot water services over +150 "F ( +66'C) or for hot dry air over +140 °F
( +60 °C).
'Services listed are General Service Recommendations only It should be noted that there are services for
which these gaskets are not recommended. Reference should always be made to the latest Victaulic
Gasket Selection Guide for specific gasket service recommendations and for a listing of services which
are not recommended.
Bolts/Nuts: Heat- treated plated carbon steel, trackhead meeting the physical and chemical
requirements of ASTM A -449 and physical requirements of ASTM A -183
9 REGISTEP.ED TRADEMARK OF VICTAULIC - 5 COPYRIGHT 2004 VICTAULIC - PRINTED IN U.S.A. - SKU 4WCAS.678NLV 1480 REV G
United States • Phone: 1. 800 - PICK-VIC (1-800-742-5842) • Fax: 610 - 250 -8817 • e -mail: pickvic@victaulic.com
Canada • Phone: 905 -884 -7444 • Fax: 905 -884 -9774 • e -mail: viccanada@victaulic.com
Europe • Phone:32-9-381-1500 • Fax: 32-9-380-4438 • e -mail: viceuro @victaulic.be
Central and South America • Phone: 610-559-3300 • Fax: 610 -559 -3608 • e -mail: vical@victaulic.com i ^ta u' i C w
Australasia • Phone: 86-21-58855151 • Fax: 86-21-58851298 • e -mail: vicap@victaulic.com
- �I
11.02-1
DIMENSIONS
Y Z Max. Dimensions- Inches/millimeters Aprx.
�� SIZE
Run X Branch Work. Hole
Press. Dia. Fern.
Thd. Grv. Wgt. Each
MI �( Lbs./kg
V �� Nominal inches Style PSI +0.13 V V Fem.
11171 ^ rii, I ur e" mm No. kPa -0.00 T ° t $ W Y Z Thd. Grv.
. -- -- - : -� +A 2 X / (a)
920N 500 1.50 2.00 2.53 - 1.61 5.35 2.75 3.1 -
- VV ` _ , 50 X 15 3450 38.1 51 64 - 41 135 70 1.5
_ f 1 1 X 2 /, (a) 920N 500 1.50 1.97 2.53 1.61 5 35 2.75 3.1
Styles 920 and 920N X 20 3450 38,1 50 61 41 136 70 1.5
w /Grooved Outlet X 1 (a) 920N 500 1.50 1.85 2.53 - 1.61 5.35 2.75 3.0 -
• X 25 3450 38.1 47 64 - 41 136 70 1.4 -
X 1'■ (a) t 920N 500 1.75 2.05 2.75 3.00 1.61 5.35 3.00 3.5 3.2
X 32 3450 44.5 52 70 76 41 136 76 1.7 1.5
4 Y �Z� X 1'1_ (a) i 920N 500 1.75 2.03 2.75 3.12 1.61 5.35 3.25 3.6 32
X 40 3450 44.5 52 70 79 41 136 83 1.7 1.5
2'/, X 1, (a) 500 1.50 2.21 2.74 1.86 5.64 2.75 3.0
r. T lf/ 65 X 15 920N
m ^ u 3450 38.1 56 70 - 17 143 70 1.4 -- mak i `�� X '1, (a) 500 1.50 2.18 2.74 - 1.86 5.64 2.75 3.0
4 111 P !6 7 =
X 20 920N 3450 38.1 55 70 47 143 70 1.4
- IA X 1 (a) 500 1.50 2.06 2.74 - 1.86 5.64 2.75 2.9
Styles 920 and 920N X 25 920N 3450 38.1 52 70 - 47 14.3 70 1.4 -
w/Female Threaded Outlet X 1'/, T (a) 920N 500 1.75 2.30 3.00 3.25 1.86 6.29 3.00 3.5 3.2
X 32 3450 - 44,5 58 76 83 47 160 76 1,7 1,5
X 1 t (a) 920N 500 2.00 2.28 3.00 3.25 1.86 6.26 3.25 3.6 3.3
X 40 3450 50.8 58 76 83 47 159 83 1,7 1,6
NOTE: Style 920 and Style 76,1 mm X '/2 (a) 920 300 1.50 2.22 2.75 - 1.88 6.46 3.16 3.9 -
920N housings cannot be X 15 2065 38,1 56 70 - 48 164 80 1.8 -
mated to achieve cross x /, (a) 300 1.50 2.19 2.75 -- 1.88 6 46 3.16 3.9 -
connections. X 20 920 2065 38.1 56 70 - 48 164 80 1.8 -
X 1 (a) 300 1.50 2.07 2.75 - 1.88 6.46 3.16 3.8 -
These new size Style X 25 920 2065 38.1 53 70 - 48 164 80 1.7 NEW 920N products require a
HOLE SIZE different hole size than X 1'/, (a) t 920N 500 1.75 2.30 3.00 3.31 1.92 6.29 3.00 3.5 3.2
the Style 920 it replaces. X 32 3450 44,5 58 76 84 49 160 76 1,6 1,5
for proper installation. X 1' /2 (a) 500 2.00 2.28 3.00 3.31 1.92 6.29 3.25 3.5 3.3
Use caution to asswe X 40 920N 3450 50.8 58 75 84 49 160 83 1,6 1,5
the proper size hole is
prepared for the specific 3 X 'h (a) 920N 500 1.50 2.52 3.05 - 2.28 6.15 2.75 3.4 -
size and style used. 80 X 15 3450 38.1 64 79 - 58 156 70 1,6 -
Failure to use the proper X 3 /, (a) 500 1.50 2.49 3.05 - 2.28 6.15 2.75 3.4 -
hole size could result in X 20 920N 3450 38.1 63 IB - 58 156 70 1,6 -
joint leakage and
property damage. X 1 (a) 920N 500 1.50 2.38 3.06 - 2.28 6.15 2.75 3.3 -
X 25 3450 38.1 61 73 - 58 156 70 1,6 -
X 1' /, (a) t 920N 500 1.75 2.55 3.25 3.56 2.28 6.15 3.00 3.8 3.7
X 32 (b) 3450 , 44,5 ' 65 83 90 58 156 76 1,8 1,8
X 1 (a) T 920N 500 2.00 2.78 3.50 3.56 2.28 6.15 3.25 4.1 3.8
X 40 (b) 3450 50,8 71 89 90 58 156 83 1.9 1.8
X 2 (a) 920N 500 2.50 2.75 3.50 3.56 2.28 6.75 3.88 4.9 4.6
X 50 3450 63,5 70 89 90 58 172 99 2,3 2.1
3'/2 X 2 920N 500 2.50 - - 3.75 2.44 6.72 3.88 - 3.8
90 X 50 3450 63,5 - - 95 62 171 99 - 1,8
4 X V2 (a) 920N 500 1.50 3.03 3.56 - 2.69 7.01 2.75 3.7 -
100 X 15 3450 38.1 77 90 - 68 178 70 1.8 -
X /, (a) 920N 500 1.50 3.00 3.56 - 2.69 7.01 2.75 3.7 -
X 20 3450 38.1 76 9D - 68 178 70 1.8 -
X 1 (a) 920N 500 1.50 2.88 3.56 - 2.69 7.01 2.75 3.6
X 25 3450 38.1 73 90 - 68 178 70 1.8 -
X 1' /, (a) t 920N 500 1.75 3.08 3.78 4.00 2.69 7.01 3.00 4.0 3.6
X 32 (o) 3450 44.5 78 96 102 68 178 76 1.9 1,8
X 1 (a) 1 920N 500 2.00 3.28 4.00 4.00 2.69 7.01 3.25 4.2 3.9
X 40 (o) 3450 50.3 83 102 102 68 178 83 2,0 1,9
• X 2 (a) 1 920N 500 2.50 3.25 4.00 4.00 2.69 7 01 3.88 5.0 4.6
X 50 3450 63.5 83 102 102 68 178 99 2.3 2.1
X 277 (a) 1 500 2.75 2.88 4.00 4.00 2.69 7.34 4.63 5.8 5.0
X 65 920 3450 69.3 73 102 102 68 186 118 2,6 2.3
X 76.1 mm 920 500 2.75 - - 4.00 2.69 7.34 4.63 - 6.4
3450 69,3 - - 102 68 t 8 118 - 2.9
X 3 (a) 1 500 3.50 3.31 4.50 4.12 2.69 7.73 5.12 8.4 6.4
X 80 920 3450 88.3 84 114 105 68 196 130 3.8 2.9
108,0 mm X 1'i, (a) 920N 500 1.75 3.08 3.78 - 2.63 7.64 3.05 5.0 -
X 32 3450 44,5 78 96 - 67 194 73 2.3 -
X 1 (a) 920N 500 2.00 3.28 4.00 - 2.63 7.64 3.25 5.0
X 40 3450 50.3 83 102 - 67 194 83 2.3 -
Table continued on page 3. See notes on Page 4
2 Styles 920 and 920N Mechanical-7 Bolted Branch Outlets
11 02
DIMENSIONS
•
' =� SIZE Max. Hole Dimensions - Inches/millimeters APrx. Wgt. Ea.
Run X Branch Work. Dia. Fem. LbsJkg
�_ ■
Nominal lnches Style Press. +0.13 Thd. Grv. Fem.
_ _ v � mm No. PSIIkPa -0.00 T" V t 8 V t W Y Z Thd. Grv.
11M1 �� °1 l 1 10' 108,0 mm X 2 (a) 500 2.50 3.25 4.00 - 2.63 7.64 4.00 4.00 5.6
r - ` - _ X 50 920N 3450 63,5 83 102 - 67 194 102 2.5
500 2.75 2.88 4.00 4.00 2.63 7.64 4.29 8.00
IV 76,1 mm 920
I 3450 69,9 73 102 102 67 194 109 203.20
Styles 920 and 920N X 3 (a) 920 500 3.50 3.31 4.50 4.00 2.63 7.63 4.88 - 6.5
w/Grooved Outlet x 80 3450 83.9 84 114 102 67 194 124 - 3,0
5 X '/, 500 2.00 4.22 4.75 3.16 9.70 3.69
125 X 15 920 3450 50.8 107 121 80 246 94
X 172 (a) t 500 2.00 4.03 4.75 4.75 3.16 9.70 3.69 7.4 7.6
Y , -1 r--Z--1 X 40
2 (a) f 920 3450 50.8 102 121 121 80 246 94 3.4 3.4
X 500 2.50 4.00 4.75 4.75 3.16 9.70 4.38 8.2 8.0
�
X 50 920 3450 63,5 102 121 121 BO 248 111 3.7 3,6
V iii ^ Iii. T ■ \ ___ _/ X 2' /z (a) 1 500 2.75 3.63 4.75 4.75 3.16 9.70 4.63 8.3 7.9 44 i } , , X 65 920 3450 69.9 92 121 121 80 246 118 3.3 3.5
{ ` �J X 3 (a) 500 3.50 3.81 5.00 4.63 3.16 9.70 5.31 8.4 8.8
V X 80 920 3450 88.9 97 127 113 80 245 135 3,3 4,0
Styles 920 and 920N 133.0 mm X 2 920N 500 2.50 3.75 4.50 3.17 8.00 3.88
w/Female Threaded Outlet X 50 3450 63.5 95 114 81 203 99
X 3 500 3.50 3.81 5.00 3.00 9.46 5.31
X 30 920 3450 88.9 97 127 76 240 135
139.7 mm X 1 t 920N 500 2.00 3.78 4.50 - 3.30 8.23 3.25
X 40 3450 50,3 96 114 - 34 209 83
NOTE: Style 920 and Style X 2 t 500 2.50 3.75 4.50 - 3.30 8.23 3.88
920N housings cannot be x 50 920N 3450 63.5 95 114 - 84 209 99
mated to achieve cross 500 2.75 3.63 4.75 - 3.13 9.85 4.63 - 8.8
connections.
X 76,1 mm (a)(b) 920 3450 69.9 92 121 - 80 250 118 - 4,0
these new size Style X 76,1 mm 920 500 3.50 4.63 3.16 9.70 5.31 11.0
NEW 920N products require e 3450 88.9 - - 118 30 246 135 5.0 -
HOLE sizE different hole size than X 3 500 3.50 3.81 5.00 4.63 3.16 9.85 5.38 14.0
. • the Style 920 it replaces. x 88,9 920 3450 88.9 96.80 127 118 80 250 137 6,4
for proper installation. 6 X 1 500 1.75 4.43 5.13 5.13 3,79 9.15 3.25 - 4.8
Use caution to assure 920N
the proper size hole is 150 X 32 (b) 3450 • 44,5 • 112 130 130 96 232 83 - 2,2
prepared for the specific. X 1 (a) t 500 2.00 4.40 5.12 5.13 3.79 9.15 3.25 5.4 5.1
size and style used X 40 (b) 920N 3450 50,8 112 130 130 96 232 83 2,4 2.3
Failure the s X 2 (a) 1 500 2.50 4.38 5.13 5.13 3.79 9.15 3.88 6.0 5.6
in
hole e size could result uet in 920N
joint leakage and X 50 3450 63,5 111 130 130 96 232 99 2,7 2,5
property damage. X 2 (a) t 500 2.75 4.01 5.13 5.12 3.69 10.51 4.63 8.3 7.6
X 65 920 3450 69.9 110 130 130 94 267 118 3,8 3,4
X 76.1 mm (a)(b) 920 500 2.75 - - 5.21 3.69 10.51 4.63 - 8.4
3 69.9 - - 132 94 267 118 - 3,8
X 3 (a) t 500 3.50 4.31 5.50 5.13 3.69 10.51 5.31 9.9 8,4
X 80 920 3450 88,9 110 140 130 94 267 135 4,5 3.8
X 4 (a) t 500 4.50 3.81 5.75 5.38 3.69 10.51 6.25 10.1 10.1
X 100 920 3450 114,3 97 146 137 94 267 159 4.6 4.6
159.0 mm X 1' /, 920N 500 1.75 4.43 5.13 3.63 9.40 3.25
X 32 3450 44,5 113 130 92 239 83
X 1 V2 (a) 920N 500 2.00 4.41 5.13 - 3.63 9.40 3.25 7.8 -
X 40 3450 50,8 112 130 - 92 239 83 3.5 -
X 2 (a) 920N 500 2.50 4.38 5.13 - 3.63 9.40 3.88 8.0 -
X 50 3450 63,5 111 130 - 92 239 99 3,6 -
X 76,1 mm 920 500 2.75 4.38 5.50 5.13 3.63 9.40 4.63
3450 69.9 111 140 130 92 239 118
X 3 500 3.50 4.31 5.50 5.13 3.63 9.40 5.31 8.10
X 80 920 3450 88,9 110 140 130 92 239 135 205.7.7
X 108.0 min 920 500 4.50 - - 5.38 3.63 9.40 6.12 - 10.0
3450 114,3 - - 137 92 239 155 - 4,5
X 114,3 mm 920 500 4.50 3.81 5.75 - 3.63 9.40 6.25 18.0 -
3350 114.3 96.80 146 - 92 239 159 8.2 -
165,1 min X 1 920N 500 1.50 3.88 4.56 3.79 9.34 2.75
X 25 3450 38.1 99 116 96 237 70
X 1'/, 920N 500 1.75 4.43 5.13 3.79 9.34 3.25
X 32 3450 44,5 113 130 96 237 83
X 1 V, (a) t 920N 500 2.00 4.41 5.13 3.79 9.34 3.25
X 40 3 50.8 112 130 96 237 33
X 2 (a) 1 920N 500 2.50 4.38 5.13 3.79 9.34 3.88
X 50 3450 63,5 111 130 96 237 99
X 2'/2 t 920 500 2.75 4.01 5.13 - 3.63 10.51 4.63 8.6 7.6
X 65 3450 69.9 110 130 - 92 267 118 3,9 3.4
Table continued on page 4. See notes on page 4.
Styles 920 and 920N Mechanical -T° Bolted Branch Outlets 3
•
'11.02 j
DIMENSIONS
r__ _z___1 SIZE Max. Hole Dimensions - Incheslmlllimeters
Run X Branch Work. Dia.
t Nominal Inches Style Press. +0.13 Aprx. Wgt. Ea.
putit
N�iV mm No. PSI/kPa -0.00 lbsJkg
Sig ^ m, \T�illf/ 165,1 mm 920 500 2.75 4.01 5.13 5.21 3.63 10.51 4.63 8.6 7.6
X 76,1 mm(a)(b)
•
l 3450 69.9 110 130 132 92 267 ltd 3.9 3.4
V X 3 (a) 1 920 500 3.50 4.31 5.50 5.13 3.63 10.51 5.31 10.2 8.4
WI 80 3450 88,9 110 140 130 92 267 135 4.6 3.8
Styles 920 and 920N X 4 (a) i 920 500 4.50 3.81 5.75 5.38 3.63 10.51 6.25 10.5 8.4
tY X 100 3450 114,3 97 146 137 92 267 159 4.8 3,8
w /Grooved Outlet 8 X 2 la) 500 2,75 5.44 6.19 - 4.81 12.42 4.50 11.6' -
• 200 X 50 920 3450 69.9 138 157 - 122 316 114 5.3 -
X 2' /7 (a) i 500 2.75 5.07 6.19 6.19 4.81 12.42 4.50 11.6 11.6
X 65 920 3450 69.9 129 157 157 122 316 114 5,3 5,3
�
Z � X 3 (a) 1
920 500 3.50 5.31 6.50 6.50 4.81 12.42 5.31 12.6 11.6
- X 80 3450 88,9 135 165 165 122 316 135 5,7 5.3
1 A .s : X 4 (a) f 500 4.50 4.81 6.75 6.38 4.81 1242 6.25 15.3 12.5
""�"" 100 920 3450 114,3 122 171 162 122 316 159 6,9 5,7
Styles 920 and 920N
w/Female Threaded Outlet
NOTE: Style 920 and Style
920N housings cannot be
mated to achieve cross
connections.
These new size Style
NEW 920N products require a
HOLE. SIZE different hole size than
the Style 920 it replaces.
for proper installation.
Use caution to assure
the proper size hole is
prepared for the specific
size and style used.
Failure to use the proper
hole size could result in
joint leakage and
property damage.
NOTES
"Center Of run to engaged pipe end.
female threaded outlet only (Dimen-
sions approximate).
1 ,Available with grooved or female
threaded outlet. Specify choice on
order.
Center of run to end of fitting.
Female threaded outlets are avail-
able to NPT and BSPT specifications.
(a) British Standard female pipe
threaded outlet is available as listed,
Specify "BSPT" clearly on order.
(b) For 76,1 mm threaded outlet, spec-
ify 2 BSPT clearly on order.
4 Styles 920 and 920N Mechanical -T' Bolted Branch Outlets
11.02;
FLOW DATA
0
I OUTLET SIZE Equivalent Length OUTLET SIZE Equivalent Length
Feet/meter of Pipe Feet/meter of Pipe
Nominal Actual Nominal Actual
Diameter Out. Dia. Female Diameter Out. Dia. Female
InJmm InJmm Grooved Threaded InJmm InJmm Grooved Threaded
I 0.840 2.0 2 2.375 9.0 10.5
15 21.3 - 0.b 50 60.3 2.7 3.2
' ll 1� /, 20 1.050 4.0 2/ 2.875 71.0 12.5
26.7 - 1,2 65 73.0 3.4 3.8
1 1.315 5.0 3 3.500 13.5 15.5
25 33.7 - 1.5 80 88.9 4.1 4.7
Exaggerated for Clarity 1 1.660 5.5 6.0 4 4.500 20.0 22.0
Flow test data has shown that 32 42.4 1.7 1.8 100 114,3 6,1 6.7
the total head loss between 11/_ 1.900 7.0 8.0
point (1) and (2) for the Style 40 48,3 2.1 2,4
920. 900N and 929
Mechanical -r fittings can Formulas for CV Values:
best be expressed in terms of
the pressure difference across AP = O'- Where:
the inlet and branch. The
pressure difference can be Cr' 0 = Flow (GPM) Cv = Flow Coefficient
obtained from the relationship O = C v x „/A-7' AP = Pressure Drop (PSI)
to the right.
Cv Values Pipe Size Pipe Size Pipe Size
Values for flow of water at Actual Actual Actual
Nominal Outside Nominal Outside Nominal Outside
+60`F ( +16'C) are shown in Diameter Diameter Cv Diameter Diameter Cv Diameter Diameter Cv
the table at right. Inches/mm Inches/mm Values Inches/mm Inches/mm Values Inches/mm Inches/mm Values
1 h 0.840 17 1' /, 1.660 45 2 2.875 135
1 5 21.3 32 42.4 65 73.0
3 /, 1.050 1 1,900 3 3.500
20 26.7 21 40 48.3 60 80 88.9 200
1 1.315 2 2.375 4 4.500
25 33.7 25 50 603 100 100 114,3 400
APPROVED PRESSURE RATINGS
The information provided below is based on the latest listing and approval data at the time of publication.
Listings /Approvals are subject to change and /or additions by the approvals agencies. Contact Victaulic
for performance on other pipe and the latest listings and approvals.
Rated Working Pressures
Run Size PSUkPa
Actual
Nominal Outside
Diameter Diameter Outlet Size Pipe
Inches/mm Inches/mm Inches/mm Schedule UL ULC FM
2'/, - 6 2.875 - 6.625 400 400 4 00
65 - 150 73.0 - 168.3 All 10, 40 2755 2755 2755
2 /-, - 4 2.875 - 4.500 All DF 300 300 300
65 • 100 73,0 - 114,3 2065 2065 2065
2'/4 - 4 2.875 - 4.500 All SF 300 300 300
65 - 100 73.0 - 114.3 2065 2065 2065
6 6.625 300 300 250
150 168.3 3,4 10 2065 2065 1724
6 6.625 300 300 300
150 168.3 3,4 30.40 2065 2065 2065
200 400
8 625 10. 40 2755
0 2 /_ - -
8 8.625 300 - 250
200 219,1 3.4 10 2065 - 1724
8 8.625 300 - 300
200 21
3,4 30.40 2065 - 2065
NOTES: 10 refers to Listed /Approved Schedule 10 steel sprinkler pipe.
40 refers to Listed /Approved Schedule 40 steel sprinkler pipe.
DF refers to Listed /Approved Dyna -Flow steel sprinkler pipe manufactured by American Tube Company.
SF refers to Listed /Approved Super -Flo steel sprinkler pipe manufactured by Allied rube and Conduit Corporation.
This product shall be manufactured by Victaulic Company. All products to be installed in accordance with current Victaulic installation /assembly instructions.
Vicla11liC reserves the right to change product specifications. designs and standard equipment 'without notice 41r10 without IoClIrnma obligations.
Styles 920 and 920N Mechanical -P Bolted Branch Outlets 5
® TDLCD www.tolco.com
a brand at NIBCO .
Revision 5/24/2001
Fig. 2 - Adjustable Band Hanger ®
Fig. 2NFPA - Adjustable Band Hanger with Reduced Rod
Size Range — Size 2 thru 4" pipe.
;.
Material — Carbon Steel, Pre - Galvanized ;
• Function — Recommended for the suspension of non - insulated ' "'' C
pipe or insulated pipe with Fig. 220 shield. __
Fig. 2NFPA accommodates the reduced rod schedule of the
National Fire Protection Association Pamphlet 13. /' '
Approvals — Underwriters' Laboratories Listed in the USA (UL)
and Canada (cUL). Factory Mutual Engineering approved. r �
Conforms to Federal Specification B ;
WW -H -171 E, Type 10 and Manufacturers Standardization Society . /
SP -69, Type 10.
Finish — Pre - Galvanized A t
Note — Available in Stainless Steel materials.
Order By — Figure number, pipe size and material
Dimensions • Weights
Pipe Max. Rec. Approx Wt. /100
Size Rod Size A B C Load Lbs. Fig. 2 Fig. 2NFPA
2 1/2* 5 4 1 600 41 40
3 1/2" 6 4'/5 1'/, 600 45 43
3 1/2" 73/8 51/4 21/8 600 52 50
4 5/8* 7 5 1 1000 59 56
5 5/8" 9 6' /e 2'/, 1250 97 95
6 3/4** 9 672 1 1250 139 105
3/8" nut is used when NFPA rod sizing is requested.
•' 1/2" nut is used when NFPA rod sizing is requested.
® Main Office /Manufacturing Facility • 1375 Sampson Ave • Corona. CA 92879 • Ph 909 737 5599 • Fax 909 737 0330
Customer Service • 800 786 5266
www.tolco.com
®TDLCD www.tolco.com
a brand of NIBCO" e ision 1
Fig. 65 and Fig. 66
Reversible C Type Beam Clamps 3 4 and 1 4 Throat Openings
Size Range ( i . and i . ) 1 and rod Co onent of tate of
• California ro ed
Material Carbon teel it ardened cu oint set scre and eis ic estraints yste � l c0
a nut
. Function eco ended for an in fro steel bea ere flan e
t ic ness does not e ceed (i . ) or 1' ( i . ).
Features II steel construction eli inates structural deficiencies
associated it castin ty e bea cla s. ay be used on to or bot B
to flan a of t e bea . ( e eled li allo s an in fro to flan e
ere clearance is li ited.) ay be installed it set sore in u or D
do n osition. ffset desi n er its unli ited rod ad ust ent by alto in t e rod to be t readed co letely t rou t e cla . en desi n er its ins ection of t read en a e ent. C
PP ) and A rovals Under riters Laboratories Listed in t e U d Canada (cU ). actory utual n ineerin a ro ed. Conf U or s to
ederal ecification 1 1 y e and anufacturers F
tandardi ation ociety y e 1 . ceeds re uire ents of t e ` ational ire rotection ssociation ( ) a let 1 rod ill
su ort 1 t ru i e 1 rod ill su ort 1 t ru i e. J A
ncluded in our eis ic estraints Catalo a ro ed by t e tate of 1��
California ffice of tate ide ealt lannin and e elo ent
( ). or additional load s acin and lace ent relatin to
ro ects lease refer to t e LC eis ic estraint
yste s uidelines.
Finish lain
Note aiiable in lectro al ani ed and finis .
Order By i ure nu ber rod si e and finis
i . atent
B
Fig. 65 D 1
Dimensions Weights Lip!
C
Rod Size Max. Rec. Approx. d r, A B C D E F oad bs. Wt. 100
1, 1 1 1 1
F
1 1' 1 1 1' 11
1' 1 1 1' 11
• a . loads for cla it set scre in u or do n osition. Fig. 66 1
• V�� A
Dimensions Weights
Rod Size ,/
Max. Rec. Approx.
A B C D E F
oad bs. Wt.100
1, 1' 1 1 1 1
1 1' 1' 1 1 1' 11
1' 1' 1 1 1' 11
a . loads for cla it set scre in u or do n osition.
OFFICE/MANUFACTURING FACILITY • 1375 SANIPSON AVE. • CORONA. CA 92879 • PH. 951.737 5599 • FAX 951 737 0330
66 CUSTOMER SERVICE • 800 786.5266
www.tolco.com
. ,
d ;
i i
, ,
-_ 4r -:
i -
; ` an App
r
E
X
L J n.
C ® US s ,_ (.
A
c ' - ---.
PPROVED
LISTED t
a
• Minimum Minimm u ; ;
BX PIN WOOD ' UL UL Max Pipe UL Test Wvod.. FM FM Max FM Test _ Wood '
Size, in Load Pipe Size Load
Thickness, in. . .- - . „ , • Thickness, in.,
`
8007957 GST 10 X CPVC 1 -1/2 300 1.5
8020957 SWG 10 X CPVC 1 -1/2 300 1.5
8008957 GST 20 X 2 -1/2 850 1.5 X 4 1475 1.5
8068925 GST 20 SS X 2 -1/2 850 1.5
8010957 GST 30 X 4 1500 1.5 X 4 1475 1.5
8009925 GST 25 -380 X 4 1500 1.5
8022925 SWG 25 -380 X 3 -1/2 - 4* 1500 1.5
8021957 SWG 20 X 2 -1/2 - 3 ** 1250 1.5
8073925 SWG 20 SS X 2 -1/2 1250 1.5
8139957 SH GST 20 X 3 1050 1.5 X 4 1475 1.5
8141957 SH GST 30 X 4 1500 1.5 X 4 1475 1.5
Minimum Minimum
BX P/N STEEL UL UL Max Pipe UL Test Steel FM FM Max FM Test Steel
Size, in. Load Thickness, in. Pipe Size Load Thickness, in.
8038957 DSTR 1 X 4 1500 0.035 X 4 1475 0.1050
8037957 DSTR 1 -1/2 X 4 1500 0.035 X 4 1475 0.1050
8039957 DSTR 516 X 4 1500 0.037 X 4 1475 0.1050
8045957 DST 516 X 4 1500 0.188 X 4 1475 0.1875
8046957 TEK 50 X 4 1500 0.250 X 4 1475 0.1875
8055957 SWDR 1 X 4 1500 0.037 X 4 1475 0.0600
8056957 SWDR 516 X 4 1500 0.037 X 4 1475 0.0600
8054957 SWDR 1 -1/2 X 4 1500 0.037 X 4 1475 0.0600
8137957 SH DSTR 1 X 4 1500 0.035 X 4 1475 0.1050
8150922 XP 20 X 2 750 0.027 X 4 1475 0.1050
8153922 XP 35 X 3 -1/2 1250 0.043 X 4 1475 0.1050
BX PIN CONCRETE FM FM Max FM Test Material
Pipe Size Load
8059957 CST 20 X 4 1475 3000 PSI
8061957 SWC 20 X 4 1475 3000 PSI
* SWG 25 -380 Maximum pipe size in composite wood joist allowed by UL is 3 -1/2"
SWG 25 -380 Maximum pipe size in wood timber or joist allowed by UL is 4"
** SWG 20 Maximum pipe size in composite wood joist allowed by UL is 2 -1/2"
** SWG 20 Maximum pipe size in wood timber or joist allowed by UL is 3"
/
UL and FM tests were performed in compliance with NFPA -13 Standards.
Fastening requirement: 5 times weight of water filled schedule 40 pipe plus 250 pounds. 1/ BUildex
www.itwbuildex.com
800 - 284 -5339
SSS26 0506
Bulletin 136 Rev.M
N.
® Model F1 FR co
Model F1FR Recessed (.)
Quick Response
cln
Sprinklers x
K
Model F1FR Sprinkler Types
Standard Upright
�`
Standard Pendent
Conventional _,-
Vertical Sidewall, - ,
Horizontal Sidewall 4,,, '
- HSW 1 Deflector
Model F1FR Recessed Sprinkler Types i - =- ' `=
Recessed Pendent Uprght Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector .
" :mow• 4...
1r
Listings & Approvals . ",. 4
1. Listed by Underwriters Laboratories, Inc. (UL) -
2. Listed b y Underwriters' Laboratories of Canada (ULC) .,
3. Certified by FM Approvals r .. -
4. Loss Prevention Council (LPC, UK) ," r f %
5. NYC BS&A No. 587 -75 -SA
6. Meets MIL- S -901C and MIL -STD 167 -1 ;
7. Verband der Schadenversicherer (VdS, Germany)
8. NYC MEA 258 -93 -E
UL Listing Category Vertical Sidewall Conventional
Sprinklers, Automatic & Open
Quick Response Sprinkler
UL Guide Number
VNIV /
r
Patents: US Patent No. 6,374,920 Applies to " r . i . I • \ ,,
Model F1FR Vertical Sidewall Sprinklers. ' A4,
Product Description Horizontal Sidewall Recessed Pendent
Reliable Models F1FR and F1FR Recessed Sprinklers are HSW 1 Deflector (Model FP Shown) I
quick response sprinklers which combine the durability of a
standard sprinkler with the attractive low profile of a decorative
sprinkler. pands, forcing the bubble smaller and smaller as the liquid
The Models F1FR and F1 FR Recessed automatic sprinklers pressure increases. Continued heating forces the liquid to
utilize a 3.0 mm frangible glass bulb. These sprinklers have push out against the bulb, causing the glass to shatter,
demonstrated response times in laboratory tests which are opening the waterway and allowing the deflector to distrib-
five to ten times faster than standard response sprinklers. This ute the discharging water.
quick response enables the Model F1 FR and F1FR Recessed
sprinklers to apply water to a fire much faster than standard Application
sprinklers of the same temperature rating. Quick response sprinklers are used in fixed fire protec-
The glass bulb consists of an accurately controlled amount tion systems: Wet, Dry, Deluge or Preaction. Care must be
• of special fluid hermetically sealed inside a precisely manu- exercised that the orifice size, temperature rating, deflector
factured glass capsule. This glass bulb is specially con- style and sprinkler type are in accordance with the latest
structed to provide fast thermal response. The balance of published standards of the National Fire Protection Asso-
parts are made of brass, copper and beryllium nickel. ciation or the approving Authority Having Jurisdiction.
At normal temperatures, the glass bulb contains the fluid Quick response sprinklers are intended for installation as
in both the liquid and vapor phases. The vapor phase can specified in NFPA 13. Quick response sprinklers and stan-
be seen as a small bubble. As heat is applied, the liquid ex- dard response sprinklers should not be intermixed.
The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552
" Model F1 FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Sprinlder Type K Factor Sprinkler identification
Standard - Upright (SSU) a Pendent (SSP) Sprinkler Approval Number (SIN)
Deflectors Marked to Indicate Position US Metric Height Organization
SSU SSP
X" (15mm) Standard Orifice with /Z" NPT (R1 <) Thread 5.6 80 2.2" (56mm) 1,2,3,4,5,6,7 R3625 1 R3615
" /,Z' (20mm) Large Orifice with %" NPT (R3) Thread I 8.0 115 2.3" (58mm) 1,2,3,4,7,8 R3622 R3612
/fi' (17mm) Small Orifice with Y" NPT (R4) Thread I 4.2 60 2.2" (56mm) 1,2,8 R3623 I R3613
r (10mm) Small Orifice with/" NPT (R/Z) Thread I 2.8 40 2.2" (56mm) 1.2,8 R3621 1 R3611
" l Omm Orifice XLH with R%" Thread 4.2 60 56mm 4,6,7 R3624 I R3614
Conventional-Install in Upright or Pendent Position
10mm Orifice XLH with R% Thread 4.2 60 56mm R3674
15mm Standard Orifice with y" NPT (RA) Thread 5.6 80 56mm 4,6,7 R3675
20mm Large Orifice with 3 /" NPT (R3/4)Thread 8.0 115 58mm 4,7 R3672
,.r . 1 13...43
Y 4i l '
r' .
Upright Pendent Conventional
Model F1 FR Quick Response Recessed Pendent Sprinkler
I Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler Approval Sprinkler Identification
Orifice Size US Metric Height Organizations Number (SIN)
/Z" (15mm) /z " NPT (R%x) I 5.6 80 2.2"(56mm) 1,2,3,4,5,7,8 R3615
"/ (20mm) y" NPT (R 8.0 115 2.3" (58mm) 1.2,3,8 R3612
' /,ti' (11 mm) y" NPT (R'h) 4.2 60 I 2.2" (56mm) 1,2,8 R3613
%" (10mm) y," NPT (R'h) 2.8 40 2.2" (56mm) 1,2,8 R3611
10mm R3, 4.2 60 56mm 4,7 R3614
(1) Refer to escutcheon data table for approvals and dimensions.
f 0 Noc 2 5 /P" OSA. "rc.7m —�
� — 1 ,ia' a* ROL / — HOLE !N .OILING
7E,;C 014 L. 2 5/75 DIA [52.?,,, - ,.1 ...
�-- ,' ., .i_ A 5UCEP T I 1 — 7' .Y 1,12" KL D1'5EK
TURN COLL4P i
NNSIL rll'Nr 1 — — — 1 i-
45 ■wST SFR `
iv, BOSS —., \ / \ /
• I —) — 7 —I
i .
L/ � -t1 J
� V • , / 1 11 ' / y1 , 1 FACE OF FIF::NC TO ' .:rVW; L_= M/ 71 —• -- '- 7 AU ✓USt. /£N/ /'7 / p3•,da \ ' �� , � C£UNC DIMENSION
• \ \ ) 6 3 f i,
i / . _._ _ __ i / �' '1 O�SV�J T O F A C F /J GF ;�,'n NG ,,.,,E.,,s,,,,,,,
: 2 i w:...).1
N . .
1 , ... , , , .,
s._,,,__,
1 27/32' Ow 4L "US LAIC; dT ,!__ _ _ _
1 I I JEF53.._
(7) R£ ER 1; I & MuTC , OATa r4jLE , •^,P .P<,?'F4LS =N0 O,MENSIONS j ;) REFER r0 FP ESCJrCHE:N 0424 t. E)LE FOR a PFPOVAL5 =NC O'S+E ^,S/Oa:5
2.
Model F1 FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Thread K Factor Sprinkler Approval Sprf icati
Nu
Orifice Size US Metric Height Organizations
Numbber er (SIN)
'/2" 1/2" NPT (R' /2) 5.6 80 2.2" (56mm) 1, 2, 3, 6, 8
R3685
15mm h" NPT (R1/2) 5.6 80 2.2" (56mm) 4 (1)
f LPC Approval is for Pendent position only.
Orientation Deflector to Ceiling
v Dimension (Min. - Max.)
Upright 4" - 12" (102mm - 305mm)
Pendent 6" - 12" (152mm - 305mm)
*Hti
Vertical Sidewall
1 US Patent No. 6,374,920
Model F1 FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Approval Organizations
K Factor ' and Type of Approval Sprinkler
Identification
Nominal Thread Sprinkler Light Ordinary Number (SIN)
Orifice Size US Metric Length Hazard Hazard
4" ( 15mm) y" NPT(R%) 5.6 80 I 2.63" (67mm) 1,2,3,5,8 1,2,5,8 j R3635
NOTE: UL, ULC and MEA Listing permits use with F1 or F2 recessed escutcheon.
66ICi4 i 7 /
r '1
" T4CF C' nr',v� r,
"# ,,,,,, , / �` .v.7L p,'d_✓`,. iC
i
/ v 'i / /Jr::;Tr
aR'R .t 1 A� 2 4E0✓CE? V r. _ _ fi f 71: 1 • ti,,,, 152.4,,,,)
Horizontal Sidewall 1 .2.x , — , — . ;, 2 2 0 , A.
R'R',' co,AR r.'f/T'L - :.\
nc-'r .4 , ^IN_ r SPR NK' -,- ' \�
:7d7N;;ri h e
r:', ,
/r)
J -1:),:121: i A.! N/ ,
il _ _ , _SC.J ._.+ OA id TALLE '•2K Ar . 4,'J4 _ %0LN,iO`S.
3.
Installation
Quick response sprinklers are intended for installation as cleaning fluids. Remove dust by using a soft brush or gen-
specified in NFPA 13. Quick response sprinklers and stan- tie vacuuming. Remove any sprinkler which has been
dard response sprinklers should not be intermixed. painted (other than factory applied) or damaged in any
The Model F1FR Recessed Quick Response Sprinklers are to way. A stock of spare sprinklers should be maintained to
be installed as shown. The Model F1 or F2 Escutcheons illus- allow quick replacement of damaged or operated sprin-
trated are the only recessed escutcheons to be used with the klers. Prior to installation, sprinklers should be maintained
Model F1FR Sprinklers. The use of any other recessed escutch- in the original cartons and packaging until used to mini -
eon will void all approvals and negate all warranties. mize the potential for damage to sprinklers that would
• When installing Model F1FR Sprinklers, use the Model D Sprin- cause improper operation or non - operation.
kler Wrench. When installing Model F1FR Recessed Pendent or
Sidewall Sprinklers, use the Model GFR1 Sprinkler Wrench. Any Sprinkler Types
. other type of wrench may damage these sprinklers. Standard Upright
Glass bulb sprinklers have orange bulb protectors to minimize Standard Pendent
bulb damage during shipping, handling and installation. RE-
MOVE THIS PROTECTION AT THE TIME THE SPRINKLER Conventional
SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Re- Sidewall (Vertical, Horizontal HSW1)
moval of the protectors before this time may leave the bulb vul- Recessed Pendent
nerable to damage. RASCO wrenches are designed to install Recessed Horizontal Sidewall HSW 1
sprinklers when covers are in place. REMOVE PROTECTORS
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS Finishes (1) `
TO REMOVE THE PROTECTORS. Standard Finishes
Temperature Sprinkler Escutcheon
emperature Ratings
Bronze Brass
Sprinkler Max. Ambient Bulb Chrome Plated Chrome Plated (3)
Classification Temperature Temp. Color White Polyester Coated White Painted (3)
° C ° F
Ordinary 57 135 100°F(38 °C) Orange Special Application Finishes
Ordinary 68 155 100°F (38 °C) Red Sprinkler Escutcheon
Intermediate 79 175 150"F (66°C) Yellow Bright Brass Bright Brass
Intermediate 93 200 150°F (66°C) Green
High (1) 141 286 225°F (107°C) Blue Black Plated Black Plated
Black Paint Black Paint
(t) Not available for recessed sprinklers. Off White Off White
Escutcheon Data Satin Chrome Satin Chrome
Face of Filing ( Other finishes and colors are available on special order.
Escutcheon
model Approvals Adustrnent Dimensicn toCeiltngor Consult the factory for details.
Wan Din (2) FM Approvals is limited to bronze and brass, chrome or black
1X " plated finishes only.
Max Recess (38.1mm) X6" 'Ye" ( FP Push - on/Thread -off escutcheon
F1 12,4,8 Min Recess X" (5mm -24mm)
(19.1mm) Ordering Information
1x „
F2 1,2,3,4,5,7,8 Max Recess (38.1 mm) /:e' - V(16" Specify:
Min Recess 1 3; 6 " (5mm -17mm) 1. Sprinkler Model
(24mm) 2. Sprinkler Type
FP 1,2 Max Recessed Y16" 1x ° (38.lmm) 3. Orifice Size
Push-on/ (11mm) 4. Deflector Type
Thread off 1,2 Min Recessed (24mm) fi 1" (25.amm) 5. Temperature Rating
No Dimensional Figure for FP 6. Sprinkler Finish
7. Escutcheon Type
Maintenance 8. Escutcheon Finish (where applicable)
The Models F1FR and F1FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system Note: When Model F1FR Recessed sprinklers are
maintained in accordance with NFPA 25. Do not clean ordered, the sprinklers and escutcheons are packaged
sprinklers with soap and water, ammonia or any other separately.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association. Factory Mutual Research
• Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States. Canada and foreign countries.
Manufactured by
® Reliable The Rel Automatic Sprinkler Co., Inc. ® R cycled
The (800)431-1588 Sales Offices
(800)848 - 6051 Sales Fax Revision lines indicate updated or new data
(914)668 -3470 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printea in J.S.A. 7/05 ?/N999957002?
Bulletin 153 Rev.E co
MN
Reliable Model F3
Dry Sprinklers W
73
CD
m
. Features
1. The Model F3 Sprinkler utilizes Belleville Spring ,....#.;t:.,.., : e � '' •' •
Closure Technology � • °
2. Styles available for Model F3 Dry Sprinklers: ; • , V. .1.
.•:( • Pendent
• Recessed Pendent ., ..‘t
• Concealed °��'' ' •,, , •
• Horizontal Sidewall ° • . , - ", .,
• Recessed Horizontal Sidewall • ' .7,---.*, o
3. 11/2" " (38mm) escutcheon adjustment on pendent 4` ,e . . • ` '
sprinkler. Concealed
4. 1 /2" (13mm) escutcheon adjustment on recessed ., _ • • ,
sprinkler with push -on /thread -off FP Model . `
escutcheon ring.
5. %" (9.5mm) cover plate adjustment on concealed
sprinkler with push -on / thread -off CCP cover. . . i
6. Attractive appearance. Employs 5mm frangible
glass bulb and galvanized nipple.
7. Lengths available to accommodate installation'
dimensions from 2" - to - 48" (51 mm - to -
/d .
1219mm), in ' (6mm) increments. ` "
8. Available in a variety of plated and painted finishes. Recessed Pendent
9. For use with wet pipe, dry pipe and all preaction
sprinkler systems.
T ,
i
U.S. Patent Numbers 5,775,431 and 5,967,240.
:16 ,
Approvals ;47-4:-----
SIN Sprinlder Type Approvals 6 -. 1
Pendent
R5314 Recessed Pendent 1(1)(2), 20)0), 3(t)(2) 4(1)(2)
CCP Concealed Pendent Pendent
R5334 Horizontal Sidewall 1 (1)(Z , (1). 4(1)(2) Recessed Horizontal Sidewall ,
• Approval Organization '
1. Listed by Underwriters Laboratories Inc. and UL
Certified for Canada (cULus) ii‘c14._ r ./
2. Certified by FM Approvals
3. LPCB EC Certificate of Conformity (CE) j t ;. i•,)
6832 CPD 2006 (EN12259-1) ` `11. � /6.°
4. NYC MEA 258 - 93 - E �
Note: (1) Light Hazard /
(2) Ordinary Hazard
(3) Ordinary Hazard, Group 1 & 2 �—
Horizontal Sidewall
The Reliable Automatic Spriinlder Co., Inc., 525 North MacQuesten Parkway, Mount Vemon, New York10552
Model F3 Dry Pendent Sprinkler
"A" Dim. I 2' to 48" (51mm to 1219mm) in 1 /4" (6mm) increments
Inlet Protru3 on Elevated
A I Pipe
Finishes "' F - __ ; f - - - - r -_
Sprinkler Escutcheon I_.- ...
.— � —— j. -1
Bronze Brass t ___:iid>l- r ,,12 �1_ -- =__j
Chrome Plated Chrome Plated I 1
White Painted`' White system Tee
Lead Plated (3) ii
Wax Coated (3) (41 ME
Wax Over Lead (3)(41 2 1 /e- pia. 1 NPT
- A - Dimension
R on (53.98 In
11 Other finishes and colors are available on special order. Consult Adjntm onga Ewe in ceiling
factory for details. 4• /4 - [ +6.3xnm]
ry -I I/4- [- 31.75mm] 1 43/64 Dio. 1 1/2 (314.10mm]
. 14 White painted sprinklers will have chrome plated can. (42.47,. ] u Total Adjustment
(4 155 ° F (68 °C) to 200°F (93 °C) rating only. sprinkler con i Gelling I, — 1/4' [31.75mm]
1u 212 °F (100 °C) brown wax may be used on 286 °F (141°C) sprinklers iE -- -;r J
/ 4 [6.3smm]
when maximum ceiling temperatures do not exceed 150 °F (66 °C) Escutcheon ' Ceiling I l -c�� E K
(66°C). Adjustment
Standard Temperature Ratings �1 ` -r.•� { ,
Nominal Position MM g 110 il b .r1 of Escutcheon 1 5 /8
``�� [4.28mm]
Max. Bulb Classlflcation T R re Ambient Temp. Color l/4 (6.
Ordinary 135 °F (57 °C) 100°F (38°C) Orange 3 [76.2Dmm]
Ordinary 155 °F (68 °C) 100 °F (38°C) Red D'k 153fC°, -c
Intermediate 200°F (93 °C) 150°F (66 ° C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications.
Note: The sprinkler can protrudes 1 /4" when escutcheon
Sprinkler Guard: Model C -2 is in nominal position. Escutcheon adjustment
provides + 1 /4" ( +6mm) to -1h/4" ( -32mm) "A"
Sprinkler Installation Wrench: dimension adjustment range.
Model G3 Sprinkler Wrench
Sprinkler Identification Number (SIN): R5314
Model F3 Dry Pendent Recessed Sprinkler
"A" Dim. 13 to 48" (89rrrn to 1219mm) in 1/4" (6rtvn) increments
r, - I7
Inlet Protrusion Elevated -'-- - - --
--
Finishes" Above Inside Pipe _ " A I "
-�1 t = d
-
Sprinkler Escutcheon � ; _ � ; L-- -Mo ti
Bronze Brass ( -- ; System red
Chrome Plated Chrome Plated =_
White Painted White
(1) Other finishes and colors are available on special order. I NPT
Consult factory for details. Cup remains unfinished.
II
Only the escutcheon will contain desired finish. 2 1/z D1°•
- A - Dimension [63.50mm) in
Adjustment Range Hole in Ceiling
*1/4"
Standard Temperature Ratings [t6.35mm] 2 19/54e 010.
Sprinkler Max" [58.34mm]
Temperature Ambient Bulb Nominal Position Sprinkler
• Classification Rating Temp. Color of Escutcheon Cup Assembly .
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red W in Escutcheon L , cei6n
. Intermediate 200°F (93 °C) 150 °F (66 °C) Green I ' ,- -
High" 286°F (141 °C) 225 °F(107 °C) _Blue `I�Q,I, ce hn,
Sprinkler cu and FP Escutcheon fabricated of steel and 1 / 4 ' n Adjust -_
P Escutcheon Adjustment
recommended for interior applications.
1/4" [6.35mm] 3 7/32" Dia.
"Listed and Certified only by cULus. EBCU'Ch°O" Adj 't'"°"t [81.76mm]
I /2 [ 12.70mm]
Sprinkler Installation Wrench: ToloI Aa ;ustme fs3FC0.2
Model G3 R/C Sprinkler Wrench
Sprinkler Identification Number (SIN): R5314 Note: Do not install the Model F3 Dry Pendent Recessed
Sprinkler in ceilings which have positive pressure
in space above.
2.
Model F3 Dry Pendent Concealed Sprinkler
"A" Dim. I 3X" to 48" (89mm to 1219mm) in' /a" (6mm) inc ranents {{
Inl et Protrusion Elevated - - T - - - ' Ag
CCP Cover Plater'► Finishes( Above Inside = P r~ ; - F_--r
Standard Finishes Special Application Finishes ti - -
Chrome Plated Bright Brass Plated ,r- , m.r -ti
White Black Plated 1 == ti
Black Paint ` ° =' s, a`em r °°
Off White ilia
Satin Chrome 1" NPT
(t) Utilizes the )2" cover plate with r" total adjustment.
(2) Other finishes and colors are available on special order. Consult factory for details. �63��mm °'
ju on ]
111
Adjustment Range Hole in Ceiling
4 3/16'
Standard Temperature Ratings [t4.76mm] 2 19/54 Dia.
[58.34mm]
Sprinkler
Temperature Cover Plate Max. Ambient Nominol Position
Classification I Rating Temp. Rating Temp. of coverplote p "Assembly
Ordinary 135 °F (57 °C) 135 °F (57 °C) 100°F (38 °C) _ �; f Coverplote
Ordinary 155 °F (68 °C) 135 °F (57 °C) 100 °F (38 °C) Ceiling 1 E — Assembly
Intermediate 200°F (93 °C) 165 °F (74 °C) 150 °F (66 °C) 1 tin ----
High* 286°F (141 °C) 165 °F (74 °C) 150 °F (66 °C) — i \u —
3/16 [4.76mm]
Sprinkler cup fabricated of steel and CCP Cover Plate fabricated of Coverplote Adjustment
brass and recommended for interior applications. 3/16 [4.76mm]
Coverplate Adjustment 3 5/16 Dio
• Listed and Certified only by cULus. 3/6• [9.53mm] [84.13mm]
Total Adjustment 13J7CO3 -C
Sprinkler Installation Wrench
Model G3 R/C Sprinkler Wrench Note: Do not install the Model F3 CCP Pendent
Sprinkler Identification Number (SIN): R5314 Concealed Sprinkler in ceilings which have
positive pressure in the space above.
Model F3 Dry Horizontal Sidewall Sprinkler
"A" Dim. 2" to 48" (51 mm to 1219mm) in 1 /4" (6mm) increments
Finishes
Sprinkler Escutcheon 1 1/2 [38.10mm]
T otal Aajustmenl
Bronze Brass n r - - -1------ 7 .-_ 17 , : – _ s
Chrome Plated Chrome Plated
White Painted White . .
Lead Plated p' L�j �; ] 4 [ 101.60mm] Min.
Wax Coated m(4' 1 1/4 [31.75mm] 12 [304.80mm] Mae.
f 7IH1 Escutcheon Adjustment
Wax Over Lead S Tee 1 ' Escutcheon 63 Adjustment
(t ' Other finishes and colors are available on special order. ,• NPT j i, [
Consult factory for details. _ e 2 3/32' [53[53.18-1 CA
-- -___rte
White painted sprinklers will have chrome plated can. [ - . , a
p1 155 °F (68 °C) to 200°F (93 °C) rating only. ,1111111� � ._._ ___ ,-_ _"! _T_.'
(4 ' 212°F (100 °C) brown wax may be used on 286 °F (141 °C) sprinklers ';'a — ) — ! [,
;;:
when maximum ceiling temperatures do not exceed 150°F (66 °C). ` 1111111111 l
Standard Temperature Ratings 2 1/6 Dia. j i . _ 1
[53.98mm] -
SprinkI ' HO* in Wall 1/4 [6.35mm]
Temperature Max. Ambient Sprinkler Con Aotn a on
• Classification Rating Temp. Bulb Color - A - O'mension .
Nominal position
Adiustment
Ordinary 135°F (57°C) 100°F (38°C) Orange 152,C„{ Range h 1/4 [ +6.35mm] of Escutcheon
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red ramp. -c - 1 1/4 [- 31.
Intermediate 200°F (93 °C) 150 °F (66 °C) Green
- High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications. Note: The sprinkler can protrudes 1 /4" when escutcheon
Sprinkler Installation Wrench: is in nominal position. Escutcheon adjustment
Model G3 Sprinkler Wrench. e provides +'/4' ( +6mm) to -11/4" " ( -32mm) "A"
dimension adjustment range.
Sprinkler Identification Number (SIN): R5334
3.
Model F3 Dry Horizontal Recessed Sidewall Sprinkler
"A" Dim. 13'/W' to 48" (89mm to 1219mm) in 1 /" (6rtm) increments
Finishest ": r - T6
Sprinkler Escutcheon L r , 1l /}2'
Bronze Brass E """"' °° r ; (35.7„,,„,
Chrome Plated Chrome Plated 1;:46-",..it.
01
White Painted White T« Cup i ;i 6'
"'Other finishes and colors are available on special order. Consult 1• NPT - -�
factory for details.
\ System
{ 1 - -- MI_ +
p
r I ____ fii _; l 7 �.
Sprinkler's can and FP Escutcheon are fabricated of steel and .+ " ii i liil
11111111111! I leLe"'l
recommended for interior applications. .; � ��u1
2 1 / 2'l6ln c 7 0 1DIA
HoM it Noa ;
2 19/6.'159.lmmIOt . 1-.J
Standard Temperature Ratings 1
' /2• [12.lmnll
u' ..„,, ion Eacul[ A°justmant
Sprinkler Max. Bulb bj °rt2"1 o
Classification Temperature Rating Ambient Temp. Color /6s ( 1 7 -o(
Ordinary 135 °F (57 °C) 100°F (38 °C) Orange
Ordinary 155 °F (68 °C) 100°F (38 °C) Red
Intermediate 200°F (93 °C) 150 °F (66°C) Green
High" 286 °F (141 °C) 225 °F (107 °C) Blue
• Listed and Certified only by cULus. Notes: Do not install the Model F3 Dry Horizontal
Recessed Sidewall Sprinkler in walls which
have positive pressure in their side space.
• Recessed Horizontal Sidewall sprinklers are
r
listed by cULus for installation of min. 4" (100mm)
Sprinkler Installation Wrench:
Model l Installation
Sprinkler Wrench - to - max. 6" (150mm) below ceiling, and FM
P approved for installation of min. 4" (100mm) - to -
Sprinkler Identification Number (SIN): R5334 max. 12" (306mm).
Technical Data Ordering Information
Orifice Size: 1/2" (15mm) Specify:
Thread size: 1" NPT per ANSI B2.1 1. Sprinkler Type (select one):
Working Pressure: 175 psi (12 bar) (a) Model F3 Dry Pendent
Nominal K Factor - US / (Metric): 5.6 / (80) (b) Model F3 Dry Recessed Pendent
Product Description (c) Model F3 Dry Concealed Pendent
Reliable Model F3 Dry Sprinklers are standard (d) Model F3 Dry Horizontal sidewall
response sprinklers utilizing a durable 5mm frangible (e) Model F3 Dry Recessed Horizontal Sidewall
glass bulb. Model F3 Dry Sprinklers are intended for use 2. Sprinkler Temperature Rating.
in dry and preaction systems and in areas subjected to
freezing temperatures, such as freezers and unheated 3. Sprinkler Finish.
portions of buildings. 4. Cover Plate/FP Escutcheon Finish.
Environments wherein dry sprinklers are employed 5. Length: "A" Dimension (face of tee to face of ceiling
can be corrosive. For this reason, Model F3 Sprinklers or wall) in 1/4 " (6.4mm) increments.
have a special wax fillet placed in the gap between the
cup that supports the bulb and the wrenching boss. This Note:
wax will not interfere with the operation of the sprinkler, 1. The "A" dimension is based on a nominally gauged
and it prevents contaminents from entering the internal pipe thread "make -up" of .600" (15mm) per ANSI
portion of the drop nipple. The wax must not be B2.1 [7 1/2 threads approximately].
removed. 2. All platings and
p g paintings are decorative and
Op glass cons
Operation intended for interior use.
he gl bulb consists of an accurately controlled 3. Acceptable appearance in conditions such as
amount of special fluid hermetically sealed inside a parking garages is generally provided with bronze
precisely manufactured glass capsule. When the sprinkler, brass cup and escutcheon for the Model F3
temperature increases sufficiently due to a fire, the bulb Pendent only.
shatters allowing operating parts to clear the waterway.
This enables the inlet seal to release air or water and
subsequently, cause water flow over the deflector in a
uniform spray pattem, controlling or extinguishing the fire.
4.
General Installation Instructions
Model F3 dry sprinklers must be installed only in E . _ i
standard (ANSI B 16.3 class 150 and ANSI B 16.4 class
125) pipe tees even at branch line ends. For these and k'.
other fittings including CPVC, the dry sprinkler should be _.
installed into a fitting to conform with protrusion into the
fitting in accordance with the diagrams. Dry sprinklers
should not be installed into elbows and into pipe
couplings located on drop nipples to the sprinklers. The aehe6:3
Odei G3
• "A" dimension of a dry sprinkler, which extends into .
freezers from wet pipe systems, should be selected to ,c�».b,
provide at least 14" (356mm) between the freezer's W ��
outside wall or ceiling and the wet pipe line.
1. Cut the specified size hole (see illustrations) for the
sprinkler in the ceiling directly in line with the tee.
2. Apply pipe joint compound to the 1" (25mm) pipe Fig. 1 - G3 R/C Wrench
threads and install sprinkler using the Model G3 or
G3 R/C Sprinkler Wrench as specified.
3. Install the Model FP push -on / thread -off escutcheon or
CCP cover plate if required.
Note: Installation of the Model F3 Sprinklers in f,' . A
copper pipe systems is not recommended,'
as this may reduce the life expectancy
of the sprinklers. i�- •
Model F3 Concealed and Recessed
Installation Instructions
• The Model G3 R/C Wrench (Fig. 1) is designed to iinaabie
locate on the wrenching pads of the Recessed
and
sprinkler while centering in the cup. A standard 1 /2 ea
drive ratchet may be used to drive this wrench. Y'`°
Figures 1 and 2 show sequentially the insertion of the
wrench. First, the wrench, with its jaws above the
sprinkler deflector, is moved laterally until centered
with the cup. Then raise the wrench inside the cup Fig. 2 - G3 R/C Wrench
until its jaws engage the sprinkler's square wrenching
pads (Fig. 3). To remove the wrench, follow this
procedure in reverse order. Care should be taken to
avoid striking the deflector with the wrench.
• Model G3 Wrench (Fig. 4) is used for installation of
Pendent and Horizontal sidewall sprinklers.
Maintenance jit
The Model F3 Dry Sprinklers should be inspected
quarterly and the sprinkler system maintained in
accordance with NFPA 25. Do not remove the factory ,,
applied thermally sensitive wax fillet between the bulb rtxtr,,...,,,ai
supporting cup and the wrenching boss. Do not replace ' and
this wax with a substitute substance. An Alternate Wmdd ...y
substance may interfere with proper operation of the
sprinkler. Do not clean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by Fig. 3 - G3 R/C Wrench
using a soft brush or gently vacuuming. Remove any
sprinkler which has been painted (other than factory
applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick
• replacement of damaged or operated sprinklers. Prior ,
• to installation, sprinklers should be maintained in the
original cartons and packaging until used to minimize A __.
- the potential for damage to sprinklers that would cause
improper operation or non - operation.
.— .
•
Fig. 4 - G3 Wrench
5.
Reliable...For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision -made Reliable products that guard life and property from fire around the clock
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers - • Check valves
• Concealed automatic sprinklers • Supertrol electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
•
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliabld The Reliable Automatic Sprinider Co., Inc. L? Pap clad
(800) 431 -1588 Sales Office
(800) 848 -6051 Sales Fax
(914) 668 - 3470 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address E.G. Printed in U.S.A 1/05. p/N ggggg70148