Specifications E314 Pa007 - 000
SIEMENS Fire Safety
HFPO -11 Intelligent Smoke Detector
Intelligent Smoke Detector for FS -250 Control Panels
ENGINEER AND ARCHITECT SPECIFICATIONS
Model HFP(,- . .
• Polarity Insensitive with SureWireTM Technology
• Pre -Alarm reporting based on fire profile selected _ - -
• Remote sensitivity measurement capability
• Detectors are self- testing, completing diagnostics _ _
every 4 seconds •
• Field cleanable chamber with replaceable chamber
parts available
• Multi -color detector status LED 1 �`
• Low Profile Design
• Two -wire operation
HFPO - 11
• Compatible Model DPU field device (Shown with DB - 11 Base)
programmer /tester unit
• Supports software based automatic
environmental compensation
• Optional fully programmable relay base,
audible base, and duct housing
• CI Listed
Introduction Description
The Siemens BuildingTechnologies, Fire Safety Division The HFPO -11 is a plug -in, two -wire, photoelectric smoke
HFP -11 Intelligent Fire Detector provides the life safety detector and is compatible with the FS -250 control panel.
industry with the most reliable detection system available Each detector consists of a dust resistant, field - cleanable
today. The HFPO -11 uses state -of- the-art microprocessor photoelectric chamber and microprocessor based elec-
circuitry with error check, detector self - diagnostics and tronics with a low- profile plastic housing.The HFPO -11
supervision programs. utilizes state -of - the -art ASIC circuitry and surface mount
technology for maximum reliability. Every HFPO -11
The HFPO -11 intelligent fire detector is compatible with detector is shipped with a protective dust cover.The
the Fire Safety Model DPU field device programmer/ HFPO -11 detector utilizes an infrared light emitting diode
tester unit, which is a compact, portable, menu - driven (IRLED), and light sensing photodiode. Under normal
accessory for electronically programming and testing conditions, light transmitted by the LED is directed away
detectors, easily and reliably.The DPU eliminates the from the photodiode and scattered through the smoke
need for cumbersome, unreliable mechanical program- chamber in a controlled pattern.The smoke chamber is
ming methods, such as dials or switches and reduces designed to manage light dissipation and extraneous
installation and service costs by electronically program- reflections from dust particles or other non -smoke
ming and testing the detector prior to installation. The airborne contaminants in such a way as to maintain
HFPO -11 fire detector is compatible with the FS -250 stable, consistent detector operation. When smoke
control panel. enters the detector chamber, light emitted from the
IRLED is scattered by the smoke particles and is
• received by the photodiode.
CATALOG NUMBER 4309
A
Communications within the detector itself and between manual stations, HTRI series interfaces, HCP output
the HFPO -11 and the control panel, or with the DPU field control devices, or HZM series of addressable, conven-
device programmer/tester unit, are supervised and safe- tional zone modules. All HFPO -11 detectors can be
guarded against disruption by reliable, microprocessor cleaned in the field, when required, by simply removing
based error checking routines. Additionally, the micro- the detector cover and unsnapping the photo chamber.
processor supervises all EEPROM memory locations and There is also the option of cleaning the interior of the
provides a high degree of EEPROM failure fault tolerance. detector with a clean, soft cloth or brush, or replacing
The HFPO -11 determines its operating status to be the labyrinth and bug screen included in the detector
normal, in alarm, or in trouble depending on the difference maintenance kit, model DMK -11.
between the alarm threshold values stored in the The HFPO -11 uses the low- profile surface mounting base,
detector's memory and the detector's latest analog model DB- 11.This base mounts on a 4 -inch octagon,
measurement.The detector then communicates changes square, or a single gang electrical box.The base utilizes
in its status to the control panel. In addition, the FS -250 screw clamp contacts for electrical connections and self -
control panel will sample the value of the HFPO -11's wiping contacts for increased reliability.The base can be
analog signal over a period of time in order to determine used with the optional LK -11 detector locking kit which
if those values indicate excessive buildup in the photo contains 50 detector locks and an installation tool, to
chamber; if so, the FS -250 control panel will indicate that prevent unauthorized removal of the detector head.The
the particular detector requires maintenance. DB -11 base has integral decorative plugs to cover the
The HFPO -11 is listed as a self- testing device.The outer mounting screw holes. All HFPO -11 detectors are
HFPO -11's visible light emitting diode (LED) flashes approved for operation within the UL specified tempera -
green every 4 seconds to indicate it is communicating ture range of 32 to 100 degrees F (0 to 38 degrees C).
with the control panel and that it has passed its internal
self -test. Should the detector sense a fault or.failure Application Data
within its systems, the LED will flash amber and the Installation of the HFPO -11 series of detectors requires a
detector.will.transmit that information to the control panel. two -wire circuit. In many retrofit cases, existing wiring
A quick visual inspection is sufficient to indicate the may be used. "T- tapping" is permitted only for Style 4
condition of the detector at any time. If more detailed (Class B) wiring. The HFPO -11 is polarity insensitive. This
information is required, a printed report can be provided feature can greatly reduce installation an debugging time.
from.the FS 250 panel indicating the status and settings HFPO -11 detectors can be applied within the maximum
assigned to each individual detector. When the HFPO -11 30 foot center spacing (900 sq. ft. areas) as referenced in
moves to the alarm mode, it will flash red and to con- NFPA 72.This applications guideline is based on ideal
tinue flashing until the system is reset at the control conditions, specifically, smooth ceiling surfaces, minimal
panel. At that same time, any user defined system alarm air movement, and no physical obstructions between
functions programmed into the system are activated. potential fire sources and the detector. Do not mount
Detector sensitivity, calibration, and identification detectors in close proximity to ventilation or heating and
are dynamically supervised by the control panel. air conditioning outlets. Exposed joints or beamed
The DPU Device Program/Test Unit accessory is used to ceilings may also affect safe spacing limitations for
program and verify the detector's address.The technician detectors. Should questions arise regarding detector
selects the accessory's program mode to enter the placement, observe NFPA 72 guidelines. Good fire
desired address.The DPU automatically sets and verifies protection system engineering and common sense
the address and tests the detector.The DPU operates on dictate how and when fire detectors are installed and
AC power or rechargeable batteries, providing flexibility used. Contact your local Siemens Fire Safety distributor
and convenience in programming and testing equipment or sales office whenever you need assistance applying
almost anywhere. FirePrint in unusual applications. Be sure to follow
NFPA guidelines and UL approved installation •
When in the test mode, the DPU will perform a series of instructions, which are included with every Siemens
diagnostic tests without altering the address or other Fire Safety detector, and local codes as for all fire
stored data, allowing technicians to determine if the protection equipment.
detector is operating properly.The HFPO -11 detector may
be installed on the same initiating circuit with HMS series
p
Dimensions
6" Dia. /
3/�
/
IF '
1 1 rz'
Va nA ,\ _ 11 2/W I . I
2 3/4' Di J
4 1/8' Dia.
NOTE: The new DB-11E base has a diameter dimension
of 4 1/2 inches. •
Ordering Information
Part
Model Description Number
3 HFP0-11 Addressable Detector 500-034800
DB -11 Detector Mounting Base for Series 11 500-094151
DB -11E Detector Base (small) 500-094151E
AD-11P Air Duct Housing for Series 11 500-095658
AD-HR Air Duct Housing w /Relay for H-Series 500m3280
Intelfgent Detector
DB -HR Relay Base for H -Series Intelligent Detectors 500-033220
ADBH -11 Audible base 500433210
RL-HC Remote (red) alarm indicator - 4' octagon box mount 500-033230
RL- -HW Remote (red) alarm indicator- single gang box mount 500-033310
LK -11 Base Locking Kit for Series 11 detectors 500695350
DMK -11 Series 11 Maint Kg (replacement labyrinth and bug 500. 695338
bug screen)
•
•
•
•
NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will
be considered a misapplication of Fire Safety equipment and as such void all warranties either
expressed or implied with regard to loss, damage, liabilities and/or service problems.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park. NJ 07932 3/04 Brampton. Ontario
Siemens Building Technologies Tel: (973) 593 -2600 5M Canada L6T 5E4
9 9 FAX: (973) 593-6670 SFS-IG Tel: (905) 799 -9937 March2004
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 -9858 supersedes thee: awed 7/03
•
SIEMENS Fire Safety
DT -1358, DT -135F DT -2008, DT -200F
• Thermal Fire Detectors
ENGINEER AND ARCHITECT SPECIFICATIONS
• ® Listed cr
•
• FM Approved
Introduction Rate -of -Rise Principle of Operation:
The Siemens BuildingTechnologies, Fire Safety Division The rate -of -rise element consists of an air chamber, a
Thermal Fire Detectors are fixed temperature or combina- flexible metal diaphragm and a moisture-proof, trouble -
tion fixed temperature rate-of -rise type.The combination free vent which is carefully calibrated.
detectors consist of two independently operated thermal
elements.The rate-of -rise element is self- restoring. It is well known that air expands as it is heated, and con -
However, the fixed temperature is of the non - restoring tracts as it is cooled. For normal, day -to-day fluctuations
type of temperature, the expansion and contraction of the air
within the chamber is automatically compensated by the
Underwriter's Laboratories, Inc., recommends the "breathing" action of the vent.
combination type thermal detector be used to protect a
maximum of 2,500 square feet, and the fixed temperature However, when a fire occurs, air temperatures rise very
type be used to protect a maximum of 625 square feet. rapidly and the air in the chamber expands faster than it
Job conditions and engineering judgment, however, often can be vented.This creates a pressure which distends
dictate closer spacing to provide faster detection. the diaphragm and closes electrical contacts.
Mounting Data
9 /,8"
tie" 1
49/,s " ---1 J
4
JUNCTION BOX MOUNTING SURFACE MOUNTING
CATALOG NUMBER 6130
The rate -of -rise action is not related to any fixed tempera- Installation
ture level, but responds with the utmost promptness •
Each detector includes a thermoplastic reversible mount-
when the rate of temperature rise exceeds 15° per ing plate. In one position it easily attaches to a 4" octagon
minute. If the heat is removed, the air within the chamber junction box, 3 " octagon box or plaster ring.
contracts and the switch moves to a normally open circuit
position. In reverse, the plate can be used for open wiring without
a junction box. A'1 space between detector and
•
mounting surface allows for wire connections. All mount -
Fixed Temperature ing screws are concealed.
Principle of Operation The detector simply attaches to the mounting plate with a
In a slow developing fire, the temperature may not push and twist motion. No tools required.
increase rapidly enough to operate a rate-of -rise element.
In cases such as described a fixed temperature principle Engineer and Architect Specifications
of operation is desired. The thermal fire detector shall be a Fire Safety
The detector utilizes a fixed temperature element made Model (insert number). It shall operate at a
of fusible alloy and is of the non-restorable type. temperature of degrees F (insert temperature).The
detectors shall be listed by Underwriters' Laboratories,
The fusible alloy will melt and activate the detector when Inc., and Factory Mutual for use with Siemens Building
the surrounding air rises above the preset level of 135 °F Technologies, Fire Safety Division systems.
or 200°F.
The external heat collector drops away when the detector
is activated therefore giving a quick visual confirmation
that the detector has alarmed.
Ordering Information
Model Number DT-135R DT-200R DT-135F 4 DT-200F
Description Rate -of -rise and fixed Rate -of -rise and fixed Fixed temperature Fixed temperature
temperature 135°F temperature 200°F only, 135 F only, 200°F
Normal temperature Normal temperature Unusually violent Unusually violent
fluctuations and ceiling fluctuations and ceiling temperature fluctue- temperature fluctua-
Applications temperatures not temperatures exceed- tions and ceiling tions and ceiling
exceeding 100 °F ing 100 °F but not 150 °F temperatures not temperatures exceed -
exceeding 100 °F ing 100 °F but not 150 °F
Identification on O O
Heat Collector
, 0
0
NONE GRAY RING GRAY SPOT GRAY SPOT AND RING
Fire Safety Fire Safety
8 Fenwwod Road 2 Kenview Boulevard
Florham Park, NJ 07932 11/02 Brampton, Ontario
Siemens Building Technologies Tel: torn Canada L6T 5E4
g F AX (973) (973) 5 -2600 670 SFSIG Tel: (905) 799-9937 November 2002
Fire Safety Website: www.sbt.siemens.comffis Printed in U.S.A FAX (905) 799-9858 supersedes meek dated aoo
SIEMENS
Fire Safety
Adapter Stand Alone Selectable Strobe
ENGINEER AND ARCHITECT SPECIFICATIONS
• The Adapter feature offers four field selectable �!
candela strobe values - 15/75, 30/75, 75 or 110 AGENT RELEASE
for ceiling and wall mount _- - -,
• Operates in either sync or non -sync mode 5 j
• Low current draw
• Integral universal mounting - single gang, AGENT RELEASE r
double gang or 4" square box
• Colors- red or off -white Agent Release Strobe
• ADA/NFPA/ANSI compliant
FIRE
• 0 UL 1971 listed for both wall and ceiling
mount -CSFM, FM and ULC Listed
s
• Made in U.S.A., ISO 9001 certified z i F
• A Dual Sync Control Module or PAD -3 is only -- 1 R
required to activate the Instant Sync feature, F 1 R E ' °' '" . E
nothing to set or change at the strobe unit
Adapter Strobe Adapter Strobe Bell Plate
Description
The U -MCS series and U- MCS-6090V, U- MCS- 6090V -W The U -MCS Series uses a terminal block for easy installa-
strobes combine state of the art electronics to provide tion and the U- MCS- 6090V, U- MCS -6090V W uses a
reliability and low current draw to meet visual life safety pigtail (4 wire) connection.
applications.The Adapter feature offers four field select-
able candela settings - 15/75, 30/75, 75 or 110. Strobe Synchronization requires the Dual Sync Module
or PAD -3.
® � Detail — Adapter Engineering Specifications
sc selector switch The visual notification appliances shall be Adapter U -MCS
Series or U- MCS-6090V, U- MCS-6090V - -W field selectable
The integral universal mounting plate of the U -MCS candela strobe appliance, or approved equal.They shall be
provides for easy installation with single gang, double listed to UL1971 (Standard for Safety Signaling Devices for
gang or4" square box mounting.The lens construction the Hearing Impaired) for indoor applications, and shall be
provides high candela output with low current consump- ADAMFPA/ANSI compliant.
tion while meeting UL and ADA standards. The strobe shall produce a flash rate of one (1) flash per
The U- MCS- 6090V, U- MCS -6090V W provides the same second over the Operating Voltage Range limits of 16 to
strobe choices and is constructed of metal for mounting 32Vdc.The strobe light shall consist of a Xenon flash tube
bell or chime devices to the plate. enclosed in a rugged, clear polycarbonate lens. Inputs
The U-MCS Series & U- MCS- 6090V, U-MCS-6090V -W shall be compatible with standard reverse polarity circuit
supervision by an FACP.The Strobe shall be of low
use a Xenon flashtube with solid state circuitry for current design, and shall provide a minimum of four (4 )
maximum reliability and efficiency. Strobes have a
• rounded dome shape made of clear polycarbonate. CATALOG NUMBER 2550
field selectable strobe intensity settings, 15/75, 30/75, 75 NOTE: These notification appliances are UL listed and rated
and 110 candela. All settings shall be UL 1971 listed for as "special application", which represents appliances which
both wall and ceiling mount applications.The selector have been investigated to operate as described in the .
switch shall be tamper - resistant. product's installation instructions.
It shall not be necessary to remove the strobe from the
mounting surface to select the strobe intensity. When Ordering Information •
synchronization is required, the strobe shall be compat-
ible with the Dual Sync Module, or other source of Stand -Alone Strobes -Wall Mount and Ceiling Mount
Siemens BuildingTechnologies, Fire Safety Division Sync Model Part
Protocol, and shall not drift out of synchronization. Number Description Number
U -MCS Multicandela Selectable Strobe- Red 500 - 699701
The U-MCS Series Stand Alone Strobe shall have an U -MCS -W Multicandela Selectable Strobe - White 500 - 699702
integral universal mounting plate that shall allow mount-
ing to single- gang, two -gang, and 4" square backboxes, Retro -Plate Wall Mount
as well as FBX -S and FBX -F Surface Boxes. A cover trim Model Part
plate shall be included to enhance appearance.There shall Number Description Number •
be no mounting holes or screw heads visible. U- MCS -6090V Retro Plate 500 - 699703
Multicandela Selectable Strobe- Red
The Series U- MCS-6090V, U- MCS -6090V W Strobe Plate U- MCS- 6090VW Retro Plate 500 - 699704
shall facilitate the addition of a strobe to a bell installation. _ Multicandela Selectable Strobe- Red
The Strobe Plate shall mount to a 4° square backbox for
flush mounting. - Stand -Alone Strobes -Wall Mount and
Ceiling Mount - for Agent Release
U -MCS Specifications Model - - Part
Number Description Number
Environmental U- MCS -AR Multicandela Selectable Strobe - Red 500 - 699746
32 °F to 120 °F (0 °C to 49 °C) at 85% RH For Agent Release
Input Voltage - -
16 -32Vdc regulated or FWR
Mounting Canadian Ordering Information
Integral universal mounting plate mounts to single
gang, double gang or 4" square box. Stand -Alone Strobes -Wall Mount and Ceiling Mount
Shipping Weight Model Part
9 oz. approx. Number Description Number
CU -MCS Multicandela Selectable Strobe- Red 500.699701C
U -MCS Dimensions CU -MCS -W Multicandela Selectable Strobe -White _ 500- 699702C
4-5/8* -I 3-1/2'
3 ---I Retro -Plate Wall Mount
Model Part
FIRE Number Description Number
CU- MCS -6090V Retro Plate 500-699703C
.......... till Multicandela Selectable Strobe- Red
`� 1 1 CU- MCS- 6090VW Retro Plate 500- 699704C
4 5 /W itO = } 1 Multicandela Selectable Strobe- Red tom` 1 i
/ Strobe intensity Setting Strobe Current Draw
FIR E �` Selector 15/75 cd 63 mA
. , Switch 30/75 cd 84 mA
75 cd 143 mA
110 cd 178 mA
Typical Wiring
Do not Loop, 'T' Tap or
♦ 4 branch connect
wires.
connectsignal
T. dreult f
From Control Panel Cut wire run to provide
POLARITY MARKING or Previous Device or i: To Next Device IS FOR SYSTEM IN For Synchronization from 1::...] s STROBE Ei i or Electrical Su
ALARM. Siemens Sync Protocol Source Device
Lid TT E .O.L Resistor Use care when poskloning
field wires so that minimum itai stress Is on the appflance.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park. NJ 07932 3/05 Brampton. Ontario
Siemens Building Technologies Tel: 593 2600 51N Canada L6T 5E4
9 9 F AX : (973) (973) 5 93 66 SFSIG Tel: (905) 799 -9937 March 2005
Fire Safety Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799-9858 Supersedes 10108, dared 6/04
•
SIEMENS Fire Safety
U -MHU Series
Models U -MHU Electronic Sync /Non -Sync Horn
ENGINEER AND ARCHITECT SPECIFICATIONS
• The Adapter /U -MCS feature offers four field
selectable candela values — 15/75, 30/75, 75 or 110
for wall & ceiling mount 1 `
• Sync strobes and sync temporal horns, with horn 11111 :: 1
silence on 2 wire
• Distinctive temporal horn a" t
• Internally adjustable volume control 1
•
• Low current draw
• Single gang and universal mount configurations •r'
lIL
• UL 1971 & UL 464 listed - CSFM, ULC,
FM &NYMEA .
at
• UL 1971 listed for both wall and ceiling mount
• ADA/NFPA/ANSI compliant i a e) `'
3
• Screw terminals accept 12 awg wire
• Synchronization requires Dual Sync Control
Module or PAD -3 •
• Made in U.S.A., ISO 9001 quality crafted
Description 15 Detail - Adapter
The U- MHU -1 G, U- MHU -1G -W and U -MHU, U -MHU -W ®� selector switch
Sync Electronic Homs and U-MHU -MCS, U- MHU -MCS -W
Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA
nous temporal tone signals on one pair of wires or output levels.
temporal or steady tone in a non -sync mode.
The U -MHU -1 G, U -MHU -1 G -W mounts to a single 3
gang box, the U -MHU, U-MHU-W and U-MHU -MCS,
U -MHU -MCS -W have a universal mounting plate for °. Volume
1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust
Siemens Fire Safety notification appliances are (factory set at max. volume)
designed with the installer in mind.They are constructed The U- MHU -MCS, U- MHU -MCS -W strobe construction
with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for
This design eliminates possible ground faults from maximum reliability and efficiency.The strobe has a
crowded electrical boxes.The Adapter /U -MCS feature rounded dome shape made of clear polycarbonate.
offers four field selectable candela settings -
15/75, 30/75, 75 or 110.
CATALOG NUMBER 2560
Replaces Catalog Sheet Number 2555
The U -MHU -1 G, U- MHU -1 G W, U -MHU, U -MHU -W and Listed operating range is 16 to 32VDC/FWRTemporal
U- MHU -MCS, U- MHU -MCS -W are used on circuits with maximum UL measurements are 83.6 db at 24VDC/FWR.
steady power or a Dual Sync Control Module or PAD -3. Steady tone maximum UL measurements are 878 db at 24 .
Not for use on coded circuits. VDC/FWR taken in free air at 360° around the device and
averaged. Typical readings are frontal sound readings taken
Environmental with a dB meter with signal mounted on wall. Rated for
32 °F to 120 °F (0 °C to 49°C) with 85% humidity indoor use 32 °F to 120 °F, (0 °C to 49 °C), at RH 85 %.
( -W: White)
OperatingVoltage Range Limits NOTE: These notification appliances are UL listed and rated
Horn: 16 orVFWR as "special application", which represents appliances which
Strobe: 16 - 32Vdc orVFWR have been investigated to operate as described in the
product's installation instructions over the voltage range of
Typical Hom Ratings at 10 Feet* 16-32VDC or VFWR.
Temporal Horn —
Maximum: 95 db @ 54 mA Strobe Intensity Setting Strobe Current Draw
Minimum: 90 db @ 30 mA 15/75 cd 63 mA
30/75 cd 84 mA
*
Typical dBA ratings are frontal sound readings 75 cd 143 mA
taken with a dB meter with signal mounted on wall. 110 cd 178 mA
Dimensions Control Module Specifications:
r I 1 J -13r4' r---- 444 - --1 x _ 1 4 , Maximum Current Output: 3 Amps Max. not
IT �� to exceed NAC rating
m i r DSC Module Operating Voltage: 16 to 32 Vdc orVFW ,-
a,rr 44 f4• o Hi DSC Module Operating Current: Non - Silenceable
Viii
I Circuit side
a a 55mA, Silenceable
Circuit side .005 Amps.
Maximum Current Output: 3 Amps max. not to
r_44,4.______.,. i - 2i/2 exceed Circuit rating
' 1, 2 or 4 Square Mounting
1 III9 , � t., - •
asr4• FIRE' J. Oi l \ !1, Q
i � �, - 0
selector 0
so,
. or
or
0 414 I
For wiring diagram for U -MHU Series Horn/Strobes refer
to Installation Instruction Sheet
Ordering Information
U -MHU Series Hom Wall Mount
Low Volume High Volume High Volume
Model Number Description Part Number Horn Current Horn Carreat dB Rating 4P10'
U- MHU -1G ELC Sync /Non -Sync Horn 24 -VDC 500-699591 30ma 54ina 95 db
U- MHU -1G -W EEC Sync /Non -Sync Horn Z4VDC 500- 699592 30ma 54ma 95 db
U -MHU ELC Sync/Non Horn 24VDC 500. 699594 30ma 54ma 95 db
U -MHU -W ELC Sync/Nan -Sync Hom 24 VDC 500.699593 30ma 54ma 95 db
Low Volume High Volume: High Volume
Model Number Description Part Number Horn Current Horn Current dB Rating 010'
4J- MHU -MCS 'EEC Sync/Non -Sync Hom w /Strobo:(Red) 500- 599587 30ma 54ma 95 db
U- MHU -MCS -W _ EEC Sync/ Non- Sync 500- 699588 30ma 54ma 95 db
*Ali current measurements made at 24VDC
Canadian Ordering Information
CU-MHU Series Hom Wall Mount
Low Volume High Volume High Volume
Model Number Description Pert Number Hors Current Horn Current dB Rating M10'
• CU- MHU -1G EEC Sync/Non-Sync Horn 24 VDC 500.699591C 17ma 25ma 95 db
CU- MHU -1G-W ELC Sync/Non -Sync Horn 24VDC 500- 699592C 17ma 25ma 95 db
CU -MHU ELC Sync /Non -Sync Horn 24VDC 500-699594C 17ma 25ma 95 db
CU -MHU -W ELC Sync/Non -Sync Horn 24 VDC 500- 699593C 17ma 25ma 95 db
Low Volume High Volume High Volume
Model Number Description Pant Number Horn Current Horn Current dB Rating H10'
CU- MHU -MCS ELC Sync/Non- Sync.Horn w /Strobe (Red) 500.699587C 17ma 25ma 95 db
CU- MHU -MCS -W ELC Sync /Non•Sync Horn w /Strobe.(White) 5004699588C 17ma 25ma 95 db
Wiring Diagrams
Typical Wiring for U- MHU -1G and U-MHU for Synchronized Operation with DSC Dual Sync Control Module
(Sync and Silenceable Operation)
Polarity Shown In Alarm Condition
( Audible Control
From control panel silenoeable Notification Appliance Cuci4t (N.A.C.)
0 0 < Audible Power
I!!i ; I I' I `, From control panel steady (notrpulsing) non-sffenoeatie Notification Appliance Circuit (NAC.)l
mi 1! I IA . .
21. 1 N 1 DSC 1 > — i Individual wires (especially heavy
`i 0 ; gauge wire) should be beret at 90'
*v 1:0.1 , - ( before attaching to screw. Wiring
DC a rtva 1.0. l — .,, _ t should then carefully be pushed
o -} '- ?< back into back box to minimize
o 0 : � is -. A. * • A. i
sasabn _ — yam, 0 stress on the terminal block.
nat wee in
smreronuedOperatior
Supervised and --,0 -° m#
powered by NonSilenoeabte •._ •
N.A.C. from Fire . To Next Device
Alarm Control Unit - — - or E.O.I.
Fig. 4
Typical Wiring for U- MHU -1G and U-MHU for Non - Synchronized Operation
Polarity Shown InAlarm Condition
I From control panel.
steady sueneeao(e Gaon Appals* Circuit (N.A.C.)
((( 1 c I Individual wires (especially heavy
O ; -- gauge wire) should be beat at
Jranper Selection — — j before attaching to screw. Wiring
f should then u be pushed
OR = Steady
On = Steady Horn al Horn t t I back Into back bOxto rllinirrdoe
-�- � – p;:� strew on the terminal block
Jumper seteaion r" '
Is only Jar use in '
Non- synducnized
operation r a —,1- 4 .
a To Ned Device
— - or E.O.I.
Fig. 8
Wiring Diagrams
Typical tiring for U- MHU -MCS for Synchronized Operation with DSC Dual Sync Control Module
Audible Signal and Strobe on Same Circuit (Audible Signal and Strobe Synchronized), Audible Signal Silenceable
Polarity Shawn In Alarm Condtion
Note: When staid* and strobe units are powered from the same source. add the currents for both devices. .
Audible Control leave Jumpers in Plate
From c o n t r o l panel skencaabie Notification Appflanoe C i r c u i t (NA.C.) ' (Strobe sr* Audibro S pred are to
Audibto and Strobe Power
Overate Same Circuit)
/• 0 0 t'� Frtxrtcontrol pan elsteady(nor►pulShp) ricre cadotApplWpaCinx&(N.AL.) `
I;(.1 DSC I ," 1 j 1
,ttaor
IA il I
oconvFU� 1,01 • I I, • Individual wires (espoela)y
mini — heavy gauge wire) should be
0 0 0 . c.» 1N 0 Li ;_ bent at 90° before coaching • to screw. Wiring should then
iF -1.. Y:d carefully be pushed back Into
� 'f �l ( '•._• j w. . i1_ r'=' Ne" • I __ back box to minimize stress
Supervised Supesed and �{ _ / _ 'l u.
_ an the terminal block
powered by i ( ! ��ii�.
NAC. from Fire w _ �j ��'I il
AC. from Fire
Alarm Control Unit • To Next Device
Jumper - or E.O.L.
net used m Synchronized Operation Fig. 6
Typical Wiring for U- MHU -MCS for Non - Synchronized Operation
Audible Signal and Strobe on Same Circuit
Polarity Shown In Alarm Condition
Note: When audible and strobe units are powered from the same source. add the currents for both devices.
Leave Jumpers in Plate
From control panel, (Strobe are Aurabte Signal are to
steady 89enceabie Noti(it: h ApPUance Circuit (NAC.) Operate on • Same Came)
a 1t _ NOTE: SQWeraeeobeMar be Comema
r IH f f tos tnd ddual wires (especial M+FW:npxotfcatimfocaeroeCia
IA. i• r y
O..Wec. to - � o o i he heavy gau� should be
Jumper Settrt .�. � � 'at-It. N. ! { bald at before attaching
On Temporal Nowt ;., ...;,.,!.....,k;.!—. I q to strew. Wifbtg should then
on * steady Nom ; I� : i - 1 - ; c efully be pushed back Into
�a'sr. ,' — _y_. is ! � a'sr .r eu i • back box to minimize stress
Jumper se(ue i n (_= _ lei ��'r f 11 - on the temrbral block
is only for - ! far use ! .
Non - synchronized . _
operation —• To Next Device
or E.O.L
Fig. 7
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 3/05 Brampton, Ontario
Siemens Buildin 'Technologies Tel: (973) 593 -2600 %I Canada L6T5E4
9 9 FAX: (973) 593-6670 SFS"IG Tel: (905) 799 -9937 March 2005
Fire Safety Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799 -9858 supersedes & set detect ero4 "
SIEMENS Fire Safety
HTRI Series
FireFinder XLS and FS -250 Intelligent Initiating Devices
Interface Modules
ENGINEER AND ARCHITECT SPECIFICATIONS
Intelligent Interface Modules for FireFinder XLS and FS -250 Series
Fire Alarm Control Panels HTRI -S, HTRI -D, HTRI -R
• Interfaces and Supervises Normally Open or Normally
Closed Contacts
• Integral SPDT Relay (up to 4 amps) on HTRI -R Model
• Dual Input on HTRI -D Model using a single address r '+
• Polarity Insensitive with SureWiren" Technology
sF -
• Multi -color L.E.D. indicates status (green, amber, red)
• Easy front access to programming port and
a ".,
wiring terminals •
• Mounts 4 inch square 2 1 4 deep box, or double gang box „; b
• Dynamic Supervision ESp -
• Comes with 5x5 inch faceplate
• Two wire operation!-
• DPU Device Program/Test Unit programs and Verifies } y ,
Device's Address and Tests Devices functionality
• Electronic Address Programming is Easy and Dependable /-_•
• ULC Listed ti y
® CFSM, FM, NYMEAApproved
Introduction
The HTRI Series Intelligent interface modules are de- monitor and report the status of the contact, while the
signed to provide the means of interfacing direct shorting HTRI -R incorporates an addressable Form C relay. The
devices to the FireFinder XLS and FS -250 Fire Alarm HTRI -R relay and contact device input are controlled at the
Control Panel loop circuit. same address. For the control panel system, the relay
The HTRI Series Intelligent interface modules provide the and input contact can be controlled as a separate function.
The relay is typically used where control or shunting of
market's most advanced method of address programming external equipment is required.
and supervision, combined with sophisticated control panel
communication. Each HTRI Series interface module The HTRI -D is a dual input module and is designed to
incorporates a microcomputer chip. The HTRI Series supervise and monitor two sets of dry contacts. The
microcomputer chip technology and its sophisticated Dual Input Module only requires one address but re-
bi- directional communication capabilities with the control sponds independently to each input. The HTRI -D is ideal
panel, achieve the state of an "Intelligence Device” for monitoring a water flow switch and its respective
valve tamper switch.
Description The HTRI has a multi -color Light Emitting Diode that
The HTRI Series intelligent interface modules are flashes green when operating normally, amber if unit
available in three models. The HTRI -S and HTRI -R are is in trouble condition, and red to indicate a change of
designed to monitor a normally open or closed dry state. The HTRI -D flashes twice, once for each ad-
contact. The interface module reports the contact's dress, the HTRI -R red L.E.D. indicates a change of
status to the control panel. The HTRI -S model can only state in the relay.
CATALOG NUMBER 6304
The device's microcomputer chip has the capacity of Mounting Data
storing, in memory, identification information as well as Addressable Interface Model HTRI -S, HTRI -D, HTRI -R
important operating status information.
mounts directly into a 4 inch square 2'4 deep box or
Siemens BuildingTechnologies, Inc., Fire Safety Division a double gang box (user supplied). A 5 inch square
innovative technology allows all HTRI Series intelligent off -white faceplate is included with each HTRI.
interface modules to be programmed by using the DPU
Device Programming/Test Unit. The DPU is a compact, MOUNTING SLOTS
portable, menu driven accessory that makes program- FOR 4 INCH
ming and testing an interface device faster, easier and swIrCHBOx
more dependable than previous methods. The DPU
eliminates the need for mechanical addressing mecha- o • 0
nisms, such as program jumpers, DIP switches or rotary
dials, because the DPU electronically sets the HTRI ill HTRI S/ - / -
interface's address into the interface's microcomputer tell I MODULE
chip nonvolatile memory. Vibration, corrosion and other ® r ; O
. conditions that deteriorate mechanical addressing mecha- '
nisms are no longer a cause for concern. 11-•1 H MOUNTING OLEES S FFO
HOLES FO
The HTRI Series is fitted with screw terminals for ► SWITCHPLATE
connection to an addressable circuit.
The HTRI Series is fully compatible on the same 0
FireFinder XLS and FS-250 circuits with all intelligent H
Series detectors, HMS Series addressable manual
stations or any other addressable intelligent modules, MOUNTING SLOTS
such as the HZM or HCP. FOR DOUBLEGANG
All HTRI Series intelligent interface modules are SWITCHBOX
UL listed.
Figure A
Environmental operating conditions for all HTRI Series Mounting the HTRI S/ -
modules are 32 °F ( °C) to 120 °F (49 °C) with a relative
humidity of not greater than 93% non -condensating.
Ordering Information Electrical Ratings
Shipping Wt. Current Draw (Active or Standby): 1 mA
Model Description Lb. Kg. Part Number HTRI - Relay Ratings
HTRI -S Single Input 7 oz 2 500. 033370 Resistive: 4A, 125 VAC
HTRI -R Single Input w /Relay 7 oz 2 500- 033300 4A, 30 VDC
• -HTRI -D Dual Input 7 oz 2 500-033360 Inductive: 3.5A, 120 VAC (0.6P.F.)
3.0A, 30 VDC (0.6PE)
2.0A, 120 VAC (0.4PF.)
2.OA, 120 VAC (0.35PE)
2.0A, 30VDC (0.35P.F.)
•
NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will
be considered a misapplication of Fire Safety equipment and as such void all warranties either
expressed or implied with regard to loss, damage, liabilities and/or service problems.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
Florham Park NJ 07932 12/04 Brampton, Ontario
Siemens Building Technologies Tel: (9
51N Canada L6T 5E4
g 9 F AX 3 66 SFSIG Tel: (905) 799 -9937 December 2004 -
Fire Safety Website: www.sbt.siemens.com/fis Printed in U.S.A. FAX: (905) 799 -9858 su erseaes sneer dated 1403
..
SIEMENS Fire Safety
HTRI-M Dev Interface Module
For Use With the FireFinder -XLS Control Panel
ENGINEER AND ARCHITECT SPECIFICATIONS
Intelligent Interface Modules For
FireFinder XLS Control Panels
h ,. ,t
• Interfaces and Supervises Normally Open (Fire Detection) k #'/
ir
or Normally Closed Contacts (Security Detection) i,°;;`
• Compact Size Allows Mounting in Single Gang Box
Behind Equipment`
• Polarity Insensitive with SureWireTMTechnology ;�
• Operates with FireFinder XLS DLC Circuit b;'
• InnovativeTechnology Supports Comprehensive r ., Er L:
System and Interface Communication
:rat 1 i atal • Dynamic Supervision
M, =mama all
• TwoWire Operation '' R ni isfi
• DPU Device Progra Unit Electronically ,y, s EM ENS ' ,
Programs and Verifies Device's Address andTests ' s,.,~„
ponouv . y orT ,
Device's Functionality 41.
• ULC Listed ��
�� CSFM, FM and NYMEA Pending
Introduction
The HTRI -M Intelligent interface module is designed Siemens Building Technologies, Inc.,Fire Safety
to provide the means of interfacing direct shorting Division innovative technology allows all HTRI -M
devices to the FireFinder XLS system's DLC loop intelligent interface modules to be programmed by
circuit. using the DPU Device Program/Test Unit. The DPU is a
The HTRI -M Intelligent interface module provides the compact, portable, menu driven accessory that makes
e a o ier and more and testing an e interface device faster,
market's most advanced method of address program- od
ming and supervision, combined with sophisticated easier and more dependable than previous methods.
n The DPU eliminates the need for mechanical address-
control panel communication. Each with sophisticated
interf
ing mechanisms, such as program jumpers, DIP
module incorporates microcomputer chip technology switches or rotary dials, because it electronically sets
and its sophisticated bi-directional communication the HTRI -M interface's address into the interface's • •
capabilities with the control panel. microcomputer chip non - volatile memory. Vibration,
corrosion and other conditions that deteriorate me-
Description chanical addressing mechanisms are no longer a cause
The HTRI -M is designed to monitor a normally open or for concern. This HTRI -M is connected to the program/
tester with the programming cable provided with the
closed dry contact and reports the contact's status to
the control panel. tester. This cable (P /N 110-694927) utilizes two (2)
alligator clip connectors, to attach to the HTRI -M.
The device's microcomputer chip has the capacity of
storing, in memory, identification information as well The HTRI -M Series has five leads, one for grounding,
as important operating status information. which are wired to the system with user supplied
wire nuts.
CATALOG NUMBER 6308
•
The HTRI -M is fully compatible on the same XLS
•
circuit with all intelligent H Series detectors, HMS
Series addressable manual stations or any other H
Series addressable intelligent modules, such as the
HZM or HCP.
All HTRI -M intelligent interface modules have been
UL and ULC submitted.
Environmental operating conditions for all HTRI -M
modules are 32 °F ( °C) to 120 °F (49 °C) with a relative
humidity of not greater than 93% non - condensating.
Ordering Information
Model Shipping Weight Part
Number Description o:. kg. Number
HTRI -M Single Input 3.5 .1 500 - 034000
HTRI -MC ULC Model for Canada 3.5 .1 500- 034000C
- Electrical Ratings
Current Draw (Active or Standby):. 1.5mA .
NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will
be considered a misapplication of Fire Safety equipment and as such void all warranties either
expressed or implied with regard to loss, damage. liabilities and/or service problems.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 1/03 Brampton, Ontario
•
Siemens Buildin Technologies Tel: (973) 593 -2600 5M Canada L6T 5E4
9 9 FAX: (973) 593-6670 SFS -IG Tel: (905) 799 -9937 January .2003
Fire Safety Website: www.sbt.siemens.corn/fis Printed in U.S.A. FAX: (905) 799 -9858 Supersedes sheetdate°1201