June 23, 2003
CITY OF TIGARD
OREGON
Brian W. Downs
1225 Ferry Street, SE
Salem, OR 97301 •
RE: INTERIOR MODIFICATION
Project Information
Building Permit: BUP2003 -00326
Mechanical Permit: MEC2003 -00295 Construction Type: II -N
Tenant Name: P.E.R.S. Occupancy Type: B
--� Address: 11410 SW 68 Parkway Occupant Load: NA
Area: No change Stories: 3
Sprinkled: NA Alarms: NA
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the
Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted
plans are approved subject to the following conditions.
GENERAL
1. Exit signs shall be illuminated at all times and shall be provided with a second source
of power that will provide 1 '/2 hours of illumination in case of primary power loss.
1003.2.8.5 OSSC
2. The means of egress shall be provided with illumination of not less than 1 foot candle
at the floor level anytime the building is occupied. The means of egress illumination
shall be provided with a second source of power in case of primary power loss.
1003.2.9.2 OSSC
3. Provide one 2 -A rated fire extinguisher in the new area. The extinguisher shall be
located so that no usable space has a distance greater than 75 feet to the extinguisher.
Standard 10 -1, Chapter 3 T'VFR99 -01.
MECHANICAL
4. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 - 2772
5. Appliances serving different areas of a building other than where they are installed
shall be permanently marked in an approved manner that uniquely identifies the
appliance and the area it serves. 304.10 OMSC
6. Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
7. Appliances installed on roofs or elevated structures exceeding 16 feet in height shall
be provided with a permanent means of access grade or floor level. 306.5 OMSC
8. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
9. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.