Correspondence o ?/- ? . -00357
July 17, 2003 �
CITY OF TIG D
OREGON
Basic Fire Protection
8135 NE Martin Luther King Junior Boulevard
Portland, OR 97211
RE: PROVIDENCE DATA ROOM, FIRE SPRINKLER SYSTEM
Project Information
Building Permit: BUP2003 -00392 Construction Type: III -N
Tenant Name: Providence Occupancy Type: B
Address: 11308 SW 68 Parkway Occupant Load: NA
Area: NA Stories: 1
Hazard: Light
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
. edition. The submitted plans are approved subject to the following.
1. A key box shall be installed within 20 feet of the riser room entrance. The bottom of
the keybox shall be not less than 8 feet nor more than 10 feet above the walking
surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 Contact TVF &R for
keybox at 503- 612 -7010
1. A supply of spare sprinklers (never less than 6) shall be maintained on the premises
so that any sprinklers that have operated or been damaged in any way can be
promptly replaced. These sprinklers shall correspond to the types and temperature
ratings of the sprinklers in the property. Standard 9 -1, section 2 -2.7.1 OSSC
2. A special sprinkler wrench shall be provided and kept in the cabinet along with the
spare sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1,
section 2 -2.7.2 OSSC
3. A minimum of 18 inches shall be maintained between top of storage and ceiling
sprinkler deflectors. The distance shall be increased to 36 inches for large drop
sprinkler heads. Standard 9 -1, section 4 -4.1.6 and 4 -4.3.2 OSSC
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
4. Sidewall sprinkler deflectors shall be located not more than 6 inches or less than 4
inches from walls and ceilings. Standard 9 -1, section 4- 4.2.3.3 OSSC
5. Clearances shall be provided around all piping extending through walls, floors,
platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 '/2
inches shall be not less than 1 inch. Minimum clearance for pipes 4 inches and larger
shall be 2 inches. Standard 9 -1, section 4- 5.4.3.4
6. Monitoring, Section 904.3.1 OSSC All valves controlling the water supply for
automatic sprinlder systems and all water flow monitoring devices shall be
electrically monitored where the number of sprinklers are;
• Twenty or more in group I, Divisions 1.1 and 1.2 Occupancies. .
• One hundred or more in all other occupancies.
7. An approved audible sprinkler flow alarm shall be provided on the exterior of the
building in an approved location. An approved audible sprinlder flow alarm to alert
the occupants shall be provided in the interior of the building in a normally occupied
location. 904.3.2 OSSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully
rian B1 .
Senior ' .1 Examiner