Specifications „)
October 29, 2003 '' 1” `\
Oregon Electric Group CITY OF TIGARD
1010 SW SE 11 Avenue
Portland, OR 97214 OREGON
• RE: PROVIDENCE HEALTH SYSTEMS
FIRE ALARM SYSTEM @ MAIL ROOM
Project Information
Building Permit: BUP2003 -00617 Construction Type: NA
Tenant Name: Providence Occupancy Type: B
Address: 11308 SW 68 Parkway Occupant Load: NA
Area: NA Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following.
General requirements
1. A key box shall be installed within 20 feet of the main entrance. The bottom of the
key box shall be not less than 8 feet nor more than 10 feet above the walking surface
unless approved by the Fire Chief. 902.4.2 TVFR99 -01 An existing key box at the
main building entrance is acceptable.
2. Upon completion of the installation, a satisfactory test of the entire system shall be
made in the presence of the Fire Chief All functions of the system or alteration shall
be tested. 1007.3.4.1 TVFR99 -01
3. The permittee shall provide written certification to the Fire Chief that the system has
been installed in accordance with the approved plans and specifications. A copy of
the completed form shall be maintained on the premises and made available to the
Fire Chief. 1007.3.4.2 TVFR99 -01.
4. Connections to the light and power service shall be on a dedicated branch circuit. The
circuit and connections shall be mechanically protected. The circuit disconnecting
means shall be accessible only to authorized personnel and shall be clearly and
permanently marked FIRE ALARM CIRCUIT CONTROL. Standard 10 -2, Section
1- 5.2.8.2, T'VFR99 -01
5. Manual Fire Alarm activation devices shall be mounted in the following reach ranges:
• Forward Reach -15 inches to 48 inches above the floor. 1109.2.3.5 OSSC
• Side Reach — 9 inches to 54 inches above the floor. 1109.2.3.6 OSSC
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684-2772
Visuals (Section 1109.14 OSSC)
1. Visual signal appliances shall be provided in the building in each of the following
areas:
• Restrooms and any other general use area (e.g., meeting rooms)
• Hallways
• Lobbies
• Common use areas.
2. Visual alarms shall be located not less than 80 inches and not more than 96 inches
above the floor level. When a low ceiling exists, the visual alarm shall be mounted at
least 6 inches below the ceiling.
3. Visual alarms shall have a minimum candela rating of 75 candelas.
4. No place in a room shall be more than 50 feet from a visual signal
5. No place in a common corridors or hallways shall be more than 50 feet from a visual
signal
6. In large rooms exceeding 100 feet across and without obstructions 6 feet or more
above the floor, devices may be placed around the perimeter spaced at a maximum of
100 feet apart.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or mad
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfull
: �l �C�
Senior Plans Examiner
PROVIDENCE TIGARD DATA CENTER
SUITE 170
11308 SW 68 PARKWAY
TIGARD, OR. 97223
FIRE ALARM SYSTEM
SUBMITTAL CONTENTS
ITEM DESCRIPTION
1. Siemens PAD 3 NAC POWER SUPPLY
2. Siemens U -MCS STROBE
3. Siemens U -MHU SERIES HORN /STROBE
4. Siemens TRI -R MODULE RECEIV
5.
OCI 16 2003
GI TY OF TIGAKv
LOiNG OWiSION
SUBMITTED BY
I.S.G /OREGON ELECTRIC
5000 N.E. COLUMBIA BLVD.
PORTLAND, OR. 97218
503 -535 -2800 BIII
SIEMENS Fire Safety
PAD 3
Auxiliary Power Supply - Notification Appliance Extender
ENGINEER AND ARCHITECT SPECIFICATIONS
• 6 amps of Notification Appliance Power
• Advanced Microprocessor Control
• 24VDC Output Voltage
• Four Power - Limited Notification Outputs f,
• Strobe Synchronization Option Built In
• Synchronized ANSI Temporal Pattern
• Class A Selectable
• Ground Fault Detection ,
• Battery Supervision
• 3 Amp Auxiliary Power Output
• Trouble Contact for Monitoring
• Multiple Module Mounting in
System 3 Enclosures ;,
• Multiple Modules Share Battery Set PAD-3
• 0 UL, ULC Listed, CSFM, NYMEA
and FM Approved
Introduction
The Model PAD -3 (PAD -3C for Canada) is a notification The PAD -3 also offers a 3 amp auxiliary output for driving
appliance circuit expander with a built -in auxiliary other portions of your fire alarm system such as door
power output. It is designed for use with Siemens holders. This 24 VDC filtered output is power limited.
BuildingTechnologies, Fire Safety Division fire alarm When using this output, the total power available from
control panels.This power source is designed to provide the PAD -3 will not exceed 6 amps.
the extra power required in buildings conforming to the
Americans with Disabilities Act. A trouble contact is provided for monitoring the PAD-3
with a fire alarm panel through the input. It also has a
Form C dry contact for trouble monitoring. Therefore,
Features the user has the option of connecting it to a conven-
The PAD-3 provides 6 amps of 24 VDC power for tional fire alarm panel's existing notification circuit, or
multiple uses. All 6 amps can be directed to 4 Notifs- controlling it with a TRI Series device on intelligent fire
cation Appliance Circuits (NAC s). Each is rated at 3 systems.
amps and is power limited. Either 1 or 2 inputs can The PAD -3 offers battery supervision and management
control the four outputs. These outputs are compatible as is required of fire alarm system components.
with all Fire Safety 24VDC notification appliances. Ground faults are transmitted as are any other trouble
The PAD-3 can be configured so that the inputs can be conditions. Trouble conditions not only change the
programmed as steady outputs, ANSI temporal state of the trouble contact in the unit, but they also
outputs, or synchronized strobe outputs. It can also break the notification circuit input to create a trouble
be programmed so that one input will silence U -MHU- signal in the fire alarm control unit.
Series horn /strobe horns while the strobes remain on
using one set of wires.
CATALOG NUMBER 3362
This product is packaged in its own sheet metal enclosure Electrical Specifications
with enough space to house the 7 amp -hour battery set
required for back -up. The enclosure comes in black or red. AC Input: 120 VAC @ 2.5 amps ,
System 3 enclosures may also be used to house multiple Output: 24VDC @ 6 amps
PAD -3 modules in a single enclosure. Two modules are Auxiliary Power Circuit: 1
capable of sharing the same battery set when mounted in
the same enclosure. Notification Circuits: 4
Output Configuration: 2 Class A or 4 Class B or
Options 1 Class A & 2 Class B •
One or both PAD -3 signal inputs control the notification Amps per Output
outputs, depending on the specific configuration setup. Circuit: 3.0
Possible configurations for the PAD-3 are: Notification Circuit
For These Control These Outputs: 24 VDC at 3.0 amps each,
Option: Inputs: Outputs: As: 24K ohm EOL resistor
required on each Class
1 Input 1 All Outputs Class B Circuits B circuit
2 Input 1 All Outputs Class B Circuits No. of Inputs: 2
Input 2• Silences horns on 1 Input Configuration: 2 Class B or 2 Class A
3 input 1 Outputs 1 and 2 Class B Circuits Input Voltage Range: 9 32 VDC
Input 2 Outputs 3 and 4 Class B Circuits
4 Input 1 Output 1 Class 8 Circuits Battery Charging
Input 2 Outputs Z3 and 4 Class 8 Crcults Capacity: 15.0 A. H
5 Input 1 Outputs 1 -2, 3 and 4 Class Circuit Pairs Trouble contact rating: 2.5A @250 VAC, 30 VDC
6 input 1 Outputs 1 -2, 3 and 4 Class Circuit Pairs Ambient Temperature: 32 °F to 120 °F
Input 2• Silences horns on 1
7 Inputs Outputs1 and2 Class A Circuit Pairs Mechanical Specifications
input Outputs 3 and 4 Class A Circuit Pairs Single Module Enclosure Model EN - PAD
8 Input 1 Outputs 1 -2 Class A Circuit Pairs Dimensions: 12"W x 16 "H x 3"D
Input 2 Outputs 3 and 4 Class 8 Circuits •
Color: Black
*When used with U -MHU- Series horn/strobe units
Indicator Lights
Supervision AC Power On: Green
The Model PAD-3 supervises a variety of functions BatteryTrouble: Yellow
including: Ground Fault: Yellow •
• Low AC power AuxiliaryTrouble: Yellow
Output 1 Trouble: Yellow
• Low battery condition Output 2Trouble: Yellow
• Earth ground fault
• Auxiliary output power limit condition
Ordering Information
• EOL supervision trouble or power limited condition Part
at an output Model Description Number
When a trouble condition occurs, the PAD-3 creates a PAD - Aux power supply w/black enclosure 599
trouble condition on the fire control signal circuits to PAD - Aux. power supply wired enclosure 599 - 699190
which it is connected. It still maintains the ability to be PAO - Aux. power supply - main board only 500 - 699080
activated by the fire control. In addition, the PAD -3 EN - PAD Black enclosure for PAD 310
provides a Form 'C' trouble relay output as an alterna - pADR Red enclosure for PAD - 310 -0150
tive to using the notification circuit trouble.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park. NJ 07932 9/03 Brampton, Ontario
Siemens Building Technologies Tel: 1973) 593 -2600 torn Canada L6T 5E4
FAX: (973) 59 66 70 SFS4G Tel: (905) 799 -9937 September 2003
Fire Safety Website: www.siemens.com/fis Printed in U.S A. FAX: (905) 799-9858 suoeneaes abet dated 6ro3
SIEMENS Fire Safety
Adapter Stand Alone Selectable Strobe
ENGINEER AND ARCHITECT SPECIFICATIONS
AGENT RELEASE
• The Adapter" feature offers four field selectable
candela strobe values - 15/75, 30/75, 75 or 110
for ceiling and wall mount —
• Operates in either sync or non -sync mode z 1
• Low current draw
• Integral universal mounting - single gang, GENT RELEASE
double gang or4" square box
Agent Release Strobe
• Colors- red or off-white
• ADA/NFPA/ANSI compliant ,
ti
• cL UL 1971 listed for both wall and ceiling
mount -CSFM and ULC Listed s
• Made in U.S.A., ISO 9001 certified E •
• A Dual Sync Control Module or PAD -3 is onl ,
Y Y
required to activate the Instant Sync feature,
nothing to set or change at the strobe unit , s
Adapter Strobe Adapter Strobe Bell Plate
Description
The U -MCS series and U- MCS- 6090V, U- MCS- 6090V -W . The U- MCS- 6090V, U- MCS- 6090V -W provides the same
strobes combine state of the art electronics to provide strobe choices and is constructed of metal for mounting
reliability and low current draw to meet visual life safety bell or chime devices to the plate.
applications.TheRdapter feature offers four field select The U -MCS Series & U- MCS- 6090V, U- MCS- 6090V -W
able candela settings - 15/75, 30/75, 75 or 110.
use a Xenon flashtube with solid state circuitry for
maximum reliability and efficiency. Strobes have a
( s Detail - Adapter rounded dome shape made of clear polycarbonate.
�� selector switch The U -MCS Series uses a terminal block for easy installa-
tion and the U- MCS- 6090V, U- MCS- 6090V -W uses a
The integral universal mounting plate of the U -MCS pigtail (4 wire) connection.
provides for easy installation with single gang, double Strobe Synchronization requires the Dual Sync Module
gang or 4" square box mounting.The lens construction or PAD -3.
provides high candela output with low current consump-
tion while meeting UL and ADA standards.
CATALOG NUMBER 2550
Engineering Specifications The Series U- MCS- 6090V, U- MCS- 6090V -W Strobe Plate
The visual notification appliances shall be Adapter U -MCS shall facilitate the addition of a strobe to a bell installation.
Series or U- MCS- 6090V, U- MCS- 6090V -W field selectable The Strobe Plate shall mount to a 4 " square backbox for
candela strobe appliance, or approved equal.They shall be flush mounting.
listed to UL1971 (Standard for Safety Signaling Devices for Ordering Information
the Hearing Impaired) for indoor applications, and shall be
ADA/NFPA/ANSI compliant. Stand -Alone Strobes -Wall Mount and Ceiling Mount
Model Part
The strobe shall produce a flash rate of one (1) flash per Number Description - Neetber •
second over the OperatingVoltage Range limits of 16 to U - MCS Multicandeia Selectable Strube Red 500499701
33Vdc.The strobe light shall consist of a Xenon flash tube U -MCS Multicandeia Selectable Strobe - White 500 699702
enclosed in a rugged, clear polycarbonate lens. Inputs ,
shall be compatible with standard reverse polarity circuit Retro -Plate Wall Mount
supervision by an FACP.The Strobe shall be of low .
current design, and shall provide a minimum of four (4) Model P
field selectable strobe intensity settings, 15/75, 30/75, 75 Number Description Number
and 110 candela. All settings shall be UL 1971 listed for U- MCS - 6090V Retie Piste 500. 839703
kilulticandeia Selectable Strobe Haa
both wall and ceiling mount applications.The selector U•MCS 6090W1 Retro Plata 500-699704
switch shall be tamper-resistant. _ Multicandela Selectable Strobe- Red _
It shall not be necessary to remove the strobe from the
mounting surface to select the strobe intensity. When Stand -Alone Strobes -Wall Mount and
synchronization is required, the strobe shall be compat- Ceiling Mount - forAgent Release
ible with the Dual Sync Module, or other source of Model Part
Siemens Building Technologies, Fire Safety Division Sync Number Description Number
Protocol, and shall not drift out of synchronization. U•MCS -AR Molticandela Selectable Strobe - Red 500- 699746
forAgent Release
The U -MCS Series Stand -Alone Strobe shall have an
integral universal mounting plate that shall allow mount-
ing to single- gang, two-gang, and 4" square backboxes, Canadian Ordering Information
as well as FBX -S and FBX -F Surface Boxes. A cover trim
plate shall be included to enhance appearance.There shall Stand -Alone Strobes -Wall Mount and Ceiling Mount
be no mounting holes or screw heads visible. Model pan
Number Description Number
U -MCS Specifications CU -MCS Multicandela Selectable Strube- Red 500- 699701C
CU•MCS -W Multicandela Selectable Strobe - White _
Environmental
32 °F to 120 °F (0 °C to 49 °C) at 85% RH Retro-Plate Wall Mount
InputVoltage Model Pan
16 - 33Vdc regulated or FWR Number Description Number •
Mounting CU- MCS -6090V Retro Plate 500-699703C
Integral universal mounting plate mounts to single Mutt :candela Selectable Strobe- Red
gang, double gang or 4" square box. CU- MCS- 609OVW Retro P13te 500.6997040
Shipping Weight , _ Multicandele Selectable Strobe- Red
9 oz. approx.
Stand -Alone Strobes -Wall Mount and
Ceiling Mount - forAgent Release
U -MCS Dimensions Model P
(( 4e r 3-1/2" Number Description Number
J
r 3• E CU- MCS -AR Multicandela Selectable Strube - Red 500.6997460
• i For Agent Release
FIRE
Strobe Intensity Setting strobe Current Draw
7 \ 15/75 cd 63 mA
Hil 4 -518' �_'£ 30!75 cd 84 mA
R:: " ?' : : :� D 75 cd 143 mA
L FIRE - -- -- -- Selector 110 cd 178 mA
Switch
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 8/03 Brampton, Ontario •
Siemens Building Technologies Tel: (973) 593 -2600 5v1 Canada ! 6T 5E4
g FAX: (973) 593 -6670 SFS-IG Tel: (905) 799.9937 August 2003
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 - 9858 swe¢edes sneer dated 3103
SIEMENS Fire Safety
U -MHU Series
Models U -MHU Electronic Sync /Non -Sync Horn
ENGINEER AND ARCHITECT SPECIFICATIONS
• The AdapterTM /U - MCS feature offers four field
selectable n
ca del values— — 1
a alp es 5175 30/7 75 or 5 50 110
for wall & ceiling mount
• Sync strobes and sync temporal horns, with horn
silence on 2 wires ! <{ f
• Distinctive temporal horn
•
Internally
I
adjustable volume ntr I
e control 1
o
•
Low current draw
• Single gang and universal mount configurations
• UL 1971 & UL 464 listed - CSFM, ULC, & N (MEA •
{.
• UL 1971 listed for both wall and ceiling mount ,!
• ADA/NFPA/ANSI compliant #'
• . :: It
• Screw terminals accept 12 awg wiref: yy
• Synchronization requires Dual Sync Control
_
Module or PAD -3
• Made in U.S.A., ISO 9001 quality crafted
Description „,,, Detail - Adapter
The U -MHU -1 G, U- MHU -1 G-W and U -MHU, U -MHU -W = selector switch
SC
Sync Electronic Horns and U -MHU -MCS, U- MHU -MCS -W
Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA
nous temporal tone signals on one pair of wires or output levels.
temporal or steady tone in a non -sync mode.
The U -MHU -1 G, U -MHU -1 G-W mounts to a single
gang box, the U -MHU, U -MHU -W and U- MHU -MCS, i 1
U- MHU -MCS -W have a universal mounting plate for K2..A ax. Valium
1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust
Siemens Fire Safety notification appliances are (factory set at max. volume)
designed with the installer in mind.They are constructed The U- MHU -MCS, U -MHU -MCS -W strobe construction
with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for
This design eliminates possible ground faults from maximum reliability and efficiency.The strobe has a
• crowded electrical boxes.The Adapter!U -MCS feature rounded dome shape made of clear polycarbonate.
offers four field selectable candela settings -
15/75, 30/75, 75 or 110.
CATALOG NUMBER 2560
Replaces Catalog Sheet Number 2555
The U -MHU -1 G, U -MHU -1 G-W, U -MHU, U -MHU -W and Listed operating range is 20 to 31 VDC /FWR
U-MHU-MCS, U- MHU -MCS -W are used on circuits with Temporal maximum UL measurements are 83.6 db at
steady power or a Dual Sync Control Module or PAD -3. 24VDC /FWR. Steady tone maximum UL measurements
Not for use on coded circuits. are 87.8 db at 24 VDC /FWR taken in free air at 360°
around the device and averaged. Typical readings are
Environmental frontal sound readings taken with a dB meter with signal
32 °F to 120 °F (0 °C to 49 °C) with 85% humidity mounted on wall. Rated for indoor use 32 °F to 120 °F, (0 °C
to 49 °C), at RH 85 %.
Operating Voltage Range Limits (-C: Ceiling Mounted)
Horn: 20-31 Vdc orVFWR ( White)
Strobe: 16- 33VdcorVFWR strobe Intensity Setting ,Strohe Current Draw
15/15 cd 63 mA
Typical Hom Ratings at 10 Feet* 30/75 cd 84 mA
Temporal Horn - 75 `d 143 "'A
110 cd 178 mA
Maximum: 95 db @ 25 mA
Minimum: 90 db @ 17 mA Control Module Specifications.,
* Typical dBA ratings are frontal sound readings Maximum Current Output: 3 Amps Max. not
taken with a dB meter with signal mounted on wall. to exceed NAC rating
DSC Module OperatingVoltage: 20 to 31 Vdc orVFW
Dimensions DSC Module Operating Current: Non - Silenceable
2oic - --1 : taw. 4.3/4` . •_ -:
- 1.y4' Circuit side
"'' v - - - ' - ''t 55mA, Silenceable
Circuit side .005 Amps.
4 - ® . a . rf.1 Maximum Current Output: 3 Amps max. not to
I exceed Circuit rating
1, 2 or 4 Square Mounting
r 3:34' _.,,, :. ,
a..tx
`1 �
• '
FIRE .. ., : , s, J" or `
;etacrtr''•; i . 8 ,� n or
strum, - f , . w .
Ordering Information For wiring diagram for U -MHU Series Horn /Strobes refer
to Installation Instruction Sheet
U -MHU Series HomWall Mount
Lew Volume High Volume Nigh Volume
Model Number Description Pert Number Horn Current Nora Current dB Rating T10'
U- MHU -1G ELC Sync/Non -Sync Hein 24VDC 500- 59959' 17ma 25(1a as db
15- MHU•16 -W ELC Syrc/Noa -Syrtc Horn 24 VDC 500- &99592 :17ma 25.'na :95 db
U -MHU ' ELC Sync/Nott -Sync Horn 7.4VDC 500. 699594 17rga 2Sfita 95 db
U- MiUU -W fLC Sm;Nor. -Svoc Hprn 24 ‘/DC _ 500.6995!3 1 7ma 25••na .95 db
LewVolunse Hieb Volume, Ilieb Volume
Model Number Description Part Number Horn Current Horn Current dB Rating 610'
U- MH11 -MCS ELC Sync/Non-Sync Horn wfSrroaa Ned) 500. 699587 lima 254na 95 dh
U- 1 MICS -w _ ELC Sy!:c/Non -Sync Horn wfSttoae ;'Whitm) 5:10.699598 17na .25erna 95 4b
*AII current measurements made at 24VDC
Fire Satety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 12/02 Brampton, Ontario
Siemens Building Technologies
Tel: `973) 593 -2600 lam Canada
FAX: (9731593 -6670 SFS-IG Tel: (905) 730 -X37 December2002
Fire Safety Website: www.sbt.siemens.corn'tis Printed in U.S.A. FAX: (9051799-9858 s, we , ;•uKs act
SIEMENS Fire Safety
TRI Series
Intelligent Initiating Devices Interface Modules
for MXL Fire Detection Panels TRI - S,TRI - D,TRI -R
ENGINEER AND ARCHITECT SPECIFICATIONS
• Interfaces and Supervises Normally Open Contacts
•
• Integral SPDT Relay (up to 4 amps) onTRI -R Model
• Input . ...... ..........:.. ... .
Dual on TRI -D Model
• l
M i
ut r '
Multi-color L.E.D. .E D. ndi
L cafes t
s atus re n
9
e amber, red)
• Easy front access to programming port and •
wiring terminals •..
• Mounts in 4 inch square 21/4 deep box, or double <
gang box
pp
• Dynamic Supervision
• Comes with 5x5 inch faceplate
�
AC 4het? ' • •
Two wire operation a
e gat
• Model DPU or FPI -32 Programs and Verifies ... _ ...
Device's Address and Tests Device's functionality
• Electronic Address Programming is Easy • :; f
and Dependable
•
UL Listed, L sled, ULC Listed •
CFSM, FM, NYMEA Approved
Introduction module reports the contact's status to the control
The TRI Series Intelligent interface modules are panel. The TRI -S model can only monitor and report the
designed to provide the means of interfacing direct status of the contact, while the TRI -R incorporates an
shorting devices to the MXL system's ALD loop addressable Form C relay. The TRI -R relay and contact
circuit. device input are controlled at the same address. For
the MXL system, the relay and input contact can be
The TRI Series Intelligent interface modules provide controlled as a separate function. The relay is typically
the market's most advanced method of address used where control or shunting of external equipment
programming and supervision, combined with sophis- is required.
ticated control panel communication. Each TRI Series
interface module incorporates a microcomputer chip. The TRI -D is a dual input module and is designed to
The TRI Series microcomputer chip technology and its supervise and monitor two sets of dry contacts. This
sophisticated bi- directional communication capabilities interface module requires two address settings. The
with the control panel, achieve the state of an "Intelli- TRI -D is ideal for monitoring a waterflow switch and its
gent Device" respective valve tamper switch.
The TRI has a multi -color Light Emitting Diode that
Description flashes green when operating normally, amber if unit
The TRI Series Intelligent interface modules are avail-
able in three models. The TRI -S and TRI -R are designed
to monitor a normally open dry contact. The interface
CATALOG NUMBER 6179
is in trouble condition, and red to indicate a change of Mounting Data
state. TheTRI -D flashes twice, once for each address, Addressable interface Model TRI S, TRI D, TRI -R
• the TRI -R red L.E.D. indicates a change of state in i
the relay. mounts directly into a 4 inch square 21/4 deep box
or a double gang box (user supplied). A 5 inch square
The device's microcomputer chip has the capacity of off -white faceplate is included with each TRI.
storing, in memory, identification information as well
as important operating status information. MOUNTING SLOTS
Siemens Building Technologies, Fire Safety Division FOR 4 INCH
SWITCH90X •
innovative technology allows all TRI Series intelligent
interface modules to be programmed by using the
model DPU or FPI -32 Programmer/Tester. The Pro- O - ■
grammer/Tester is a compact, portable, menu driven
accessory that makes programming and testing an [ 1 1 TRI
interface device faster, easier and more dependable ��; ): `I MODULE
than previous methods. I[l a� Q
VI:
T
00'
he DPU or FPI -32 eliminates the need for mechanical e J.-- M OUNTING
addressing mechanisms, such as program jumpers, s - 1 HOLES FOR
DIP switches or rotary dials, because the Programmer /
A S'JVITCHPLATE
Tester electronically sets the TRI interface's address
into the interface's microcomputer chip nonvolatile 0 .
memory. Vibration, corrosion and other conditions that
deteriorate mechanical addressing mechanisms are no
longer a cause for concern.
MOUNTING SLOTS
The TRI Series is fitted with screw terminals for FOR COUBLEGANG
connection to an addressable circuit. . SWITCHBOX
The TRI Series is fully compatible on the same MXL Figure A
circuit with all intelligent FF IL and ID-60 Series Mounting the TRI S / - / -
detectors, MSI Series addressable manual stations
or any other addressable intelligent modules, such
as the CZM or ICP - Electrical Ratings
All TRI Series intelligent interface modules are Current Draw (Active or Standby): 1.5mA
UL listed.
Environmental operating conditions for all TRI Series TRI -R Relay Ratings
modules are 32 °F ( °C) to 120 °F (49 °C) with a relative Resistive: 4A, 125 VAC
humidity of not greater than 93% non - condensating. 4A, 30 VDC
Inductive: 3.5A, 120 VAC (0.6P.F.)
Ordering Information 3.0A, 30 VDC (0.6P.F.)
2.0A, 120 VAC (0.4P.F.)
Shippieg Wt. 2.0A, 120 VAC (0.35P.F.)
Model Description Lb. Kg.
2.0A, 30 VDC (0.35P.F.)
TRI -S Single Input 7 az 2
TRI -R Single Input w /Relay 7 oz. 2
TRI•D Dual Input 7 oz. 2
I
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 7/03 Brampton, Ontario
Siemens Building Technologies Tel: 1973) 593 -2600 5M Canada L6T 5E4
FAX: (973) 593 -6670 SFS-IG Tel: (905) 799 -9937 July 2003
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799-9858 swm.e0sssivaidiro ucr3
SIEMENS Fire Safety
PAD 3
Auxiliary Power Supply - Notification Appliance Extender
ENGINEER AND ARCHITECT SPECIFICATIONS
• 6 amps of Notification Appliance Power •
•
• Advanced Microprocessor Control
• 24 VDC Output Voltage 9 ...... yf
• Four Power - Limited Notification Outputs
• Strobe Synchronization Option Built In
• Synchronized ANSI Temporal Pattern
• Class A Selectable • • Ground Fault Detection : ,
• • Battery Supervision
• 3 Amp Auxiliary Power Output
• Trouble Contact for Monitoring
• Multiple Module Mounting in
System 3 Enclosures { €
• Multiple Modules Share Battery Set PAD
• 0 UL, ULC Listed, CSFM, NYMEA
and FM Approved
Introduction
The Model PAD -3 (PAD -3C for Canada) is a notification The PAD -3 also offers a 3 amp auxiliary output for driving
appliance circuit expander with a built -in auxiliary other portions of your fire alarm system such as door
power output. It is designed for use with Siemens holders.This 24VDC filtered output is power limited.
Building Technologies, Fire Safety Division fire alarm When using this output, the total power available from
control panels.This power source is designed to provide the PAD -3 will not exceed 6 amps.
the extra power required in buildings conforming to the
Americans with Disabilities Act. A trouble contact is provided for monitoring the PAD-3
with a fire alarm panel through the input. It also has a
Form C dry contact for trouble monitoring. Therefore,
Features the user has the option of connecting it to a conven-
The PAD-3 provides 6 amps of 24 VDC power for tional fire alarm panel's existing notification circuit, or
multiple uses. All 6 amps can be directed to 4 Notifi- controlling it with aTRI Series device on intelligent fire
cation Appliance Circuits (NAC s). Each is rated at 3 systems.
amps and is power limited. Either 1 or 2 inputs can The PAD -3 offers battery supervision and management
control the four outputs. These outputs are compatible as is required of fire alarm system components.
with all Fire Safety 24VDC notification appliances. Ground faults are transmitted as are any other trouble
The PAD-3 can be configured so that the inputs can be conditions. Trouble conditions not only change the
programmed as steady outputs, ANSI temporal state of the trouble contact in the unit, but they also
outputs, or synchronized strobe outputs. It can also break the notification circuit input to create a trouble
be programmed so that one input will silence U -MHU signal in the fire alarm control unit.
Series horn /strobe horns while the strobes remain on
using one set of wires.
CATALOG NUMBER 3362
This product is packaged in its own sheet metal enclosure Electrical Specifications
with enough space to house the 7 amp -hour battery set
required for back - up.The enclosure comes in black or red. AC Input: 120 VAC @ 2.5 amps
System 3 enclosures may also be used to house multiple Output: 24VDC @ 6 amps
PAD -3 modules in a single enclosure. Two modules are Auxiliary Power Circuit: 1
capable of sharing the same battery set when mounted in
the same enclosure. Notification Circuits: 4
Output Configuration: 2 Class A or 4 Class B or
Options 1 Class A & 2 Class B .
One or both PAD -3 signal inputs control the notification Amps per Output
outputs, depending on the specific configuration setup. Circuit: 3.0
Possible configurations for the PAD-3 are: Notification Circuit
For These Control These Outputs: 24 VDC at 3.0 amps each,
Option: Inputs: Outputs: As: 24K ohm EOL resistor
required on each Class
1 input 1 All Outputs .. Class 8 Circuits B circuit •
2 Input 1 All Outputs Class B Circuits No. of Inputs: 2
Input 2* Silences hums on 1 Input Configuration: 2 Class B or 2 Class A
3 Input 1 Outputs 1 and 2 Class B Circuits Input Voltage Range: 9 32 VDC
Input 2 Outputs 3 and 4 Class 8 Circuits
4 input 1 Output 1 Class 8 Circuits Battery Charging
Input2 Outputs2,3and4 Class B Circuits Capacity: 15.0A.H
5 Input 1 Outputs 1-2.3 and 4 Class A Circuit Pairs Trouble contact rating: 2.5A @250 VAC, 30 VDC
6 Inputl Outputs 1-Z 3 and 4 ClassACircuitPairs Ambient Temperature: 32 °F to 120 °F
Input 2* Silences horns on 1
7 input1 . Outputs1 and2 Class A Circuit Pairs Mechanical Specifications
Input Outputs ClassACucuitPairs Single Module Enclosure Model EN - PAD
8 Input 1 Outputs 1.2 Class A Circuit Pairs Dimensions: 12"W x 16 "H x 3"D
Input 2 Outputs 3 and 0 Class B Circuits
Color: Black
When used with U -MHU- Series horn/strobe units
Indicator Lights
Supervision AC Power On: Green
The Model PAD-3 supervises a variety of functions BatteryTrouble: Yellow
including: Ground Fault: Yellow •
• Low AC power AuxiliaryTrouble: Yellow
Output 1 Trouble: Yellow
• Low battery condition Output 2Trouble: Yellow
• Earth ground fault
• Auxiliary output power limit condition
Ordering Information
• EOL supervision trouble or power limited condition Para
at an output Model Description Number
When a trouble,condition occurs, the PAD-3 creates a PAD Aux power supply w/black enclosure 599 499189
trouble condition on the fire control signal circuits to PAD - Aux power supplywired enclosure 599 - 699190
which it is connected. it still maintains the ability to be PAD - Aux power supply - main board only 500 - 699080
activated by the fire control. In addition, the PAD -3 EN - PAD Black enclosure for PAD-3 31073
provides a Form 'C' trouble relay output as an alterna - pADR Red enclosure for PAD 310
tive to using the notification circuit trouble.
Fire Safety, Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 9/03 Brampton, Ontario .
Siemens Building Technologies Tel 593 2600 10M Canada L6T 5E4
g Thl FAX: (973) (973) 59 SFS-IG Tel: (905) 799 -9937 September2003
Fire Safety Website: www.siemens.com/fis Printed in U.SA. FAX: (905) 799 -9858 Supersedes sheet dated 6/033
SIEMENS Fire Safety
Adapter Stand Alone Selectable Strobe
• ENGINEER AND ARCHITECT SPECIFICATIONS
AGENT RELEASE
• The Adapter" feature offers four field selectable
candela strobe values — 15/75, 30/75, 75 or 110
for ceiling and wall mount
• Operates in either sync or non -sync mode •
• Low current draw
• Integral universal mounting - single gang,
AGENT REEA
double gang or 4" square box
Agent Release Strobe
• Colors- red or off -white
• ADA/NFPA/ANSI compliant
• UL 1971 listed for both wall and ceiling
�� mount -CSFM and ULC Listed t` r,
•
• Made in U.S.A., ISO 9001 certified L ,
• A Dual Sync Control Module or PAD -3 is only
required to activate the Instant Sync feature,
nothing to set or change at the strobe unit
Adapter Strobe Adapter Strobe Bell Plate
Description
The U -MCS series and U- MCS- 6090V, U- MCS- 6090V -W The U- MCS- 6090V, U- MCS- 6090V -W provides the same
strobes combine state of the art electronics to provide strobe choices and is constructed of metal for mounting
reliability and low current draw to meet visual life safety bell or chime devices to the plate.
applications.The Adapter feature offers four field select-
able candela settings 15/75, 30/75, 75 or 110. The U -MCS Series & U- MCS- 6090V, U- MCS -6090V W
use a Xenon flashtube with solid state circuitry for
maximum reliability and efficiency. Strobes have a
s ' Detail - Adapter rounded dome shape made of clear polycarbonate.
''- selector switch The U -MCS Series uses a terminal block for easy installa-
tion and the U- MCS- 6090V, U- MCS- 6090V -W uses a
The integral universal mounting plate of the U -MCS pigtail (4 wire) connection.
provides for easy installation with single gang, double Strobe Synchronization requires the Dual Sync Module
gang or4" square box mounting.The lens construction or PAD -3.
provides high candela output with low current consump-
tion while meeting UL and ADA standards.
CATALOG NUMBER 2550
Engineering Specifications The Series U- MCS- 6090V, U- MCS -6090V W Strobe Plate
The visual notification appliances shall be Adapter U -MCS shall facilitate the addition of a strobe to a bell installation.
Series or U- MCS- 6090V, U- MCS- 6090V -W field selectable The Strobe Plate shall mount to a 4" square backbox for
candela strobe appliance, or approved equal.They shall be flush mounting.
listed to UL1971 (Standard for Safety Signaling Devices for Ordering Information
the Hearing Impaired) for indoor applications, and shall be g
ADA/NFPA/ANSI compliant. Stand-Alone Mount and Ceiling Mount
The strobe shall produce a flash rate of one (1) flash per Nn
Modal Description Num ber
second over the Operating Voltage Range limits of 16 to U - MCS Multicande9a Selectable Strube Red 500.859701 -
33Vdc.The strobe light shall consist of a Xenon flash tube U•MCS - e MA,ltican:le :a Selectable Strobe White 500 - 699702
enclosed in a rugged, clear polycarbonate lens. Inputs
shall be compatible with standard reverse polarity circuit Retro -Plate Wall Mount
supervision by an FACP.The Strobe shall be of low
current design, and shall provide a minimum of four (4) Model Pen
field selectable strobe intensity settings, 15/75, 30/75, 75 Number Description Number
and 110 candela. All settings shall be UL 1971 listed for U•MCS - 6090V Retro Plste 500.699703
Multicendela SelectabiuSStrobe Red
both wall and ceiling mount applications.The selector U - MCS•6090W1 Retro Plata 500.69970.4
switch shall be tamper - resistant. Multicandel/i Selectable Strobe Red
It shall not be necessary to remove the strobe from the
mounting surface to select the strobe intensity. When Stand -Alone Strobes -Wall Mount and
synchronization is required, the strobe shall be compat- Ceiling Mount - for Agent Release
ible with the Dual Sync Module, or other source of M odel Part
Siemens Building Technologies, Fire Safety Division Sync Number Description Number
Protocol, and shall not drift out of synchronization. U- MCS -AR Multicandela Selectable Strobe - Red 500- 699746
For Agent Release
The U -MCS Series Stand -Alone Strobe shall have an
integral universal mounting plate that shall allow mount-
ing to single- gang, two-gang, and 4" square backboxes, Canadian Ordering Information
as well as FBX -S and FBX -F Surface Boxes. A cover trim
plate shall be included to enhance appearance.There shall Stand -Alone Strobes -Wall Mount and Ceiling Mount
be no mounting holes or screw heads visible. Model Pan
Number Description Number
U-MCS Specifications CU-MCS Multicande9a Selectable Strube. Red 500- 6997040
Cil.MCS.W Multicande9a Selectahle Strobe- White 500.6997070
Environmental - .
32 °F to 120 °F (0 °C to 49 °C) at 85% RH Retro -Plate Wall Mount
InputVoltage Model Part
16 - 33Vdc regulated or FWR Number Description Number -
Mounting CU- MCS -6090V Retro Plate 500 - 6997030
Integral universal mounting plate mounts to single Melt :candela Seiectab'.e Strobe• Fed
gang, double gang or 4" square box. CU•MCS•60911vW Retro Plate 500-699704C
Shipping Weight _ Mutt:candela Seiectab a Strobe- Red
9 oz. approx. -
Stand -Alone Strobes -Wall Mount and
Ceiling Mount - for Agent Release
U -MCS Dimensions Model - Part
arm. - 312• Number Description Number
E 3 I CU- MCS -AR Mulrcande)a Selectable Strube • Red 500- 899746C
y t For Agent Release
FIRE
♦`
•
Strobe IntRn4lty Setting $ trobe Current Draw
r` "i'i ;: 15/75 cd 63 mA
4-518' Ant �:
';: D 30/75 cd 84 mA
��t i
R:: "'` -..i D 75 cd 143 mA
E FIRE ` ' - selector _ 110 cd 178 mA
t~ Switch
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 8/03 Brampton, Ontario �
Siemens Building Technologies Tel: (9731 593 -2600 5M Canada L6T 5E4
g FAX: (973) 593-6670 SFS-IG Tel: (905) 799 -9937 August 2003
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799-9858 swamies she., data 103
SIEMENS Fire Safety
U -MHU Series
Models U -MHU Electronic Sync /Non -Sync Horn
ENGINEER AND ARCHITECT SPECIFICATIONS
• The AdapterTM /U -MCS feature offers four field
selectable n —
ca dela values— 1 or 110
va � es 5/75 3 /7 75 0
0 5 5
for wall & ceiling mount
"::f :$viii : :i : :r rw'•' is
• Sync strobes and sync temporal horns, with horn
Y P
silence on 2 wires
• Distinctive tem P oral horn
•
Internally
t l v I
adjustable ab volume control
e ou eco t l
0
• Low current draw 1�.
• Single gang and universal mount configurations
• UL 1971 & UL 464 listed - CSFM, ULC, & NYMEA
• UL 1971 listed for both wall and ceiling mount
• ADA/NFPA/ANSI compliant
• Screw terminals accept 12 awg wire % : : < ' : :< ;<;<y
• Synchronization requires Dual Sync Control .._
Module o PAD -3 •
• Made in U.S.A., ISO 9001 quality crafted
Description Detail - Adapter
The U-MHU-1G, U-MHU-1G-W and U -MHU, U -MHU -W � 15 8 selector switch
Sync Electronic Horns and U- MHU -MCS, U- MHU -MCS -W
Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA
nous temporal tone signals on one pair of wires or output levels.
temporal or steady tone in a non -sync mode.
The U-MHU-1G, U-MHU-1G-W mounts to a single
gang box, the U -MHU, U -MHU -W and U- MHU -MCS, )
U- MHU -MCS -W have a universal mounting plate for _ amax.vizurne
1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust
Siemens Fire Safety notification appliances are (factory set at max. volume)
designed with the installer in mind.They are constructed The U -MHU -MCS, U -MHU -MCS -W strobe construction
with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for
This design eliminates passible ground faults from maximum reliability and efficiency The strobe has a
crowded electrical boxes.The Adapter!U -MCS feature rounded dome shape made of clear polycarbonate.
offers four field selectable candela settings —
15/75, 30/75, 75 or 110.
CATALOG NUMBER 2560
Replaces Catalog Sheet Number 2555
•
The U -MHU -1 G, U -MHU -1 G-W, U -MHU, U -MHU -W and Listed operating range is 20 to 31 VDC /FWR
U- MHU -MCS, U- MHU -MCS -W are used on circuits with Temporal maximum UL measurements are 83.6 db at
steady Dower or a Dual Sync Control Module or PAD -3. 24VDC /FWR. Steady tone maximum UL measurements
Not for use on coded circuits. are 87.8 db at 24 VDC /FWR taken in free air at 360°
around the device and averaged. Typical readings are
Environmental frontal sound readings taken with a dB meter with signal -
32 °F to 120 °F (0 °C to 49 °C) with 85% humidity mounted on wall. Rated for indoor use 32 °F to 120 °F, (0 °C
to 49 °C), at RH 85 %.
Operating Voltage Range Limits (C: Ceiling Mounted •
Horn: 20-31 Vdc orVFWR (-W White)
Strobe: 16-33 Vdc orVFWR $troha Intensity Setting Atroha Current Draw
15!75 cd 63 mA
Typical Horn Ratings at 10 Feet* 30/75 cd 84 mA
Temporal Horn - 75 cd 143 mA
110cd 178mA
Maximum: 95 db @ 25 mA
Minimum: 90 db @ 17 mA Control Module Specifications;
* Typical dBA ratings are frontal sound readings Maximum Current Output: 3 Amps Max. not
taken with a dB meter with signal mounted on wall. to exceed NAC rating
DSC Module OperatingVoltage: 20 to 31 Vdc orVFW
Dimensions DSC Module Operating Current: Non - Silenceable
— 244" - y t -ar4' 1• 4324' -.i - •.t•ya Circuit side
•' . 4,7 -- I I — -tez 55mA, Silenceable • --- .."
• Circuit side .005 Amps.
• 41.7 I M� r• a. P P Maximum Current Output: 3 Amps max. not to
exceed Circuit rating
1, 2 or 4 Square Mounting
;, .
F . ;:,. ( LJ:
:ice. .ice :� ,/ •
FIRE ty, .',�,
• ...- ; "' • ' Or
• 'iar+rrxx I --..:.• , '�� • or
' ,,i v .
i
..
For wiring diagram for U -MHU Series Horn /Strobes refer
Ordering Information to Installation instruction Sheet
U -MHU Series HornWall Mount
Low Volume High Volume High Volume
Model Member Description Part Number Horn Current Horn Current dB Rating 610'
1 .14.4HU -1G ELLSy-^-c/Nob- Syac Horn 24`DC 500- 599:59 - i7rra 25ma 9544
li- bARU -16 -W FLC Sync/Non-Sync Horn 2 500. 699592 :7ma 25me :95 dt,
U -MHU FIX Sy><r. /Nor -Sync Horn 74 VJC 5:101699594 lima 2bmn 95 db
1J -11/4.11111-W EtC Sync /Non -S,nc Horn 24VDC 54'10- 699593 17ma fiord 95 db
LOW Wyllie High Volume. HighVoleme
Model Number Deseriptloo Part Number Horn Current Horn Current . dB Rating 4101'
U- 6,114U-MCS .FU; Sync/Non-Sync Horn w%S1raba CRedi 500-699587 _ lima 25ma 95 db
U- MHU -MCS -w ELC Sync/Non-Sync Horn w /St•obe )Witte) 510. 1;99588 17ma 7..5,-na 95 db
*AII current measurements made at 24VDC
Fire Satety Fire Safety
8 Fernwood Road 2 Kenv:ew Boulevard
Florham Park, NJ 07932 12/02 Brampton, Ontario
Siemens Building Technologies Tel: 1973) 593 -2600 1- l Canada L6T5E4
FAX:1973) 593.6670 SFS.IG el: 1905) 799-9937 December 2002
Fire Safety Website: www.sbt.siemer•s.com/tia Printed in L.S.A. FAX: 19051 799 - 9853 s„oerr 1. ,.w:„, ,;scar a2•z
SIEMENS Fire Safety
TRI Series
Intelligent Initiating Devices Interface Modules
for MXL Fire Detection Panels TRI - S,TRI - D,TRI -R
ENGINEER AND ARCHITECT SPECIFICATIONS
• Interfaces and Supervises Normally Open Contacts
• Integral SPDT Relay (up to 4 amps) onTRI -R Model
• Dual Input on TRI -D Model
• Multi -color L.E.D. indicates status (green, amber, red)
• Easy front access to programming port and
wiring
terminals
min I
s
• Mounts in 4 inch square 21/4 deep box, or double
gang box
• Dynamic Supervision •
• • Comes with 5x5 inch faceplate •
?Y*
uu �
u h "siA�ss,�
• Two wire operation + 34.
• Model DPU or FPI -32 Programs and Verifies
Device's Address and Tests Device's functionality
• Electronic Address Programming is Easy
and Dependable
• ID UL Listed, ULC Listed
CFSM, FM, NYMEA Approved
Introduction module reports the contact's status to the control
The TRI Series Intelligent interface modules are panel. The TRI -S model can only monitor and report the
designed to provide the means of interfacing direct status of the contact, while theTRl -R incorporates an
shorting devices to the MXL system's ALD loop addressable Form C relay. The TRI -R relay and contact
circuit. device input are controlled at the same address. For
the MXL system, the relay and input contact can be
The TRI Series Intelligent interface modules provide controlled as a separate function. The relay is typically
the market's most advanced method of address used where control or shunting of external equipment
programming and supervision, combined with sophis- is required.
ticated control panel communication. Each TRI Series
interface module incorporates a microcomputer chip. The TRI -D is a dual input module and is designed to
The TRI Series microcomputer chip technology and its supervise and monitor two sets of dry contacts. This
sophisticated bi- directional communication capabilities interface module requires two address settings. The
with the control panel, achieve the state of an "Intelli TRI -D is ideal for monitoring a waterflow switch and its
gent Device" respective valve tamper switch.
The TRI has a multi -color Light Emitting Diode that
Description flashes green when operating normally, amber if unit
• The TRI Series Intelligent interface modules are avail-
able in three models. The TRI -S and TRI -R are designed
to monitor a normally open dry contact. The interface
CATALOG NUMBER 6179
is in trouble condition, and red to indicate a change of Mounting Data
state. TheTRI -D flashes twice, once for each address, Addressable interface Model TRI S, TRI D, TRI -R
theTRl -R red L.E.D. indicates a change of state in mounts directly into a 4 inch square 2' /o deep box
the relay. or a double gang box (user supplied). A 5 inch square
The device's microcomputer chip has the capacity of off-white faceplate is included with each TRI.
storing, in memory, identification information as well
as important operating status information. MOUNTING SLOTS
Siemens Building Technologies, Fire Safety Division FOR 4 :NCH
SWITCH90X -
innovative technology allows all TRI Series intelligent
interface modules to be programmed by using the
model DPU or FPI -32 Programmer/Tester. The Pro- O
grammer/Tester is a compact, portable, menu driven
accessory that makes programming and testing an [a7 I TRI S / - / -
interface device faster, easier and more dependable 17 Plr;`I MODULE
than previous methods. 4l ry� Q
[ —1
The DPU or FPI -32 eliminates the need for mechanical 8 _ MOUNTING
addressing mechanisms, such as program jumpers, �-�' 7 ._ HOLES FOR
DIP switches or rotary dials, because the Programmer / SVvrrCHPLATE
Tester electronically sets the TRI interface's address �
into the interface's microcomputer chip nonvolatile 0
memory. Vibration, corrosion and other conditions that
deteriorate mechanical addressing mechanisms are no /
longer a cause for concern.
MOUNTING SLOTS
The TRI Series is fitted with screw terminals for FOR COUBLEGANG
connection to an addressable circuit. SWITCHBOX
The TRI Series is fully compatible on the same MXL Figure A
circuit with all intelligent FP IL and ID-60 Series Mounting the TRI- S / -R / -D
detectors, MSI Series addressable manual stations
or any other addressable intelligent modules, such Sri
as the CZM or ICP. ,
Electrical Ratings
All TRI Series intelligent interface modules are Current Draw (Active or Standby): 1.5mA
UL listed.
Environmental operating conditions for all TRI Series
TRI-R Relay tive: 4AA, 1, 125s 25 VAC
modules are 32 °F ( °C) to 120 °F (49 °C) with a relative
humidity of not greater than 93% non - condensating. 4A, 30 VDC
Inductive: 3.5A, 120 VAC (0.6P.F.)
Ordering Information 3.0A, 30 VDC (0.6P.F.)
2.0A, 120 VAC (0.4P.F.)
Shipping Wt. 2.OA, 120 VAC (0.35P.F.)
Model Description Lb. Kg.
2.0A, 30 VDC (0.35P.F)
TRI -S Single Input 7 az. 2
' TRI -R Single Input w /Relay 7 oz 2
TRI -D Dual Input 7 oz 2
I
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 7/03 Brampton, Ontario
Siemens Building Technologies Tel: (973) 593-2600 5M Canada I-6T 5E4
FAX: (973) 593 -6670 SFS -IG Tel: (905) 799 -9937 July 2003
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799-9858 syp3,3�33bgmtml,p0
SIEMENS Fire Safety
PAD 3
Auxiliary Power Supply - Notification Appliance Extender
ENGINEER AND ARCHITECT SPECIFICATIONS
• 6 amps of Notification Appliance Power
• Advanced Microprocessor Control
• 24 VDC Output Voltage i. ' .2.2M
• Four Power - Limited Notification Outputs ,, ,
• Strobe Synchronization Option Built In 4 ' • '
• Synchronized ANSI Temporal Pattern
• Class A Selectable
• Ground Fault Detection
• Battery Supervision m
• 3 Amp Auxiliary Power Output
• Trouble Contact for Monitoring
• Multiple Module Mounting in
System 3 Enclosures
• Multiple Modules Share Battery Set PAD-3
• 0 UL, ULC Listed, CSFM, NYMEA
and FM Approved
Introduction
The Model PAD -3 (PAD -3C for Canada) is a notification The PAD -3 also offers a 3 amp auxiliary output for driving
appliance circuit expander with a built -in auxiliary other portions of your fire alarm system such as door
power output. It is designed for use with Siemens holders.This 24VDC filtered output is power limited.
Building Technologies, Fire Safety Division fire alarm When using this output, the total power available from
control panels.This power source is designed to provide the PAD -3 will not exceed 6 amps.
the extra power required in buildings conforming to the
Americans with Disabilities Act. A trouble contact is provided for monitoring the PAD-3
with a fire alarm panel through the input. It also has a
Form C dry contact for trouble monitoring. Therefore,
Features the user has the option of connecting it to a conven-
The PAD-3 provides 6 amps of 24 VDC power for tional fire alarm panel's existing notification circuit, or
multiple uses. All 6 amps can be directed to 4 Notifi- controlling it with a TRI Series device on intelligent fire
cation Appliance Circuits (NAC s). Each is rated at 3 systems.
amps and is power limited. Either 1 or 2 inputs can The PAD -3 offers battery supervision and management
control the four outputs. These outputs are compatible as is required of fire alarm system components.
with all Fire Safety 24VDC notification appliances. Ground faults are transmitted as are any other trouble
The PAD -3 can be configured so that the inputs can be conditions. Trouble conditions not only change the
programmed as steady outputs, ANSI temporal state of the trouble contact in the unit, but they also
outputs, or synchronized strobe outputs. It can also break the notification circuit input to create a trouble
be programmed so that one input will silence U -MHU- signal in the fire alarm control unit.
Series horn /strobe horns while the strobes remain on
using one set of wires.
CATALOG NUMBER 3362
This product is packaged in its own sheet metal enclosure Electrical Specifications
with enough space to house the 7 amp -hour battery set
required for back - up.The enclosure comes in black or red. AC Input: 120 VAC @ 2.5 amps '
System 3 enclosures may also be used to house multiple Output: 24VDC @ 6 amps
PAD -3 modules in a single enclosure. Two modules are Auxiliary Power Circuit: 1
capable of sharing the same battery set when mounted in
the same enclosure. Notification Circuits: 4
Output Configuration: 2 Class A or 4 Class B or
Options 1 Class A & 2 Class B .
One or both PAD -3 signal inputs control the notification Amps per Output
outputs, depending on the specific configuration setup. Circuit: 3.0
Possible configurations for the PAD-3 are: Notification Circuit
For These Control These Outputs: 24VDC at 3.0 amps each,
Option: Inputs: Outputs: As: 24K ohm EOL resistor
required on each Class
1 Input 1 All Outputs, Class B Circuits B circuit
2 Input 1 All Outputs Class B Circuits No. of Inputs: 2
Input 2* Silences horns on 1 Input Configuration: 2 Class B or 2 Class A
3 Input 1 Outputs 1 and 2 Class B C'ir'cuits Input Voltage Range: 9-32 VDC
Input 2 Outputs 3 and 4 Class B Circuits
4 Input 1 Output 1 Class B Circuits Battery Charging
Input 2 Outputs 2,3 and 4 Class B Circuits Capacity: 15.0 A. H
5 Input 1 Outputs 1 -2, 3 and 4 Class Circuit Pairs Trouble contact rating: 2.5A @250 VAC, 30 VDC
6 Input l Outputs 1-2,3 and 4 Class Circuit Pairs Ambient Temperature: 32 °F to 120 °F
lnput2' Silences horns on 1
7 Input 1 ' Outputs 1 and 2 Class Circuit Pairs Mechanical Specifications
Input Outputs GessACircuitPairs Single Module Enclosure Model EN -PAD •
8 Input 1 Outputs 1.2 Class Circuit Pairs Dimensions: 12"W x 16 "H x 3"D
Input 2 Outputs 3 and 4 Class B Circuits Color: Black
*When used with U -MHU- Series horn/strobe units
Indicator Lights
Supervision AC Power On: Green
The Model PAD -3 supervises a variety of functions BatteryTrouble: Yellow
including: Ground Fault: Yellow •
• Low AC power AuxiliaryTrouble: Yellow
Output 1 Trouble: Yellow
• Low battery condition Output 2Trouble: Yellow
• Earth ground fault
• Auxiliary output power limit condition Ordering Information
• EOL supervision trouble or power limited condition Part
at an output Model Description Number
When a trouble condition occurs, the PAD-3 creates a PAD -3 Aux power supply wJblack enclosure 599 - 6`39189
trouble condition on the fire control signal circuits to PAO-3R Aux. power supply wired enclosure 599 - 699190
which it is connected. It still maintains the ability to be PAO Aux. power supply - main board only 500
activated by the fire control. In addition, the PAD - EN -PAD Black enclosure for PAD-3 310-099073
provides a Form 'C' trouble relay output as an alterna EN -PAOR Red enclosure for PAD-3 310 - 099150
tive to using the notification circuit trouble.
•
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park. NJ 07932 9/03 Brampton, Ontario
Siemens Building Technologies Tel: (973) 2600 tarn Canada L6T 5E4
FAX: (973) 66 70 SFS4G Tel: (905) 799 -9937 September 2003
Fire Safety Website: www.siemens.comlfis Printed in U.S.A. FAX )905) 799 -9858 Supersedes sheet dined rrm
SIEMENS Fire Safety
Adapter Stand Alone Selectable Strobe
ENGINEER AND ARCHITECT SPECIFICATIONS
ENT RELEASE .. !.
• The Adapter" feature offers four field selectable
candela strobe values - 15/75, 30/75, 75 or 110
for ceiling and wall mount " ��
f .
• Operates in either sync or non-sync mode s `
P Y Y
• Low current draw
• Integral universal mounting - single gang, AGENT RELEA
double gang or 4" square box
Agent Release Strobe
• Colors- red or off -white
• ADA/NFPA/ANSI compliant 44-
A I
• v UL 1971 listed for both wall and ceiling
mount -CSFM and ULC Listed E
F
Made in A. certified s qk •
• M 1
ad U S , ISO 9001
r >�
• A Dual Sync Control Module or PAD -3 is only ! ., �� �
required to activate the Instant Sync feature,
nothing to set or change at the strobe unit
Adapter Strobe Adapter Strobe Bell Plate
Description
The U -MCS series and U- MCS- 6090V, U- MCS- 6090V -W The U- MCS- 6090V, U- MCS- 6090V -W provides the same
strobes combine state of the art electronics to provide strobe choices and is constructed of metal for mounting
reliability and low current draw to meet visual life safety bell or chime devices to the plate.
applications.The Adapter feature offers four field select-
able candela settings 15/75, 30/75, 75 or 110. The U -MCS Series & U- MCS- 6090V, U- MCS- 6090V -W
use a Xenon flashtube with solid state circuitry for
maximum reliability and efficiency. Strobes have a
Detail - Adapter rounded dome shape made of clear polycarbonate.
(�� selector switch The U -MCS Series uses a terminal block for easy installa-
tion and the U- MCS- 6090V, U- MCS- 6090V -W uses a
The integral universal mounting plate of the U -MCS pigtail (4 wire) connection.
provides for easy installation with single gang, double Strobe Synchronization requires the Dual Sync Module
gang or 4" square box mounting.The lens construction or PAD -3.
provides high candela output with low current consump-
tion while meeting UL and ADA standards.
CATALOG NUMBER 2550
Engineering Specifications The Series U- MCS- 6090V, U- MCS- 6090V -W Strobe Plate
The visual notification appliances shall be Adapter U -MCS shall facilitate the addition of a strobe to a bell installation. ,
Series or U- MCS- 6090V, U- MCS- 6090V -W field selectable The Strobe Plate shall mount to a 4" square backbox for '
candela strobe appliance, or approved equal.They shall be flush mounting.
listed to UL1971 (Standard for Safety Signaling Devices for Ordering Information
the Hearing Impaired) for indoor applications, and shall be •
ADA/NFPA/ANSI compliant. Stand - Alone Strobes -Wall Mount and Ceiling Mount
Model Part
The strobe shall produce a flash rate of one (1) flash per Number Description Number
second over the Operating Voltage Range limits of 16 to U -MCS Multicende&a Selectable Strube Red 500. 899701 .
33Vdc.The strobe light shall consist of a Xenon flash tube U- MCS - Mrrlticandela Selectahle Strobe 500 - 699702
enclosed in a rugged, clear polycarbonate lens. Inputs
shall be compatible with standard reverse polarity circuit Retro -Plate Wall Mount
supervision by an FACP.The Strobe shall be of low -
current design, and shall provide a minimum of four (4) Model Pen
field selectable strobe intensity settings, 15/75, 30/75, 75 Number Description Number
and 110 candela. All settings shall be UL 1971 listed for U- MCS - 6090V Retrc Plate 500. 699703
Multicandela Selectable Strobe Had
both wall and ceiling mount applications.The selector U FRCS 6tl90VVY Retrc Plata 500 699)04
switch shall be tamper - resistant. _ Muiticandela Selectnh:r. Strobe - Red
It shall not be necessary to remove the strobe from the
mounting surface to select the strobe intensity. When Stand -Alone Strobes -Wall Mount and
synchronization is required, the strobe shall be compat- Ceiling Mount - for Agent Release
ible with the Dual Sync Module, or other source of Model Part
Siemens Building Technologies, Fire Safety Division Sync Number Description Number
Protocol, and shall not drift out of synchronization. U- MCS -AR Mu(ticandela Selectable Strobe - Red 500- 699746
for Agent Release
The U -MCS Series Stand -Alone Strobe shall have an
integral universal mounting plate that shall allow mount-
ing to single- gang, two-gang, and 4" square backboxes, Canadian Ordering Information
as well as FBX -S and FBX -F Surface Boxes. A cover trim
plate shall be included to enhance appearance.There shall Stand -Alone Strobes -Wall Mount and Ceiling Mount
be no mounting holes or screw heads visible. Model Pan
Number Description Number
U-MCS Specifications CU -MCS Municandela Selectable Strube- Red 500.699701C
CU -MCS -W Mult(cendsta Selectable Strobe - Whits 500-6997070
Environmental •
32 °F to 120 °F (0 °C to 49 °C) at 85% RH Retro -Plate Wall Mount
InputVoltage Modal - Part
16-33Vdc regulated or FWR • Humber Description Number
Mounting CU Rego Plate 500-699703C
Integral universal mounting plate mounts to single Mntticandela Selectable Strobe- Red
gang, double gang or 4" square box. CU- MCS -6090 W Retro Mats 500.6997040
ShippingWeight Mutticandela Selectable Strobe - Red
9 oz. approx.
Stand -Alone Strobes -Wall Mount and
Ceiling Mount - for Agent Release
U -MCS Dimensions Model - Part
r 4-5/8" — -
3-1/2' i Number _ Description Number
• 9 CU- MCS - AR Mu(ticande!e Selectable Strube - Red 500-6997460
i ,
- ` For Agent Release
FIRE
_____"..,1 Strobe Intensity Bettina strobe Current Draw
15/75 cd 63 mA
4- Sr8'�t 3 0775 cd 84 mA
� I::: --- : : :� 75 cd 143 mA
- 110 cd 178 mA
t FIRE - septa -
Switch
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 8/03 Brampton, Ontario I.
Siemens Building Technologies Tel: (973) 593 -2600 Ss/1 1 Canada L6T 5E4
g IeS FAX: (973) 593 -6670 SFS;G Tel: (905) 799 -9937 August 2003
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S A. FAX: (905) 799-9858 Supe'ce°ee sneer axed 3103
SIEMENS Fire Safety
U -MHU Series
Models U -MHU Electronic Sync /Non -Sync Horn
ENGINEER AND ARCHITECT SPECIFICATIONS
• The Adapter /U -MCS feature offers four field
I —
selectable ble n i
candela values— es 1 /7
a a � 5 5 30/7 75 or 1
5 50 1 0
for wall & ceiling
g ount
pis'''
• Sync strobes and sync temporal horns, with horn
Y F ..; ;
silence on 7 wires
• Distinctive temporal horn
• r'
I� rn�l
t I
e a adjustable volume v lu control
be o eco t
Y d
1 t
a
• Low current draw
• Single gang and universal mount configurations
• UL 1971 & UL 464 listed - CSFM, ULC, & NYMEA
• UL 1971 listed for both wall and ceiling mount
• ADA/NFPA/ANSI compliant
•
• Screw terminals accept 12 awg wire
• Synchronization requires Dual Sync Control
Module or PAD-3
odu e o PAD 3
• Made in U.S.A., ISO 9001 quality crafted
Description Detail - Adapter
The U -MHU -1 G, U -MHU -1 G-W and U -MHU, U -MHU -W C5).„„ selector switch
Sync Electronic Horns and U -MHU -MCS, U- MHU -MCS -W
Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA
nous temporal tone signals on one pair of wires or output levels.
temporal or steady tone in a non -sync mode.
The U- MHU -1 G, U- MHU -1 G-W mounts to a single
gang box, the U -MHU, U -MHU -W and U- MHU -MCS, t°
U- MHU -MCS -W have a universal mounting plate for r--'4 Max. Vuiume
1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust
Siemens Fire Safety notification appliances are (factory set at max. volume)
designed with the installer in mind.They are constructed The U- MHU -MCS, U -MHU -MCS -W strobe construction
with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for
This design eliminates possible ground faults from maximum reliability and efficiency.The strobe has a
crowded electrical boxes.The Adapter/U -MCS feature rounded dome shape made of dear polycarbonate.
offers four field selectable candela settings -
15/75, 30/75, 75 or 110.
CATALOG NUMBER 2560
Replaces Catalog Sheet Number 2565
The U -MHU -1 G, U -MHU -1 G-W, U -MHU, U -MHU -W and Listed operating range is 20 to 31 VDC /FWR •
U -MHU -MCS, U- MHU -MCS -W are used on circuits with Temporal maximum UL measurements are 83.6 db at
steady Dower or a Dual Sync Control Module or PAD-3. 24VDC /FWR. Steady tone maximum UL measurements
Not for use on coded circuits. are 87.8 db at 24 VDC /FWR taken in free air at 360°
around the device and averaged. Typical readin s are
Environmental frontal sound readings taken with a dB meter w h signal
32 °F to 120 °F (0 °C to 49 °C) with 85% humidity mounted on wall. Rated for indoor use 32 °F to 1 0 °F, (0 °C
to 49 °C), at RH 85 %.
Operating Voltage Range Limits f C: Ceiling Mounted
Horn: 20-31 Vdc orVFWR
( -W: White)
Strobe: 16 -33Vdc orVFWR $trnhe Intansity Setting ,Strobe Current Draw
15(75 cd 63 mA
Typical Hom Ratings at 10 Feet* 30/75 cd 84 mA
Temporal Horn - 75 `d 143 mA
110cd 178mA
Maximum: 95 db @ 25 mA
Minimum: 90 db @ 17 mA Control Module Specifications;
* Typical dBA ratings are frontal sound readings Maximum Current Output: 3 Amps Ma:. not
taken with a dB meter with signal mounted on wall. to exceed NAC rating
DSC Module OperatingVcltage: 20 to 31 Vdc orVFW
Dimensions DSC Module Operating Current: Non - Silences ble
-2. 4 "•- f 1 .34' 4.3:4' ; -- 1.34' Circuit side
--v-- , '' i - -• - f. i -''� 55mA, Silen ;cable
Circuit side A005 Amps.
4 - . ra a. ; : Maximum Current Output: 3 Amps mat . not to
exceed CircL it rating
1, 2 or 4 Square Mounting
..4 •.r ^. . -.
4.3'a 0 '• '' 4J
--"•••
.
I t 4 .... ".- I or
For wiring diagram for U -MHU Series Horn /Strob ss refer
Ordering Information to Installation Instruction Sheet
U -MHU Series HomWall Mount
Low Volume High Volume High Vela no
Model Number Description Part Nuneher Horn Current Horn CiReut dB Rating O10'
al- MHU -1G ELC SY• ^•c /Nof? -Syae Hem 24 VDC 500-699591 171ra 25ma •95 db
II-MHO-16 ELC Sync/Nos -$y:ic Horn 24 VOC 500- 699592 t ima• 25:na 95 db
U -MHU • RC Sync/Non -Sync Horn 74 VOC W- 699594 lira 25rna 95 db
U•1litiii -W _ ELC Sync /Non -51; Ciip.rn24t10C 500. 699591 _ 17ma 2S,toa 95 rib
LowVolunite High Valuate. High Vole rte
Model Number Description Part Number Horn Current Hesn COReat _ d8 Rating C#10'
U- M1 ELC Sync Non -Sync H,ra w/S +rota pled) 500- 699587 i7rna 2.5tna .95 db
El- MKLI -MCS.W _ fl.0 Sync/Non-Sync Hcrn wi /Strobe;'u4 _ 530- ti99598 _ 17rn..a 2Stna 95 rib
*AII current measurements made at 24VDC •
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 12/02 Brampton, Ontario
Siemens Building Technologies el: 1973) 593 -2600 10M Canada L6T5E4
FAX: (973) 593.6670 SFS1G Tel: (905) 799 -9937 December 2002
Fire Safety Website: v vnv.sb .siemer•.s.com,fis Printed in U.S.A. FAX: (9051 7 99 -9859 s :pen :tW, y • drag.: EM2
SIEMENS Fire Safety
TRI Series
Intelligent Initiating Devices Interface Modules
• for MXL Fire Detection Panels TRI - S,TRI - D,TRI -R
ENGINEER AND ARCHITECT SPECIFICATIONS
• Interfaces and Supervises Normally Open Contacts
• Integral SPDT Relay (up to 4 amps) onTRI -R Model
• Dual Input onTRI -D Model •
• Multi -color L.E.D. indicates status (green, amber, red)
• Easy front access to programming port and
wiring n terminals
s
• Mounts in 4 inch square 21/4 deep box, or double
gang box
•
D n is
am Supervision
Y
• Comes with 5x5 inch faceplate 1 >
• Two wire operation "i a: "�ft . ,
•
Model DPU or FPI -32 Programs and Verifies
;; y
Device's Address and Tests Device's functionality § '
"mss s s.
•
• Electronic Address Programming is Easy
and Dependable
• 43 UL Listed, ULC Listed
CFSM, FM, NYMEA Approved
Introduction module reports the contact's status to the control
The TRI Series Intelligent interface modules are panel. The TRI -S model can only monitor and report the
designed to provide the means of interfacing direct status of the contact, while the TRI -R incorporates an
shorting devices to the MXL system's ALD loop addressable Form C relay. The TRI -R relay and contact
circuit. device input are controlled at the same address. For
the MXL system, the relay and input contact can be
The TRI Series Intelligent interface modules provide controlled as a separate function. The relay is typically
the market's most advanced method of address used where control or shunting of external equipment
programming and supervision, combined with sophis- is required.
ticated control panel communication. Each TRI Series
interface module incorporates a microcomputer chip. The TRI D is a dual input module and is designed to
The TRI Series microcomputer chip technology and its supervise and monitor two sets of dry contacts. This
sophisticated bi- directional communication capabilities interface module requires two address settings. The
with the control panel, achieve the state of an " lntelli TRI -D is ideal for monitoring a waterflow switch and its
gent Device" respective valve tamper switch.
The TRI has a multi -color Light Emitting Diode that
Description flashes green when operating normally, amber if unit
• The TRI Series Intelligent interface modules are avail-
able in three models. The TRI -S and TRI -R are designed
to monitor a normally open dry contact. The interface
CATALOG NUMBER 6179
is in trouble condition, and red to indicate a change of Mounting Data
state. TheTRI -D flashes twice, once for each address, Addressable interface Model TRI -S, TRI -D, TRI -R
the TRI -R red L.E.D. indicates a change of state in mounts direct) into a 4 inch square 2'/4 deep b x
the relay. Y q p
or a double gang box (user supplied). A 5 inch - quare
The device's microcomputer chip has the capacity of off -white faceplate is included with each TRI.
storing, in memory, identification information as well •
as important operating status information. MOUNTING SLOTS
Siemens Building Technologies, Fire Safety Division FOR 4 :NCH
SWITCH3UX
innovative technology allows all TRI Series intelligent
interface modules to be programmed by using the
model DPU or FPI -32 Programmer/Tester. The Pro- 0
grammer/Tester is a compact, portable, menu driven
accessory that makes programming and testing an [_)• TRI S / - 0/ -
interface device faster, easier and more dependable [I) 1:- e I MODULE
I r, p
than previous methods. I
The DPU or FPI-32 eliminates the need for mechanica 8 _ )11110' MOUNTING
addressing mechanisms, such as program jumpers, 7 _ HOLES FOR
DIP switches or rotary dials, because the Programmer / � S'vVITCHPLATE
Tester electronically sets the TRI interface's address � __
into the interface's microcomputer chip nonvolatile
memory. Vibration, corrosion and other conditions that . 4, /L
deteriorate mechanical addressing mechanisms are no /
longer a cause for concern.
MOUNTING SLOTS
The TRI Series is fitted with screw terminals for FOR DOUBLEGANG
connection to an addressable circuit. SWITCHBOX
The TRI Series is fully compatible on the same MXL Figure A
circuit with all intelligent FF IL and ID-60 Series Mounting the TRI- S / -R / -D
detectors, MSI Series addressable manual stations
or any other addressable intelligent modules, such ft
as the CZM or ICP. Electrical Ratings
All TRI Series intelligent interface modules are Current Draw (Active or Standby): 1.5mA
UL listed.
Environmental operating conditions for all TRI Series TRI -R Relay Ratings
modules are 32 °F ( °C) to 120 °F (49 °C) with a relative Resistive: 4A, 125 VAC
humidity of not greater than 93% non - condensating. 4A, 30 VDC •
Inductive: 3.5A, 120 VAC (0.6P.F.)
Ordering Information 3.0A, 30 VDC (0.6PF.)
2.0A, 120 VAC (0.4P..F.)
Slapping Wt. 2.0A, 120 VAC (0.35P.F.)
Model Description Lb. Kg.
TRI -S Single Input 7az 2 2.0A, 30 VDC (0.35P.F.)
TRI -R Single Input w /Relay 7 oz. 2
TRI -D Dual Input 7 oz. 2
1 )•
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 7/03 Brampton, Ontario
Siemens Building Technologies Tel: (973) 593 -2600 5M Canada L6T 5E4
FAX: (973) 593 -6670 SFS-IG Tel: (905) 799 -9937 July • .03
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 -9858 S°ersede7- .. dated SRO