Specifications „) October 29, 2003 '' 1” `\ Oregon Electric Group CITY OF TIGARD 1010 SW SE 11 Avenue Portland, OR 97214 OREGON • RE: PROVIDENCE HEALTH SYSTEMS FIRE ALARM SYSTEM @ MAIL ROOM Project Information Building Permit: BUP2003 -00617 Construction Type: NA Tenant Name: Providence Occupancy Type: B Address: 11308 SW 68 Parkway Occupant Load: NA Area: NA Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. General requirements 1. A key box shall be installed within 20 feet of the main entrance. The bottom of the key box shall be not less than 8 feet nor more than 10 feet above the walking surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 An existing key box at the main building entrance is acceptable. 2. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the Fire Chief All functions of the system or alteration shall be tested. 1007.3.4.1 TVFR99 -01 3. The permittee shall provide written certification to the Fire Chief that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. 1007.3.4.2 TVFR99 -01. 4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL. Standard 10 -2, Section 1- 5.2.8.2, T'VFR99 -01 5. Manual Fire Alarm activation devices shall be mounted in the following reach ranges: • Forward Reach -15 inches to 48 inches above the floor. 1109.2.3.5 OSSC • Side Reach — 9 inches to 54 inches above the floor. 1109.2.3.6 OSSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684-2772 Visuals (Section 1109.14 OSSC) 1. Visual signal appliances shall be provided in the building in each of the following areas: • Restrooms and any other general use area (e.g., meeting rooms) • Hallways • Lobbies • Common use areas. 2. Visual alarms shall be located not less than 80 inches and not more than 96 inches above the floor level. When a low ceiling exists, the visual alarm shall be mounted at least 6 inches below the ceiling. 3. Visual alarms shall have a minimum candela rating of 75 candelas. 4. No place in a room shall be more than 50 feet from a visual signal 5. No place in a common corridors or hallways shall be more than 50 feet from a visual signal 6. In large rooms exceeding 100 feet across and without obstructions 6 feet or more above the floor, devices may be placed around the perimeter spaced at a maximum of 100 feet apart. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or mad fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfull : �l �C� Senior Plans Examiner PROVIDENCE TIGARD DATA CENTER SUITE 170 11308 SW 68 PARKWAY TIGARD, OR. 97223 FIRE ALARM SYSTEM SUBMITTAL CONTENTS ITEM DESCRIPTION 1. Siemens PAD 3 NAC POWER SUPPLY 2. Siemens U -MCS STROBE 3. Siemens U -MHU SERIES HORN /STROBE 4. Siemens TRI -R MODULE RECEIV 5. OCI 16 2003 GI TY OF TIGAKv LOiNG OWiSION SUBMITTED BY I.S.G /OREGON ELECTRIC 5000 N.E. COLUMBIA BLVD. PORTLAND, OR. 97218 503 -535 -2800 BIII SIEMENS Fire Safety PAD 3 Auxiliary Power Supply - Notification Appliance Extender ENGINEER AND ARCHITECT SPECIFICATIONS • 6 amps of Notification Appliance Power • Advanced Microprocessor Control • 24VDC Output Voltage • Four Power - Limited Notification Outputs f, • Strobe Synchronization Option Built In • Synchronized ANSI Temporal Pattern • Class A Selectable • Ground Fault Detection , • Battery Supervision • 3 Amp Auxiliary Power Output • Trouble Contact for Monitoring • Multiple Module Mounting in System 3 Enclosures ;, • Multiple Modules Share Battery Set PAD-3 • 0 UL, ULC Listed, CSFM, NYMEA and FM Approved Introduction The Model PAD -3 (PAD -3C for Canada) is a notification The PAD -3 also offers a 3 amp auxiliary output for driving appliance circuit expander with a built -in auxiliary other portions of your fire alarm system such as door power output. It is designed for use with Siemens holders. This 24 VDC filtered output is power limited. BuildingTechnologies, Fire Safety Division fire alarm When using this output, the total power available from control panels.This power source is designed to provide the PAD -3 will not exceed 6 amps. the extra power required in buildings conforming to the Americans with Disabilities Act. A trouble contact is provided for monitoring the PAD-3 with a fire alarm panel through the input. It also has a Form C dry contact for trouble monitoring. Therefore, Features the user has the option of connecting it to a conven- The PAD-3 provides 6 amps of 24 VDC power for tional fire alarm panel's existing notification circuit, or multiple uses. All 6 amps can be directed to 4 Notifs- controlling it with a TRI Series device on intelligent fire cation Appliance Circuits (NAC s). Each is rated at 3 systems. amps and is power limited. Either 1 or 2 inputs can The PAD -3 offers battery supervision and management control the four outputs. These outputs are compatible as is required of fire alarm system components. with all Fire Safety 24VDC notification appliances. Ground faults are transmitted as are any other trouble The PAD-3 can be configured so that the inputs can be conditions. Trouble conditions not only change the programmed as steady outputs, ANSI temporal state of the trouble contact in the unit, but they also outputs, or synchronized strobe outputs. It can also break the notification circuit input to create a trouble be programmed so that one input will silence U -MHU- signal in the fire alarm control unit. Series horn /strobe horns while the strobes remain on using one set of wires. CATALOG NUMBER 3362 This product is packaged in its own sheet metal enclosure Electrical Specifications with enough space to house the 7 amp -hour battery set required for back -up. The enclosure comes in black or red. AC Input: 120 VAC @ 2.5 amps , System 3 enclosures may also be used to house multiple Output: 24VDC @ 6 amps PAD -3 modules in a single enclosure. Two modules are Auxiliary Power Circuit: 1 capable of sharing the same battery set when mounted in the same enclosure. Notification Circuits: 4 Output Configuration: 2 Class A or 4 Class B or Options 1 Class A & 2 Class B • One or both PAD -3 signal inputs control the notification Amps per Output outputs, depending on the specific configuration setup. Circuit: 3.0 Possible configurations for the PAD-3 are: Notification Circuit For These Control These Outputs: 24 VDC at 3.0 amps each, Option: Inputs: Outputs: As: 24K ohm EOL resistor required on each Class 1 Input 1 All Outputs Class B Circuits B circuit 2 Input 1 All Outputs Class B Circuits No. of Inputs: 2 Input 2• Silences horns on 1 Input Configuration: 2 Class B or 2 Class A 3 input 1 Outputs 1 and 2 Class B Circuits Input Voltage Range: 9 32 VDC Input 2 Outputs 3 and 4 Class B Circuits 4 Input 1 Output 1 Class 8 Circuits Battery Charging Input 2 Outputs Z3 and 4 Class 8 Crcults Capacity: 15.0 A. H 5 Input 1 Outputs 1 -2, 3 and 4 Class Circuit Pairs Trouble contact rating: 2.5A @250 VAC, 30 VDC 6 input 1 Outputs 1 -2, 3 and 4 Class Circuit Pairs Ambient Temperature: 32 °F to 120 °F Input 2• Silences horns on 1 7 Inputs Outputs1 and2 Class A Circuit Pairs Mechanical Specifications input Outputs 3 and 4 Class A Circuit Pairs Single Module Enclosure Model EN - PAD 8 Input 1 Outputs 1 -2 Class A Circuit Pairs Dimensions: 12"W x 16 "H x 3"D Input 2 Outputs 3 and 4 Class 8 Circuits • Color: Black *When used with U -MHU- Series horn/strobe units Indicator Lights Supervision AC Power On: Green The Model PAD-3 supervises a variety of functions BatteryTrouble: Yellow including: Ground Fault: Yellow • • Low AC power AuxiliaryTrouble: Yellow Output 1 Trouble: Yellow • Low battery condition Output 2Trouble: Yellow • Earth ground fault • Auxiliary output power limit condition Ordering Information • EOL supervision trouble or power limited condition Part at an output Model Description Number When a trouble condition occurs, the PAD-3 creates a PAD - Aux power supply w/black enclosure 599 trouble condition on the fire control signal circuits to PAD - Aux. power supply wired enclosure 599 - 699190 which it is connected. It still maintains the ability to be PAO - Aux. power supply - main board only 500 - 699080 activated by the fire control. In addition, the PAD -3 EN - PAD Black enclosure for PAD 310 provides a Form 'C' trouble relay output as an alterna - pADR Red enclosure for PAD - 310 -0150 tive to using the notification circuit trouble. Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park. NJ 07932 9/03 Brampton, Ontario Siemens Building Technologies Tel: 1973) 593 -2600 torn Canada L6T 5E4 FAX: (973) 59 66 70 SFS4G Tel: (905) 799 -9937 September 2003 Fire Safety Website: www.siemens.com/fis Printed in U.S A. FAX: (905) 799-9858 suoeneaes abet dated 6ro3 SIEMENS Fire Safety Adapter Stand Alone Selectable Strobe ENGINEER AND ARCHITECT SPECIFICATIONS AGENT RELEASE • The Adapter" feature offers four field selectable candela strobe values - 15/75, 30/75, 75 or 110 for ceiling and wall mount — • Operates in either sync or non -sync mode z 1 • Low current draw • Integral universal mounting - single gang, GENT RELEASE double gang or4" square box Agent Release Strobe • Colors- red or off-white • ADA/NFPA/ANSI compliant , ti • cL UL 1971 listed for both wall and ceiling mount -CSFM and ULC Listed s • Made in U.S.A., ISO 9001 certified E • • A Dual Sync Control Module or PAD -3 is onl , Y Y required to activate the Instant Sync feature, nothing to set or change at the strobe unit , s Adapter Strobe Adapter Strobe Bell Plate Description The U -MCS series and U- MCS- 6090V, U- MCS- 6090V -W . The U- MCS- 6090V, U- MCS- 6090V -W provides the same strobes combine state of the art electronics to provide strobe choices and is constructed of metal for mounting reliability and low current draw to meet visual life safety bell or chime devices to the plate. applications.TheRdapter feature offers four field select The U -MCS Series & U- MCS- 6090V, U- MCS- 6090V -W able candela settings - 15/75, 30/75, 75 or 110. use a Xenon flashtube with solid state circuitry for maximum reliability and efficiency. Strobes have a ( s Detail - Adapter rounded dome shape made of clear polycarbonate. �� selector switch The U -MCS Series uses a terminal block for easy installa- tion and the U- MCS- 6090V, U- MCS- 6090V -W uses a The integral universal mounting plate of the U -MCS pigtail (4 wire) connection. provides for easy installation with single gang, double Strobe Synchronization requires the Dual Sync Module gang or 4" square box mounting.The lens construction or PAD -3. provides high candela output with low current consump- tion while meeting UL and ADA standards. CATALOG NUMBER 2550 Engineering Specifications The Series U- MCS- 6090V, U- MCS- 6090V -W Strobe Plate The visual notification appliances shall be Adapter U -MCS shall facilitate the addition of a strobe to a bell installation. Series or U- MCS- 6090V, U- MCS- 6090V -W field selectable The Strobe Plate shall mount to a 4 " square backbox for candela strobe appliance, or approved equal.They shall be flush mounting. listed to UL1971 (Standard for Safety Signaling Devices for Ordering Information the Hearing Impaired) for indoor applications, and shall be ADA/NFPA/ANSI compliant. Stand -Alone Strobes -Wall Mount and Ceiling Mount Model Part The strobe shall produce a flash rate of one (1) flash per Number Description - Neetber • second over the OperatingVoltage Range limits of 16 to U - MCS Multicandeia Selectable Strube Red 500499701 33Vdc.The strobe light shall consist of a Xenon flash tube U -MCS Multicandeia Selectable Strobe - White 500 699702 enclosed in a rugged, clear polycarbonate lens. Inputs , shall be compatible with standard reverse polarity circuit Retro -Plate Wall Mount supervision by an FACP.The Strobe shall be of low . current design, and shall provide a minimum of four (4) Model P field selectable strobe intensity settings, 15/75, 30/75, 75 Number Description Number and 110 candela. All settings shall be UL 1971 listed for U- MCS - 6090V Retie Piste 500. 839703 kilulticandeia Selectable Strobe Haa both wall and ceiling mount applications.The selector U•MCS 6090W1 Retro Plata 500-699704 switch shall be tamper-resistant. _ Multicandela Selectable Strobe- Red _ It shall not be necessary to remove the strobe from the mounting surface to select the strobe intensity. When Stand -Alone Strobes -Wall Mount and synchronization is required, the strobe shall be compat- Ceiling Mount - forAgent Release ible with the Dual Sync Module, or other source of Model Part Siemens Building Technologies, Fire Safety Division Sync Number Description Number Protocol, and shall not drift out of synchronization. U•MCS -AR Molticandela Selectable Strobe - Red 500- 699746 forAgent Release The U -MCS Series Stand -Alone Strobe shall have an integral universal mounting plate that shall allow mount- ing to single- gang, two-gang, and 4" square backboxes, Canadian Ordering Information as well as FBX -S and FBX -F Surface Boxes. A cover trim plate shall be included to enhance appearance.There shall Stand -Alone Strobes -Wall Mount and Ceiling Mount be no mounting holes or screw heads visible. Model pan Number Description Number U -MCS Specifications CU -MCS Multicandela Selectable Strube- Red 500- 699701C CU•MCS -W Multicandela Selectable Strobe - White _ Environmental 32 °F to 120 °F (0 °C to 49 °C) at 85% RH Retro-Plate Wall Mount InputVoltage Model Pan 16 - 33Vdc regulated or FWR Number Description Number • Mounting CU- MCS -6090V Retro Plate 500-699703C Integral universal mounting plate mounts to single Mutt :candela Selectable Strobe- Red gang, double gang or 4" square box. CU- MCS- 609OVW Retro P13te 500.6997040 Shipping Weight , _ Multicandele Selectable Strobe- Red 9 oz. approx. Stand -Alone Strobes -Wall Mount and Ceiling Mount - forAgent Release U -MCS Dimensions Model P (( 4e r 3-1/2" Number Description Number J r 3• E CU- MCS -AR Multicandela Selectable Strube - Red 500.6997460 • i For Agent Release FIRE Strobe Intensity Setting strobe Current Draw 7 \ 15/75 cd 63 mA Hil 4 -518' �_'£ 30!75 cd 84 mA R:: " ?' : : :� D 75 cd 143 mA L FIRE - -- -- -- Selector 110 cd 178 mA Switch Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 8/03 Brampton, Ontario • Siemens Building Technologies Tel: (973) 593 -2600 5v1 Canada ! 6T 5E4 g FAX: (973) 593 -6670 SFS-IG Tel: (905) 799.9937 August 2003 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 - 9858 swe¢edes sneer dated 3103 SIEMENS Fire Safety U -MHU Series Models U -MHU Electronic Sync /Non -Sync Horn ENGINEER AND ARCHITECT SPECIFICATIONS • The AdapterTM /U - MCS feature offers four field selectable n ca del values— — 1 a alp es 5175 30/7 75 or 5 50 110 for wall & ceiling mount • Sync strobes and sync temporal horns, with horn silence on 2 wires ! <{ f • Distinctive temporal horn • Internally I adjustable volume ntr I e control 1 o • Low current draw • Single gang and universal mount configurations • UL 1971 & UL 464 listed - CSFM, ULC, & N (MEA • {. • UL 1971 listed for both wall and ceiling mount ,! • ADA/NFPA/ANSI compliant #' • . :: It • Screw terminals accept 12 awg wiref: yy • Synchronization requires Dual Sync Control _ Module or PAD -3 • Made in U.S.A., ISO 9001 quality crafted Description „,,, Detail - Adapter The U -MHU -1 G, U- MHU -1 G-W and U -MHU, U -MHU -W = selector switch SC Sync Electronic Horns and U -MHU -MCS, U- MHU -MCS -W Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA nous temporal tone signals on one pair of wires or output levels. temporal or steady tone in a non -sync mode. The U -MHU -1 G, U -MHU -1 G-W mounts to a single gang box, the U -MHU, U -MHU -W and U- MHU -MCS, i 1 U- MHU -MCS -W have a universal mounting plate for K2..A ax. Valium 1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust Siemens Fire Safety notification appliances are (factory set at max. volume) designed with the installer in mind.They are constructed The U- MHU -MCS, U -MHU -MCS -W strobe construction with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for This design eliminates possible ground faults from maximum reliability and efficiency.The strobe has a • crowded electrical boxes.The Adapter!U -MCS feature rounded dome shape made of clear polycarbonate. offers four field selectable candela settings - 15/75, 30/75, 75 or 110. CATALOG NUMBER 2560 Replaces Catalog Sheet Number 2555 The U -MHU -1 G, U -MHU -1 G-W, U -MHU, U -MHU -W and Listed operating range is 20 to 31 VDC /FWR U-MHU-MCS, U- MHU -MCS -W are used on circuits with Temporal maximum UL measurements are 83.6 db at steady power or a Dual Sync Control Module or PAD -3. 24VDC /FWR. Steady tone maximum UL measurements Not for use on coded circuits. are 87.8 db at 24 VDC /FWR taken in free air at 360° around the device and averaged. Typical readings are Environmental frontal sound readings taken with a dB meter with signal 32 °F to 120 °F (0 °C to 49 °C) with 85% humidity mounted on wall. Rated for indoor use 32 °F to 120 °F, (0 °C to 49 °C), at RH 85 %. Operating Voltage Range Limits (-C: Ceiling Mounted) Horn: 20-31 Vdc orVFWR ( White) Strobe: 16- 33VdcorVFWR strobe Intensity Setting ,Strohe Current Draw 15/15 cd 63 mA Typical Hom Ratings at 10 Feet* 30/75 cd 84 mA Temporal Horn - 75 `d 143 "'A 110 cd 178 mA Maximum: 95 db @ 25 mA Minimum: 90 db @ 17 mA Control Module Specifications., * Typical dBA ratings are frontal sound readings Maximum Current Output: 3 Amps Max. not taken with a dB meter with signal mounted on wall. to exceed NAC rating DSC Module OperatingVoltage: 20 to 31 Vdc orVFW Dimensions DSC Module Operating Current: Non - Silenceable 2oic - --1 : taw. 4.3/4` . •_ -: - 1.y4' Circuit side "'' v - - - ' - ''t 55mA, Silenceable Circuit side .005 Amps. 4 - ® . a . rf.1 Maximum Current Output: 3 Amps max. not to I exceed Circuit rating 1, 2 or 4 Square Mounting r 3:34' _.,,, :. , a..tx `1 � • ' FIRE .. ., : , s, J" or ` ;etacrtr''•; i . 8 ,� n or strum, - f , . w . Ordering Information For wiring diagram for U -MHU Series Horn /Strobes refer to Installation Instruction Sheet U -MHU Series HomWall Mount Lew Volume High Volume Nigh Volume Model Number Description Pert Number Horn Current Nora Current dB Rating T10' U- MHU -1G ELC Sync/Non -Sync Hein 24VDC 500- 59959' 17ma 25(1a as db 15- MHU•16 -W ELC Syrc/Noa -Syrtc Horn 24 VDC 500- &99592 :17ma 25.'na :95 db U -MHU ' ELC Sync/Nott -Sync Horn 7.4VDC 500. 699594 17rga 2Sfita 95 db U- MiUU -W fLC Sm;Nor. -Svoc Hprn 24 ‘/DC _ 500.6995!3 1 7ma 25••na .95 db LewVolunse Hieb Volume, Ilieb Volume Model Number Description Part Number Horn Current Horn Current dB Rating 610' U- MH11 -MCS ELC Sync/Non-Sync Horn wfSrroaa Ned) 500. 699587 lima 254na 95 dh U- 1 MICS -w _ ELC Sy!:c/Non -Sync Horn wfSttoae ;'Whitm) 5:10.699598 17na .25erna 95 4b *AII current measurements made at 24VDC Fire Satety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 12/02 Brampton, Ontario Siemens Building Technologies Tel: `973) 593 -2600 lam Canada FAX: (9731593 -6670 SFS-IG Tel: (905) 730 -X37 December2002 Fire Safety Website: www.sbt.siemens.corn'tis Printed in U.S.A. FAX: (9051799-9858 s, we , ;•uKs act SIEMENS Fire Safety TRI Series Intelligent Initiating Devices Interface Modules for MXL Fire Detection Panels TRI - S,TRI - D,TRI -R ENGINEER AND ARCHITECT SPECIFICATIONS • Interfaces and Supervises Normally Open Contacts • • Integral SPDT Relay (up to 4 amps) onTRI -R Model • Input . ...... ..........:.. ... . Dual on TRI -D Model • l M i ut r ' Multi-color L.E.D. .E D. ndi L cafes t s atus re n 9 e amber, red) • Easy front access to programming port and • wiring terminals •.. • Mounts in 4 inch square 21/4 deep box, or double < gang box pp • Dynamic Supervision • Comes with 5x5 inch faceplate � AC 4het? ' • • Two wire operation a e gat • Model DPU or FPI -32 Programs and Verifies ... _ ... Device's Address and Tests Device's functionality • Electronic Address Programming is Easy • :; f and Dependable • UL Listed, L sled, ULC Listed • CFSM, FM, NYMEA Approved Introduction module reports the contact's status to the control The TRI Series Intelligent interface modules are panel. The TRI -S model can only monitor and report the designed to provide the means of interfacing direct status of the contact, while the TRI -R incorporates an shorting devices to the MXL system's ALD loop addressable Form C relay. The TRI -R relay and contact circuit. device input are controlled at the same address. For the MXL system, the relay and input contact can be The TRI Series Intelligent interface modules provide controlled as a separate function. The relay is typically the market's most advanced method of address used where control or shunting of external equipment programming and supervision, combined with sophis- is required. ticated control panel communication. Each TRI Series interface module incorporates a microcomputer chip. The TRI -D is a dual input module and is designed to The TRI Series microcomputer chip technology and its supervise and monitor two sets of dry contacts. This sophisticated bi- directional communication capabilities interface module requires two address settings. The with the control panel, achieve the state of an "Intelli- TRI -D is ideal for monitoring a waterflow switch and its gent Device" respective valve tamper switch. The TRI has a multi -color Light Emitting Diode that Description flashes green when operating normally, amber if unit The TRI Series Intelligent interface modules are avail- able in three models. The TRI -S and TRI -R are designed to monitor a normally open dry contact. The interface CATALOG NUMBER 6179 is in trouble condition, and red to indicate a change of Mounting Data state. TheTRI -D flashes twice, once for each address, Addressable interface Model TRI S, TRI D, TRI -R • the TRI -R red L.E.D. indicates a change of state in i the relay. mounts directly into a 4 inch square 21/4 deep box or a double gang box (user supplied). A 5 inch square The device's microcomputer chip has the capacity of off -white faceplate is included with each TRI. storing, in memory, identification information as well as important operating status information. MOUNTING SLOTS Siemens Building Technologies, Fire Safety Division FOR 4 INCH SWITCH90X • innovative technology allows all TRI Series intelligent interface modules to be programmed by using the model DPU or FPI -32 Programmer/Tester. The Pro- O - ■ grammer/Tester is a compact, portable, menu driven accessory that makes programming and testing an [ 1 1 TRI interface device faster, easier and more dependable ��; ): `I MODULE than previous methods. I[l a� Q VI: T 00' he DPU or FPI -32 eliminates the need for mechanical e J.-- M OUNTING addressing mechanisms, such as program jumpers, s - 1 HOLES FOR DIP switches or rotary dials, because the Programmer / A S'JVITCHPLATE Tester electronically sets the TRI interface's address into the interface's microcomputer chip nonvolatile 0 . memory. Vibration, corrosion and other conditions that deteriorate mechanical addressing mechanisms are no longer a cause for concern. MOUNTING SLOTS The TRI Series is fitted with screw terminals for FOR COUBLEGANG connection to an addressable circuit. . SWITCHBOX The TRI Series is fully compatible on the same MXL Figure A circuit with all intelligent FF IL and ID-60 Series Mounting the TRI S / - / - detectors, MSI Series addressable manual stations or any other addressable intelligent modules, such as the CZM or ICP - Electrical Ratings All TRI Series intelligent interface modules are Current Draw (Active or Standby): 1.5mA UL listed. Environmental operating conditions for all TRI Series TRI -R Relay Ratings modules are 32 °F ( °C) to 120 °F (49 °C) with a relative Resistive: 4A, 125 VAC humidity of not greater than 93% non - condensating. 4A, 30 VDC Inductive: 3.5A, 120 VAC (0.6P.F.) Ordering Information 3.0A, 30 VDC (0.6P.F.) 2.0A, 120 VAC (0.4P.F.) Shippieg Wt. 2.0A, 120 VAC (0.35P.F.) Model Description Lb. Kg. 2.0A, 30 VDC (0.35P.F.) TRI -S Single Input 7 az 2 TRI -R Single Input w /Relay 7 oz. 2 TRI•D Dual Input 7 oz. 2 I Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 7/03 Brampton, Ontario Siemens Building Technologies Tel: 1973) 593 -2600 5M Canada L6T 5E4 FAX: (973) 593 -6670 SFS-IG Tel: (905) 799 -9937 July 2003 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799-9858 swm.e0sssivaidiro ucr3 SIEMENS Fire Safety PAD 3 Auxiliary Power Supply - Notification Appliance Extender ENGINEER AND ARCHITECT SPECIFICATIONS • 6 amps of Notification Appliance Power • • • Advanced Microprocessor Control • 24 VDC Output Voltage 9 ...... yf • Four Power - Limited Notification Outputs • Strobe Synchronization Option Built In • Synchronized ANSI Temporal Pattern • Class A Selectable • • Ground Fault Detection : , • • Battery Supervision • 3 Amp Auxiliary Power Output • Trouble Contact for Monitoring • Multiple Module Mounting in System 3 Enclosures { € • Multiple Modules Share Battery Set PAD • 0 UL, ULC Listed, CSFM, NYMEA and FM Approved Introduction The Model PAD -3 (PAD -3C for Canada) is a notification The PAD -3 also offers a 3 amp auxiliary output for driving appliance circuit expander with a built -in auxiliary other portions of your fire alarm system such as door power output. It is designed for use with Siemens holders.This 24VDC filtered output is power limited. Building Technologies, Fire Safety Division fire alarm When using this output, the total power available from control panels.This power source is designed to provide the PAD -3 will not exceed 6 amps. the extra power required in buildings conforming to the Americans with Disabilities Act. A trouble contact is provided for monitoring the PAD-3 with a fire alarm panel through the input. It also has a Form C dry contact for trouble monitoring. Therefore, Features the user has the option of connecting it to a conven- The PAD-3 provides 6 amps of 24 VDC power for tional fire alarm panel's existing notification circuit, or multiple uses. All 6 amps can be directed to 4 Notifi- controlling it with aTRI Series device on intelligent fire cation Appliance Circuits (NAC s). Each is rated at 3 systems. amps and is power limited. Either 1 or 2 inputs can The PAD -3 offers battery supervision and management control the four outputs. These outputs are compatible as is required of fire alarm system components. with all Fire Safety 24VDC notification appliances. Ground faults are transmitted as are any other trouble The PAD-3 can be configured so that the inputs can be conditions. Trouble conditions not only change the programmed as steady outputs, ANSI temporal state of the trouble contact in the unit, but they also outputs, or synchronized strobe outputs. It can also break the notification circuit input to create a trouble be programmed so that one input will silence U -MHU signal in the fire alarm control unit. Series horn /strobe horns while the strobes remain on using one set of wires. CATALOG NUMBER 3362 This product is packaged in its own sheet metal enclosure Electrical Specifications with enough space to house the 7 amp -hour battery set required for back - up.The enclosure comes in black or red. AC Input: 120 VAC @ 2.5 amps System 3 enclosures may also be used to house multiple Output: 24VDC @ 6 amps PAD -3 modules in a single enclosure. Two modules are Auxiliary Power Circuit: 1 capable of sharing the same battery set when mounted in the same enclosure. Notification Circuits: 4 Output Configuration: 2 Class A or 4 Class B or Options 1 Class A & 2 Class B . One or both PAD -3 signal inputs control the notification Amps per Output outputs, depending on the specific configuration setup. Circuit: 3.0 Possible configurations for the PAD-3 are: Notification Circuit For These Control These Outputs: 24 VDC at 3.0 amps each, Option: Inputs: Outputs: As: 24K ohm EOL resistor required on each Class 1 input 1 All Outputs .. Class 8 Circuits B circuit • 2 Input 1 All Outputs Class B Circuits No. of Inputs: 2 Input 2* Silences hums on 1 Input Configuration: 2 Class B or 2 Class A 3 Input 1 Outputs 1 and 2 Class B Circuits Input Voltage Range: 9 32 VDC Input 2 Outputs 3 and 4 Class 8 Circuits 4 input 1 Output 1 Class 8 Circuits Battery Charging Input2 Outputs2,3and4 Class B Circuits Capacity: 15.0A.H 5 Input 1 Outputs 1-2.3 and 4 Class A Circuit Pairs Trouble contact rating: 2.5A @250 VAC, 30 VDC 6 Inputl Outputs 1-Z 3 and 4 ClassACircuitPairs Ambient Temperature: 32 °F to 120 °F Input 2* Silences horns on 1 7 input1 . Outputs1 and2 Class A Circuit Pairs Mechanical Specifications Input Outputs ClassACucuitPairs Single Module Enclosure Model EN - PAD 8 Input 1 Outputs 1.2 Class A Circuit Pairs Dimensions: 12"W x 16 "H x 3"D Input 2 Outputs 3 and 0 Class B Circuits Color: Black When used with U -MHU- Series horn/strobe units Indicator Lights Supervision AC Power On: Green The Model PAD-3 supervises a variety of functions BatteryTrouble: Yellow including: Ground Fault: Yellow • • Low AC power AuxiliaryTrouble: Yellow Output 1 Trouble: Yellow • Low battery condition Output 2Trouble: Yellow • Earth ground fault • Auxiliary output power limit condition Ordering Information • EOL supervision trouble or power limited condition Para at an output Model Description Number When a trouble,condition occurs, the PAD-3 creates a PAD Aux power supply w/black enclosure 599 499189 trouble condition on the fire control signal circuits to PAD - Aux power supplywired enclosure 599 - 699190 which it is connected. it still maintains the ability to be PAD - Aux power supply - main board only 500 - 699080 activated by the fire control. In addition, the PAD -3 EN - PAD Black enclosure for PAD-3 31073 provides a Form 'C' trouble relay output as an alterna - pADR Red enclosure for PAD 310 tive to using the notification circuit trouble. Fire Safety, Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 9/03 Brampton, Ontario . Siemens Building Technologies Tel 593 2600 10M Canada L6T 5E4 g Thl FAX: (973) (973) 59 SFS-IG Tel: (905) 799 -9937 September2003 Fire Safety Website: www.siemens.com/fis Printed in U.SA. FAX: (905) 799 -9858 Supersedes sheet dated 6/033 SIEMENS Fire Safety Adapter Stand Alone Selectable Strobe • ENGINEER AND ARCHITECT SPECIFICATIONS AGENT RELEASE • The Adapter" feature offers four field selectable candela strobe values — 15/75, 30/75, 75 or 110 for ceiling and wall mount • Operates in either sync or non -sync mode • • Low current draw • Integral universal mounting - single gang, AGENT REEA double gang or 4" square box Agent Release Strobe • Colors- red or off -white • ADA/NFPA/ANSI compliant • UL 1971 listed for both wall and ceiling �� mount -CSFM and ULC Listed t` r, • • Made in U.S.A., ISO 9001 certified L , • A Dual Sync Control Module or PAD -3 is only required to activate the Instant Sync feature, nothing to set or change at the strobe unit Adapter Strobe Adapter Strobe Bell Plate Description The U -MCS series and U- MCS- 6090V, U- MCS- 6090V -W The U- MCS- 6090V, U- MCS- 6090V -W provides the same strobes combine state of the art electronics to provide strobe choices and is constructed of metal for mounting reliability and low current draw to meet visual life safety bell or chime devices to the plate. applications.The Adapter feature offers four field select- able candela settings 15/75, 30/75, 75 or 110. The U -MCS Series & U- MCS- 6090V, U- MCS -6090V W use a Xenon flashtube with solid state circuitry for maximum reliability and efficiency. Strobes have a s ' Detail - Adapter rounded dome shape made of clear polycarbonate. ''- selector switch The U -MCS Series uses a terminal block for easy installa- tion and the U- MCS- 6090V, U- MCS- 6090V -W uses a The integral universal mounting plate of the U -MCS pigtail (4 wire) connection. provides for easy installation with single gang, double Strobe Synchronization requires the Dual Sync Module gang or4" square box mounting.The lens construction or PAD -3. provides high candela output with low current consump- tion while meeting UL and ADA standards. CATALOG NUMBER 2550 Engineering Specifications The Series U- MCS- 6090V, U- MCS -6090V W Strobe Plate The visual notification appliances shall be Adapter U -MCS shall facilitate the addition of a strobe to a bell installation. Series or U- MCS- 6090V, U- MCS- 6090V -W field selectable The Strobe Plate shall mount to a 4" square backbox for candela strobe appliance, or approved equal.They shall be flush mounting. listed to UL1971 (Standard for Safety Signaling Devices for Ordering Information the Hearing Impaired) for indoor applications, and shall be g ADA/NFPA/ANSI compliant. Stand-Alone Mount and Ceiling Mount The strobe shall produce a flash rate of one (1) flash per Nn Modal Description Num ber second over the Operating Voltage Range limits of 16 to U - MCS Multicande9a Selectable Strube Red 500.859701 - 33Vdc.The strobe light shall consist of a Xenon flash tube U•MCS - e MA,ltican:le :a Selectable Strobe White 500 - 699702 enclosed in a rugged, clear polycarbonate lens. Inputs shall be compatible with standard reverse polarity circuit Retro -Plate Wall Mount supervision by an FACP.The Strobe shall be of low current design, and shall provide a minimum of four (4) Model Pen field selectable strobe intensity settings, 15/75, 30/75, 75 Number Description Number and 110 candela. All settings shall be UL 1971 listed for U•MCS - 6090V Retro Plste 500.699703 Multicendela SelectabiuSStrobe Red both wall and ceiling mount applications.The selector U - MCS•6090W1 Retro Plata 500.69970.4 switch shall be tamper - resistant. Multicandel/i Selectable Strobe Red It shall not be necessary to remove the strobe from the mounting surface to select the strobe intensity. When Stand -Alone Strobes -Wall Mount and synchronization is required, the strobe shall be compat- Ceiling Mount - for Agent Release ible with the Dual Sync Module, or other source of M odel Part Siemens Building Technologies, Fire Safety Division Sync Number Description Number Protocol, and shall not drift out of synchronization. U- MCS -AR Multicandela Selectable Strobe - Red 500- 699746 For Agent Release The U -MCS Series Stand -Alone Strobe shall have an integral universal mounting plate that shall allow mount- ing to single- gang, two-gang, and 4" square backboxes, Canadian Ordering Information as well as FBX -S and FBX -F Surface Boxes. A cover trim plate shall be included to enhance appearance.There shall Stand -Alone Strobes -Wall Mount and Ceiling Mount be no mounting holes or screw heads visible. Model Pan Number Description Number U-MCS Specifications CU-MCS Multicande9a Selectable Strube. Red 500- 6997040 Cil.MCS.W Multicande9a Selectahle Strobe- White 500.6997070 Environmental - . 32 °F to 120 °F (0 °C to 49 °C) at 85% RH Retro -Plate Wall Mount InputVoltage Model Part 16 - 33Vdc regulated or FWR Number Description Number - Mounting CU- MCS -6090V Retro Plate 500 - 6997030 Integral universal mounting plate mounts to single Melt :candela Seiectab'.e Strobe• Fed gang, double gang or 4" square box. CU•MCS•60911vW Retro Plate 500-699704C Shipping Weight _ Mutt:candela Seiectab a Strobe- Red 9 oz. approx. - Stand -Alone Strobes -Wall Mount and Ceiling Mount - for Agent Release U -MCS Dimensions Model - Part arm. - 312• Number Description Number E 3 I CU- MCS -AR Mulrcande)a Selectable Strube • Red 500- 899746C y t For Agent Release FIRE ♦` • Strobe IntRn4lty Setting $ trobe Current Draw r` "i'i ;: 15/75 cd 63 mA 4-518' Ant �: ';: D 30/75 cd 84 mA ��t i R:: "'` -..i D 75 cd 143 mA E FIRE ` ' - selector _ 110 cd 178 mA t~ Switch Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 8/03 Brampton, Ontario � Siemens Building Technologies Tel: (9731 593 -2600 5M Canada L6T 5E4 g FAX: (973) 593-6670 SFS-IG Tel: (905) 799 -9937 August 2003 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799-9858 swamies she., data 103 SIEMENS Fire Safety U -MHU Series Models U -MHU Electronic Sync /Non -Sync Horn ENGINEER AND ARCHITECT SPECIFICATIONS • The AdapterTM /U -MCS feature offers four field selectable n — ca dela values— 1 or 110 va � es 5/75 3 /7 75 0 0 5 5 for wall & ceiling mount "::f :$viii : :i : :r rw'•' is • Sync strobes and sync temporal horns, with horn Y P silence on 2 wires • Distinctive tem P oral horn • Internally t l v I adjustable ab volume control e ou eco t l 0 • Low current draw 1�. • Single gang and universal mount configurations • UL 1971 & UL 464 listed - CSFM, ULC, & NYMEA • UL 1971 listed for both wall and ceiling mount • ADA/NFPA/ANSI compliant • Screw terminals accept 12 awg wire % : : < ' : :< ;<;<y • Synchronization requires Dual Sync Control .._ Module o PAD -3 • • Made in U.S.A., ISO 9001 quality crafted Description Detail - Adapter The U-MHU-1G, U-MHU-1G-W and U -MHU, U -MHU -W � 15 8 selector switch Sync Electronic Horns and U- MHU -MCS, U- MHU -MCS -W Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA nous temporal tone signals on one pair of wires or output levels. temporal or steady tone in a non -sync mode. The U-MHU-1G, U-MHU-1G-W mounts to a single gang box, the U -MHU, U -MHU -W and U- MHU -MCS, ) U- MHU -MCS -W have a universal mounting plate for _ amax.vizurne 1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust Siemens Fire Safety notification appliances are (factory set at max. volume) designed with the installer in mind.They are constructed The U -MHU -MCS, U -MHU -MCS -W strobe construction with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for This design eliminates passible ground faults from maximum reliability and efficiency The strobe has a crowded electrical boxes.The Adapter!U -MCS feature rounded dome shape made of clear polycarbonate. offers four field selectable candela settings — 15/75, 30/75, 75 or 110. CATALOG NUMBER 2560 Replaces Catalog Sheet Number 2555 • The U -MHU -1 G, U -MHU -1 G-W, U -MHU, U -MHU -W and Listed operating range is 20 to 31 VDC /FWR U- MHU -MCS, U- MHU -MCS -W are used on circuits with Temporal maximum UL measurements are 83.6 db at steady Dower or a Dual Sync Control Module or PAD -3. 24VDC /FWR. Steady tone maximum UL measurements Not for use on coded circuits. are 87.8 db at 24 VDC /FWR taken in free air at 360° around the device and averaged. Typical readings are Environmental frontal sound readings taken with a dB meter with signal - 32 °F to 120 °F (0 °C to 49 °C) with 85% humidity mounted on wall. Rated for indoor use 32 °F to 120 °F, (0 °C to 49 °C), at RH 85 %. Operating Voltage Range Limits (C: Ceiling Mounted • Horn: 20-31 Vdc orVFWR (-W White) Strobe: 16-33 Vdc orVFWR $troha Intensity Setting Atroha Current Draw 15!75 cd 63 mA Typical Horn Ratings at 10 Feet* 30/75 cd 84 mA Temporal Horn - 75 cd 143 mA 110cd 178mA Maximum: 95 db @ 25 mA Minimum: 90 db @ 17 mA Control Module Specifications; * Typical dBA ratings are frontal sound readings Maximum Current Output: 3 Amps Max. not taken with a dB meter with signal mounted on wall. to exceed NAC rating DSC Module OperatingVoltage: 20 to 31 Vdc orVFW Dimensions DSC Module Operating Current: Non - Silenceable — 244" - y t -ar4' 1• 4324' -.i - •.t•ya Circuit side •' . 4,7 -- I I — -tez 55mA, Silenceable • --- .." • Circuit side .005 Amps. • 41.7 I M� r• a. P P Maximum Current Output: 3 Amps max. not to exceed Circuit rating 1, 2 or 4 Square Mounting ;, . F . ;:,. ( LJ: :ice. .ice :� ,/ • FIRE ty, .',�, • ...- ; "' • ' Or • 'iar+rrxx I --..:.• , '�� • or ' ,,i v . i .. For wiring diagram for U -MHU Series Horn /Strobes refer Ordering Information to Installation instruction Sheet U -MHU Series HornWall Mount Low Volume High Volume High Volume Model Member Description Part Number Horn Current Horn Current dB Rating 610' 1 .14.4HU -1G ELLSy-^-c/Nob- Syac Horn 24`DC 500- 599:59 - i7rra 25ma 9544 li- bARU -16 -W FLC Sync/Non-Sync Horn 2 500. 699592 :7ma 25me :95 dt, U -MHU FIX Sy><r. /Nor -Sync Horn 74 VJC 5:101699594 lima 2bmn 95 db 1J -11/4.11111-W EtC Sync /Non -S,nc Horn 24VDC 54'10- 699593 17ma fiord 95 db LOW Wyllie High Volume. HighVoleme Model Number Deseriptloo Part Number Horn Current Horn Current . dB Rating 4101' U- 6,114U-MCS .FU; Sync/Non-Sync Horn w%S1raba CRedi 500-699587 _ lima 25ma 95 db U- MHU -MCS -w ELC Sync/Non-Sync Horn w /St•obe )Witte) 510. 1;99588 17ma 7..5,-na 95 db *AII current measurements made at 24VDC Fire Satety Fire Safety 8 Fernwood Road 2 Kenv:ew Boulevard Florham Park, NJ 07932 12/02 Brampton, Ontario Siemens Building Technologies Tel: 1973) 593 -2600 1- l Canada L6T5E4 FAX:1973) 593.6670 SFS.IG el: 1905) 799-9937 December 2002 Fire Safety Website: www.sbt.siemer•s.com/tia Printed in L.S.A. FAX: 19051 799 - 9853 s„oerr 1. ,.w:„, ,;scar a2•z SIEMENS Fire Safety TRI Series Intelligent Initiating Devices Interface Modules for MXL Fire Detection Panels TRI - S,TRI - D,TRI -R ENGINEER AND ARCHITECT SPECIFICATIONS • Interfaces and Supervises Normally Open Contacts • Integral SPDT Relay (up to 4 amps) onTRI -R Model • Dual Input on TRI -D Model • Multi -color L.E.D. indicates status (green, amber, red) • Easy front access to programming port and wiring terminals min I s • Mounts in 4 inch square 21/4 deep box, or double gang box • Dynamic Supervision • • • Comes with 5x5 inch faceplate • ?Y* uu � u h "siA�ss,� • Two wire operation + 34. • Model DPU or FPI -32 Programs and Verifies Device's Address and Tests Device's functionality • Electronic Address Programming is Easy and Dependable • ID UL Listed, ULC Listed CFSM, FM, NYMEA Approved Introduction module reports the contact's status to the control The TRI Series Intelligent interface modules are panel. The TRI -S model can only monitor and report the designed to provide the means of interfacing direct status of the contact, while theTRl -R incorporates an shorting devices to the MXL system's ALD loop addressable Form C relay. The TRI -R relay and contact circuit. device input are controlled at the same address. For the MXL system, the relay and input contact can be The TRI Series Intelligent interface modules provide controlled as a separate function. The relay is typically the market's most advanced method of address used where control or shunting of external equipment programming and supervision, combined with sophis- is required. ticated control panel communication. Each TRI Series interface module incorporates a microcomputer chip. The TRI -D is a dual input module and is designed to The TRI Series microcomputer chip technology and its supervise and monitor two sets of dry contacts. This sophisticated bi- directional communication capabilities interface module requires two address settings. The with the control panel, achieve the state of an "Intelli TRI -D is ideal for monitoring a waterflow switch and its gent Device" respective valve tamper switch. The TRI has a multi -color Light Emitting Diode that Description flashes green when operating normally, amber if unit • The TRI Series Intelligent interface modules are avail- able in three models. The TRI -S and TRI -R are designed to monitor a normally open dry contact. The interface CATALOG NUMBER 6179 is in trouble condition, and red to indicate a change of Mounting Data state. TheTRI -D flashes twice, once for each address, Addressable interface Model TRI S, TRI D, TRI -R theTRl -R red L.E.D. indicates a change of state in mounts directly into a 4 inch square 2' /o deep box the relay. or a double gang box (user supplied). A 5 inch square The device's microcomputer chip has the capacity of off-white faceplate is included with each TRI. storing, in memory, identification information as well as important operating status information. MOUNTING SLOTS Siemens Building Technologies, Fire Safety Division FOR 4 :NCH SWITCH90X - innovative technology allows all TRI Series intelligent interface modules to be programmed by using the model DPU or FPI -32 Programmer/Tester. The Pro- O grammer/Tester is a compact, portable, menu driven accessory that makes programming and testing an [a7 I TRI S / - / - interface device faster, easier and more dependable 17 Plr;`I MODULE than previous methods. 4l ry� Q [ —1 The DPU or FPI -32 eliminates the need for mechanical 8 _ MOUNTING addressing mechanisms, such as program jumpers, �-�' 7 ._ HOLES FOR DIP switches or rotary dials, because the Programmer / SVvrrCHPLATE Tester electronically sets the TRI interface's address � into the interface's microcomputer chip nonvolatile 0 memory. Vibration, corrosion and other conditions that deteriorate mechanical addressing mechanisms are no / longer a cause for concern. MOUNTING SLOTS The TRI Series is fitted with screw terminals for FOR COUBLEGANG connection to an addressable circuit. SWITCHBOX The TRI Series is fully compatible on the same MXL Figure A circuit with all intelligent FP IL and ID-60 Series Mounting the TRI- S / -R / -D detectors, MSI Series addressable manual stations or any other addressable intelligent modules, such Sri as the CZM or ICP. , Electrical Ratings All TRI Series intelligent interface modules are Current Draw (Active or Standby): 1.5mA UL listed. Environmental operating conditions for all TRI Series TRI-R Relay tive: 4AA, 1, 125s 25 VAC modules are 32 °F ( °C) to 120 °F (49 °C) with a relative humidity of not greater than 93% non - condensating. 4A, 30 VDC Inductive: 3.5A, 120 VAC (0.6P.F.) Ordering Information 3.0A, 30 VDC (0.6P.F.) 2.0A, 120 VAC (0.4P.F.) Shipping Wt. 2.OA, 120 VAC (0.35P.F.) Model Description Lb. Kg. 2.0A, 30 VDC (0.35P.F) TRI -S Single Input 7 az. 2 ' TRI -R Single Input w /Relay 7 oz 2 TRI -D Dual Input 7 oz 2 I Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 7/03 Brampton, Ontario Siemens Building Technologies Tel: (973) 593-2600 5M Canada I-6T 5E4 FAX: (973) 593 -6670 SFS -IG Tel: (905) 799 -9937 July 2003 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799-9858 syp3,3�33bgmtml,p0 SIEMENS Fire Safety PAD 3 Auxiliary Power Supply - Notification Appliance Extender ENGINEER AND ARCHITECT SPECIFICATIONS • 6 amps of Notification Appliance Power • Advanced Microprocessor Control • 24 VDC Output Voltage i. ' .2.2M • Four Power - Limited Notification Outputs ,, , • Strobe Synchronization Option Built In 4 ' • ' • Synchronized ANSI Temporal Pattern • Class A Selectable • Ground Fault Detection • Battery Supervision m • 3 Amp Auxiliary Power Output • Trouble Contact for Monitoring • Multiple Module Mounting in System 3 Enclosures • Multiple Modules Share Battery Set PAD-3 • 0 UL, ULC Listed, CSFM, NYMEA and FM Approved Introduction The Model PAD -3 (PAD -3C for Canada) is a notification The PAD -3 also offers a 3 amp auxiliary output for driving appliance circuit expander with a built -in auxiliary other portions of your fire alarm system such as door power output. It is designed for use with Siemens holders.This 24VDC filtered output is power limited. Building Technologies, Fire Safety Division fire alarm When using this output, the total power available from control panels.This power source is designed to provide the PAD -3 will not exceed 6 amps. the extra power required in buildings conforming to the Americans with Disabilities Act. A trouble contact is provided for monitoring the PAD-3 with a fire alarm panel through the input. It also has a Form C dry contact for trouble monitoring. Therefore, Features the user has the option of connecting it to a conven- The PAD-3 provides 6 amps of 24 VDC power for tional fire alarm panel's existing notification circuit, or multiple uses. All 6 amps can be directed to 4 Notifi- controlling it with a TRI Series device on intelligent fire cation Appliance Circuits (NAC s). Each is rated at 3 systems. amps and is power limited. Either 1 or 2 inputs can The PAD -3 offers battery supervision and management control the four outputs. These outputs are compatible as is required of fire alarm system components. with all Fire Safety 24VDC notification appliances. Ground faults are transmitted as are any other trouble The PAD -3 can be configured so that the inputs can be conditions. Trouble conditions not only change the programmed as steady outputs, ANSI temporal state of the trouble contact in the unit, but they also outputs, or synchronized strobe outputs. It can also break the notification circuit input to create a trouble be programmed so that one input will silence U -MHU- signal in the fire alarm control unit. Series horn /strobe horns while the strobes remain on using one set of wires. CATALOG NUMBER 3362 This product is packaged in its own sheet metal enclosure Electrical Specifications with enough space to house the 7 amp -hour battery set required for back - up.The enclosure comes in black or red. AC Input: 120 VAC @ 2.5 amps ' System 3 enclosures may also be used to house multiple Output: 24VDC @ 6 amps PAD -3 modules in a single enclosure. Two modules are Auxiliary Power Circuit: 1 capable of sharing the same battery set when mounted in the same enclosure. Notification Circuits: 4 Output Configuration: 2 Class A or 4 Class B or Options 1 Class A & 2 Class B . One or both PAD -3 signal inputs control the notification Amps per Output outputs, depending on the specific configuration setup. Circuit: 3.0 Possible configurations for the PAD-3 are: Notification Circuit For These Control These Outputs: 24VDC at 3.0 amps each, Option: Inputs: Outputs: As: 24K ohm EOL resistor required on each Class 1 Input 1 All Outputs, Class B Circuits B circuit 2 Input 1 All Outputs Class B Circuits No. of Inputs: 2 Input 2* Silences horns on 1 Input Configuration: 2 Class B or 2 Class A 3 Input 1 Outputs 1 and 2 Class B C'ir'cuits Input Voltage Range: 9-32 VDC Input 2 Outputs 3 and 4 Class B Circuits 4 Input 1 Output 1 Class B Circuits Battery Charging Input 2 Outputs 2,3 and 4 Class B Circuits Capacity: 15.0 A. H 5 Input 1 Outputs 1 -2, 3 and 4 Class Circuit Pairs Trouble contact rating: 2.5A @250 VAC, 30 VDC 6 Input l Outputs 1-2,3 and 4 Class Circuit Pairs Ambient Temperature: 32 °F to 120 °F lnput2' Silences horns on 1 7 Input 1 ' Outputs 1 and 2 Class Circuit Pairs Mechanical Specifications Input Outputs GessACircuitPairs Single Module Enclosure Model EN -PAD • 8 Input 1 Outputs 1.2 Class Circuit Pairs Dimensions: 12"W x 16 "H x 3"D Input 2 Outputs 3 and 4 Class B Circuits Color: Black *When used with U -MHU- Series horn/strobe units Indicator Lights Supervision AC Power On: Green The Model PAD -3 supervises a variety of functions BatteryTrouble: Yellow including: Ground Fault: Yellow • • Low AC power AuxiliaryTrouble: Yellow Output 1 Trouble: Yellow • Low battery condition Output 2Trouble: Yellow • Earth ground fault • Auxiliary output power limit condition Ordering Information • EOL supervision trouble or power limited condition Part at an output Model Description Number When a trouble condition occurs, the PAD-3 creates a PAD -3 Aux power supply wJblack enclosure 599 - 6`39189 trouble condition on the fire control signal circuits to PAO-3R Aux. power supply wired enclosure 599 - 699190 which it is connected. It still maintains the ability to be PAO Aux. power supply - main board only 500 activated by the fire control. In addition, the PAD - EN -PAD Black enclosure for PAD-3 310-099073 provides a Form 'C' trouble relay output as an alterna EN -PAOR Red enclosure for PAD-3 310 - 099150 tive to using the notification circuit trouble. • Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park. NJ 07932 9/03 Brampton, Ontario Siemens Building Technologies Tel: (973) 2600 tarn Canada L6T 5E4 FAX: (973) 66 70 SFS4G Tel: (905) 799 -9937 September 2003 Fire Safety Website: www.siemens.comlfis Printed in U.S.A. FAX )905) 799 -9858 Supersedes sheet dined rrm SIEMENS Fire Safety Adapter Stand Alone Selectable Strobe ENGINEER AND ARCHITECT SPECIFICATIONS ENT RELEASE .. !. • The Adapter" feature offers four field selectable candela strobe values - 15/75, 30/75, 75 or 110 for ceiling and wall mount " �� f . • Operates in either sync or non-sync mode s ` P Y Y • Low current draw • Integral universal mounting - single gang, AGENT RELEA double gang or 4" square box Agent Release Strobe • Colors- red or off -white • ADA/NFPA/ANSI compliant 44- A I • v UL 1971 listed for both wall and ceiling mount -CSFM and ULC Listed E F Made in A. certified s qk • • M 1 ad U S , ISO 9001 r >� • A Dual Sync Control Module or PAD -3 is only ! ., �� � required to activate the Instant Sync feature, nothing to set or change at the strobe unit Adapter Strobe Adapter Strobe Bell Plate Description The U -MCS series and U- MCS- 6090V, U- MCS- 6090V -W The U- MCS- 6090V, U- MCS- 6090V -W provides the same strobes combine state of the art electronics to provide strobe choices and is constructed of metal for mounting reliability and low current draw to meet visual life safety bell or chime devices to the plate. applications.The Adapter feature offers four field select- able candela settings 15/75, 30/75, 75 or 110. The U -MCS Series & U- MCS- 6090V, U- MCS- 6090V -W use a Xenon flashtube with solid state circuitry for maximum reliability and efficiency. Strobes have a Detail - Adapter rounded dome shape made of clear polycarbonate. (�� selector switch The U -MCS Series uses a terminal block for easy installa- tion and the U- MCS- 6090V, U- MCS- 6090V -W uses a The integral universal mounting plate of the U -MCS pigtail (4 wire) connection. provides for easy installation with single gang, double Strobe Synchronization requires the Dual Sync Module gang or 4" square box mounting.The lens construction or PAD -3. provides high candela output with low current consump- tion while meeting UL and ADA standards. CATALOG NUMBER 2550 Engineering Specifications The Series U- MCS- 6090V, U- MCS- 6090V -W Strobe Plate The visual notification appliances shall be Adapter U -MCS shall facilitate the addition of a strobe to a bell installation. , Series or U- MCS- 6090V, U- MCS- 6090V -W field selectable The Strobe Plate shall mount to a 4" square backbox for ' candela strobe appliance, or approved equal.They shall be flush mounting. listed to UL1971 (Standard for Safety Signaling Devices for Ordering Information the Hearing Impaired) for indoor applications, and shall be • ADA/NFPA/ANSI compliant. Stand - Alone Strobes -Wall Mount and Ceiling Mount Model Part The strobe shall produce a flash rate of one (1) flash per Number Description Number second over the Operating Voltage Range limits of 16 to U -MCS Multicende&a Selectable Strube Red 500. 899701 . 33Vdc.The strobe light shall consist of a Xenon flash tube U- MCS - Mrrlticandela Selectahle Strobe 500 - 699702 enclosed in a rugged, clear polycarbonate lens. Inputs shall be compatible with standard reverse polarity circuit Retro -Plate Wall Mount supervision by an FACP.The Strobe shall be of low - current design, and shall provide a minimum of four (4) Model Pen field selectable strobe intensity settings, 15/75, 30/75, 75 Number Description Number and 110 candela. All settings shall be UL 1971 listed for U- MCS - 6090V Retrc Plate 500. 699703 Multicandela Selectable Strobe Had both wall and ceiling mount applications.The selector U FRCS 6tl90VVY Retrc Plata 500 699)04 switch shall be tamper - resistant. _ Muiticandela Selectnh:r. Strobe - Red It shall not be necessary to remove the strobe from the mounting surface to select the strobe intensity. When Stand -Alone Strobes -Wall Mount and synchronization is required, the strobe shall be compat- Ceiling Mount - for Agent Release ible with the Dual Sync Module, or other source of Model Part Siemens Building Technologies, Fire Safety Division Sync Number Description Number Protocol, and shall not drift out of synchronization. U- MCS -AR Mu(ticandela Selectable Strobe - Red 500- 699746 for Agent Release The U -MCS Series Stand -Alone Strobe shall have an integral universal mounting plate that shall allow mount- ing to single- gang, two-gang, and 4" square backboxes, Canadian Ordering Information as well as FBX -S and FBX -F Surface Boxes. A cover trim plate shall be included to enhance appearance.There shall Stand -Alone Strobes -Wall Mount and Ceiling Mount be no mounting holes or screw heads visible. Model Pan Number Description Number U-MCS Specifications CU -MCS Municandela Selectable Strube- Red 500.699701C CU -MCS -W Mult(cendsta Selectable Strobe - Whits 500-6997070 Environmental • 32 °F to 120 °F (0 °C to 49 °C) at 85% RH Retro -Plate Wall Mount InputVoltage Modal - Part 16-33Vdc regulated or FWR • Humber Description Number Mounting CU Rego Plate 500-699703C Integral universal mounting plate mounts to single Mntticandela Selectable Strobe- Red gang, double gang or 4" square box. CU- MCS -6090 W Retro Mats 500.6997040 ShippingWeight Mutticandela Selectable Strobe - Red 9 oz. approx. Stand -Alone Strobes -Wall Mount and Ceiling Mount - for Agent Release U -MCS Dimensions Model - Part r 4-5/8" — - 3-1/2' i Number _ Description Number • 9 CU- MCS - AR Mu(ticande!e Selectable Strube - Red 500-6997460 i , - ` For Agent Release FIRE _____"..,1 Strobe Intensity Bettina strobe Current Draw 15/75 cd 63 mA 4- Sr8'�t 3 0775 cd 84 mA � I::: --- : : :� 75 cd 143 mA - 110 cd 178 mA t FIRE - septa - Switch Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 8/03 Brampton, Ontario I. Siemens Building Technologies Tel: (973) 593 -2600 Ss/1 1 Canada L6T 5E4 g IeS FAX: (973) 593 -6670 SFS;G Tel: (905) 799 -9937 August 2003 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S A. FAX: (905) 799-9858 Supe'ce°ee sneer axed 3103 SIEMENS Fire Safety U -MHU Series Models U -MHU Electronic Sync /Non -Sync Horn ENGINEER AND ARCHITECT SPECIFICATIONS • The Adapter /U -MCS feature offers four field I — selectable ble n i candela values— es 1 /7 a a � 5 5 30/7 75 or 1 5 50 1 0 for wall & ceiling g ount pis''' • Sync strobes and sync temporal horns, with horn Y F ..; ; silence on 7 wires • Distinctive temporal horn • r' I� rn�l t I e a adjustable volume v lu control be o eco t Y d 1 t a • Low current draw • Single gang and universal mount configurations • UL 1971 & UL 464 listed - CSFM, ULC, & NYMEA • UL 1971 listed for both wall and ceiling mount • ADA/NFPA/ANSI compliant • • Screw terminals accept 12 awg wire • Synchronization requires Dual Sync Control Module or PAD-3 odu e o PAD 3 • Made in U.S.A., ISO 9001 quality crafted Description Detail - Adapter The U -MHU -1 G, U -MHU -1 G-W and U -MHU, U -MHU -W C5).„„ selector switch Sync Electronic Horns and U -MHU -MCS, U- MHU -MCS -W Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA nous temporal tone signals on one pair of wires or output levels. temporal or steady tone in a non -sync mode. The U- MHU -1 G, U- MHU -1 G-W mounts to a single gang box, the U -MHU, U -MHU -W and U- MHU -MCS, t° U- MHU -MCS -W have a universal mounting plate for r--'4 Max. Vuiume 1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust Siemens Fire Safety notification appliances are (factory set at max. volume) designed with the installer in mind.They are constructed The U- MHU -MCS, U -MHU -MCS -W strobe construction with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for This design eliminates possible ground faults from maximum reliability and efficiency.The strobe has a crowded electrical boxes.The Adapter/U -MCS feature rounded dome shape made of dear polycarbonate. offers four field selectable candela settings - 15/75, 30/75, 75 or 110. CATALOG NUMBER 2560 Replaces Catalog Sheet Number 2565 The U -MHU -1 G, U -MHU -1 G-W, U -MHU, U -MHU -W and Listed operating range is 20 to 31 VDC /FWR • U -MHU -MCS, U- MHU -MCS -W are used on circuits with Temporal maximum UL measurements are 83.6 db at steady Dower or a Dual Sync Control Module or PAD-3. 24VDC /FWR. Steady tone maximum UL measurements Not for use on coded circuits. are 87.8 db at 24 VDC /FWR taken in free air at 360° around the device and averaged. Typical readin s are Environmental frontal sound readings taken with a dB meter w h signal 32 °F to 120 °F (0 °C to 49 °C) with 85% humidity mounted on wall. Rated for indoor use 32 °F to 1 0 °F, (0 °C to 49 °C), at RH 85 %. Operating Voltage Range Limits f C: Ceiling Mounted Horn: 20-31 Vdc orVFWR ( -W: White) Strobe: 16 -33Vdc orVFWR $trnhe Intansity Setting ,Strobe Current Draw 15(75 cd 63 mA Typical Hom Ratings at 10 Feet* 30/75 cd 84 mA Temporal Horn - 75 `d 143 mA 110cd 178mA Maximum: 95 db @ 25 mA Minimum: 90 db @ 17 mA Control Module Specifications; * Typical dBA ratings are frontal sound readings Maximum Current Output: 3 Amps Ma:. not taken with a dB meter with signal mounted on wall. to exceed NAC rating DSC Module OperatingVcltage: 20 to 31 Vdc orVFW Dimensions DSC Module Operating Current: Non - Silences ble -2. 4 "•- f 1 .34' 4.3:4' ; -- 1.34' Circuit side --v-- , '' i - -• - f. i -''� 55mA, Silen ;cable Circuit side A005 Amps. 4 - . ra a. ; : Maximum Current Output: 3 Amps mat . not to exceed CircL it rating 1, 2 or 4 Square Mounting ..4 •.r ^. . -. 4.3'a 0 '• '' 4J --"••• . I t 4 .... ".- I or For wiring diagram for U -MHU Series Horn /Strob ss refer Ordering Information to Installation Instruction Sheet U -MHU Series HomWall Mount Low Volume High Volume High Vela no Model Number Description Part Nuneher Horn Current Horn CiReut dB Rating O10' al- MHU -1G ELC SY• ^•c /Nof? -Syae Hem 24 VDC 500-699591 171ra 25ma •95 db II-MHO-16 ELC Sync/Nos -$y:ic Horn 24 VOC 500- 699592 t ima• 25:na 95 db U -MHU • RC Sync/Non -Sync Horn 74 VOC W- 699594 lira 25rna 95 db U•1litiii -W _ ELC Sync /Non -51; Ciip.rn24t10C 500. 699591 _ 17ma 2S,toa 95 rib LowVolunite High Valuate. High Vole rte Model Number Description Part Number Horn Current Hesn COReat _ d8 Rating C#10' U- M1 ELC Sync Non -Sync H,ra w/S +rota pled) 500- 699587 i7rna 2.5tna .95 db El- MKLI -MCS.W _ fl.0 Sync/Non-Sync Hcrn wi /Strobe;'u4 _ 530- ti99598 _ 17rn..a 2Stna 95 rib *AII current measurements made at 24VDC • Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 12/02 Brampton, Ontario Siemens Building Technologies el: 1973) 593 -2600 10M Canada L6T5E4 FAX: (973) 593.6670 SFS1G Tel: (905) 799 -9937 December 2002 Fire Safety Website: v vnv.sb .siemer•.s.com,fis Printed in U.S.A. FAX: (9051 7 99 -9859 s :pen :tW, y • drag.: EM2 SIEMENS Fire Safety TRI Series Intelligent Initiating Devices Interface Modules • for MXL Fire Detection Panels TRI - S,TRI - D,TRI -R ENGINEER AND ARCHITECT SPECIFICATIONS • Interfaces and Supervises Normally Open Contacts • Integral SPDT Relay (up to 4 amps) onTRI -R Model • Dual Input onTRI -D Model • • Multi -color L.E.D. indicates status (green, amber, red) • Easy front access to programming port and wiring n terminals s • Mounts in 4 inch square 21/4 deep box, or double gang box • D n is am Supervision Y • Comes with 5x5 inch faceplate 1 > • Two wire operation "i a: "�ft . , • Model DPU or FPI -32 Programs and Verifies ;; y Device's Address and Tests Device's functionality § ' "mss s s. • • Electronic Address Programming is Easy and Dependable • 43 UL Listed, ULC Listed CFSM, FM, NYMEA Approved Introduction module reports the contact's status to the control The TRI Series Intelligent interface modules are panel. The TRI -S model can only monitor and report the designed to provide the means of interfacing direct status of the contact, while the TRI -R incorporates an shorting devices to the MXL system's ALD loop addressable Form C relay. The TRI -R relay and contact circuit. device input are controlled at the same address. For the MXL system, the relay and input contact can be The TRI Series Intelligent interface modules provide controlled as a separate function. The relay is typically the market's most advanced method of address used where control or shunting of external equipment programming and supervision, combined with sophis- is required. ticated control panel communication. Each TRI Series interface module incorporates a microcomputer chip. The TRI D is a dual input module and is designed to The TRI Series microcomputer chip technology and its supervise and monitor two sets of dry contacts. This sophisticated bi- directional communication capabilities interface module requires two address settings. The with the control panel, achieve the state of an " lntelli TRI -D is ideal for monitoring a waterflow switch and its gent Device" respective valve tamper switch. The TRI has a multi -color Light Emitting Diode that Description flashes green when operating normally, amber if unit • The TRI Series Intelligent interface modules are avail- able in three models. The TRI -S and TRI -R are designed to monitor a normally open dry contact. The interface CATALOG NUMBER 6179 is in trouble condition, and red to indicate a change of Mounting Data state. TheTRI -D flashes twice, once for each address, Addressable interface Model TRI -S, TRI -D, TRI -R the TRI -R red L.E.D. indicates a change of state in mounts direct) into a 4 inch square 2'/4 deep b x the relay. Y q p or a double gang box (user supplied). A 5 inch - quare The device's microcomputer chip has the capacity of off -white faceplate is included with each TRI. storing, in memory, identification information as well • as important operating status information. MOUNTING SLOTS Siemens Building Technologies, Fire Safety Division FOR 4 :NCH SWITCH3UX innovative technology allows all TRI Series intelligent interface modules to be programmed by using the model DPU or FPI -32 Programmer/Tester. The Pro- 0 grammer/Tester is a compact, portable, menu driven accessory that makes programming and testing an [_)• TRI S / - 0/ - interface device faster, easier and more dependable [I) 1:- e I MODULE I r, p than previous methods. I The DPU or FPI-32 eliminates the need for mechanica 8 _ )11110' MOUNTING addressing mechanisms, such as program jumpers, 7 _ HOLES FOR DIP switches or rotary dials, because the Programmer / � S'vVITCHPLATE Tester electronically sets the TRI interface's address � __ into the interface's microcomputer chip nonvolatile memory. Vibration, corrosion and other conditions that . 4, /L deteriorate mechanical addressing mechanisms are no / longer a cause for concern. MOUNTING SLOTS The TRI Series is fitted with screw terminals for FOR DOUBLEGANG connection to an addressable circuit. SWITCHBOX The TRI Series is fully compatible on the same MXL Figure A circuit with all intelligent FF IL and ID-60 Series Mounting the TRI- S / -R / -D detectors, MSI Series addressable manual stations or any other addressable intelligent modules, such ft as the CZM or ICP. Electrical Ratings All TRI Series intelligent interface modules are Current Draw (Active or Standby): 1.5mA UL listed. Environmental operating conditions for all TRI Series TRI -R Relay Ratings modules are 32 °F ( °C) to 120 °F (49 °C) with a relative Resistive: 4A, 125 VAC humidity of not greater than 93% non - condensating. 4A, 30 VDC • Inductive: 3.5A, 120 VAC (0.6P.F.) Ordering Information 3.0A, 30 VDC (0.6PF.) 2.0A, 120 VAC (0.4P..F.) Slapping Wt. 2.0A, 120 VAC (0.35P.F.) Model Description Lb. Kg. TRI -S Single Input 7az 2 2.0A, 30 VDC (0.35P.F.) TRI -R Single Input w /Relay 7 oz. 2 TRI -D Dual Input 7 oz. 2 1 )• Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 7/03 Brampton, Ontario Siemens Building Technologies Tel: (973) 593 -2600 5M Canada L6T 5E4 FAX: (973) 593 -6670 SFS-IG Tel: (905) 799 -9937 July • .03 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 -9858 S°ersede7- .. dated SRO