Loading...
Specifications g 4..X.)/r — 1 4 April 2, 2003 CITY OF TIG,ik • Oregon Electric Group OREGON 1010 SW SE 11`'' Avenue Portland, OR 97214 RE: PROVIDENCE HEALTH SYSTEMS FIRE ALARM SYSTEM Project Information Building Permit: BUP2003 -00147 Construction Type: NA Tenant Name: Providence Occupancy Type: B Address: 11308 SW 68 Parkway, Suite -1-26- Occupant Load: NA Area: NA Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. 1. Add manual pull station at exit of open office area 153. Visuals (Section 1109.14 OSSC) 2. Visual signal appliances shall be provided in the building in each of the following areas: • Restrooms and any other general use area (e.g., meeting rooms) • Hallways • Lobbies • Common use areas. 3. Visual alarms shall be located not less than 80 inches and not more than 96 inches above the floor level. When a low ceiling exists, the visual alarm shall be mounted at least 6 inches below the ceiling. 4. Visual alarms shall have a minimum candela rating of 75 candelas. 5. No place in a room shall be more than 50 feet from a visual signal. 6. No place in a common corridors or hallways shall be more than 50 feet from a visual signal. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 7. In large rooms exceeding 100 feet across and without obstructions 6 feet or more above the floor, devices may be placed around the perimeter spaced at a maximum of 100 feet apart. General requirements 1. A key box shall be installed within 20 feet of the main entrance. The bottom of the key box shall be not less than 8 feet nor more than 10 feet above the walking surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 An existing key box at the main building entrance is acceptable. 2. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the Fire Chief. All functions of the system or alteration shall be tested. 1007.3.4.1 TVFR99 -01 3. The permittee shall provide written certification to the Fire Chief that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. 1007.3.4.2 TVFR99 -01. 4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL. Standard 10 -2, Section 1- 5.2.8.2, TVFR99 -01 5. Manual Fire Alarm activation devices shall be mounted in the following reach ranges: • Forward Reach - 15 inches to 48 inches above the floor. 1109.2.3.5 OSSC • Side Reach — 9 inches to 54 inches above the floor. 1109.2.3.6 OSSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, rian Blal. Senior Plans Examiner FIRE ALARM SYSTEM ADDITION Providence Healthcare Tigard Data Center Suite 125 DATA SHEETS FOR • OPERATION AND MAINTENANCE MANUAL SUBMITTED BY INTEGRATED SYSTEMS GROUP An OEG Company 5000 N.E. COLUMBIA BLVD. PORTLAND, OR. 97218 503 -535 -2800 SIEMENS Fire Safety U -MHU Series Models U -MHU Electronic Sync /Non -Sync Horn ENGINEER AND ARCHITECT SPECIFICATIONS • The AdapterTM /U -MCS feature offers four field selectable candela values — 15/75, 30/75, 75 or 110 for wall & ceiling mount 11111 - • Sync strobes and sync temporal horns, with horn ;; silence on 2 wires (- • Distinctive temporal horn FIRE • Internally adjustable volume control • Low current draw • Single gang and universal mount configurations • UL 1971 & UL 464 listed - CSFM, ULC, & NYMEA Y _ • UL 1971 listed for both wall and ceiling mount • • ADA/NFPA/ANSI compliant l ( 1 • Screw terminals accept 12 awg wire�.� • Synchronization requires Dual Sync Control FIRE - Module or PAD -3 • Made in U.S.A., ISO 9001 quality crafted Description ° is Detail - Adapter The U -MHU -1 G, U -MHU -1 G -W and U -MHU, U -MHU -W selector switch Sync Electronic Horns and U- MHU -MCS, U- MHU -MCS -W Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA nous temporal tone signals on one pair of wires or output levels. temporal or steady tone in a non -sync mode. 2 3 The U -MHU -1 G, U -MHU -1 G -W mounts to a single gang box, the U -MHU, U -MHU -W and U- MHU -MCS, U -MHU -MCS -W have a universal mounting plate for 1 4 Max. Volumc 1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust Siemens Fire Safety notification appliances are (factory set at max. volume) designed with the installer in mind.They are constructed The U- MHU -MCS, U- MHU -MCS -W strobe construction with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for This design eliminates possible ground faults from maximum reliability and efficiency.The strobe has a crowded electrical boxes.The Adapter /U -MCS feature rounded dome shape made of clear polycarbonate. offers four field selectable candela settings - 15/75, 30/75, 75 or 110. CATALOG NUMBER 2560 Replaces Catalog Sheet Number 2555 The U -MHU -1 G, U -MHU -1 G -W, U -MHU, U -MHU -W and Listed operating range is 20 to 31 VDC /FWR U- MHU -MCS, U- MHU -MCS -W are used on circuits with Temporal maximum UL measurements are 83.6 db at steady power or a Dual Sync Control Module or PAD -3. 24VDC /FWR. Steady tone maximum UL measurements Not for use on coded circuits. are 878 db at 24VDC /FWR taken in free air at 360° around the device and averaged. Typical readings are - Environmental frontal sound readings taken with a dB meter with signal 32 °F to 120 °F (0 °C to 49 °C) with 85 % humidity mounted on wall. Rated for indoor use 32 °F to 120 °F, (0 °C to 49 °C), at RH 85 %. - Operating Voltage Range Limits (-C: Ceiling Mounted) ( -W: White) Horn: 20 -31 Vdc orVFWR Strobe: 16 -33Vdc orVFWR Strobe Intensity Setting Strobe Current Draw 15/75 cd 63 mA Typical Hom Ratings at 10 Feet* 30/75 cd 84 mA 75 cd 143 mA Temporal Horn — 110 cd 178 mA Maximum: 95 db @ 25 mA Minimum: 90 db @ 17 mA Control Module Specifications * Typical dBA ratings are frontal sound readings Maximum Current Output: 3 Amps Max. not taken with a dB meter with signal mounted on wall. to exceed NAC rating DSC Module OperatingVoltage: 20 to 31 Vdc orVFW Dimensions DSC Module Operating Current: Non - Silenceable 2.3r4 I I _13 /4 r — 4 -3ra — t -1.3ra Circuit side _ ,n. ! -1) C 5 5 Silen ceable Circuit side .005 Amps. 4 VIII ED 14 ° 11111 Maximum Current Output: 3 Amps max. not to exceed Circuit rating .1____ L LI 1, 2 or 4 Square Mounting 4-3r4• — 2 -1:71 6 , ..,.i.,... 1 .A ; j, 1 VIII p ,«. 0 t ill . 1 ' , C I FIRE s it t NI Selector Switch -_... ./\ For wiring diagram for U -MHU Series Horn /Strobes refer Ordering Information to Installation Instruction Sheet U -MHU Series Hom WaII Mount Low Volume High Volume High Volume Model Number Description Part Number Horn Current Horn Current dB Rating 010 U- MHU -1G ELC Sync /Non -Sync Horn 24VDC 500 - 699591 17ma 25ma 95 db U- MHU -1G -W ELC Sync /Non -Sync Horn 24VDC 500. 699592 17ma 25ma 95 db U -MHU ELC Sync /Non -Sync Horn 24VDC 500 - 699594 17ma 25ma 95 db U- MHU -W ELC Sync /Non -Sync Horn 24VDC 500 - 699593 17ma 25ma 95 db Low Volume High Volume High Volume Model Number Description Part Number Horn Current Horn Current dB Rating 010' U- MHU -MCS ELC Sync /Non -Sync Horn w /Strobe (Red) 500. 699587 lima 25ma 95 db U -MHU -MCS -W ELC Sync /Non -Sync Horn w /Strobe (White) _ 500. 699588 _ 17ma 25ma 95 db *All current measurements made at 24VDC Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard Florham Park, NJ 07932 12/02 Brampton, Ontario Siemens Building Technologies Tel: (973) 10M CanadaL6T5E4 g Thli g FAx: (97 3) 5 5 9 9 3 3 -2 6 6 6 0 7 0 0 • SFS-IG Tel: (905) 799.9937 December 2102 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799-9858 Supetcedes sheet dated 8102 wheeloc.k me. .'mil ZK+ Di; . M INC. EA FIRE ALARM SYSTEMS Helping People Take Action SERIES SM AND DSM SYNC MODULES Description Wheelock's Series SM and DSM Sync Modules are utilized with the Series AS /AH, Series NS /NS4 /NH, Series RSS, Series RSSP, • Series SL /SLM and selected strobe applications with other Wheelock combination appliances. When used with Series AS Audible Strobes and /or Series NS Horn Strobes, the SM and DSM Sync Modules provide independent operation of synchronized temporal pattern (code 3) horn and synchronized strobe flash, as well as the ability to silence the horn while maintaining the strobe flash. while using only a single pair of • • wires. The sync modules are available in two versions; the SM 12/24 for control of a Class B NAC circuit; and a dual output Series SM or DSM version, the DSM 12/24 for control of either a Class A or two (2) Class B NAC circuits. Features • Approvals include: Underwriters Laboratories (UL 1971) Listing, New York City (MEA), California State Fire Marshal (CSFM) and Chicago (BFP) on all models. • Uniquely designed to accept an independent strobe and audible input from the FACP and convert to a single output that connects to Wheelock's Series AS or Series NS family of audible strobes. • Series SM and DSM Sync Modules can also be used to synchronize Wheelock's Series RSS, RSSP, SL and SLM Sync Strobes. • 3 ampere per circuit current handling at 12 or 24 VDC. • Low operating current draw. • Compatible with all standard fire alarm control panels. • Meets the NFPA -72 (1999) requirement for Temporal Pattern when used with the Series AS /AH and /or Series NS /NS4 /NH. • 3 year warranty. Copyright 2000 Wheelock, Inc. All rights reserved. NOTE: All CAUTIONS and WARNINGS are identified by the symbol0 . All wamings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU . AND /OR OTHERS. Table 1: Sync Module (SM) Current Requirement (AMPS) Table 2: Dual Sync Module (DSM) Current Requirement (AMPS) Rated Average Rated Peak Rated Inrush Rated Average Rated Peak Rated Inrush Voltage Current Current Current Voltage Current Current Current Strobe Audible Strobe Audible Strobe Audible Strobe Audible Strobe Audible Strobe Audible 10.5 VDC 0.008 0.004 0.032 0.004 0.032 0.004 10.5 VDC 0.015 0.003 0.112 0.003 0.299 0.053 12.0 VDC 0.009 0.005 0.036 0.005 0.034 0.005 12.0 VDC 0.016 0.004 0.117 0.004 0.352 0.065 24.0 VDC 0.015 0.010 0.074 0.010 0.062 0.010 24.0 VDC 0.030 0.008 0.130 0.008 0.662 0.118 31.0 VDC 0.018 0.012 0.090 0.012 0.078 0.012 31.0 VDC 0.040 0.010 0.138 0.010 0.831 0.152 10.5 VRMS 0.014 0.006 0.066 0.006 0.058 0.006 10.5 VRMS 0.025 0.010 0.158 0.010 0.416 0.068 12.0 VRMS 0.015 0.007 0.072 0.007 0.066 0.007 12.0 VRMS 0.027 0.011 0.158 0.011 0.479 0.083 24.0 VRMS 0.030 0.013 0.108 0.013 0.078 0.013 24.0 VRMS 0.044 0.022 0.194 0.022 0.838 0.138 31.0 VRMS 0.040 0.017 0.122 0.017 0.086 0.017 31.0 VRMS 0.054 0.028 0.218 0.028 1.111 0.213 A WARNING: MAKE SURE THAT THE TOTAL CURRENT REQUIRED BYALLAPPLIANCES THATARE CONNECTED TOASM OR DSM DOES NOT EXCEED 3.0AOR EXCEED THE RATING OF THE FIRE ALARM CONTROL PANEL'S PRIMARY AND SECONDARY POWER SOURCES AND NAC CIRCUITS. OVERLOADING THESE SOURCES COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. When calculating the total current, use Tables 1 & 2 to determine the highest value of "Rated Average Current" for the SM or DSM (across the listed voltage range), then add this value to the total current for any other appliances powered by the same source and include any required safety factors. Refer to Instruction Sheet for addtional information. A WARNING: MAKE SURE THATALL FUSES USED ON NAC CIRCUITS ARE RATED TO HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL APPLIANCES ON THOSE CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE NAC CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. Table 3: Current Consumption of the SM and DSM Modules Current Required Current Required SM DSM from FACP from FACP Output Circuit Description of SM /DSM Module Module Module Audible NAC Circuit Strobe NAC Circuit Ref. Fig. Class "B" with Audible Silence (single circuit) Y 0.010 0.015 1 Class "B" with No Audible Silence (single circuit) Y 0.025 2 Class "B" with Audible Silence (single circuit) Y 0.008 0.030 3 Class "B" with No Audible Silence (single circuit) Y 0.038 4 Class "B" with Audible Silence (dual circuit) Y 0.008 0.030 3 Class "B" with No Audible Silence (dual circuit) Y 0.038 4 Class "A" with Audible Silence (single circuit) Y 0.008 0.030 5 Class "A" with No Audible Silence (single circuit) - Y 0.038 6 Note: SM Sync Modules are rated for 3.0 amperes at 12/24 VDC; DSM Dual Sync Modules are rated for 3.0 amperes per circuit. The maximum number of interconnected DSM modules is twenty (20). A CAUTION: Use SM or DSM Sync Modules only on NAC circuits with continuously applied voltage. Do not use SM or DSM Sync Modules on coded or interrupted NAC circuits in which the applied voltage is cycled on and off. ACAUTION: Power Boosters may be used in conjunction with the SM or DSM Sync Modules only in the order shown below. Only one SM or DSM Sync Module shall be allowed on a NAC circuit. Do not connect Power Booster to the NAC circuit after the one SM or DSM Sync Module. Refer to Power Booster instruction manual for proper application and installation. ACAUTION: SM and DSM Sync Modules may be used in conjunction with a POWERPATH only in the order shown below. Each output can use Sync Module (SM or DSM) to drive audible or visual synchronized appliances. Do not connect POWERPATH to the NAC after a Sync Module. FIRE POWERPATH AS/AH, ALARM OR NS /NS4 /NH, CONTROL OTHER SM OR DSM RSS, RSSP, PANEL POWER SL, SLM (FACP) BOOSTERS APPLIANCES SM or DSM Connection Diagram with Power Booster 9u t3D CF LINE RLSSICR law SW CBE 9C 1 + CLR !6 P6 Ai Ni 0 CIFICUT •1 �� + INI U 0!# MN.S7 M 'a ALOBLE 9340 ,i • , ,I + C Ur *1 TO NEXT FR NS AK i N • i.4 Ord AI - B1E Cfi E11R Important: AS, NS, NH and AEI appliances draw power from strobe appliance circuit only. FIG. 1 SINGLE CLASS "B" CIRCUIT WITH AUDIBLE SILENCE FEATURE SM • - • STROBE • - •---• STROBE C OUT 1124114311 L A EOR P SEE • • AUDIBLE NOTE 1 NOTES 1 8 2 NAC CIRCUIT ` • V AUDIBLE FIG. 2 SINGLE CLASS "B" CIRCUIT WITH NOAUDIBLE SILENCE FEATURE DSM • SYNC • • SYNC STROBE NAC • OUT 1 CIRCUIT /1 • IN ' L Cia/C112 EOLR MINUS 1 1 � ♦ SEE SEE NOTE 1 NOTES 1 8 2 AUDIBLE it EOLR AUDIBLE CIRCUIT/2 AUDIBLE NOTES • OUT 2 El ©� ©�© E L - • IN 2 STROBE NAC _ MINUS 2 CIRCUIT /2 SEE SEE SEE NOTE] NOTE 1 NOTES 1 a 2 FIG. 3 DUAL CLASS "B" CIRCUIT WITH AUDIBLE SILENCE FEATURE DSM • SYNC • • SYNC • OUT 1 Flaractiol • IN 1 1 MINUS 1 • AUDIBLE OTE EE NOTE 1 NOTES S 1 8 2 NAC CIRCUI AUDIBLE • • IN 2 Inciallal - MINUS 2 NAC CIRCUIT 82 SEE NOTE] NOTE 1 NOTES 1 82 FIG. 4 DUAL CLASS "B" CIRCUIT WITH NO AUDIBLE SILENCE FEATURE DSM •SYNC • • SYNC • OUT1 �V��� CIRCUIT OUT • IN 1 19 • - MINUS 1 SEE SEE '. • AUDIBLE NOTE 1 NOTES 1 & 2 Z _ STROBENAC • AUDIBLE AUDIBLE NAC CIRCUIT RETURN 3 . STRO M IN D ` U 1��©1©1121 1© • • CIRCUIT RETURN ©• NS SEE SEE SEE NOTE 3 NOTE 1 NOTES 1 6 2 FIG. 5 SINGLE CLASS "A" CIRCUIT WITH AUDIBLE SILENCE FEATURE DSM • SYNC • • SYNC • OUT 1 1y �© �: 0 • IN 1 1 MINUS 1 I • AUDIBLE NOTE 1 NOTES 1 6 2 AUDIBLE MAC CIRCUIT OUT AUDIBLE NOTE 5 • OUT �� IFIES 1 p • 6 • - MINUS 2 AUDIBLE NAC CIRCUIT RETURN SEE SEE NOTE 1 NOTES 1 6 2 FIG. 6 SINGLE CLASS "A" CIRCUIT WITHOUT AUDIBLE SILENCE FEATURE DSM N = MAXIMUM OF DSM DSM 2 20 DSM S YY J ti f> J "2, I. m O 00 C 3 o ? Win? _? g ? ~ 0 0 ? < c Wi n; 33 '< a o3 QQ o-3 < < o - o33 • o < • • 2 • • • 1 • • 2 • • • 2 • • 2 J1A1 _ • • i SEE 000 Ik O 000 000 Q ‘.._ Q 1 0043 m00 0� NOTE FROM FACP AA • MAC CIRCUIT , • FOR HORN SILENCE FIG. 7 DSM'S WIRED FOR MULTIPLE SIGNAL CIRCUITS ALL IN SYNCHRONIZATION, • 20 CLASS "A" CIRCUITS OR 40 CLASS "B" CIRCUITS MAX DSM POWER BOOSTER • SYNC • o•��,� • SYNC fft$ CIR � : : ELI anal a Eaa SEE N OTE 1 _ F • AUDIBLE NOTE 1 NOTESE 6 2 A NAC CIRCUIT EOLN P • • AUDIBLE • 11.•••••■• • Si 2 risionaca - . . STROBE NAC SEE CIRCUIT 62 SEE SEE NOTE 5 NOTE 1 NOTES 16 2 FIG. 8 DUAL CLASS "B" CIRCUIT WITH AUDIBLE SILENCE FEATURE CONNECTED WITH POWER BOOSTER Notes 1. Non -Sync Appliances can be installed before or after a SM or DSM. If the Non -Sync appliance requires audible silence, four wire connection is necessary with the strobe circuit connected before the SM or DSM NAC circuit, and the audible leads connected to a silenceable NAC circuit from the FACP. 2. The audible appliance produces a momentary interruption (approximately 25ms) each time the strobes flash. 3. Circuit #2 may be omitted if only 1 circuit is required when using the DSM. 4. Power Boosters may be used in conjunction with the SM or DSM Sync Modules ONLY in the order shown in Figure 8. Only one SM or DSM Sync Module Output shall be allowed on a NAC circuit. Do not connect Power Booster to the NAC circuit after the one SM or DSM Sync Module. Refer to Power Booster instruction manuals for proper application and installation (Installation Instruction P83123 or SM & P83177 DSM). 5. Non -Sync Audible Appliances can be installed on the audible NAC. Be aware of the current requirement . for the SM or DSM module. See table 3. Q WARNING: ALTHOUGH ULTESTING HAS VERIFIED THAT SYNC MODULES FUNCTION EVEN AT 80% OF THEIR MINIMUM RATING AND 110% OF THEIR MAXIMUM RATING, WHEELOCK STRONGLY RECOMMENDS THATTHE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED INPUT VOLTAGE RANGE. THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/ • OR OTHERS. Wheelock products must be used within their published specifications and must be PROPERLY specified, . applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amend- ments and the requirements of the local authority having jurisdiction (AHJ). A WARNING: CONTACT WHEELOCK FOR INSTALLATION INSTRUCTIONS" (P83123 -SM & P83177 -DSM) AND "GENERAL INFORMATION" SHEET ON THESE PRODUCTS. These documents do undergo periodic changes. It is important that you have current information on these products. These materials contain important information that should be read prior to specifying or installing these products including: • TOTAL CURRENT REQUIRED BYALLAPPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NAC CIRCUITS TO HANDLE MAXIMUM INRUSH OR PEAK CURRENTS FROM ALL APPLIANCES ON THOSE NAC CIRCUITS. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED IN PUT VOLTAGE RANGE. • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON NAC CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBE ON CODED OR INTERRUPTED NAC CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH. Ordering Information Average Order Input Current Moundng Model Code Vbttage @ 1 Options SM-24-R 6369 VV1DD2C� 24 .014 W 24 .025 W f' DSM -24-R' 6374 12 .020 W 24 .038 W R = Red * Average current per actual Wheelock Production Listing @ 12 & 24 VDC Nominal Voltage. ** Refer to Data sheet # S -7000 for Mounting Options. * ** The maximum number of interconnected DSM modules is twenty (20). The total distance from the first to the last DSM shall not exceed 1,000 feet of #18 AWG wire. Use only #18 AWG wire. Architects and Engineers Specifications The sync modules shall be Wheelock Series SM or DSM Sync Modules. Series SM or DSM Sync Modules shall be the master controllers for Wheelock Series AS /AH, NS /NS4 /NH, RSS, RSSP, SL, SLM appliances where a synchronized audible /visual audible or visual only appliance is specified. All modules shall be UL listed under Standard 464. Series SM and DSM modules shall be designed to interface with Series AS Audible Strobe Appliances and NS Horn Strobe Appliances to produce a synchronized temporal (Code 3) horn as well as synchronized strobe flash on a two-wire alarm circuit. Other synchronized products are the Wheelock Series RSS, RSSP, SL, SLM visual only appliances and - Series AH and NH Hom Appliances. SM Sync Module shall incorporate two input NAC circuits for power connection from the Fire Alarm Control Panel; one for the strobe NAC circuit and one for the audible NAC circuit. DSM modules shall provide an additional strobe circuit input/output for control of either two Class "B" NAC circuits or a single Class "A" NAC circuit. Upon activation of the audible silence function at the Fire Alarm Control Panel, the audible signal component of Series AS Audible Strobe and/ or the Series NS Horn Stobe may be silenced while maintaining strobe activation. Series SM or DSM module shall be designed and available in two versions; the SM 12/24 for control of a single Class B NAC circuit and a dual output version, the DSM -12/24 for control of either Class Atwo (2) Class B NAC circuits. The DSM dual circuit version shall provide the additional capability of "daisy- chaining ", that is, the ability to interconnect multiple DSM's for synchronous horn and strobe operation on multiple NAC circuits. Interconnection capability shall be for a maximum of 40 NAC circuits. All modules shall operate on either 12 or 24 VDC. Rated average current requirement for the SM 12/24 shall be .014 amperes © 12 VDC and .025 amperes @ 24 VDC. The DSM 12/24 shall be .020 amperes @ 12 VDC and .038 amperes © 24 VDC. A single circuit SM Sync Module shall be capable of handing a 3 ampere Toad at 12 or 24 VDC and the dual circuit DSM Sync Module shall be capable of handling a Toad of 3 amperes per NAC circuit at 12 or 24 VDC. All versions shall be polarized for DC supervision and shall incorporate screw terminals for in /out field wiring of #18 to #12 AWG wire size. The SM and DSM Sync modules shall mount to a 4- 11/16" x 2 -1/8" deep backbox. MADE IN THE USA NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Distributed By: NATIONAL SALES OFFICE 800 - 631 -2148 3 YEAR WARRANTY Canada 800 - 397 -5777 XENIA E -Mail: Info @wheelockinc.com http: / /www.wheelockinc.com Member 273 BRANCHPORT AVENUE • LONG BRANCH, NJ 07740 • TEL: 732 - 222 - 6880 • FAX: 732 - 222 - 2588 S3000 08/00 SIEMENS Fire Safety U -MHU Series Models U -MHU Electronic Sync /Non -Sync Horn ENGINEER AND ARCHITECT SPECIFICATIONS • The AdapterTM /U -MCS feature offers four field selectable candela values — 15/75, 30/75, 75 or 110 r _ _ for wall & ceiling mount • Sync strobes and sync temporal horns, with horn 11111 r i silence on 2 wires • Distinctive temporal horn FIRE • Internally adjustable volume control • Low current draw • Single gang and universal mount configurations t' ksi • UL 1971 & UL 464 listed - CSFM, ULC, & NYMEA _ __ _ • UL 1971 listed for both wall and ceiling mount TT • • ADA/NFPA/ANSI compliant E_1�.. ` • Screw terminals accept 12 awg wire • Synchronization requires Dual Sync Control FIRE' Module or PAD -3 • Made in U.S.A., ISO 9001 quality crafted Description Detail - Adapter The U -MHU -1 G, U -MHU -1 G -W and U -MHU, U -MHU -W �15 W8 selector switch Sync Electronic Horns and U- MHU -MCS, U- MHU -MCS -W Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA nous temporal tone signals on one pair of wires or output levels. temporal or steady tone in a non -sync mode. 2 3 The U -MHU -1 G, U -MHU -1 G -W mounts to a single gang box, the U -MHU, U -MHU -W and U- MHU -MCS, U- MHU -MCS -W have a universal mounting plate for 1 4 Max.Volumc 1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust Siemens Fire Safety notification appliances are (factory set at max. volume) designed with the installer in mind.They are constructed The U- MHU -MCS, U- MHU -MCS -W strobe construction with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for This design eliminates possible ground faults from maximum reliability and efficiency.The strobe has a crowded electrical boxes.The Adapter /U -MCS feature rounded dome shape made of clear polycarbonate. offers four field selectable candela settings - 15/75, 30/75, 75 or 110. CATALOG NUMBER 2560 Replaces Catalog Sheet Number 2555 The U -MHU -1 G, U -MHU -1 G -W, U -MHU, U -MHU -W and Listed operating range is 20 to 31 VDC /FWR U- MHU -MCS, U- MHU -MCS -W are used on circuits with Temporal maximum UL measurements are 83.6 db at steady power or a Dual Sync Control Module or PAD -3. 24VDC /FWR. Steady tone maximum UL measurements Not for use on coded circuits. are 87.8 db at 24VDC /FWR taken in free air at 360° around the device and averaged. Typical readings are - Environmental frontal sound readings taken with a dB meter with signal 32 °F to 120 °F (0 °C to 49°C) with 85 % humidity mounted on wall. Rated for indoor use 32 °F to 120 °F, (0 °C to 49 °C), at RH 85 %. - OperatingVoltage Range Limits (-C: Ceiling Mounted) ( -W: White) Horn: 20 -31 Vdc orVFWR Strobe: 16 -33Vdc orVFWR Strobe Intensity Setting Strobe Current Draw 15/75 cd 63 mA Typical Horn Ratings at 10 Feet* 30/75 cd 84 mA Tem Temporal Horn — 110 cd 178 mA P 110 cd 178 mA Maximum: 95 db @ 25 mA Minimum: 90 db @ 17 mA Control Module Specifications: * Typical dBA ratings are frontal sound readings Maximum Current Output: 3 Amps Max. not taken with a dB meter with signal mounted on wall. to exceed NAC rating DSC Module OperatingVoltage: 20 to 31 Vdc orVFW Dimensions DSC Module Operating Current: Non - Silenceable z•ya ,ar4• 4-3/4'.-7 t•aa Circuit side I t--1-3/4' -I _r ~ � ,n 55mA, Silenceable 1 40 Circuit side .005 Amps. 4•1 r r s•3/4' ° IIIII Maximum Current Output: 3 Amps max. not to 1 IIIII exceed Circuit rating 6 , [1 .r__- L 1, 2 or 4 Square Mounting r -- 4.314• -- _ 2 -1, •. o ' IIII - 0 , (...- 1 . \ I 1 . k. '.N„ , : ., : e i . FIRE - it o r selector �II Switch - si ` I l For wiring diagram for U -MHU Series Horn /Strobes refer Ordering Information to Installation Instruction Sheet U -MHU Series HomWall Mount Low Volume High Volume High Volume Model Number Description Part Number Horn Current Horn Current dB Rating @10 U- MHU -1G ELC Sync /Non -Sync Horn 24VDC 500-699591 17ma 25ma 95 db U- MHU -1G -W ELC Sync /Non -Sync Horn 24VDC 500.699592 _ 17ma 25ma 95 db U-MHU ELC Sync /Non -Sync Horn 24VDC 500- 699594 17ma 25ma 95 db U -MHU -W ELC Sync /Non -Sync Horn 24VDC 500 - 699593 17ma 25ma . 95 db Low Volume High Volume High Volume Model Number Description Part Number Horn Current Horn Current dB Rating 010' U- MHU•MCS ELC Sync /Non -Sync Horn w /Strobe (Red) 500 - 699587 17ma 25ma 95 db U- MHU•MCS -W ELC Sync /Non -Sync Horn w /Strobe (White) 500 - 699588 _ 17ma 25ma 95 db *AII current measurements made at 24VDC Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard Florham Park. NJ 07932 12/02 Brampton, Ontario Siemens Buildin Technolo ieS Tel: (973) 593-2600 10M Canad L6T 5E4 g g FAX: (973) 593-6670 SFS•IG Tel: (905) 799-9937 December 2002 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 -9858 Supercedes sheet dared 8/02 Wheelock �_ ,.cam+,► •.• �'I h e . eloc kNC. & EA FIRE ALARM SYSTEMS Helping People Take Action SERIES SM AND DSM SYNC MODULES Description Wheelock's Series SM and DSM Sync Modules are utilized with the Series AS /AH, Series NS /NS4 /NH, Series RSS, Series RSSP, • • Series SL /SLM and selected strobe applications with other Wheelock combination appliances. When used with Series AS Audible Strobes and /or Series NS Hom Strobes, the SM and DSM Sync Modules provide independent operation of synchronized temporal pattern (code 3) horn and synchronized strobe flash, as well as the ability to silence the horn while maintaining the strobe flash. while using only a single pair of • • wires. The sync modules are available in two versions; the SM 12/24 for control of a Class B NAC circuit; and a dual output Series SM or DSM version, the DSM 12/24 for control of either a Class A or two (2) Class B NAC circuits. Features • Approvals include: Underwriters Laboratories (UL 1971) Listing, New York City (MEA), California State Fire Marshal (CSFM) and Chicago (BFP) on all models. • Uniquely designed to accept an independent strobe and audible input from the FACP and convert to a single output that connects to Wheelock's Series AS or Series NS family of audible strobes. • Series SM and DSM Sync Modules can also be used to synchronize Wheelock's Series RSS, RSSP, SL and SLM Sync Strobes. • 3 ampere per circuit current handling at 12 or 24 VDC. • Low operating current draw. • Compatible with all standard fire alarm control panels. • Meets the NFPA -72 (1999) requirement for Temporal Pattem when used with the Series AS /AH and /or Series NS /NS4 /NH. • 3 year warranty. Copyright 2000 Wheelock, Inc. All rights reserved. NOTE: All CAUTIONS and WARNINGS are identified by the symbol/ . All wamings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. Table 1: Sync Module (SM) Current Requirement (AMPS) Table 2: Dual Sync Module (DSM) Current Requirement (AMPS) Rated Average Rated Peak Rated Inrush Rated Average Rated Peak Rated Inrush • Voltage Current Current Current Voltage Current Current Current Strobe Audible Strobe Audible Strobe Audible Strobe Audible Strobe Audible Strobe Audible 10.5 VDC 0.008 0.004 0.032 0.004 0.032 0.004 10.5 VDC 0.015 0.003 0.112 0.003 0.299 0.053 12.0 VDC 0.009 0.005 0.036 0.005 0.034 0.005 12.0 VDC 0.016 0.004 0.117 0.004 0.352 0.065 24.0 VDC 0.015 0.010 0.074 0.010 0.062 0.010 24.0 VDC 0.030 0.008 0.130 0.008 0.662 0.118 31.0 VDC 0.018 0.012 0.090 0.012 0.078 0.012 31.0 VDC 0.040 0.010 0.138 0.010 0.831 0.152 10.5 VRMS 0.014 0.006 0.066 0.006 0.058 0.006 10.5 VRMS 0.025 0.010 0.158 0.010 0.416 0.068 12.0 VRMS 0.015 0.007 0.072 0.007 0.066 0.007 12.0 VRMS 0.027 0.011 0.158 0.011 0.479 0.083 24.0 VRMS 0.030 0.013 0.108 0.013 0.078 0.013 24.0 VRMS 0.044 0.022 0.194 0.022 0.838 0.138 31.0 VRMS 0.040 0.017 0.122 0.017 0.086 0.017 31.0 VRMS 0.054 0.028 0.218 0.028 1.111 0.213 A WARNING: MAKE SURE THAT THE TOTAL CURRENT REQUIRED BYALLAPPLIANCES THATARE CONNECTED TO A SM OR DSM DOES NOT EXCEED 3.0AOR EXCEED THE RATING OF THE FIRE ALARM CONTROL PANEL'S PRIMARY AND SECONDARY POWER SOURCES AND NAC CIRCUITS. OVERLOADING THESE SOURCES COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGEAND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. When calculating the total current, use Tables 1 & 2 to determine the highest value of "Rated Average Current" for the SM or DSM (across the listed voltage range), then add this value to the total current for any other appliances powered by the same source and include any required safety factors. Refer to Instruction Sheet for addtional information. A WARNING: MAKE SURE THATALL FUSES USED ON NAC CIRCUITS ARE RATED TO HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL APPLIANCES ON THOSE CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE NAC CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. Table 3: Current Consumption of the SM and DSM Modules Current Required Current Required SM DSM from FACP from FACP Output Circuit Description of SM /DSM Module Module Module Audible NAC Circuit Strobe NAC Circuit Ref. Fig. Class "B" with Audible Silence (single circuit) Y 0.010 0.015 1 Class "B" with No Audible Silence (single circuit) Y 0.025 2 Class "B" with Audible Silence (single circuit) Y 0.008 0.030 3 Class "B" with No Audible Silence (single circuit) Y 0.038 4 Class "B" with Audible Silence (dual circuit) Y 0.008 0.030 3 Class "B" with No Audible Silence (dual circuit) Y 0.038 4 Class "A" with Audible Silence - (single circuit) Y 0.008 0.030 5 Class "A" with No Audible Silence (single circuit) Y 0.038 6 Note: SM Sync Modules are rated for 3.0 amperes at 12/24 VDC; DSM Dual Sync Modules are rated for 3.0 amperes per circuit. The maximum number of interconnected DSM modules is twenty (20). A CAUTION: Use SM or DSM Sync Modules only on NAC circuits with continuously applied voltage. Do not use SM or DSM Sync Modules on coded or interrupted NAC circuits in which the applied voltage is cycled on and off. ACAUTION: Power Boosters may be used in conjunction with the SM or DSM Sync Modules only in the order shown below. Only one SM or DSM Sync Module shall be allowed on a NAC circuit. Do not connect Power Booster to the NAC circuit after the one SM or DSM Sync Module. Refer to Power Booster instruction manual for proper application and installation. ACAUTION: SM and DSM Sync Modules may be used in conjunction with a POWERPATH only in the order shown below. Each output can use Sync Module (SM or DSM) to drive audible or visual synchronized appliances. Do not connect POWERPATH to the NAC after a Sync Module. FIRE POWERPATH AS /AH, ALARM OR NS /NS4 /NH, CONTROL OTHER SM OR DSM RSS, RSSP, PANEL POWER SL, SLM (FACP) BOOSTERS APPLIANCES SM or DSM Connection Diagram with Power Booster .7 9N ENS CF- UE REf3SICR (Eflfa E SITE 9& + . * OJf7 OS Na Jri Ni GfT aN Q Co + INI MN1 M + n>JBLE 11, 'I + A.OBLE 9 W XT iQ NS pi NI CLlJT 01 S R I/ PLOB<E Important: AS, NS, NH and A9 appliances draw power from strobe appliance circuit only. FIG. 1 SINGLE CLASS "B" CIRCUIT WITH AUDIBLE SILENCE FEATURE SM • • STROBE • •.•--• STROBE F c OUT ® © • our A r't EOLR C OUT • • • AUDIBLE NOTE 1 NOTES 1 6 2 NAC CIRCUIT • 1 • AUDIBLE FIG. 2 SINGLE CLASS "B" CIRCUIT WITH NOAUDIBLE SILENCE FEATURE DSM • SYNC • • SYNC STROBE NAC .• fNU' 1 111131111 CIRCUIT 11 EOLR - MINUS 1 • AUDIBLE SEE SEE NOTE 1 NOTES 1 8 2 AUDIBLE NAC EOLR AUDIBLE CIRCUIT 12 NOTE 5 it • IN S 2 2 2 111 Z© 3112 EOLR - MINU NOV CIRCUIT 12 SEE SEE SEE NOTE 3 NOTE 1 NOTES 1 8 2 FIG. 3 DUAL CLASS "B" CIRCUIT WITH AUDIBLE SILENCE FEATURE DSM • SYNC • • SYNC • OUT 1 1113C ���© EOLR • OUT 1 ' MINUS 1 SEE • AUDIBLE NOTE 1 NOTES 1 6 2 NA CIRCUIT AUDIBLE • OUT 2 I11Ii0i - • IN 2 EOL MINUS 2 NAC CIRCUIT 12 - SEE SEE SEE NOTE 3 NOTE 1 NOTES 1 6 2 FIG. 4 DUAL CLASS "B" CIRCUIT WITH NOAUDIBLE SILENCE FEATURE DSM •SYNC • • SYNC • STROBE NAC • IN 1 1 IZD1 CIRCUIT OUT - MINUS 1 AUDIBLE NAC IR IT O T SEE SEE • AUDIBLE NOTE 1 NOTES 1 8 2 �• AUDIBLE AUDIBLE NAC CIRCUIT RETURN "..11.31.3m,• NOTES • OUT 2 � • IN STROBE MAC MINUS 2 • CIRCUIT RETURN SE E SEE SEE NOTE 2 NOTE 1 NOTES 1 8 2 FIG. 5 SINGLE CLASS "A" CIRCUIT WITH AUDIBLE SILENCE FEATURE DSM • SYNC • • SYNC �7 r� • y� ©�© �.IIt� c: • INOUT I 1 Z . • �+�' • • 1 MINUS 1 • AUDIBLE N OTE SEE 1 NOTES 1 .12 AUDIBLE NAC I CIRCUIT OUT AUDIBLE NOTE 5 - YINUS 2 I rila 2 2.10: 21 • AUDIBL NAC CIRCUIT E RETURN SEE NOTE 1 NOTES 1 8 2 FIG. 6 SINGLE CLASS "A" CIRCUIT WITHOUTAUDIBLE SILENCE FEATURE DSM N = MAXIMUM OF DSM DSM 2 20 DSM S J NU) m J w NN ii J n NN O O N 00 5 > > > ~ s QQ S - > a �i : 00 ,-z el a Si <i ^ 03 3 < < 'b3 03 3 < '< O- 3 • w 3 3 SEE m00 • (k 00 0 000 • 4 000 000 0 0 000 • NOTE4 FROM FACP MAC CIRCUIT FOR HORN SILENCE FIG. 7 DSM'S WIRED FOR MULTIPLE SIGNAL CIRCUITS ALL IN SYNCHRONIZATION, • 20 CLASS "A" CIRCUITS OR 40 CLASS "B" CIRCUITS MAX DSM POWER BOOSTER • SYNC • o•����t • SYNC ai$ C RCS " Rni s i ' Filloiillac . SEE N OTE 1 o SEE SEE F • • AUDIBLE NOTE 1 NOTES 1 8 2 A NAC CIRCUIT EOLR P • • AUDIBLE • • -• • wz•� E•IR • • "wus ] ©• ©• �• ®• STROBE NAC SEE CIRCUIT 02 SEE SEE NOTE 5 NOTE 1 NOTES 1 8 2 FIG. 8 DUAL CLASS "B" CIRCUIT WITH AUDIBLE SILENCE FEATURE CONNECTED WITH POWER BOOSTER Notes 1. Non -Sync Appliances can be installed before or after a SM or DSM. If the Non -Sync appliance requires audible silence, four wire connection is necessary with the strobe circuit connected before the SM or DSM NAC circuit, and the audible leads connected to a silenceable NAC circuit from the FACP. 2. The audible appliance produces a momentary interruption (approximately 25ms) each time the strobes flash. 3. Circuit #2 may be omitted if only 1 circuit is required when using the DSM. 4. Power Boosters may be used in conjunction with the SM or DSM Sync Modules ONLY in the order shown in Figure 8. Only one SM or DSM Sync Module Output shall be allowed on a NAC circuit. Do not connect Power Booster to the NAC circuit after the one SM or DSM Sync Module. Refer to Power Booster instruction manuals for proper application and installation (Installation Instruction P83123 or SM & P83177 DSM). 5. Non -Sync Audible Appliances can be installed on the audible NAC. Be aware of the current requirement . for the SM or DSM module. See table 3. A WARNING:ALTHOUGH UL TESTING HAS VERIFIED THAT SYNC MODULES FUNCTION EVEN AT 80% OF THEIR MINIMUM RATING AND 110% OF THEIR MAXIMUM RATING, WHEELOCK STRONGLY RECOMMENDS THAT THE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED INPUT VOLTAGE RANGE. THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/ OR OTHERS. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amend- ments and the requirements of the local authority having jurisdiction (AHJ). A WARNING: CONTACT WHEELOCK FOR "INSTALLATION INSTRUCTIONS" (P83123 -SM & P83177 -DSM) AND "GENERAL INFORMATION" SHEET ON THESE PRODUCTS. These documents do undergo periodic changes. It is important that you have current information on these products. These materials contain important information that should be read prior to specifying or installing these products including: • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NAC CIRCUITS TO HANDLE MAXIMUM INRUSH OR PEAK CURRENTS FROM ALL APPLIANCES ON THOSE NAC CIRCUITS. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED IN PUT VOLTAGE RANGE. • INSTALLATION IN OFFICE AREASAND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON NAC CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBE ON CODED OR INTERRUPTED NAC CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH. Ordering Information Average Order but Current Mounting Model Code Voltage @ 12 or Options"' VDC 24VDC SM -24-R 6369 12 .014 W 24 .025 W F-7 , ; DSM -24-12 6374 12 .020 W 24 .038 W R = Red Average current per actual Wheelock Production Listing @ 12 & 24 VDC Nominal Voltage. ** Refer to Data sheet # S -7000 for Mounting Options. "' The maximum number of interconnected DSM modules is twenty (20). The total distance from the first to the last DSM shall not exceed 1,000 feet of #18 AWG wire. Use only #18 AWG wire. Architects and Engineers Specifications The sync modules shall be Wheelock Series SM or DSM Sync Modules. Series SM or DSM Sync Modules shall be the master controllers for Wheelock Series AS /AH, NS /NS4 /NH, RSS, RSSP, SL, SLM appliances where a synchronized audible /visual audible or visual only appliance is specified. All modules shall be UL listed under Standard 464. Series SM and DSM modules shall be designed to interface with Series AS Audible Strobe Appliances and NS Horn Strobe Appliances to produce a synchronized temporal (Code 3) hom as well as synchronized strobe flash on a two-wire alarm circuit. Other synchronized products are the Wheelock Series RSS, RSSP, SL, SLM visual only appliances and - Series AH and NH Hom Appliances. SM Sync Module shall incorporate two input NAC circuits for power connection from the Fire Alarm Control Panel; one for the strobe NAC circuit and one for the audible NAC circuit. DSM modules shall provide an additional strobe circuit input/output for control of either two Class "B" NAC circuits or a single Class "A" NAC circuit. Upon activation of the audible silence function at the Fire Alarm Control Panel, the audible signal component of Series AS Audible Strobe and/ or the Series NS Horn Stobe may be silenced while maintaining strobe activation. Series SM or DSM module shall be designed and available in two versions; the SM 12/24 for control of a single Class B NAC circuit and a dual output version, the DSM -12/24 for control of either Class Atwo (2) Class B NAC circuits. The DSM dual circuit version shall provide the additional capability of "daisy- chaining ", that is, the ability to interconnect multiple DSM's for synchronous horn and strobe operation on multiple NAC circuits. Interconnection capability shall be for a maximum of 40 NAC circuits. All modules shall operate on either 12 or 24 VDC. Rated average current requirement for the SM 12/24 shall be .014 amperes @ 12 VDC and .025 amperes @ 24 VDC. The DSM 12/24 shall be .020 amperes @ 12 VDC and .038 amperes © 24 VDC. A single circuit SM Sync Module shall be capable of handing a 3 ampere load at 12 or 24 VDC and the dual circuit DSM Sync Module shall be capable of handling a Toad of 3 amperes per NAC circuit at 12 or 24 VDC. All versions shall be polarized for DC supervision and shall incorporate screw terminals for in /out field wiring of #18 to #12 AWG wire size. The SM and DSM Sync modules shall mount to a 4- 11/16" x 2 -1/8" deep backbox. MADE IN THE USA NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Distributed By: NATIONAL SALES OFFICE 800 - 631 -2148 3 YEAR WARRANTY Canada 800 - 397 -5777 XENIA E -Mail: Info@wheelockinc.com http: / /www.wheelockinc.com Member _ I 273 BRANCHPORTAVENUE • LONG BRANCH, NJ 07740 • TEL: 732 - 222 - 6880 • FAX: 732 222 - 2588 S3000 08/00 SIEMENS Fire Safety U -MHU Series Models U -MHU Electronic Sync /Non -Sync Horn ENGINEER AND ARCHITECT SPECIFICATIONS • The AdapterTM /U -MCS feature offers four field selectable candela values — 15/75, 30/75, 75 or 110 for wall & ceiling mount • Sync strobes and sync temporal horns, with horn I11I1 silence on 2 wires . • Distinctive temporal horn p FIRE _ ,_ • Internally adjustable volume control • Low current draw • Single gang and universal mount configurations • UL 1971 & UL 464 listed - CSFM, ULC, & NYMEA • UL 1971 listed for both wall and ceiling mount 1 • ADA/NFPA/ANSI compliant 111. • Screw terminals accept 12 awg wire • Synchronization requires Dual Sync Control FIRE f .`,a #; Module or PAD -3 • Made in U.S.A., ISO 9001 quality crafted Description '‘!1/41/8 5 Detail - Adapter The U-MHU-1G, U -MHU -1 G -W and U -MHU, U -MHU -W SC selector switch Sync Electronic Horns and U- MHU -MCS, U- MHU -MCS -W Horn Strobes provide synchronous strobes with synchro- An internal volume control provides adjustment of dBA nous temporal tone signals on one pair of wires or output levels. temporal or steady tone in a non -sync mode. 2 3 The U -MHU -1 G, U -MHU -1 G -W mounts to a single gang box, the U -MHU, U -MHU -W and U- MHU -MCS, U- MHU -MCS -W have a universal mounting plate for t 4 Max. Volume 1 gang, 2 gang or 4" square box mounting. Detail - Volume adjust Siemens Fire Safety notification appliances are (factory set at max. volume) designed with the installer in mind.They are constructed The U- MHU -MCS, U- MHU -MCS -W strobe construction with the electronics in the housing and not in the box. consists of a Xenon flashtube with solid state circuitry for This design eliminates possible ground faults from maximum reliability and efficiency.The strobe has a crowded electrical boxes.The Adapter /U -MCS feature rounded dome shape made of clear polycarbonate. offers four field selectable candela settings - 15/75, 30/75, 75 or 110. CATALOG NUMBER 2560 Replaces Catalog Sheet Number 2555 , 0 The U -MHU -1 G, U -MHU -1 G -W, U -MHU, U -MHU -W and Listed operating range is 20 to 31 VDC /FWR U- MHU -MCS, U- MHU -MCS -W are used on circuits with Temporal maximum UL measurements are 83.6 db at steady power or a Dual Sync Control Module or PAD -3. 24VDC /FWR. Steady tone maximum UL measurements Not for use on coded circuits. are 87.8 db at 24VDC /FWR taken in free air at 360° around the device and averaged. Typical readings are . Environmental frontal sound readings taken with a dB meter with signal 32 °F to 120 °F (0 °C to 49 °C) with 85 % humidity mounted on wall. Rated for indoor use 32 °F to 120 °F, (0 °C to 49 °C), at RH 85 %. _ Operating Voltage Range Limits ( -ite Mounted) ( -WW : White) Horn: 20 -31 Vdc orVFWR Strobe: 16 -33Vdc orVFWR Strobe Intensity Setting Strobe Current Draw 15/75 cd 63 mA Typical Hom Ratings at 10 Feet* 30/75 cd 84 mA 75 cd 143 mA Temporal Horn — 110 cd 178 mA Maximum: 95 db @ 25 mA Minimum: 90 db @ 17 mA Control Module Specifications: * Typical dBA ratings are frontal sound readings Maximum Current Output: 3 Amps Max. not taken with a dB meter with signal mounted on wall. to exceed NAC rating DSC Module OperatingVoltage: 20 to 31 Vdc orVFW Dimensions DSC Module Operating Current: Non - Silenceable � t y 4 _ , 3f4 Circuit side _� y I I .1F. tn , � - ( �.tn• 55mA, Silenceable 1 W Circuit side .005 Amps. 4.,n• a�4' °V III Maximum Current Output: 3 Amps max. not to VIII exceed Circuit rating a t -.- L 1, 2 or 4 Square Mounting i . 4.314' --- --2 -112' O -t/Y .. 0 V III !� 4-314 O . T 'u I , / FIRE \ J < --- J or selector t I or Switch - -. e' For wiring diagram for U -MHU Series Horn /Strobes refer Ordering Information to Installation Instruction Sheet U -MHU Series Hom Wall Mount Low Volume High Volume High Volume Model Number Description Part Number Horn Current Horn Current dB Rating @10' U- MHU -1G ELC Sync /Non -Sync Horn 24VDC 500-699591 17ma 25ma 95 db U- MHU -1G -W ELC Sync /Non -Sync Horn 24VDC 500 - 699592 17ma 25ma 95 db U -MHU ELC Sync /Non -Sync Horn 24 VDC 500-699594 17ma 25ma 95 db _ U- MHU -W ELC Sync /Non -Sync Horn 24VDC 500-699593 17ma 25ma 95 db Low Volume High Volume High Volume Model Number Description Part Number Horn Current Horn Current dB Rating @10' U- MHU -MCS ELC Sync /Non -Sync Horn w /Strobe (Red) 500- 699587 17ma 25ma 95 db U- MHU -MCS -W ELC Sync /Non -Sync Horn w /Strobe (White) 500-699588 _ 17ma 25ma 95 db *AII current measurements made at 24VDC Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard Florham Park. NJ 07932 12/02 Brampton, Ontario Siemens Building Technologies Tel: 2 10M Canada L6T 5E4 9 9 F AX. (973) (973) 593 593. 0 SFS-IG Tel: (905) 799 -9937 December 2002 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799.9858 Supmcedes sheet dated 8107 fE L MEA INC. FIRE ALARM SYSTEMS Helping People Take Action . SERIES SM AND DSM SYNC MODULES Description Wheelock's Series SM and DSM Sync Modules are utilized with the Series AS /AH, Series NS /NS4 /NH, Series RSS, Series RSSP, • • Series SL /SLM and selected strobe applications with other Wheelock combination appliances. When used with Series AS Audible Strobes and /or Series NS Horn Strobes, the SM and DSM Sync Modules provide independent operation of synchronized temporal pattern (code 3) horn and synchronized strobe flash, as well as the ability to silence the horn while maintaining the strobe flash. while using only a single pair of • • wires. The sync modules are available in two versions; the SM 12/24 for control of a Class B NAC circuit; and a dual output Series SM or DSM version, the DSM 12/24 for control of either a Class A or two (2) Class B NAC circuits. Features • Approvals include: Underwriters Laboratories (UL 1971) Listing, New York City (MEA), California State Fire Marshal (CSFM) and Chicago (BFP) on all models. • Uniquely designed to accept an independent strobe and audible input from the FACP and convert to a single output that • connects to Wheelock's Series AS or Series NS family of audible strobes. • Series SM and DSM Sync Modules can also be used to synchronize Wheelock's Series RSS, RSSP, SL and SLM Sync Strobes. • 3 ampere per circuit current handling at 12 or 24 VDC. • Low operating current draw. • Compatible with all standard fire alarm control panels. • Meets the NFPA -72 (1999) requirement for Temporal Pattern when used with the Series AS /AH and /or Series NS /NS4 /NH. • 3 year warranty. Copyright 2000 Wheelock. Inc. All rights reserved. NOTE: All CAUTIONS and WARNINGS are identified by the symbol0 . All wamings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. Table 1: Sync Module (SM) Current Requirement (AMPS) Table 2: Dual Sync Module (DSM) Current Requirement (AMPS) Rated Average Rated Peak Rated Inrush Rated Average Rated Peak Rated Inrush Voltage Current Current Current Voltage Current Current Current Strobe Audible Strobe Audible Strobe Audible Strobe Audible Strobe Audible Strobe Audible 10.5 VDC 0.008 0.004 0.032 0.004 0.032 0.004 10.5 VDC 0.015 0.003 0.112 0.003 0.299 0.053 12.0 VDC 0.009 0.005 0.036 0.005 0.034 0.005 12.0 VDC 0.016 0.004 0.117 0.004 0.352 0.065 24.0 VDC 0.015 0.010 0.074 0.010 0.062 0.010 24.0 VDC 0.030 0.008 0.130 0.008 0.662 0.118 31.0 VDC 0.018 0.012 0.090 0.012 0.078 0.012 31.0 VDC 0.040 0.010 0.138 0.010 0.831 0.152 10.5 VRMS 0.014 0.006 0.066 0.006 0.058 0.006 10.5 VRMS 0.025 0.010 0.158 0.010 0.416 0.068 12.0 VRMS 0.015 0.007 0.072 0.007 0.066 0.007 12.0 VRMS 0.027 0.011 0.158 0.011 0.479 0.083 24.0 VRMS 0.030 0.013 0.108 0.013 0.078 0.013 24.0 VRMS 0.044 0.022 0.194 0.022 0.838 0.138 31.0 VRMS 0.040 0.017 0.122 0.017 0.086 0.017 31.0 VRMS 0.054 0.028 0.218 0.028 1.111 0.213 A WARNING: MAKE SURE THAT THE TOTAL CURRENT REQUIRED BYALLAPPLIANCES THAT ARE CONNECTED TO A SM OR DSM DOES NOT EXCEED 3.0AOR EXCEED THE RATING OF THE FIRE ALARM CONTROL PANEL'S PRIMARY AND SECONDARY POWER SOURCES AND NAC CIRCUITS. OVERLOADING THESE SOURCES COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGEAND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. When calculating the total current, use Tables 1 & 2 to determine the highest value of "Rated Average Current" for the SM or DSM (across the listed voltage range), then add this value to the total current for any other appliances powered by the same source and include any required safety factors. Refer to Instruction Sheet for addtional information. WARNING: MAKE SURE THATALL FUSES USED ON NAC CIRCUITS ARE RATED TO HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL APPLIANCES ON THOSE CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE NAC CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. Table 3: Current Consumption of the SM and DSM Modules Current Required Current Required SM DSM from FACP from FACP Output Circuit Description of SM /DSM Module Module Module Audible NAC Circuit Strobe NAC Circuit Ref. Fig. Class "B" with Audible Silence (single circuit) Y 0.010 0.015 1 Class "B" with No Audible Silence (single circuit) Y 0.025 2 Class "B" with Audible Silence (single circuit) Y 0.008 0.030 3 Class "B" with No Audible Silence (single circuit) Y 0.038 4 Class "B" with Audible Silence (dual circuit) Y 0.008 0.030 3 Class "B" with No Audible Silence (dual circuit) Y 0.038 4 Class "A" with Audible Silence (single circuit) Y 0.008 0.030 5 Class "A" with No Audible Silence (single circuit) Y 0.038 6 Note: SM Sync Modules are rated for 3.0 amperes at 12/24 VDC; DSM Dual Sync Modules are rated for 3.0 amperes per circuit. The maximum number of interconnected DSM modules is twenty (20). £ CAUTION: Use SM or DSM Sync Modules only on NAC circuits with continuously applied voltage. Do not use SM or DSM Sync Modules on coded or interrupted NAC circuits in which the applied voltage is cycled on and off. ACAUTION: Power Boosters may be used in conjunction with the SM or DSM Sync Modules only in the order shown below. Only one SM or DSM Sync Module shall be allowed on a NAC circuit. Do not connect Power Booster to the NAC circuit after the one SM or DSM Sync Module. Refer to Power Booster instruction manual for proper application and installation. ACAUTION: SM and DSM Sync Modules may be used in conjunction with a POWERPATH only in the order shown below. Each output can use Sync Module (SM or DSM) to drive audible or visual synchronized appliances. Do not connect POWERPATH to the NAC after a Sync Module. FIRE POWERPATH AS /AH, ALARM OR NS /NS4 /NH, CONTROL OTHER SM OR DSM RSS, RSSP, PANEL POWER SL, SLM (FACP) BOOSTERS APPLIANCES SM or DSM Connection Diagram with Power Booster sa END CF- LIFE R®SI:2 (EELRI STROBE 9C14 + 0.111 Pa 1.6, Arl rH Cacur + Bvt �.0 fi Mr161 • AD- � i • :, , 1I 10 NW AS NS Ali NI CtRCI.rr at le _) CR B1fi 4 � / . Alf8 E Important: AS, NS, NH and AH appliance draw power from strobe appliance clrcait auly. FIG. 1 SINGLE CLASS "B" CIRCUIT WITH AUDIBLE SILENCE FEATURE SM • • STROBE • -• STROBE OUT C • OUT �'� al �..� ®I© A fii • PCi • • EOLR SE •-• • AUDIBLE E 1 NOTESE NOT & 2 NAC CIRCUIT • •• AUDIBLE FIG. 2 SINGLE CLASS "B" CIRCUIT WITH NO AUDIBLE SILENCE FEATURE DSM • SYNC • • SYNC STROBE MAC • OUT 1 1/2221:121 CIRCUIT 01 EOLR - MINUS • AUDIBLE SEE SEE NOTE 1 NOTES 1 & 2 AUDIBLE NAC EOLR CIRCUIT 02 AUDIBLE NOTE 5 • OUT 2 y211 10 • IN 2 2 EOLR STROBE MA _MINUS 2 CIRCUIT 52 SEE SEE SEE NOTE 5 NOTE 1 NOTES 1 8 2 FIG. 3 DUAL CLASS "B" CIRCUIT WITH AUDIBLE SILENCE FEATURE DSM • SYNC • • SYNC • OUT 1 • IN 1 11 IC �©© � IC EOLR I 1 MINU31 SEE • AUDIBLE NOTE 1 NOTES 1 d 2 NAC CIRCUI AUDIBLE - Ii11]EOLR • ` MINUS 2 NAC CIRCUIT 02 - SEE SEE SEE NOTE 2 NOTE 1 NOTES 1 8 2 FIG. 4 DUAL CLASS "B" CIRCUIT WITH NO AUDIBLE SILENCE FEATURE DSM O SYNC • • SYNC STROBE NAC • OUT 1 11113112 © CIRCUIT OUT • IN 1 - MINUS 1 AUDIBLE NAC IRCUIT OUT SEE SEE . • AUDIBLE NOTE 1 NOTES 1 & 2 �• AUDIBLE AUDIBLE NAC CIRCUIT RETURN • NOTE S -• IOUT 2 1138 101 • • MINUS 2 , STROBE NAC CIRCUIT RETURN - SEE SEE SEE NOTE 3 NOTE 1 NOTES 1 & 2 FIG. 5 SINGLE CLASS "A" CIRCUIT WITH AUDIBLE SILENCE FEATURE DSM • SYNC • O SYNC • OUT 1 121 � ©w� ®�© • IN 1 MINUS 1 I • AUDIBLE N0 1 • OUT 2 SEE NOTES 1 6 2 Liiiii UDIBLE NAC IRCUIT OUT AUDIBLE ��� ©� ©�� ©�m - • N 2 • AUDIBLE NAC MIN 2 CIRCUIT RETURN SEE SEE NOTE NOTES 1&2 FIG. 6 SINGLE CLASS "A" CIRCUIT WITHOUTAUDIBLE SILENCE FEATURE DSM N = MAXIMUM OF DSM DSM 2 20 DSM S • • • 22 22 Z Z W N C O J N N j J o • - N H J J N I O O M N N \\ N 3 G N O N N O f M a r . N V l C 3 i < < O = 3 o i= a < = 2 g o W _ • • 2 • • • 2 • • 2 _to • • 2 • • 2 AAI _ • • 2 SEE mmm 5k \ 000 m m m p\ Q m m m m m m 0 0 0 53 0 NOTE• FROM FACP \ • NAC CIRCUIT FOR HORN SILENCE FIG. 7 DSM'S WIRED FOR MULTIPLE SIGNAL CIRCUITS ALL IN SYNCHRONIZATION, 20 CLASS "A" CIRCUITS OR 40 CLASS "B" CIRCUITS MAX DSM POWER BOOSTER • SYNC • 0���� +1 • SYNC SEE F NOTE 1 O • AuoIBIE A NOTE 1 NOTES 6 2 C NAC CIRCUIT EOLR P • - AUDIBLE • OUT I ��� ©� ©V� ©�� E OLR IN 2 O • OU • • , STROBE NAC MINUS 2 SEE CIRCUIT 02 SEE SEE NOTE5 NOTE NOTESI&2 FIG. 8 DUAL CLASS "B" CIRCUIT WITH AUDIBLE SILENCE FEATURE CONNECTED WITH POWER BOOSTER Notes 1. Non -Sync Appliances can be installed before or after a SM or DSM. If the Non -Sync appliance requires audible silence, four wire connection is necessary with the strobe circuit connected before the SM or DSM NAC circuit, and the audible leads connected to a silenceable NAC circuit from the FACP. 2. The audible appliance produces a momentary interruption (approximately 25ms) each time the strobes flash. 3. Circuit #2 may be omitted if only 1 circuit is required when using the DSM. 4. Power Boosters may be used in conjunction with the SM or DSM Sync Modules ONLY in the order shown in Figure 8. OnIy one SM or DSM Sync Module Output shall be allowed on a NAC circuit. Do not connect Power Booster to the NAC circuit after the one SM or DSM Sync Module. Refer to Power Booster instruction manuals for proper application and installation (Installation Instruction P83123 or SM & P83177 DSM). 5. Non -Sync Audible Appliances can be installed on the audible NAC. Be aware of the current requirement for the SM or DSM module. See table 3. AWARNING: ALTHOUGH UL TESTING HAS VERIFIED THAT SYNC MODULES FUNCTION EVENAT 80% OF THEIR MINIMUM RATING AND 110% OF THEIR MAXIMUM RATING, WHEELOCK STRONGLY RECOMMENDS THAT THE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED INPUT VOLTAGE RANGE. THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/ OR OTHERS. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the • time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amend- ments and the requirements of the local authority having jurisdiction (AHJ). A WARNING: CONTACT WHEELOCK FOR "INSTALLATION INSTRUCTIONS" (P83123 -SM & P83177 -DSM) AND "GENERAL INFORMATION" SHEET ON THESE PRODUCTS. These documents do undergo periodic changes. It is important that you have current information on these products. These materials contain important information that should be read prior to specifying or installing these products including: • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NAC CIRCUITS TO HANDLE MAXIMUM INRUSH OR PEAK CURRENTS FROM ALL APPLIANCES ON THOSE NAC CIRCUITS. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHINAPERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED IN PUT VOLTAGE RANGE. • INSTALLATION IN OFFICEAREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON NAC CIRCUITS WITH CONTINUOUSLYAPPLIED OPERATING VOLTAGE. DO NOT USE STROBE ON CODED OR INTERRUPTED NAC CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH. Ordering Information • Average - Order Input Cum3nt Model Code Voltage ©12 • SM-24-R 6369 VV f .014 W 24 .025 W F; : DSM -24-R' 6374 12 .020 W 24 .038 W R = Red * Average current per actual Wheelock Production Listing @ 12 & 24 VDC Nominal Voltage. ** Refer to Data sheet # S - 7000 for Mounting Options. * ** The maximum number of interconnected DSM modules is twenty (20). The total distance from the first to the last DSM shall not exceed 1,000 feet of #18 AWG wire. Use only #18 AWG wire. Architects and Engineers Specifications The sync modules shall be Wheelock Series SM or DSM Sync Modules. Series SM or DSM Sync Modules shall be the master controllers for Wheelock Series AS /AH, NS /NS4 /NH, RSS, RSSP, SL, SLM appliances where a synchronized audible /visual audible or visual only appliance is specified. All modules shall be UL listed under Standard 464. Series SM and DSM modules shall be designed to interface with Series AS Audible Strobe Appliances and NS Horn Strobe Appliances to produce a synchronized temporal (Code 3) horn as well as synchronized strobe flash on a two-wire alarm circuit. Other synchronized products are the Wheelock Series RSS, RSSP, SL, SLM visual only appliances and . Series AH and NH Hom Appliances. SM Sync Module shall incorporate two input NAC circuits for power connection from the Fire Alarm Control Panel; one for the strobe NAC circuit and one for the audible NAC circuit. DSM modules shall provide an additional strobe circuit input/output for control of either two Class "B" NAC circuits or a single Class "A" NAC circuit. Upon activation of the audible silence function at the Fire Alarm Control Panel, the audible signal component of Series AS Audible Strobe and/ or the Series NS Horn Stobe may be silenced while maintaining strobe activation. Series SM or DSM module shall be designed and available in two versions; the SM 12/24 for control of a single Class B NAC circuit and a dual output version, the DSM -12/24 for control of either Class A two (2) Class B NAC circuits. The DSM dual circuit version shall provide the additional capability of "daisy- chaining ", that is, the ability to interconnect multiple DSM's for synchronous horn and strobe operation on multiple NAC circuits. Interconnection capability shall be for a maximum of 40 NAC circuits. All modules shall operate on either 12 or 24 VDC. Rated average current requirement for the SM 12/24 shall be .014 amperes @ 12 VDC and .025 amperes © 24 VDC. The DSM 12/24 shall be .020 amperes @ 12 VDC and .038 amperes © 24 VDC. A single circuit SM Sync Module shall be capable of handing a 3 ampere load at 12 or 24 VDC and the dual circuit DSM Sync Module shall be capable of handling a load of 3 amperes per NAC circuit at 12 or 24 VDC. All versions shall be polarized for DC supervision and shall incorporate screw terminals for in /out field wiring of #18 to #12 AWG wire size. The SM and DSM Sync modules shall mount to a 4-11/16" x 2-1/8" deep backbox. MADE IN THE USA NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Distributed By: NATIONAL SALES OFFICE 800 - 631 -2148 3 YEAR WARRANTY Canada 800 - 397 -5777 NEM E -Mail: Info @wheelockinc.com http: / /www.wheelockinc.com Memb - 273 BRANCHPORTAVENUE • LONG BRANCH, NJ 07740 • TEL: 732 - 222 -6880 • FAX: 732- 222 -2588 S3000 08/00 •