Report Underwriters Laboratories Inc. - 2600 N.W. Lake Rd. Underwriters Camas, WA 98607 -8542 877 -UL -HELPS Laboratories Inc.() I - v August 4, 2009 FE5693, 09CA22264 Turn -key Controls Ltd 15 Kolibri Way Vernon, V1 H 1 E3 Canada Attention: Mr. Doug Halvorson Subject: Field Evaluation of Motor Control Center (5 sections) - 1 unit Dear Mr. Halvorson: On May 20, 2009, UL conducted a Field Evaluation on the above subject equipment. It was determined that one or more of the products evaluated did not comply with the applicable requirements and UL's Field Evaluated products Mark(s) were not applied to the product(s). A Discrepancy Report was submitted to you on May 26, 2009. Please find attached a copy of the Preliminary Findings Report(s). This report should be reviewed to verify that the information provided is complete and correct. The report provides the details of the evaluation up to this time and identifies each of the non - conforming issues along with the required corrective actions. When the corrective actions have been completed and the equipment is ready to complete the evaluation, please contact our FE coordinator to schedule a return visit, at 877 -UL -HELPS (877- 854 - 3577), ext. 44701 or email: fieldevaluations @us.ul.com (please add " *Melissa A. Hanney" on subject line). Please note that on August 20, 2009 we will be closing this project for no activity, and bill you for the remaining charges. If you should have technical questions regarding this report, please contact me as noted below. Very Truly Yours, Titus S. Vader Field Engineering Services Direct Line: 503 - 349 -8015 Email: Titus.S.Vader @us.ul.com cc: Mr. Gary Noble - Senior Electrical Inspector, CITY OF TIGARD Underwriters Laboratories Inc. 2600 N.W. Lake Rd. ■ Camas, WA 98607 -8542 ' " ',. Underwriters 877-UL-HELPS Laboratories Inc. Preliminary Findings Report For Motor Control Center (5 sections) - 1 unit Installation Site: Durham Advanced Wastewater Treatment Facility 16580 SW 85th Avenue Tigard, OR 97224 Requested by: Turn -key Controls Ltd 15 Kolibri Way Vernon, V1 H 1E3 Jurisdiction: CITY OF TIGARD Tigard, OR 97223 UL Reference No.: Proj.: 09CA22264 Submitted by: = I4 File: FE5693 Titus S. V Field Engineer Date: August 4, 2009 Reviewed by: eQ L 41 °'�""j Sudiptb Chakraborty Field Engineer Table of Contents 1.0 Executive Summary 1 2.0 Conditions of Acceptability 2 3.0 Referenced Standards 3 4.0 Product Evaluated 3 5.0 Construction Evaluation 4 6.0 Electrical Test Results 9 7.0 Evaluation Discrepancies 9 8.0 Reserved 9 9.0 Test Equipment 12 APPENDIX A - Photographs Al 1.0 Executive Summary Federal OSHA and many local jurisdictional regulations require products to be Listed or Evaluated by a recognized testing organization. Field Evaluations are one means to assure that custom or otherwise non - certified products meet applicable product safety standards, Codes, Safety Orders, or other industry standards. A Field Evaluation provides an unbiased independent assessment of products to the essential requirements of applicable product safety standard(s) for a specific end use location. The engineering assessment provides the Authority Having Jurisdiction with information to assist in the decision on approval of the product and related installation. The purpose of this project was to provide an assessment on a product that was not Listed or otherwise found not to be certified by a testing laboratory recognized by the Authority Having Jurisdiction. Products undergoing this evaluation process do not result in establishing a UL Listing, UL Recognition, or UL Classification. UL has not established a factory follow -up service program to determine the conformance of any subsequently produced, relocated, or otherwise altered product(s) or system(s). At the request of Mr. Doug Halvorson of Turn -key Controls Ltd, a Field Evaluation project was initiated. The preliminary evaluation was completed at the Durham Advanced Wastewater Treatment Facility, 16580 SW 85th Avenue, Tigard, OR, on May 20, 2009 by UL Engineer, Titus S. Vader. The results of the preliminary evaluation and testing identified items that are not in compliance with the applicable product safety standard(s) and therefore require corrective action(s) as detailed in Section 7.0 of this report. When these discrepancies are corrected, a final inspection and any remaining testing will be required to complete the Field Evaluation. If this follow -up evaluation determines all issues are resolved and the product to be in compliance, UL will consider the product acceptable and will apply the Field Evaluated Product Mark. Please note that final approval of this product and the installation is by the CITY OF TIGARD inspecting authority. Field Engineering Services Report Page 1 2.0 Conditions of Acceptability Except where otherwise stated in the product description and evaluation sections of this report, this evaluation and the application of the Field Evaluated Product Mark is subject to the following Conditions of Acceptability. 2.1 Except for like- for -like component replacement in the event of component failure, no change, alteration, or addition to the product or system shall be made that would alter the construction, operation, function, layout, source of supply, physical location, or any other change, alteration, or addition that may be made to the product. If such changes, alterations, or additions to the product occur, the Field Evaluated Product Mark shall be considered invalid and a separate evaluation shall be required to determine compliance with the applicable product safety Standards under the changed conditions. 2.2 The completed evaluation and application of the UL Field Evaluated Product Mark by UL does not assume liability on the part of UL and does not relieve the manufacturer, installer, user, or other relevant parties of their responsibilities. The product evaluation is based on adherence to sound engineering practices, and compliance with the applicable product safety standards and installation Code. 2.3 This evaluation considered the risks associated with electric shock, fire, and casualty hazards as specified in the evaluation section of the report only. No other hazards were evaluated during this evaluation. 2.4 Unless otherwise stated in the product description, this product was evaluated for installation in an indoor, dry, normal environment only. The product was not evaluated for installation in any hazardous classified location as defined in the latest edition National Electrical Code as adopted by the National Fire Protection Association. The product was not evaluated for installation in an environment where subject to rainfall, water spray, steam, or exposure to any corrosive chemicals that will cause deterioration of the enclosure or components. If such environment is encountered in the future, the product will require re- evaluation. 2.5 The UL Field Evaluated Product Mark shall not be considered as equivalent to the UL Listing Mark, UL Recognized Component Mark, or UL Classified Product Mark. The UL Field Evaluated Product Mark indicates compliance with the applicable parts of the Standards referenced in Section 3 at the time the Mark was applied and with consideration only for the final installation site. The applicable parts included in the evaluation are the construction review, markings, and those testing protocols that are non - destructive. Field Engineering Services Report Page 2 3.0 Referenced Standards • UL 845, Standard for Motor Control Centers, 5th edition, revised: August 25, 2006 • NFPA 70 National Electrical Code (NEC), 2008 Note: The NEC is only referenced for those construction features necessary to ensure the product can be properly installed in accordance with the NEC. 4.0 Product Evaluated 4.1 Motor Control Center (5 sections) - 1 unit The equipment is a new Motor Control Center. 4.2 Nameplate Data Manufacturer: ECM Model number: EEMAC Serial number: SO 0811 -920 Electrical ratings: Voltage 480 Volts AC Current (FLA) Horizontal: 600 A Verical: 300 A Phase 3 phase, 3 wire Frequency 60 Hertz 4.3 Main Overcurrent Protection The main overcurrent protection was provided by: Manufacturer's instructions properly specify the over current protection to be provided by the installer. Field Engineering Services Report Page 3 5.0 Construction Evaluation The following specific areas were evaluated using the procedure indicated. Unless stated otherwise in Section 7.0, all the following items were found to comply with the applicable part(s) of the referenced standard(s). Additional characteristics and features unique to the product, with consideration for the final installation site, were further addressed as required by the standard procedure and applicable product safety standard(s). 5.1 Construction Inspection Method: A construction inspection was completed with particular emphasis on the following items. • Critical component certification • Spacings • Guarding of live parts • Wiring and wiring methods • Grounding and bonding • Terminations • Overcurrent protection • Separation of circuits • Drawings and instructions • Markings • Conductor ampacities • Damaged components Results: The product was found to comply with the construction requirements identified above and the standard(s) indicated in section 3. 5.2 Critical Components Method: The following critical components were inspected for evidence of Listing or Recognition in accordance with UL policies: • Circuit breakers • Fuses and fuse holders • Wire and cable assemblies • Power disconnecting devices • Transformer and power supplies • Terminal blocks • Relays • Receptacles • Motors • Contactors • Heater loads • User interface control devices • Motor overload devices • Enclosures • Safety circuit components Results: The critical components identified above were found to be Listed or Recognized by a testing laboratory acceptable to UL in accordance with UL policies. Field Engineering Services Report Page 4 5.3 Grounding and Bonding Method: All accessible metal parts were verified visually and by test to be bonded together and to be connected to the supply equipment - grounding conductor. Where applicable, a bonding continuity test was conducted and the results recorded. Results: The product was verified to be grounded and bonded in accordance with applicable standards referenced in Section 3 and Article 250 of the NEC. The product had an identified terminal for the connection of the supply equipment - grounding conductor or had a suitable cord supplied with equipment - grounding conductor included. 5.4 Guarding of Live Parts Method: The product was visually inspected to ensure that all components were assembled in a suitable enclosure and made effectively inaccessible to unauthorized persons. An articulated finger probe was used to measure access where necessary. Vent openings were verified not to align with potential discharge paths for gases expelled from circuit breakers when clearing fault conditions. Results: Enclosures were found to prevent contact with moving parts, electrically energized parts, and hot parts. Enclosures provided an acceptable degree of protection for internal components (according to the product's installation environment). All electrically live parts external to the enclosure were guarded as required by the applicable standards. There were no electrically hazardous energized parts accessible from the exterior of the ultimate enclosure as required by Section 110.27 of the NEC. 5.5 Wiring and Wiring Methods Method: All conductors were inspected for Listing or Recognition by a recognized testing laboratory in accordance with UL policies. The conductors were examined for proper ratings (voltage, ampacity, temperature, flexibility, flame rating and environmental) as required for the application. The wiring methods were verified to comply with the applicable standards and provide proper physical protection including strain relief where applicable. The wiring terminations were inspected for correct application, number of conductors in accordance with their Listing and correct ampacity based on temperature ratings. Field Engineering Services Report Page 5 Results: Detailed as follows. 5.5.1 Supply Connections - The supply connection point(s) was examined and determined to have proper terminals and identification provided. 5.5.2 Wiring Methods — Internal wiring methods conformed to the applicable standard. All wiring was routed, secured, and protected from moving parts, external heat sources, and sharp edges. 5.5.3 Separation of Circuits — Unless provided with insulation rated for the highest voltage involved, wiring of low voltage and line voltage circuits within enclosures were found to be segregated or separated by barriers. The product wiring for low voltage and line voltage circuits external to enclosures were found installed in separate raceways or wireways. 5.5.4 Wire Terminations - All wire terminations were found to be suitable for the number and the size conductor installed. 5.5.5 Strain Relief — External conductors and cable assemblies entering enclosures and internal conductors were found to be adequately secured to prevent strain from being transmitted to terminations. 5.5.6 Conduit Connections All conduits, gutters, and wireways were found to be properly sized for the number and size of conductors and to be properly supported. 5.6 Overcurrent Protection Method: The product was inspected to ensure proper overcurrent protection was provided for the internal conductors and components. Overcurrent devices were inspected for proper ratings including voltage, ampere rating, interrupting rating, suitability as branch circuit protection, where required, and Listing. Field Engineering Services Report Page 6 Results: Detailed as follows: 5.6.1 Supply The product was verified as having main overcurrent protection as indicated in section 4.3, Main Overcurrent Protection. Internal overcurrent protection was verified as being properly rated for the intended application. All devices designed to open under fault conditions were verified as having proper short circuit interrupting ratings. 5.6.2 Conductors Internal conductors to the product or installed as part of the product were determined to have proper overcurrent protection. 5.6.3 Components Components such as transformers, heater elements, and motors were verified to have overcurrent protection with the correct ratings and proper type. 5.7 Suitability for Installation Method: The product was inspected to ensure suitability for installation in accordance with the NEC as specified in the referenced standard(s). This inspection specifically determined if correct working space and clearances could be provided, that proper wire bending space for all field wiring was provided, provisions for mounting were provided, and areas for conduit entries, as applicable, were in place. Results: Detailed as follows: 5.7.1 Wire Bending & Gutter Space Wire bending space for all field wiring was verified as being in accordance with the NEC. 5.7.2 Clearance and Working Space The product was verified that it is or could be installed with acceptable access, clearances, working spaces and distances from combustibles. Field Engineering Services Report Page 7 5.8 Markings Method: The product nameplate was inspected to ensure all applicable information was provided. Other markings including hazard - warning labels, fuse replacement markings, environmental limitations and installation type markings were verified as being present, in the proper location, and provided in the correct format. Results: Required Markings were evaluated for the product according to the applicable UL Standard(s). Additional markings were identified for the installation site, as the working environment requires. 5.8.1 Unit Nameplate A permanent nameplate, suitable for the intended installation environment and with all the applicable information was verified as being present. The nameplate was verified as being visible or accessible after installation, or located for access in accordance with the provisions in the referenced standard(s). 5.8.2 Fuse Replacement Fuse replacement markings were provided and installed at all fuse locations or on a permanent chart suitable for the environment affixed to the product enclosure. 5.8.3 Hazard Warning Labels Applicable hazard warning markings were installed on or internal to the product identifying known hazards. Field Engineering Services Report Page 8 6.0 Electrical Test Results Testing was completed to verify the product was operating within normally expected parameters. Unless stated otherwise in Section 7.0, all the following items were found to comply with the applicable part(s) of the referenced standard(s), The testing completed, detailed in the following paragraphs, followed the production testing requirements in the applicable product safety standards but as a minimum included: 6.1 Grounding and Bonding Method: Grounding and bonding continuity was verified by the ohmmeter method. The ohmmeter method verified only the grounding continuity from the supply equipment grounding conductor termination to any exposed conductive metal part that is likely to become energized. The maximum resistance measured or calculated from the current test must be less than or equal to the requirement in the referenced product safety standard. Results: The grounding continuity and /or bonding test results indicate that adequate electrical continuity or bonding is provided on the product. 7.0 Evaluation Discrepancies 7.1 Horizontal Bus Rating The horizontal bus supplying power to each section as well as the supply bus to the motor control center (MCC) is undersized for the rating of the overall MCC. The bus is 1 -1/2 "x1/4" with a cross sectional area of 0.375 square inches, hence its rating being 375 Amps max. The MCC is rated 600 Amps. Action Required: Since the horizontal bus must have a continuous current rating of 600A or higher, de- rating the MCC is not acceptable. Install another bus 1 -1/2 "x1/4" on top of the existing horizontal bus and supply connection bus to increase the rating to 600 Amps. Reference: UL 845, Section 5.3.2 and 8.2.16.2 Field Engineering Services Report Page 9 7.2 Markings The MCC was provided with two nameplates on two sections. However, the following information shall be given by the manufacturer for each section: a) Manufacturer's name or trademark b) Type designation, serial number, or equivalent c) Section number (i.e. Section 1 of 5, Section 2 of 5 etc.) d) Electrical ratings as noted below 1) Voltage (Volt, V, Vac, Vdc); 2) Phase (0, phase); 3) Frequency (Hz, hertz); 4) Horizontal power bus ampacity (i.e. 600 A) 5) Vertical power bus ampacity (i.e. 300 A) 6) Bus short- circuit current ratings (A rms sym, or A dc V max). e) Enclosure type; f) Termination and wiring information, as follows: 1) Tightening torque for field- installed conductors (lb-in, or N -m). 2) Required temperature rating for field installed power conductors ( °C); 3) Material requirements for conductors (Cu, Al, Cu -AI, AI -Cu). Action Required: Provide nameplates that include the information as noted above for each section. Reference: UL 845, Chapter 6 7.3 Short Circuit Current Rating The short circuit current rating could not be determined since the circuit breakers used in many of the units are instantaneous type and are not rated. According to the referenced standard, when the short- circuit protective device is an instantaneous -trip circuit breaker, it shall be evaluated by design tests. Action Required: Provide test data information showing that using the circuit breakers installed in the units, that the short circuit current rating of 42 KA rms sym. is adequate. Reference: UL 845, Section 5.4.2 Field Engineering Services Report Page 10 7.4 Fuse Replacement Markings Fuse replacement markings specifying the electrical ratings of replacement fuse sizes were not found at the fuseholder or on a chart provided in some of the units. Ensuring continued proper overcurrent protection requires adequate markings for replacement fuses when installed. Providing the fuse type is also recommended for added assurance of correct replacements. Action Required: Provide fuse replacement markings at each fuseholder indicating the voltage and current at the minimum. Alternatively, provide a chart indicating the fuse identification and replacement information specified above. The chart shall be permanently affixed so that is visible when the door or cover is opened. The markings or chart are to be permanent and suitable for the intended installation environment. Reference: UL 845, Section 6.3.45 7.5 Overload Rating The units that contain the Profibus Current Transformer type units (that communicate with the drives and PLC) are marked based on the rating of this device (2.4 to 25 Amps) rather that the range of the adjustable motor overload relay connected to the motor contactor. Action Required: Revise the nameplates to show the overload relay range based on the overload relay connected to the contactor. Reference: UL 845, Section 6.2.2 7.6 Electrical Schematics Branch circuit short circuit and overload protection could not be verified since electrical schematics were not provided. Action Required: Provided electrical schematics showing the voltage, HP and FLA rating of the motors and Toads that the MCC controls, and ensure that the branch circuit overcurrent protection and the branch circuit overload protection is adequate based on the loads involved. Field Engineering Services Report Page 11 8.0 Test Equipment The following test equipment was used as part of the evaluation and testing on this project. The table below identifies this equipment along with the calibration information. Equipment Name Equipment Calibration Identification Due Date Performance Testing Fluke 87V Digital Multimeter 33830 04/03/2010 Field Engineering Services Report Page 12 APPENDIX A - Photographs as f _ _� ',� . yy + Y"-wa _ i a o E �l - l • r C� . ,, § I , . . ' .„via fu Iv' r , . 0 . o u Y t v c ANN "" f - ^� (�-� 'u „, • , - .. %. ';-,), els* ' el el - t------..2 Mg f'D ift to c;) 1,) g! ", ---- '----:—.1111414* ' 4 " * " A P t or - - '-libt, ti,- , - , . . . S Photo 1 _ ) .w.r� IG i li I LW 1 • r it x iora f 1 -` i 2. l ed g e SS LL�, ,, rtiif Photo 2 Field Engineering Services Report Page Al ..... . _ i i I, i ' i •._- I , , , r'. tit CM -.'-,C i31 - i . , c=, . IIII t'''.&:': 1 • ill::;;„ Snail , . __ IIIIIII i I ./ 07 . , ir 4 111111 . . . htva t am a 1 . , • , r--.1., ■ ' Li 4 , p......... ' ''' a ;fle4fo' • - r= 6 - 1111111° "-•• 2 , ---yt- ' _"'•;._ ., ',' • Photo 3 1 win • •• ,,,,,1 ..-....., , ' 1 , I , .., . , tip ' 1 At. l, ' * 0 i.i!ti , I tX I )011 :' '. " ,,, ■ . . "" ''''. .. :• „, t ii ' • itliN '''^ ' ' I l l , 4:1' .. . )1 11 " *--1-1 i - ' '• , I ; ¢•*•*••;! . . i ..- , , int '' .• ' , :jiiii1 ' : I) ,.L, ...„,,,,, , .,...„. 4 ..1.,..._..7%,,,,,--. , .. i. -. •, Photo 4 Field Engineering Services Report Page A2 . , / ... ... , . . , 1 ....----- - . ^ „.....' . _ _ ,:, , , _, „...1, I ? • i i / / - - ;b s'• i .i , , ,/ 4 , 1 0 / 1 ......, \,:t y ;7 4,1 • 1,, , _ ,.: ! ....., ... Itter.' r,,i1 - , ' , / f ill i P , , \ k ;,';';>. r - , I:_, \ 4 , • '' i 4 ,., ,,,, .::,,, , i ' ,., ,-. ir- . - .....0 ,'• :,-,:,,,:. ,,:ff ( 1 ' .i'=2 ' I t . g i . - ,,,, / , ...i... • ■.....■-....... C.' .... .,:.) 6 :, I . L, , . . 2 , • ' ' , Illi MM. 1 I I il ' I P 0 To 0 ‘‘'''' ,r. . .. I — •Kur - Photo 5 E.C.M. ,.. 01 02 03R 04 0 ., C.S.AJENCI. CIA $12 03 04X 0 , 4 8 0 volts Ac/cA 3 Prose 60 Ht. 600 • , 0 H.P. RATED • EEMAC SIZE ILO- 08 I I - 920 ost• 08.12.22, . Intorruptirte Cspacity 42 scA toptelti 4* Augurs EIECTRIC&L CONTROLS El:MON INC eh . ,c.s..A. C Sit Adti in Anod,a F atoorprfi 41 Cilr!,1:13 l LR 1'1114 4119 4 - 4 , DANGER 1114 t t====.11111111 • Photo 6 Field Engineering Services Report Page A3 iii i i i I II I il TyV�{( ' .,1 t o - ammo's • � a Ns r ..,, 1• mat al% • ; ; .. .. _. : .„. 1 J}4' 1 .'',,�i'„1' #'I t P r i. f yy ,tS . y + r t'� �, f _ 4 Photo 7 .a. a . • j ��� J' r 41 4 P r € n : �;!"o. .,ice t # • , xq \ .r 1j1 3 i'� _ K .4& s I E . t - z �' 1 . ' ,. .,- f f • 'Hr' '.d st�� +�y�`iV '�k 2O '. i? . t X114 X47 * /iii161 ,:'' ''.:" 1 ift ' ' '.:'41 • 2 71 1 410Vi,,,, - - ` . ' " Photo 8 Page A4 Field Engineering Services Report