Correspondence N\-cc 1 tog()
City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
July 30, 2007
RE: MECHANICAL FOR GEORGE FOX T I
Project Information
Building Permit: MEC2007 -00409 Construction Type: NA
Tenant Name: George Fox Occupancy Type: B
Address: 12753 SW 68 St. Occupant Load: NA
Area: NA Stories: 2
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The
following corrections shall be submitted prior to issuance of this plan. The response should
be numbered as per the correction list.
1) Please provide details showing support for VAV's and FPB's along with anti -sway
measures to be taken.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
r espectfully, i
�
(1 an Nelson,
Senior Plans Examiner
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
July 30, 2007 UI
RE: MECHANICAL FOR GEORGE FOX TI GARD
r ..
Project Information
Building Permit: MEC2007 -00409 Construction Type: NA
Tenant Name: George Fox Occupancy Type: B
Address: 12753 SW 68 St. Occupant Load: NA
Area: NA Stories: 2
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition.
1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
2. Each appliance shall be provided with a shutoff valve separate from the appliance.
The shutoff valve shall be located in the same room and within six feet of the
appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC
3. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
4. Permanent equipment supported by the structure, 400 lbs and over, shall have their
attachments designed in accordance with the Building Code. 301.16 OMSC
5. Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
6. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
7. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
8. Smoke detectors shall be installed in return air systems with a design capacity
greater than 2000 cfm. Upon activation, the smoke detector shall shut down
• the air distribution system. Smoke detectors shall be connected to a fire alarm
system and shall activate an audible and visible alarm at a constantly attended
location. 606.2, 606.4 & 606.4.1 OMSC
9. Suspended -type unit heaters shall be supported by non - combustible elements that
are designed and constructed to accommodate the weight and dynamic loads and
shall be sway braced.
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard or.gov • TTY Relay: 503.684.2772
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectful)
Dan Nelson,
Senior Plans Examiner
•