Correspondence N\-cc 1 tog() City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 July 30, 2007 RE: MECHANICAL FOR GEORGE FOX T I Project Information Building Permit: MEC2007 -00409 Construction Type: NA Tenant Name: George Fox Occupancy Type: B Address: 12753 SW 68 St. Occupant Load: NA Area: NA Stories: 2 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The following corrections shall be submitted prior to issuance of this plan. The response should be numbered as per the correction list. 1) Please provide details showing support for VAV's and FPB's along with anti -sway measures to be taken. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. r espectfully, i � (1 an Nelson, Senior Plans Examiner Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 July 30, 2007 UI RE: MECHANICAL FOR GEORGE FOX TI GARD r .. Project Information Building Permit: MEC2007 -00409 Construction Type: NA Tenant Name: George Fox Occupancy Type: B Address: 12753 SW 68 St. Occupant Load: NA Area: NA Stories: 2 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. 1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) 2. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC 3. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 4. Permanent equipment supported by the structure, 400 lbs and over, shall have their attachments designed in accordance with the Building Code. 301.16 OMSC 5. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 6. Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC 7. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC 8. Smoke detectors shall be installed in return air systems with a design capacity greater than 2000 cfm. Upon activation, the smoke detector shall shut down • the air distribution system. Smoke detectors shall be connected to a fire alarm system and shall activate an audible and visible alarm at a constantly attended location. 606.2, 606.4 & 606.4.1 OMSC 9. Suspended -type unit heaters shall be supported by non - combustible elements that are designed and constructed to accommodate the weight and dynamic loads and shall be sway braced. Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard or.gov • TTY Relay: 503.684.2772 When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectful) Dan Nelson, Senior Plans Examiner •