City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
February 5, 2008
1
RE: MECHANICAL
Proiect Information T I GARD
Building Permit: MEC2008 -00063 Construction Type: 5 -B
Tenant Name: HP Northwest Occupancy Type: B
Address: 12511 SW Pacific Hwy. Occupant Load: NA
Area: NA Stories: NA
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The
submitted plans are approved subject to the following.
1. Each appliance shall be provided with a shutoff valve separate from the
appliance. The shutoff valve shall be located in the same room and within six feet
of the appliance served. Access shall be provided to the shutoff valve. C409.5
OMSC
2. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
3. Appliances shall be accessible for inspection, service, repair or replacement
without removal of permanent construction. 306.1 OMSC
4. Manufacturer's installation instructions shall be available on the jobsite at the
time of inspection. 304.1 OMSC
5. Condensate from cooling coils or evaporators shall be collected and discharged
to an approved plumbing fixture or disposal area. 307.1 OMSC
6. Compressor shall be mechanically connected to the roof.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
inspectors throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson,
Senior Plans Examiner
(503)718 -2436
dann c@tigard- or.com
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
,- -� • * ,"
Submittal Data System 24CL FUJITSU 0
ASU24CL & AOU24CL
Job Name: Location:
Purchaser:
Engineer: -
Submitted To: For: ❑ Reference ❑ Approval ❑ Construction
Submitted By: .
OUTLINE AND DIMENSIONS
IINENI
Capacities: _ I a
Cooling 24200 BTU/h
Min/Max Cooling 5,200- 26,000BTU/h
Outdoor Design Temperature F° DB /WB 95/75
39.114• 9•
SEER . _ 18.0
EER 10.5 h� 31 -1/8' 2 411 , 1 2 -
Low Ambient Temp F. 14
IONS N111•11111111•1•1•111111■■•■1•1111■1 Mom
Voltage/Frequency /Phase 208 - 230/60/1 - -7'.--- -_i I
Indoor Unit: �`
Noise Level db (A) - H /M/VQ 47/41/36/32 e = — ___ - - *roof I
Weight 31 lbs. _ —
Outdoor Unit: — _ —_____
Noise Level db (A) _ 52 =
AIM
Recommended Fuse Size _ 29A -
Min. Ampacity 21A 8118
Running Current (Rated/Max) 10.1/12.0 Standard Features:
Weight 97 lbs.
Refrigerant Piping: • Six year compressor warranty • Sleep timer; 24 hour timer
Max Ht. Difference 66 ft. • Two year parts warranty • Built in Low Ambient
Max Total or Combined Length - 98 R. • Refrigerant R410A • Auto Restart/ Reset
Discharge Vapor Line (O.D.) 1 /4.in.
Suction (O.D.) 5/8 in. • Auto Louver: 4 Way • Dry Mode
Note: Figures are based on 230 Volts • Auto Mode: Quiet Mode • Power Diffuser
• Ion Deodorizing Filter • Apple Catechin Filter
CITY OF TIGARD
• Cold Prevention • Optional Wired Remote
Appeved ••••••• Control
Conditionally Approved • Digital Wireless Remote
S00 latilar t FollOil 3 Control
Atd
N _ 7 t :N
sr- .. , 2
OFFICE COPY