Correspondence (468) • 63p2e:os- -.601 -
/ / /�i�nlldl�ll��lulll,���i' ILj
May 13 , 2005 I
CITY OF TIGARD
OREGON
Triplett Wellman, Inc.
Nick Wellman
1717 Mount Jefferson Ave
Woodburn, OR 97071
RE: PLAN REVIEW
Project Information
Site Permit: BUP2005 -00148 Construction Type: V - B
Tenant Name: Cascade Veterinary Occupancy Type: B
Address: 11140 SW 68 Parkway Occupant Load: 50 +
Area: 1 7,960 sf, 2 °a 1,650 sf Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R. The following information is
required in order to complete the review.
1. The laundry room is a incidental use area and over 100 sq ft therefore requires a one hour
separation per Table 302.1.1. Provide information on one hour wall separation or
information on sprinkler system for that are as per foot note (a) of this table.
RESPONSE ACCEPTED 5/13/05
2. Provide design information on Glass wall as per chapter 21 of OSSC.
RESPONSE ACCEPTED 5/13/05
3. Stair does not show rise and run details. Provide info.
RESPONSE ACCEPTED 5/13/05
4. Provide roof system information with regards to rigid insulation as required per chapter 26 of
OSSC.
RESPONSE ACCEPTED 5/13/05
1. ** Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc,
will be charged a deferred submittal fee based on the valuation of the portion of the work
being deferred. The minimum fee shall be $200.00.
* *Please provide three sets of plans with the revisions included as noted above.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will be
charged a deferred submittal fee based on the valuation of the portion of the work being deferred.
The minimum fee shall be $200.00.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
•
Res e
al He e,
Senior Plans Examiner
April29, 2005
CaTY OF TIGARD
Triplett Wellman, Inc. OREGON
Nick Wellman
1717 Mount Jefferson Ave
Woodburn, OR 97071
RE: PRELIMINARY PLAN REVIEW
Project Information
Site Permit: BUP2005 -00148 Construction Type: V - B
Tenant Name: Cascade Veterinary Occupancy Type: B
Address: 11140 SW 68 Parkway Occupant Load: 50 +
Area: 1 7,960 sf 2' 1,650 sf Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R. The following information is
required in order to complete the review.
1. The laundry room is a incidental use area and over 100 sq. ft. therefore requires a one hour
separation per Table 302.1.1. Provide information on one hour wall separation or
information on sprinkler system for that area as per foot note (a) of this table.
2. Provide design information on Glass masonry wall as per chapter 21 of OSSC.
3. Stair design does not show rise and run details. Provide info.
4. Provide roof system information with regards to rigid insulation as required per chapter 26 of
OSSC.
Please provide an item by item response.
When issues are resolved provide three sets of plans for permit approval.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Resp
V He ,
Senior Plans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
TRANSMISSION VERIFICATION REPORT
TIME : 05/13/2005 13:45
NAME : TIGARD BUILDING DEPT
FAX : 5036243681
TEL .
SER.# : BROD4J479592
DATE,TIME 05/13 13:44
FAX NO. /NAME 5039820390
DURATION 00:00:27
PAGE(S) 03
RESULT OK
MODE STANDARD
ECM
May 13 , 2005 '�:..!w' �.
CITY OF TIGARD
OREGON
Triplett Wellman, Inc.
Nick Wellman
1717 Mount Jefferson Ave
Woodburn, OR 97071
RE: PLAN REVIEW
ProjectInformation
Site Permit: BTJP2005 -00148 Construction Type: V - B
Tenant Name: Cascade Veterinary Occupancy Type: B
Address: 11140 SW 68 Parkway Occupant Load: 50 +
Area: 1 7,960 sf 2" 1,650 sf Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R. The following information is
required in order to complete the review.
1. The laundry room is a incidental use area and over 100 sq ft therefore requires a one hour
separation per Table 302,1.1. Provide information on one hour wall separation . or
information on sprinlder system for that are as per foot note (a) of this table.
RESPONSE ACCEPTED 5 /13/05
2. Provide design information on Glass wall as per chapter 21 of OSSC.
RESPONSE ACCEPTED 5/13/05
' �0� _
/44 Form 2a Project 'E e: . , , , Page: 1
Ap p SUMMARY As
Project 1. Project Name �� DANG prvts ‘ Cascade Veterinary Referral Center
2. Project Address 11140 68th Parkway
3. City/Town Tigard 5. County I Washington _j
4. Building, Gross Area (ft2) 9,612 6. No. of Floors I 2
7. Construction Site Elevation Above 2,000 ft? ❑ YES ENO
Attached Chapter Type ID Description Attach
Forms and Building Envelope Form 3a Building Envelope - General IN
Worksheets 3b Prescriptive Path - All Climate Zones MI
* CodeComp Report for Simplified Trade -off ❑
* In lieu of 3b * Floppy disc with .occ CodeComp file ❑
Check boxes to Worksheet 3a Wall U- factor MI
indicate attached 3b Roof U- factor MI
forms and 3c Floor U- factor ❑
worksheets 3d Window /Skylight Schedule 51
. Systems Form 4a Systems - General ❑
4b Complex Systems ❑
Worksheet 4a Unitary Air Conditioners - Air Cooled ❑
4b Unitary Air Cond. - Water & Evap Cooled ❑
4c Unitary Heat Pump - Air Cooled ❑
4d Unitary Heat Pump - Water Cooled ❑
4e Packaged Terminal A.C. - Air Cooled ❑
4f Packaged Terminal Heat Pump - Air Cooled ❑
4g Water Chilling Pkgs - Water & Air Cooled ❑
4h Heat Rejection Equipment ❑
4i Boiler - Gas -Fired and Oil-Fired ❑
4j Furnace & Unit Heaters - Gas and Oil -Fired ❑
4k Simultaneous Heating and Cooling ❑
41 Air Transport Energy ❑
4m Natural Ventilation ❑
Lighting Form 5a Lighting - General ❑
5b Interior Lighting Power - Tenant Method ❑
5c Int. Ltng. Power - Space -by -Space Method ❑
Worksheet 5a Lighting Schedule ❑
5b Interior Lighting Power ❑
Applicant 7. Name Leonard dder, AIA 10. Telephone 503.390.6500
8. Company Studio Architecture, Inc 11. Date 04/18/05
9. Si nature
L
Attached No. of Pages Description of Documentation
Document-
ation
Compliance with OSSC, effective 01/01/05
Form 3a Project Name: Cascade Veterinary Referral Center Page: 2
BUILDING ENVELOPE - GENERAL
Check all boxes that 1. Exceptions (Section 1312)
apply. 0 No Envelope Components. The building plans do not call for new or altered building envelope
components, e.g., walls, floors or roof /ceilings.
0 A Non - conditioned Building. The proposed structure has no spaces heated or cooled by
an HVAC system.
Exceptions 0 Exception. All new or altered building envelope components do not comply with the
Discussion of qualifying requirements, Section 1312, but qualify for Exception: O -1 0 -2 0 -3 0- O -5
exceptions in instructions
Section, Portions of the building that qualify:
Plans /Specs
Show compliance by The plans/specs show compliance in the following locations:
including a drawing sheet,
detail number, specification -
section and/or subparagraph. 2. Air Leakage (Section 1312.1.1)
® Complies. Plans require penetrations in building envelope are sealed and windows and
doors are caulked, gasketed or weatherstripped.
The plans/specs show compliance in the following locations:
A3 and A8 series drawings, Details and Sections. Specification Section 07900
3. Suspended Ceiling (Section 1312.1.2.1)
® Complies. Building plans do not show suspended ceaings used to separate conditioned
space from unconditioned space. No exceptions permitted.
4. Recessed Light Fixtures (Section 1312.1.2.2)
O Complies. The building plans do not show recessed light fixtures installed in ceilings
separating conditioned spaces from unconditioned spaces.
® Exception. The building plans require that fixtures installed in direct contact with insulation
be insulation coverage (IC) rated. The plans /specs show compliance in the following locations:
5. Moisture Control (Section 1312.1.4)
® Complies. A one -perm vapor retarder is installed on the warm side (in winter) of all exterior
floors, walls and ceilings, and a ground cover installed in the crawl space of both new and
existing buildings where insulation is installed.
The plans/specs show compliance in the following locations:
O Exception. All new or altered building envelope components do not comply with the vapor
retarder requirements of the code, but qualify for an exception. Note applicable exception.
Section 1312.1.4, Exception: 0 -1 0 -2
Portions of the building that comply:
Climate 6. Climate Zones
Zones ® Zone 1 - A building site is in Climate Zone 1 if its elevation is less than 3000 feet above
sea level and it is in one of the following counties: Benton, Columbia, Clackamas, Clatsop,
Coos, Curry, Douglas, Jackson, Josephine, Lane, Lincoln, Linn, Marion, Multnomah, Polk,
Tillamook, Yamhill, or Washington.
Yart�. 0 Zone 2 - Building sites not in Zone 1, or where construction site elevation is 3000 feet or
higher in Zone 1, are in Zone 2.
3-1
Compliance with OSSC. effective 01/01/05
Form 3b Project Name: Cascade Veterinary Referral Center Page: 3
PRESCRIPTIVE PATH Part 1 of 4
CLIMATE
ZONE 1
Exterior Wall
Window Area Area Maximum Glazing Fraction
(total rough frame ft2) (gross ft2) Glazing % Complies
Glazing Conditioned 1,856 j 8,206 X 100 = 22.6% Yes
Percent Cale. space
ulation
Semi -
See instruction Conditioned - X 100 = Yes
section for a Space
discussion of glazing
percent calculation.
Conditioned
Mechanical + X 100 = Yes
Penthouse
Windows Window Max Minimum Window Shading Minimum
From Work -sheet (from worksheet 3d) U- Factor Assembly (from woAateat3d) Coefficient Assembly
3d, place the highest
Overall Window U- N/A N/A SI N/A N/A ta
factor and highest
Center - of - Glass SC. U - Value Complies N/A SC Complies N/A
Or check minimum
assembly and Required Minimum
identify window. Assembly (Fixed Double glazed with 0 inch Required Minimum Assembly Tinted outdoor pane
Windows) airspace, low-e coating, alum frame
Required Mini mum Double -glazed window with a 0.5
Assembly (Operable inch air space, low-e coating and
Windows and thermally broken frame
Curtainwall)
The plans /specs show window compliance in the following locations:
Notes 'From Worksheet 3d, place the highest Overall Window U- factor or check (Minimum Assembly). See - Window Requirements in table on the following page for specific MA
requirements. Excel version will automatically insert minimum assembly requirements or greatest U -value from Worksheet 3d.
'From Worksheet 3d, place the highest - center-of- glass' shading coefficient (SC) for glass or check MA (Minimum Assembly). See - Window Require- ments' in following table
for specific MA requirements. Excel version will automatically insert minimum assembly requirements or greatest SC from Worksheet 3d. Shading Coefficient (SC) can be
calculated from Solar Heat Gain Coefficient using the equation: SC = SHGC + 0.87. Manufacturers data may also be used to document SC.
Walls R -Value
Wall / Insulation Type Insulation Only U- Factor
See instructions for
a discussion of wall Exterior Framed Wall R -21 or
require - ments.
• or
1 a
or
_ or
Below -Grade R - Value
Walls Insulation Only U- Factor
See instructions for a Below -Grade Walls (Min. R -7.5) (Max. 0.11)
discussion of
requirements. Concrete walls built into grade R -10 or ",... x
.. ' i rr.':K
Notes 3 Submit Worksheet 3a for each calculated assembly U- factor xctr -�-�
3-2
Compliance with OSSC, effective 01/01/05
Form 3b Project Name: Cascade Veterinary Referral Center Page: 4
PRESCRIPTIVE PATH Part 2 of 4
Code Requirements - Zone 1
Discussion of these requirements in the instruction section.
ZONE 1
Wall Requirements Window Requirements
Max. Glazing R•Value Max. Shading
Fraction' Wall / Insulation Type Insulation Only U- Factor Max. U- Factor Coefficient
CMU 'Masonry w/integral loose fill insulation N/A or 0.300
Up to 15% Masonry or concrete w /cunt. exterior insulation 1.4 or 0.300 0.540 0.57
CMU Masonry w/integral rigid fill insulation N/A or 0.210
Masonry or concrete w /nterior insulation 11 or 0.130
Up to 30% Masonry or concrete w /cost. exterior insulation 2.8 or 0.210 0.540' 0.57
Frame (wood or metal framing) 13 or 0.130
Other (provide short description) 13 or 0.130
CMU Masonry w/integral rigid fill insulation WA or 0.210
Masonry or concrete wfinterior insulation 11 or 0.130
Up to 40% Masonry or concrete w /cunt. exterior insulation 2.8 or 0.210 0.370 10
0.35
Frame (wood or metal framing) 13 or 0.130
Other (provide short description) 13 Of 0.130
Code Requirements - Zone 2
Discussion of these requirements in the instruction section.
ZONE 2
Wall Requirements Window Requirements
Wall / Insulation Type
Max. Shading
Max. Glazing R -Value U•Factor Max. U- Factor Coefficient
Fraction' Insulation Only
CMU ' Masonry w/integral loose fill insulation N/A or 0.300 11 11
Up to 15% 0.500 0.57
Masonry or concrete , w /cont. exterior insulation 1.8 or 0.270
CMU Masonry w/integral rigid fill insulation N/A Or 0.160
Masonry or concrete w /interior insulation 13 or 0.090
Up to 25% Masonry or concrete w /cont. exterior insulation 4.3 or 0.160 0.500 0.57
Frame (wood or metal framing) 19 or 0.090
Other (provide short description) 19 or 0.090
CMU Masonry w /integral rigid fill insulation N/A or 0.160
Masonry or concrete wfinterior insulation 13 or 0.090
Up to 33% Masonry or concrete w /cont. exterior insulation 4.3 or 0.160 0.370 0.43
Frame (wood or metal framing) 19 or 0.090
Other (provide short description) 1 9 or 0.090
Notes ' The Simplified Trade -off Approach must be used if glazing fraction exceeds allowable percentages.
5 Minimum weight of masonry and concrete walls = 45 lb/112 of wall face area
e All cores to be filled. At least 50% of cores must be filled with vermiculite or equivalent fill insulation.
7 Prescriptive MA (Minimum Assembly) - For Fixed Windows: double - glazed window with a 0.5 inch air space, low-e coating and aluminum frame. MA shading coefficient
description is a tinted outboard pane of glass. For Operable Windows or Curtainwall: double - glazed window with a 0.5 inch air space, low-e coating and thermally
broken frame. MA shading coefficient description is a tinted outboard pane of glass.
8 All cores except bond beams must contain rigid insulation inserts approved for use in reinforced masonry walls
a Batt insulation installed in metal or wood frame walls shall be insulated to the full depth of the cavity, up to 6 inches in depth.
10 Prescriptive MA (Minimum Assembly) - For Fixed Windows: double - glazed window with a 0.5 inch argon filled space, low-e coating (e<= 0.05) and thermal break frame.
For Operable Windows or Curtainwall: only use Max ll- Factor. MA shading coefficient description is a 0.25 -inch thick glass with low -e coating (e <= 0.05) with a tinted
outboard pane.
11 Prescriptive MA (Minimum Assembly) - For Fixed Windows: double - glazed window with a 0.5 inch air space, low-e coating and aluminum frame. For Operable Windows
or Curtainwall: double - glazed window with a 0.5 inch air space, low-e coating (e <= 0.1) and thermally broken frame. MA maemum shading coefficient description is a
tinted outboard pane of glass.
-•? .y_ 12 Prescriptive MA (Minimum Assembly) - For Fixed Windows, a double - glazed window with a 0.5 inch argon filled space, low-e coating (e <= 0.05) and thermal break frame.
• •, '!� For Operable Windows or Curtainwall, only use Max U- Factor. MA shading coefficient description is a 0.25 -inch thick glass with low-e coating (e <= 0.05).
II' f
0
3-3
Compliance with OSSC, effective 01/01/05
i Form 3b Project Name: Cascade Veterinary Referral Center Page: 5
PRESCRIPTIVE PATH Part 3 of 4
Roofs/ R -Value
Ceilings Insulation Only U- Factor
See instructions for a R oof / Ceiling" (Min. R -19) (Max 0.050)
dicussion of Flat roof w/ insulation above deck R -23 or
roofs /ceilings.
Notes 11 Write-in a short description for assembly with the lowest insulation R -value or the highest assembly U- factor.
12 Submit Worksheet 3b for each calculated roof /ceiling assembly U- factor.
Skylight Area Roof Area Skylight % Maximum Skylight
(total rough frame ft2) (gross ft2) 13 Fraction Complies
Skylights Conditioned
Includes glazed Space 0 + 7,962 X 100 = 0.0% Yes
smoke vents.
See instructions fora Semi -
dicussion of Conditioned X 100 = N/A
skylights. Space
Conditioned
Mechanical ÷ X 100 = N/A
Penthouse
Skylight Area Roof/Ceiling Area Skylight
(total rough frame ,s
82) (gross ft2) Percent
Skylights Skylights Max Minimum Skylights Shading Minimum
From Worksheet 3d,
place highest Overall (from Worksheet 3d) U Assembly (from wodoteet3d) Coefficient' Assembly
Vertical Window U- #N /A - D #N /A - N/A
factor and highest
Center -of -Glass SC.
U -Value Complies Yes SC Complies Yes
Required Minimum
NIA Required Minimum Assembly N/A (must use SC)
Assembly .
The plans /specs show window compliance in the following locations:
Code Thermal Performance Shading Coefficient
Require- Compliance Option Overall Vertical U -Factor Center of Glass SC
meats Performance U -1.230 for overall assembly in overhead plane SC -0.47 center -of -glass
Min. Assembly Double glazed, 0.5 -inch airspace N/A
(MA)
Notes 13
Skylight percentage area is based on total skylight and smoke vent rough frame area divided by total conditioned roof area. Percentage must not exceed 6 percent of total
roof /ceiling area in conditioned building space. The Simplified Trade-off Approach must be used if glazing fraction exceeds allowable percentages.
14 From Worksheet 3d, place the highest Overall Vertical U- factor or write -in MA (Minimum Assembly). See 'Skylight Requirements' in table above for specific MA
requirements.
15 From Worksheet 3e, place the highest 'center-of-glass' shading coefficient (SC) for glass. See 'Skylight Requirements' in table above for specific MA requirements.
Shading Coefficient (SC) can be calculated from the Solar Heat Gain Coefficient using the equation: SC = SHGC i 0.87. Manufacturers data may also be used to
document SC.
3-4
Compliance with OSSC, effective 01/01/05
Form 3b Project Name: Cascade Veterinary Referral Center Page: 6
PRESCRIPTIVE PATH Part 4 of 4
Floors
See instructions for R - Value
a dicussion of Floors over Unconditioned Spaces' Insulation Only U Factor
floors' or
Heated Concrete Slab Edge R -Value
Insulation Only
Heated Slab -on -Grade (Section 1312.1.2.4)
O Complies. Building plans show insulation extending downward from the top of the slab a minimum
distance of 24 inches or downward and under the slab for a combined minimum distance of 24
inches or to the bottom of the thickened edge of the of slabs used as a foundation.
The plans /specs show compliance in the following locations:
Notes 18 Write -in a short description for assembly with the lowest insulation R -value or the highest assembly U- factor.
11 Submit Worksheet 3c for each calculated floor assembly U- factor.
18 Write -in a short description for Heated Slab, which has heat, integrated into slab such as hydronic heat. If more than one floor type, enter the lowest
insulation R -value or the highest component U- factor of any floor.
Code Compliance Options
Require Min. R -Value
meats Component Insulation Only Max. U- Factor
Floor over Unconditioned Spaces 1 11 1 or 1 0.070
Climate Climate
Component Zone 1 Zone 2
Heated Concrete Slab Edge, Min. R -Value 1 7.5 or I 10.0
Doors
See instructions for R - Value U - Factor
a dicussion of doors. Doors" Insulation Only Center -of -Panel
opaque, with leaf width greater than 4' (Min. R -5) (Max. 0.20)
or
Notes 19
Write -in a start description for Doors. If more than one door type, enter the lowest insulation R -value or the highest center -of -panel U- factor of any
door. The following doors are exempt from door and window U- factor and shading coefficient requirement
3-5
•
Compliance with OSSC, effective 01/01/05