Loading...
Correspondence 11/ c rN= 55 • 410 February 23, 1996 C1TY OF TIG ORE Ross & Vicki Mercer 11535 SW 67th Tigard, OR 97223 Re: MERCER OFFICE BUILDING 11565 SW 67th MEC95 -0353 The plans and specifications have been reviewed for conformity to applicable codes. Please submit three (3) sets of revised plans and specifications incorporating the following requirements:. a 4: Provide the calculations, specifications, and source of combustion air for AH -1 and AH -2 [OMSC, Section 601(a)]. Provide an equipment schedule that corresponds with equipment shown on the plan, and the amount of outside air being continuously provided. A. The heating /ventilation system must provide 5 cubic feet per minute (cfm) of outside air per occupant with a total circulation of not less than 15 cfm per occupant in all portions of the building [UBC Sections 605 and 705]. 3/ Each individual roof - mounted HVAC shall be permanently labeled as to the areas it serves [Section 504(e)]. In addition, each unit shall be equipped with a power disconnect and a 120 -volt receptacle shall be located within 25' of each unit [Section 509] . 4„, Illustrate area of gas meter and gas pressure [OMSC, Section 2219]. If you wish to discuss any of these items, please give me a call. Sincerely, 7Q James Funk Plans Examiner mec95- 0353 \rossmrcr 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772