Re: MERCER OFFICE BUILDING
11565 SW 67th
MEC95 -0353
The plans and specifications have been reviewed for conformity to
applicable codes. Please submit three (3) sets of revised plans
and specifications incorporating the following requirements:.
a 4: Provide the calculations, specifications, and source of
combustion air for AH -1 and AH -2 [OMSC, Section 601(a)].
Provide an equipment schedule that corresponds with equipment
shown on the plan, and the amount of outside air being
continuously provided.
A. The heating /ventilation system must provide 5 cubic feet
per minute (cfm) of outside air per occupant with a total
circulation of not less than 15 cfm per occupant in all
portions of the building [UBC Sections 605 and 705].
3/ Each individual roof - mounted HVAC shall be permanently labeled
as to the areas it serves [Section 504(e)]. In addition, each
unit shall be equipped with a power disconnect and a 120 -volt
receptacle shall be located within 25' of each unit [Section
509] .
4„,
Illustrate area of gas meter and gas pressure [OMSC, Section
2219].
If you wish to discuss any of these items, please give me a call.