Attached is the substitute UL Design No. 305 for the 1 hour bearing wall detail for this
project. Andy Cunningham at Beacon Home NW indicated this is acceptable to you.
Please indicate city approval and mail me a copy.
Th ��u!
ALA / j r 4 /,, l
D 4VA. Bi : "ett (AIA, .BARB r
Cc: Andy Cunningham
File
' .I1 1 ,
/ AID ETT
• es R . ON
I r \ cad
c c
4;OFO
322 NW 5th Avenue • Portland, Oregon 97209 • (503) 226 -6785 • Fax (503) 224 -2311
08/11/04 WED 09:33 FAX 503 684 0954 CARLSON TESTING i1002
Main Office Salem Office Bend Office
P.O. Box 23814 4060 Hudson Ave_, NE P.O. Box 7918
Testing Tigard, Oregon 97281 Salem, OR 97301 Bend, OR 97708
Carlson Inc. Phone (503) 684-3460 Phone (503) 589 -1252 Phone (541) 330 -9155
FAX (503) 684 0954 FAX (503) 589.1309 FAX (541) 330 -9163
Special Inspection
FINAL SUMMARY LETTER
August 11, 2004
T0405670_CTI
City of Tigard
13125 SW Hall Blvd., FILE C
Tigard, OR 97223 -8199
Attn: Building Department
Re: Spectrum Office — Tenant Improvement
12703 SW 67 Avenue, Tigard, OR
Permit No.: BUP2004 -00089
Dear Sir or Madam:
This is to certify that in accordance with Section 1701 of the Uniform Building Code, Title 24, we have
performed special inspection of the following item(s) per our inspection reports only:
Installation of Adhesive Anchors
All inspections and tests were performed and reported according to the requirements of Project Documents
and, to the best of our knowledge, the work was in conformance with the approved plans and
specifications, approved change orders and applicable workmanship provisions of the State Building Code
and Standards, as well as the structural engineer's design changes, approvals and verbal instructions.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be
reproduced, except in full, without prior authorization from this office.
if there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING, INC.
es) - /?7, '/?4
Andrew M. Ewing
President
mbw
CC: Beacon Homes NW Inc — Andrew Gillingham
Sherman Engineering Inc
April 8, 2004
CITY OF TIGARD
David A. Bissett OREGON
DAVID BISSETT & ASSOCIATES
322 NW 5 Avenue, #301
Portland, OR 97209
RE: SPECTRUM OFFICE BUILDING /SITE PERMIT
Site Permit: BUP2004 -00089 Construction Type: VN
Tenant Name: Speculative Occupancy Type: B
Address: 12703 SW 67 Avenue Occupant Load: 23
Area: 2,310 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following conditions.
1. NORTH, SOUTH & WEST walls shall be 1 hour rated due to location on property.
2. Openings are not permitted in the North & South walls. The structure will have
openings framed in but will be in- filled until the property line has been adjusted to
permit openings.
3. Parapet walls are required on the North & South sides of the structure.
4. The "Covered Entry" will require 2 layers of gypsum applied to the underside of the
roof joist to comply with section 709.4.1 Exception 5.2 OSSC See attached item 21-
1.1, from Table 7 -C. No vents within 5 feet of property line.
5. The means of egress shall be provided with illumination of not less than 1 foot candle
at the floor level anytime the building is occupied. The means of egress illumination
shall be provided with a second source of power in case of primary power loss.
1003.2.9.2 OSSC
6. Provide one 2 -A rated fire extinguisher in the new area. The extinguisher shall be
located so that no usable space has a distance greater than 75 feet to the extinguisher.
Standard 10 -1, Chapter 3 TVFR99 -01.
Deferred submittals such as Mechanical, Truss Joist Shop Drawings, etc, will be charged a
} deferred submittal fee based on the valuation of the portion of the work being deferred. The
minimum fee shall be $200.00.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the
Building Official has issued a certificate of occupancy 109.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully
an Blame
Senio ans Examiner