Loading...
Correspondence Vision Wordl - TI Page 1 of 1 • 1)6) ZOLL C(2 q)1' Ron Nielsen From: Tim Agnew [TAgnew @tmrippey.com] • Sent: Wednesday, October 01, 2008 3:18 PM To: Ron Nielsen Subject: Vision Wordl - TI Ron, Regarding detail 6/S3. It is acceptable to replace the LSL blocking between the wall studs with a lower 1 1/4 x 9 1/2 LSL ledger pushed tight under the 1 1/4 x 16 LSL ledger. Nail lower ledger to each wall stud with (3) 16d sinkers. All wall studs need to be 8" o /c, even over the windows. At the new shearwall location install the sheathing to the underside of the 1 1/4 x 16 LSL ledger, install the 1 1/4 x 9 1/2 LSL ledger with (3) 16d sinkers into each wall stud. Nail ledger to the OSB sheathing with 10d common nails at 6" o /c. Connect the lower ledger with the upper ledger with Simpson 'LTP4' clips at 2' -0" o /c. If you need anything else let me know. Thanks, Timothy Agnew, P.E. TM Rippey Consulting Engineers 7650 SW Beveland St. Suite 100 Tigard, Oregon 97223 Phone: 503 1 443 1 3900 Fax: 503 1 443 1 3700 10/1/2008