Correspondence (507) FILE COPY
August 7, 2006 /gy p ZcbE 02ud
1s review, June 5, 2006 my OF TI
OREGON
Mildren Design Group, PC
Dan Vasquez
1650 SW Beveland St #120
Tigard, OR 97223
RE: TRIANGLE COMMONS BUILDING ONE - NEW BUILDING - REVIEW
Project Information
Building Permit: BUP2006 -00206 Construction Type: III -B
Tenant Name: Pacific Northwest Property Occupancy Type: B
Address: 11850 SW 67 Ave. Occupant Load: 487 ( +1 -)
Area: 48,667 sq ft Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition
and 2004 Oregon Fire Code as amended by TVF&R. The following information is required in order to
complete the review.
SITE
1. Our files show no site permit was issued. Please submit site plan with permit application along with
valuation of site work. Complete form to show all impervious area, excavation, grading and fill
volumes. Please complete both sides of the form. Forms attached. (RESPONSE received 6/5/06)
2. Provide attached TVF &R form with permit. RESPONSE ACCEPTED 8/7/06
STRUCTURAL **( This review does not include privacy wall, this wall located in site plan
submittal review permit # SIT2006 -00006
3. The structural review was completed by Miller Consulting. The plan review #1 dated June 1, 2006, was
E- Mailed to Mildren Design Group for response (review doc. attached).
** RESPONSE SENT TO MILLER 7/27/06
FIRE LIFE AND SAFETY / GENERAL -
4. Suspended ceiling not listed as deferred submittal, please provide design per ch 16 OSSC.
RESPONSE ACCEPTED 8/7/06
5. Egress path and occupant load 1004, 1013, 1014 (The construction documents shall show in sufficient detail the
location, construction, size and character of all portions of the means of egress in compliance with the provisions of this code.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
The construction documents shall designate the number of occupants to be accommodated on eve y floor, and in all rooms and
.paces. OSSC 106.1.2) RESPONSE ACCEPTED 8/7/06
6. Provide roof assembly design information showing roofing meets performance requirements per
OSSC 1504, chapter 16 and OSSC 2603. RESPONSE ACCEPTED 8/7/06
7. Provide locations /information on overflow drains or scuppers being used as required by OSSC 1504.
RESPONSE ACCEPTED 8/7/06
8. Provide lateral load design information on exterior glazing per OSSC 2404.
RESPONSE ACCEPTED 8/7/06
9. Fire protection systems (106.1.1.1 Fire protection system shop drawings. Shop drawings for the fire
protection systems) shall be submitted to indicate conformance with this code and the construction documents and shall be
approved prior to the start of system installation. Shop drawings shall contain all information as required by the referenced
installation standards in Chapter 9) RESPONSE ACCEPTED 8/7/06
10. Fire resistive rated structural member locations and assembly 714, 715
RESPONSE ACCEPTED 8/7/06
11. Deferred submittals: Deferred Items: As noted on sheet A0.1
*Steel joist * Joist girders *Steel stairs
*Component anchorage * Block retaining wall
(electrical /mechanical)
"Documents for deferred submittal items shall be submitted to the registered design professional in responsible charge who
shall review them and forward them to the building official with a notation indicating that the deferred submittal documents
have been reviewed and been found to be in general conformance to the design of the building. The deferred submittal items
shall not be installed until the design and submittal documents have been approved by the building officiaL Oregon
Structural Specialty Code Section 106.3.4.2"
NOT PART OF THIS REVIEW:
*Mechanical (HVAC) *Pluming *Fire sprinkler *Electrical *Fire alarm *Low voltage
NOTE: **Provide 2 complete sets of plans when structural review is approved by Miller
Consulting.
When submitting revised drawings or additional information, please attach a copy of the enclosed City of
Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and
processing the documents.
Respectfully,
Val Henzel,
Senior Plans Examiner