August 28, 2006 gP
CO CITY OF TIG
OREGON
Mildren Design Group, PC
Dan Vasquez
1650 SW 105 Ave, Suite 175 r �. n
Tigard, OR 97223 f(
RE: TRIANGLE COMMONS BUILDING ONE - NEW BUILDING - RE VIEW r ..
Project Information $:'''<.-,: , 7 .
Building Permit BUP2006 -00206 Construction Type : \( III B
Tenant Name: Pacific Northwest Property Occupanry , '‘
Address: 11850 SW 67t Ave. Oc r t Load: ) 487
Area: 7
48,667 sq ft Stones• `�. 2
The plan review was performed under the State of Oregon Structural Spec Code (OSSC) 2004 edition
and 2004 Oregon Fire Code as amended by TVF&R. The'subiitted plans are approved subject to the
following conditions. s';,-
.
1. The structural review was approved by Miller-;Consultmg Engineers August 25, 2006.
(review doc. attached). ,
2. Special inspection is required for ciga ere w reinforcing stee4 bolting, welded studs,
embed plates, bolts in concrete masonry, sor7s, structural steel fabrication and erection,
adhesive and expansion anchor installation, (as items listed on sheet A0.1 and Miller Consulting
Engineers approved review letter)_The special inspection agency of record shall furnish inspection
reports to the Engineer of Record;�`Afghan Associates, the General Contractor, and the City of Tigard,
Building Division, attention Hap Watkins. All discrepancies shall be brought to the immediate
attention of the generar on for correction. The special inspector shall submit a final signed
report stating whether the work requiring special inspection was, to the best of the inspector's
knowledge, in conformance with the approved plans and specifications and the applicable workmanship
provisions. Of the co'de.1704, 1705, 1707, 1708 OSSC
3. Structural Observations is required per section 1709 Oregon Structural Specialty Code (OSSC).
The.owner shall employ a registered design professional to perform structural observations as defined
in Sectior OSSC. Structural observations is required for concrete foundation, retaining
walls'reinforcing, reinforcing steel in tilt -up panels, before concrete placement at second floor,
placement of floor joist and girders, and roof deck welding (as items listed on Miller Consulting
Engineers approved review letter). Deficiencies shall be reported in writing to the owner and to the
City of Tigard, Building Division, attention Hap Watkins. FYI The structural observations do not
waive the framing inspection required by code.
4. Live Loads Posted: The live loads for which each floor has been designed to exceed 50 psf shall
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
be conspicuously posted by the owner in that part of each story in which they apply, using durable
metal signs, and it shall be unlawful to remove or deface such notices. The occupant of the building
shall be responsible for keeping the actual load below the allowable limits. 1603.3 OSSC
FIRE LIFE AND SAFETY / GENERAL
5. The main exterior door or doors are permitted to be equipped with key- operated locking devices from
the egress side provided:
1. The locking device is readily distinguishable as locked, A
2. A readily visible durable sign is posted on the egress side on or adjacent to the door:
stating. THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING=IS<OCCUPIED.
The sign shall be in letters 1 inch (25 mm) high on a contrasting background._ Sec. 10081.8.3
6. All exit doors shall be openable from the inside without the use of a key or any4ecsal knowledge
or effort Sec. 1008.1.8 y
i f
7. Exits and exit access doors shall be marked by an approved exit•signn readily :visible from any
direction of egress travel. Access to exits shall be marked by readily-visible exit signs in cases
where the exit or the path of egress travel is not immediately visible tg.-the occupants. Sec. 1011.1
8. Exit signs shall be illuminated at all times and shal�-be.provn led with a second source of power
that will provide 1 1/2 hours of illumination in case'of pnmary loss. Sec. 1006.3 FYI
aty
Additional exit signs may be required by the, field`inspector to clearly indicate the path of
egress. • » 4 ' t t� � )"
j
9. The means of egress shall be provided vithAumination of not less than 1 foot candle at the floor
level anytime the building is occupied.':Tbe means of egress illumination shall be provided with a
second source of power in case of primaryrpower loss. Sec. 1006.2
10. All elevators, required or provided, shall be located on an accessible route and shall be designed
and constructed to comply with 30 and the Oregon Elevator Specialty Code.
1108.3.2 OSSC
11. Floor drains shall rot be.located within the clear floor space at a lavatory, water closet, urinal, or
bathtub oc shower Floors shall not slope in excess of 1 unit vertical in 50 units horizontal (2 % slope).
Floor drains shall comply with Section 1109.4.5 and be without abrupt changes of level. Exception:
Floor drains be located within a clear floor space at a fixtwr pmvided the openings in the drain corner shall not
exceed % inch (12.7 mm) in any direction and the drain cover shall be no more than 118 inch below the level of the
surrounding - f niched floor surface. 1109.10.1 OSSC
12. Safety glazing including but not limited to: the following locations: Each unit of glazing shall be
permanently identified by the manufacturer. Sec. 2406. Some of these locations are as follows:
a. Glazing in ingress and means of egress doors.
b. Glazing in an individual fixed or operable panel adjacent to a door where the nearest vertical
edge is within a 24" arc of the door in a closed position and whose bottom edge is less than
• t;
60" above the floor or walking surface except when there is an intervening wall or other
permanent barrier between the door and the glazing.
13. Deferred Items: As noted on Miller Consulting Structural review document dated 8/8/06 &
sheet A0.1
* Steel open web joist and girders * Steel decking *Steel stairs *Component anchorage
* Calculations & details for canopy * Calculations & details for glazed storefront system
The minimum fee shall be $200.00. This fee is in addition to the project plan review fee,bas d th`e total
project value. OAR 918-050-0150
`Documents for deferred submittal items shall be submitted to the registered design pmfessional'inr� ii _ sir i e who
shall review them and fonvanl them to the bui /ding official with a notation indicating that the d f6`irr d submittal
documentr have been reviewed and been found to be in general conformance to the design /&iildi g The defend
submittal items shall not be installed until the design and submittal documents have been #a the building
official Oregon Structural Specialty Code Section 1063.4.2" 0
(electdca1 /methanua0
NOT PART OF THIS REVIEW:.
* Electrical * Fire Sprinklers * Mec System.,( * Plumbing
A
ti
American with Disabilities Act (ADA): It shall be ihe;tesponsibility of the Architect, Engineer,
Designer, Contractor, Owner and Lessee to researchtlie app$cabty of the ADA requirements for the
structure. The City of Tigard reviews the plans and;ii pects the,structure only for compliance with
Chapter 11 of the OSSC, which may not include'all of the,requ ements of the ADA.
Approved Plans: 1 set of approved plans; bearing e,City of Tigard approval stamp, shall be maintained
on the jobsite. The plans shall be available tp the,Building Division inspectors throughout all phases of
construction. 106.3.1 OSSC
Certificate of Occupancy: No' budding or structure shall be used or occupied until the Building Official
has issued a certificate of occupancy OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such
a position as to be•,plainly visible nd legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed City of
Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and
processing the documents.
ii
Respe soy,
17/t/
Val Henzel,
Senior Plans Examiner